Introduction
The APC Smart-UPS RT is a high-performance, uninterruptible power system (UPS), designed to
prevent blackouts, brownouts, sags and surges from reaching your computers, servers, and other
sensitive electronic equipment.
1: INSTALLATION
Attention: Read the safety information sheet before installation.
Unpacking
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents:
UPS (with batteries disconnected)
Two front bezels
Literature kit containing:
Software
Smart-UPS User Manuals CD
XLI model only: Six output power cords
Serial cable
Product documentation, safety and warranty information
SNMP/Web Card User Manual
Removing the Batteries
The unit is heavy. To lighten the unit, remove the batteries. Refer to the unpacking instructions on
the carton in which the unit is shipped.
Placement
Attention: The UPS is heavy. Select a location sturdy enough to handle the weight.
Do not operate the UPS in excessive dust or in temperature and humidity outside the specified limits.
Ensure the air vents on the front and rear of the UPS are not blocked.
Refer to the APC web site, www.apc.com
1
for details.
Hardwiring
Attention: Wiring must be performed by a qualified electrician.
1. Install a utility circuit breaker in accordance with local electrical codes (see tables below) for
input wiring only.
2. Switch the UPS input circuit breaker (see A) and utility circuit breakers OFF.
3. Remove the access panel (see B).
4. Remove circular knockouts.
5. Run wires through access panel to terminal blocks. Wire to ground block first. Adhere to all
national and local electrical codes. (See tables and graphics.)
6. Use appropriate glands to achieve strain-relief on the hardwired input and output power cables.
XLT, XLJ, AND XLTW MODELS
Input Connection Output Connection (optional)
Wire to L1, L2, and .
System Wiring Voltage Current
SURT7500XLJ,
SURT7500XLT,
SURT7500XLTW
SURT10000XLJ,
SURT10000XLT,
SURT10000XLTW
Input & Output 200/208/220V 40 amps
Input & Output 200/208/220V 54 amps
Wire to L1A, L2A, and
Full Load
(Nominal)
XLTW- 38 amps
XLTW-50 amps
XLI MODELS
Input Connections Output Connection (optional)
Single-Phase: Wire to L1, N, and .
Three-Phase: Wire to L1, L2, L3, N, and
System Wiring Number
SURT7500XLI
SURT10000XLI
Input 1 220/230/240V 38 amps 50 amps / 2-pole 10mm2
Input 3+
Output 1 220/230/240V 38 amps (not required) 10mm
Input 1 220/230/240V 50 amps 63 amps / 2-pole 16mm2
Input 3+
Output 1 220/230/240V 50 amps (not required) 16mm
of
Phases
Neutral
Neutral
.
Voltage Current
380/400/415V 14 amps / phase when
380/400/415V 18 amps / phase when
Wire to L1A, N1, and
Full Load
(Nominal)
online, 38 amps on L1
in bypass
online, 50 amps on L1
in bypass
.
External Input
Circuit Breaker
(typical)
50 amps / 2-pole for
Input Wiring Only
70 amps / 2-pole for
Input Wiring only
.
External Input
Circuit Breaker
(typical)
50 amps / 4-pole 10mm2
63 amps / 4-pole 16mm2
Wire Size
(typical)
#8AWG/
2
10mm
#6AWG/
2
16mm
Wire Size
(typical)
2
2
2
7. XLI model only: For three-phase input, set the Input Phase Selector switch (see C) to ‘3’. For
single-phase input, leave switch in default position of ‘1’.
XLT/XLJ/XLTW MODELS
OUTPUT
L1A
L2A
INPUT
L1
L2
B
XLI MODEL
UTPUT
O
L1A
N1
INPUT
L1
L2
L3
N
C
B
8. Switch the circuit breakers ON.
9. Check line voltages.
10. Replace the access panel.
3
Installing and Connecting the Batteries and Attaching the Front Bezel
4
C
ONNECTING POWER AND EQUIPMENT TO THE UPS
1. Hardwire the UPS (see Hardwiring).
2. Connect equipment to the UPS (cables not included for XLT/XLJ/XLTW models).
3. Turn on all connected equipment. To use the UPS as a master on/off switch, be sure that all
connected equipment is switched ON.
4. Press the
• The battery charges to 90% capacity during the first three hours of normal operation. Do not
button on the front panel to power up the UPS.
expect full battery run capability during this initial charge period.
5. Configure the Web/SNMP management card (optional).
PTIONS
O
Refer to the APC web site, www.apc.com
External Battery Pack SURT192XLBP
Rail Kit SURTRK2
Isolation Transformer
Service Bypass Panel
IRCUIT BREAKERS
C
Input Circuit Breaker
7500/10000 VA
The UPS is protected from extreme overloads when in ON position.
The breaker must be on for the UPS to operate.
for available accessories.
XLI/XLJ/XLT/XLTW
Output Circuit Breaker
7500/10000 VA
XLJ/XLT/XLTW
L6-20
250V 20A
L6-30
250V 30A
Output Circuit Breaker
7500/10000 VA XLI
IEC 320-C13
10A for each
receptacle
IEC 320-C19
16A for each
receptacle
5