Inspect the package contents upon receipt. Notify the carrier and
dealer if there is any damage.
SAVE THESE INSTRUCTIONS - This section contains important
instructions that should be followed during installation and maintenance
of the UPS and batteries.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• This UPS is intended for indoor use only.
• Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive
dust or humidity.
• Connect the UPS power cable directly to a wall outlet.
• Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
• Servicing of batteries should be performed or supervised by personnel knowledgeable about
batteries and required precautions.
• A battery can present a risk of electric shock and burns by high short−circuit current.
• Failed batteries can reach temperatures that exceed the burn thresholds for touchable
surfaces.
Failure to follow these instructions will result in death or serious injury.
Inventory
Page 2
Connect the Battery
bu024
c
bu057b
The UPS is shipped with the battery disconnected.
BR650MI /BR900MI
bu025c
Remove the battery door.
Push the battery into the unit.
BR1300MI / BR1600MI
Remove the battery door.
Flip or turn the battery 180 degrees
upward/downward to let green side of the
label face up.
Remove the battery. Connect the wire.
bu026c
Replace the battery door.
bu055b
Remove the battery.
bu059b
bu058b
Push the battery into the unit.
bu060 b
Replace the battery door.
Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI2
Page 3
Install PowerChute™ Personal Edition Software
bu484a
bu485a
Use PowerChute Personal Edition software to configure the UPS settings. During a
power outage, PowerChute will save any open files on your computer and shut it down.
When power is restored, it will restart the computer.
Note: PowerChute is only compatible with a Windows operating system. If you are
using Mac OSX, use the native shutdown feature to protect your system. See the
documentation provided with your computer.
Installation
Use the cable supplied with the Back-UPS to connect the data port on the Back-UPS to
the USB port on your computer. On the computer, go to www.apc.com Search for
“PowerChute Personal Edition” then click on “View Details” to download the latest
version of PCPE software. Click the download link and select Software product. Select
the appropriate operating system. Follow directions to download the software.
Connect the Equipment
Battery backup and surge protected outlets
When the Back-UPS is receiving input power, the Battery Backup with Surge Protection
outlets will supply power to connected equipment. During a power outage or other AC
problems, the Battery Backup outlets receive power for a limited time from the BackUPS.
Connect equipment such as printers, fax machines, scanners, or other peripherals that do
not need battery backup power to the Surge Protection Only outlets. These outlets
provide full-time protection from surges even if the Back-UPS is switched OFF.
BR650MI / BR900MIBR1300MI /BR1600MI
Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI
3
Page 4
USB and Serial
Data port
Telephone Cable
Surge Protected
ports
AC Power Input Use the supplied power cable to connect the unit to AC power.
Battery Backup
outlets with Surge
Protection
Circuit Breaker Use to reset the system after an overload condition has occurred causing
In/OutEthernet
surge-protected
ports
Surge Protected
outlets
To use PowerChute Personal Edition, connect the supplied USB cable or
an optional serial cable (not supplied).
Connect a telephone cable to the IN port, and connect a modem to the
OUT port.
During a power outage or other AC problems, the Battery Backup outlets
receive power for a limited time from the Back-UPS. Connect critical
equipment such as desktop computer, computer monitor, modem or other
data sensitive devices into these outlets.
the circuit breaker to trip.
Use an Ethernet cable to connect a cable modem to the IN port, and
connect a computer to the O
These outlets provide full-time protection from surges, even if the BackUPS is off. Connect equipment such as printers and scanners that do not
require battery backup protection.
UT port.
Operation
Power saving display
The display interface can be configured to be continuously illuminated, or to save
energy, it can be configured to darken after a period of inactivity.
1. Full Time Mode: Press and hold DISPLAY for two seconds. The display will
illuminate and the Back-UPS will beep to confirm the Full Time mode.
2. Power Saving Mode: Press and hold DISPLAY for two seconds. The display will
darken and the Back-UPS will beep to confirm the Power Saving mode. While in
Power Saving Mode, the display will illuminate if a button is pressed, it then
darkens after 60 seconds of no activity.
Unit sensitivity
Adjust the sensitivity of the Back-UPS to control when it will switch to battery power;
the higher the sensitivity, the more often the Back-UPS will switch to battery power.
1. Ensure the Back-UPS is connected to AC power, but is OFF.
2. Press and hold the POWER button for six seconds. The LOAD CAPACITY bar will
flash on and off, indicating that the Back-UPS is in programming mode.
3. Press POWER again to rotate through the menu options. Stop at selected
sensitivity. The Back-UPS will beep to confirm the selection.
Generator SensitivityDefaultSensitive Loads
Low sensitivityMedium sensitivity
High sensitivity
(Default)
156-300 Vac176-294 Vac176-288 Vac
Input voltage is extremely
low or high. (Not
recommended for
The Back-UPS frequently
switches to battery power.
The connected equipment
is sensitive to voltage
fluctuations.
computer loads.)
Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI4
Page 5
Front panel buttons and display interface
bu109g
Use the three buttons on the front panel of the Back-UPS and the display interface to
configure the Back-UPS.
Front panel
Mute button
Power On/Off
button
Display button
Display interface
On Line: The Back-UPS is supplying conditioned AC power to connected
equipment
Load Capacity: The load is indicated by the number of sections illuminated,
one to five. Each bar represents 20% of the load.
Battery Charge: The battery charge level is indicated by the number of
sections illuminated. When all five blocks are illuminated, the Back-UPS is at
full charge. When one block is filled, the Back-UPS is near the end of its battery
capacity, the indicator will flash and the Back-UPS will beep continuously.
Overload: The power demand from the load has exceeded the capacity of the
Back-UPS.
Event: The event counter shows the number of events that occurred that caused
the Back-UPS to switch to on-battery operation.
Automatic Voltage Regulation:
When illuminated, the Back-UPS is compensating for low input
voltage
When illuminated, the Back-UPS is compensating for high input
voltage.
In: Input voltage.
Out: Output voltage.
System Error Detected: The system has an error. The error number will
illuminate on the display interface. See “System errors” on page 7.
Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI
5
Page 6
Mute: If the line through the speaker icon is illuminated, the audible alarm has
been turned off.
Replace Battery: The battery is nearing the end of its useful life. Replace the
battery as early as possible.
On Battery: The Back-UPS is supplying battery backup power to the
connected equipment, it will beep four times every 30 seconds.
Alarms and System Errors
Audible indicators
Four Beeps Every 30 Seconds
Continuous Beeping
Continuous toneBattery Backup outputs are overloaded.
Chirps every 2 Seconds with the Load
Capacity Bar flashing
Continuous chirping with the Load
Capacity Bar and Replace Battery icon
alternately flashing
Status icons
If these icons are
illuminated...This may be the problem.
The Back-UPS is operating on AC power, but is overloaded. Disconnect one
of the items connected to the Back-UPS. If the Overload icon stops flashing,
the Back-UPS is no longer overloaded and will continue to operate
normally.
The Back-UPS is operating on battery power, but is overloaded. Disconnect
one of the items connected to the Back-UPS. If the Overload icon stops
flashing, the Back-UPS is no longer overloaded and will continue to operate
normally.
The Back-UPS is operating on AC power, but the battery is not functioning
properly. Contact Schneider Electric IT (SEIT) Customer Service to order a
replacement battery. See “Battery Replacement” on page 11.
Back-UPS is running on battery. You should consider saving
any work in progress.
Low battery condition and battery run-time is very low.
Promptly save any work in progress, exit all open
applications, and shut down the operating system.
Battery is disconnected.
Battery did not pass the automatic diagnostic test and should
be replaced as early as possible. Pressing the
pauses the chirping.
MUTE button
The Back-UPS is operating on battery power and the battery power is
getting low. Shut down all connected equipment to avoid losing an unsaved
data. When possible, connect the Back-UPS to AC power to recharge the
battery.
Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI6
Page 7
System errors
bu088a
The Back-UPS will display these error messages. Except for errors F01 and F02, contact
SEIT Technical Support.
Turn the Back-UPS off.
On-Battery Overload
F01
On-Battery Output
F02
Short
On-Battery Xcap
F03
Overload
Clamp Short
F04
Charge Error
F05
Relay Welding
F06
Temperature
F07
Fan Error (for
F08
BR1600MI only)
Internal Error
F09
Disconnect non-essential
equipment from the Battery
Backup outlets and the turn
Back-UPS on.
Turn the Back-UPS off.
Disconnect all equipment from
the Battery Backup outlets and
the turn Back-UPS on.
Re-connect equipment one item
at a time. If the output is tripped
again, disconnect the device that
caused the error.
Errors F03-F09 cannot be
corrected by the user, contact
SEIT Technical Support for
assistance.
Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI
7
Page 8
Function Button Quick Reference
FunctionButton
Power
Power On0.2Off
Power Off2On
Display
Status
Inquiry
Full-Time/
PowerSaving
mode
Mute
General
Status
Enable/
Disable
Sensitivity6Off
Self-Test
(manual)
Event
Reset
Error
Reset
Timing
(seconds)
0.2On
2On
2On
6On
0.2On
2Error
UPS
StatusDescription
Press P
input power is not available, the Back-UPS will run on
battery power.
The Back-UPS is not receiving input AC power, but is
providing surge protection.
Verify the status or condition of the Back-UPS. The
LCD will illuminate for 60 seconds. Press the button
the toggle into various information.
The LCD will illuminate and the Back-UPS will beep
to confirm the Full-Time mode. The LCD will darken
and the Back-UPS will beep to confirm the PowerSaving mode. While in Power-Saving Mode, the LCD
will illuminate if a button is pressed, then darkens after
60 seconds of no activity.
Enable or disable the audible alarms. The Mute icon
will illuminate and the Back-UPS will beep one time.
The Mute function will not activate unless the BackUPS is operating on battery power.
The Load Capacity icon will blink, indicating that the
Back-UPS is in programming mode. Use the P
button to scroll through Low, Medium, and High, stop
at selected sensitivity. The Back-UPS will beep to
confirm selection. See "Unit sensitivity" for details.
The Back-UPS will perform a test of the internal
battery. Note: This will happen automatically when the
Back-UPS is turned ON or when the Back-UPS
previously detected a bad battery.
When the Event screen is visible, press and hold
D
ISPLAY, then press POWER, to clear the detected error
event counter.
After an error has been identified, press P
remove the visual indication and return to standby
status.
OWER to start receiving input AC power. If AC
OWER
OWER to
Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI8
Page 9
Troubleshooting
ProblemPossible CauseCorrective Action
Back-UPS will not
switch on.
The Back-UPS
does not provide
power during a AC
power outage.
The Back-UPS is
operating on
battery power,
while connected to
AC power.
The Back-UPS
does not provide
the expected
amount of backup
time.
EPLACE
The R
BATTERY indicator
is illuminated.
The O
VERLOAD
indicator is
illuminated.
YSTEM ERROR
The S
indicator is
illuminated, all the
front panel
indicators are
flashing.
The Back-UPS is not connected to
AC power.
The circuit breaker has been
tripped.
The internal battery is not
connected.
The AC input voltage is out of
range.
Ensure that essential equipment is
not plugged into a S
URGE ONLY
outlet.
The plug has partially pulled out of
the wall outlet, the wall outlet is no
longer receiving AC power, or the
circuit breaker has been tripped.
The Back-UPS is performing an
automatic self test.
The AC input voltage is out of
range, the frequency is out of
range, or the waveform is distorted.
Battery Backup outlets may be
fully or improperly loaded.
The battery was recently
discharged due to a power outage
and has not fully recharged.
The battery has reached the end of
its useful life.
The battery has reached the end of
its useful life.
The equipment connected to the
Back-UPS is drawing more power
than the Back-UPS can provide.
There is an internal error.Determine which internal error
Ensure that the Back-UPS is securely
connected to an AC outlet.
Disconnect non-essential equipment
from the Back-UPS. Reset the circuit
breaker. Re-connect equipment one
item at a time. If the circuit breaker is
tripped again, disconnect the device
that caused the trip.
Connect the battery.
Adjust the transfer voltage and
sensitivity range.
Disconnect equipment from the
SURGE ONLY outlet and re-connect to
a Battery Backup outlet.
Ensure that the plug is fully inserted
into the wall outlet. Ensure that the
wall outlet is receiving AC power by
checking it with another device.
No action is necessary.
Adjust the transfer voltage and
sensitivity range.
Disconnect non-essential equipment
from the Battery Backup outlets and
connect the equipment to S
outlets.
Charge the battery cartridge for 16
hours.
Replace the battery.
Replace the battery as early as
possible.
Disconnect non-essential equipment
from the Battery Backup outlets and
connect the equipment to S
outlets.
message is displayed by matching
the number displayed on the LCD
with the corresponding Error
Message (see "System errors") and
contact SEIT Technical Support.
URGE
URGE
Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI
9
Page 10
Specifications
ModelBR650MIBR900MIBR1300MIBR1600MI
VA650 VA900 VA1300 VA1600 VA
Maximum Load390 W540 W780 W960 W
Nominal Input Voltage220 - 240 Vac
Online Input Voltage
Range
Automatic Voltage
Regulation
Frequency Range50/60 Hz ± 3 Hz
Battery TypeLead acid, 12V with 1 batteryLead acid, 12V with 2 batteries
On-battery WaveshapeStep-approximated sine-wave
Typical Recharge Time12 hours16 hours
Tra n s f e r Time8 ms (typical), 10 ms (maximum)
On Battery RuntimeGo to: www.apc.com
InterfaceUSB
Operating Temperature0 to 40C (32 to 104F)
Storage Temperature-5 to 45C (23 to 113F)
IP RatingIP20
Unit Dimensions
Unit Weight
Boost by +11.5% when input voltage drops below limit
Trim by -11.5% when input voltage exceeds limit
19 x 9.1 x 31 cm
(7.5 x 3.6 x 12.2 in)
6.8 kg
(15 lbs)
176 - 294 Vac
7.2 kg
(15.9 lbs)
25 x 10 x 38.2 cm
(9.8 x 3.9 x 15 in)
10.2 kg
(22.5 lbs)
11.0 kg
(24.3 lbs)
Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI10
Page 11
Battery Replacement
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
• Replace the battery at least every 5 years.
• Replace the battery immediately when the UPS indicates battery replacement is necessary.
• Replace battery at the end of its service life.
• Replace batteries with the same number and type of batteries as originally installed in the
equipment.
• Replace the battery immediately when the UPS indicates a battery over−temperature
condition, or UPS internal over−temperature, or when there is evidence of electrolyte leakage.
Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate
the UPS until the batteries have been replaced.
Failure to follow these instructions can result in minor or moderate injury and
equipment damage.
The battery typically lasts for 3 to 5 years, a shorter period if subjected to frequent
outages or elevated temperatures. Battery replacement parts for Back-UPS BR650MI is
APCRBC110, for BR900MI is APCRBC164, for BR1300MI is APCRBC165, and for
BR1600MI is APCRBC166. Delaying the replacement of parts may corrode the
batteries in the cartridge. Recycle spent battery cartridges.
Warranty
The standard warranty is three (3) years from the date of purchase, valid in European
Community. For all other regions, the standard warranty is two (2) years from the date of
purchase. Schneider Electric IT (SEIT) standard procedure is to replace the original unit
with a factory reconditioned unit. Customers who must have the original unit back due to
the assignment of asset tags and set depreciation schedules must declare such a need at
first contact with an SEIT Technical Support representative. SEIT will ship the
replacement unit once the defective unit has been received by the repair department, or
cross-ship upon the receipt of a valid credit card number. The customer pays for shipping
the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement
unit to the customer.
Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI
11
Page 12
APC by Schneider Electric IT Customer Support
Worldwide
For country specific customer support, go to the APC by Schneider Electric Web site,
www.apc.com.