Do not install
the UPS in
direct
sunlight, in
excessive heat,
humidity, or in contact with fluids.
bu001a
Overview
Front panelRear Panel
Mute
Power On/Off
Display/Menu
Display interface
Ethernet ports
Circuit breaker
Master outlet
Battery Back-UPS outlets
Surge protected outlets
Controlled outlets
Data port
Do not connect a laser printer or hair
dryer to the unit.
Ensure that the connected equipment
does not exceed the maximum load.
MASTER
Controlled by
MASTER
bu017a
bu045a
Connect the battery
bu050a
Charge the battery for at least 16 hours
5
before use.
bu048a
bu049a
bu047a
Connect the equipment
Connect the equipment
1.Connect equipment to the Battery Backupand Surge Protection
outlets. When the Back-UPS is receiving AC power, these
outlets will supply power to connected equipment. During a
power outage or other utility problems, the Battery Backup
outlets receive power for a limited time from the unit.
MASTER
Controlled by
MASTER
2.Use the AC power cord to connect the Back-UPS directly to a
utility power outlet.
3.Connect a router or cable modem to the corresponding ports.
Install PowerChute® Personal Edition software
1. Connect the supplied USB software interface cable to the data
port, and the other end to a computer with access to the internet.
2. Go to www.apc.com/tools/download.
3.Select PowerChute Personal Edition. Then select the appropriate operating system and follow the instructions to
download the software.
Operation
Display interface
bu046a
Description, if the icon is illuminated:
On Line—The UPS is supplying utility power to connected equipment
Power-Saving—Master and controlled outlets are enabled, saving
power when the master device goes into sleep or standby mode
Load Capacity—The load is indicated by the number of sections
illuminated, one to five. If the load exceeds the rated capacity, the
Overload symbol will flash off and on.
Battery Charge—The battery charge level is indicated by the number
of sections illuminated. When all five blocks are illuminated, the BackUPS is at full charge. When one block is filled, the Back-UPS is near the
end of its battery capacity, the indicator will flash and the unit will beep
continuously.
Overload—The power demand from the load has exceeded the capacity
of the Back-UPS.
Event—An event has occurred and the unit needs attention.
bu002 b
Automatic Voltage Regulation—The unit is compensating for
extremely low input voltage, but is not using battery power.
In—Input voltage.
Out—Output voltage.
System Faults—The system has a fault. The fault number will
illuminate on the display interface. See “System Faults” on page 4.
Mute—The audible alarm has been turned off.
Replace Battery—The battery is not connected or is nearing the end of
its useful life. Replace the battery.
On Battery—The unit is supplying battery backup power to the
connected equipment, it will beep four times every 30 seconds.
Back-UPS® RS Installation and Operation2
Modes of operation
Press DISPLAY to scroll through the display screens.
On Line ModeOn Battery Mode
Input VoltageEstimated runtime in minutes
CounterPower Event Counter
Estimated run timeOutput Voltage
Load in Watts Input Voltage
Load in % Load in Watts
Output VoltageLoad in %
Output FrequencyOutput Frequency
Other status indicators
AVR: The Automatic Voltage Regulation (AVR) feature will compensate for excessively low input
voltages, without using battery power .When the AVR symbol is illuminated on the LCD, the unit is
in Boost mode, using the AVR feature.
Configuration
Power-Saving Master and Controlled outlets
To conserve electricity, configure the Back-UPS to recognize a Master device, such as a desktop
computer or an A/V receiver, and Controlled peripheral devices, such as a printer, speakers, or a scanner.
When the Master device goes into Sleep or Standby mode, or turns OFF, the Controlled device(s) will
shut down as well, saving electricity.
Enable the Power-Saving feature. Press and hold MUTE and DISPLAY simultaneously for two seconds. The unit
will beep to indicate that the feature is enabled. The leaf icon on the display will illuminate.
Disable the Power-Saving feature. Press and hold MUTE and DISPLAY simultaneously for two seconds. The unit
will beep to indicate that the feature is disabled. The leaf icon on the display will darken.
Setting the threshold. The amount of power used by a device in Sleep or Standby mode varies between devices. It
may be necessary to adjust the threshold at which the Master outlet signals the Controlled outlets to shut down.
1.Ensure a master device is connected to the Master outlet. Put that device into Sleep or Standby mode, or turn it
OFF.
2.Press
DISPLAY and MUTE simultaneously and hold for six seconds, until the leaf icon flashes three times and the unit
beeps three times.
3.The Back-UPS unit will now recognize the threshold level of the Master device and save it as the new threshold
setting.
Power-Saving LCD Display
When unit power is On, the LCD may remain illuminated or be darkened for energy savings.
1.Full Time LCD Mode: Press and hold
DISPLAY for two seconds. The LCD will illuminate and the unit will beep to
confirm the Full-Time mode.
2.Power-Saving Mode: Press and hold
DISPLAY for two seconds. The LCD will darken and the unit will beep to
confirm the Power-Saving mode. While in Power-Saving Mode, the LCD will illuminate if a button is pressed, it
then darkens after 60 seconds of no activity.
Back-UPS® RS Installation and Operation
3
Unit sensitivity
Adjust the sensitivity of the UPS to control when it will switch to battery power; the higher the sensitivity, the more
often the unit will switch to battery power.
1. Ensure the unit is connected to utility power, but is OFF.
2. Press and hold the
POWER button for six seconds. The LOAD CAPACITY bar will flash on and off, indicating that the
unit is in programming mode.
3.Press
POWER again to rotate through the menu options. Stop at selected sensitivity. The unit will beep to confirm
the selection.
Low sensitivityMedium sensitivityHigh sensitivity
156-288 Vac176-282 Vac176-276 Vac
Input voltage is extremely low or
high. (Not recommended for
computer loads.)
The Back-UPS frequently switches to
battery power.
Warnings and System Faults
Warnings
Press DISPLAY to scroll through the display screens.
Warning 1
ON LINE overload condition,
indicated by the illuminated ON
LINE icon, and the flashing
overload icon.
Warning 3
The connected equipment is
sensitive to voltage fluctuations.
In ON LINE mode, and there is a
bad battery, indicated by the
flashing icon.
Warning 2
Backup battery (ON BATT)
overload condition. This is
indicated by the flashing overload
icon.
Warning 4
The battery charge is low, and
the Battery Charge indicator bar
is flashing.
System Faults
The unit will display the fault messages. Contact APC Technical Support for additional support.
• F01 - On-Battery Overload
• F02 - On-Battery Output Short
• F03 - On-Battery Xcap Overload
• F04 - Clamp Short
• F05 - Charge Fault
• F06 - Relay Welding
• F07 - Temperature
• F08 - Fan Fault
• F09 - Internal Fault
bu021a
Back-UPS® RS Installation and Operation4
Function Button Quick-Reference
FunctionButton
Power
Power On
Power Off
Display
Status Inquiry
Full-Time/PowerSaving mode
Mute
Event Specific
General Status Enable/
Disable
Timing
(seconds)
0.2Off
2On
0.2On
2On
0.2On
2On
UPS
Status
Description
Press
POWER to start receiving input utility power. If A/C input
power is not available, the unit will run on battery power.
The unit is not receiving input utility power, but is providing
surge protection.
Verify the status or condition of the unit. The LCD will illuminate
for 60 seconds.
The LCD will illuminate and the unit will beep to confirm the
Full-Time mode. The LCD will darken and the unit will beep to
confirm the Power-Saving mode. While in Power-Saving Mode,
the LCD will illuminate if a button is pressed, then darkens after
60 seconds of no activity.
Disable any audible alarms caused by an event.
Enable or disable the audible alarms. The Mute icon will
illuminate and the unit will beep one time. The Mute function will
not activate unless the UPS is operating on battery power.
Sensitivity
Master/Controlled
outlet Enable/Disable
Master/Enable
Threshold
Calibration
Self-Test (manual)
Event Reset
Fault Reset
6Off
2On
6On
6On
0.2On
2Fault
The Load Capacity icon will blink, indicating that the unit is in
programming mode. Use the
Low, Medium, and High, stop at selected sensitivity . The unit will
beep to confirm selection. See Configuration for details.
The leaf icon will darken indicating that the Master Outlet feature
is disabled or illuminate to indicate the Master Outlet feature is
enabled. The unit will beep once.
While calibrating the threshold setting, the device connected to
the Master Outlet should be turned off or placed in Standby or
Sleep mode. Upon completion, Power-Saving icon will flash 3
and beep 3 times.
The UPS will perform a test of the internal battery. Note: This
will happen automatically when the unit is turned ON.
When the Event screen is visible, press and hold
press
After a fault has been identified, press
visual indication and return to standby status.
POWER button to scroll through
DISPLAY, then
POWER, to clear the utility failure event counter.
POWER to remove the
Back-UPS® RS Installation and Operation
5
Troubleshooting
ProblemPossible CauseCorrective Action
Back-UPS will not switch on.The unit is not connected to utility power.Ensure that the unit is securely connected to an
AC outlet.
The circuit breaker has been tripped.Disconnect non-essential equipment from the
unit. Reset the circuit breaker. Re-connect
equipment one item at a time. If the circuit
breaker is tripped again, disconnect the device
that caused the trip.
The internal battery is not connected.Connect the battery.
The utility input voltage is out of range.Adjust the transfer voltage and sensitivity range.
The unit does not provide
power during a utility power
outage.
The unit is operating on
battery power, while connected
to utility power.
The unit does not provide the
expected amount of backup
time.
The
REPLACE BATTERY
indicator is illuminated.
VERLOAD indicator is
The O
illuminated.
The
SYSTEM FAULT indicator is
illuminated, all the front panel
indicators are flashing.
Power is not supplied to some
outlets.
The Controlled Outlets are not
supplying power, even though
the Master device is not in sleep
mode.
Ensure that essential equipment is not
plugged into a
The plug has partially pulled out of the wall
outlet, the wall outlet is no longer receiving
utility power, or the circuit breaker has been
tripped.
The unit is performing an automatic self
test.
The utility input voltage is out of range, the
frequency is out of range, or the waveform
is distorted.
Battery Backup outlets may be fully or
improperly loaded.
The battery was recently discharged due to a
power outage and has not fully recharged.
The battery has reached the end of its useful
life.
The battery has reached the end of its useful
life.
The equipment connected to the unit is
drawing more power than the unit can
provide.
There is an internal fault.Determine which internal fault message is
Power to the Controlled Outlets has
intentionally been turned off.
The Master Outlet threshold may be
incorrectly set.
SURGE ONLY outlet.
Disconnect equipment from the
outlet and re-connect to a
outlet.
Ensure that the plug is fully inserted into the
wall outlet. Ensure that the wall outlet is
receiving utility power by checking it with
another device.
No action is necessary.
Adjust the transfer voltage and sensitivity range.
Disconnect non-essential equipment from the
BATTERY BACKUP outlets and connect the
equipment to
Charge the battery cartridge for 16 hours.
Replace the battery.
Replace the battery.
Disconnect non-essential equipment from the
BATTERY BACKUP outlets and connect the
equipment to
displayed by matching the number displayed on
the LCD with the corresponding Fault Message
(see System Faults) and contact APC Technical
Support.
Confirm that the correct peripherals are
connected to Controlled Outlets. If this feature is
not desired, disable the Power-Saving Master
and Controlled Outlets.
Adjust the threshold when the Master outlet
signals the Controlled Outlets to shut down.
SURGE ONLY outlets.
SURGE ONLY outlets.
SURGE ONLY
BATTERY BACKUP
Back-UPS® RS Installation and Operation6
Specifications
t
VA
Maximum Load
Nominal Input Voltage
Online Input Voltage Range
Frequency Range
On-battery Waveshape
Typical Recharge Time
Trans fer Time
Operating Temperature
Storage Temperature
Unit Weight
Interface
EMI Classification
Approvals
1 Hz
Step-approximated sine-wave
12 hours
8 ms, maximum
32° to 104°F (0° to 40°C)
23° to 113°F (-5° to 45°C)
14.8 lbs (6.7 kg)
USB
CE, C-Tick, KETI
CE, TUV-GS, GOST, A-Tick, KETI,
TISI
Service
If the Back-UPS arrived damaged, notify the carrier.
If the Back-UPS requires service, do not return it to the dealer.
1.Consult the Troubleshooting section to eliminate common
problems.
2.If the problem persists, go to http://www.apc.com/support/.
3.If the problem still persists, contact APC Technical Support.
Have the Back-UPS model number, serial number and date of
purchase available. Be prepared to troubleshoot the problem
with an APC Technical Support representative. If this is not
successful, APC will issue a Return Merchandise Authorization (RMA) number and a shipping address.
Warranty
The standard warranty is three (3) years from the date of pur-
chase in the European Community. For all other regions, the
standard warranty is two (2) years from the date of purchase.
The APC standard procedure is to replace the original unit with
a factory reconditioned unit. Customers who must have the
original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact
with an APC Technical Support representative. APC will ship
the replacement unit once the defective unit has been received
by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit
to APC. APC pays ground freight transportation costs to ship
the replacement unit to the customer
.
Customer support and warranty information is available at the APC Web site, www.apc.com.