American Power Conversion 480kW400V User Manual

APC Silcon
480kW 400V UPS Installation Guide
Copyright 2001 APC Japan Inc
This manual is subject to change without
on the part of the vendor
Thank You!
Thank you for chosing the APC Silcon Series UPS. Please read this Installation Guide thoroughly prior to installing the system. It provides important information on safe and efficient installation.
The installation and use of this product must comply with national, federal, state, municipal and local codes.
Safety Symbols used in this manual
WARNING! Indicates a hazard which, if not avoided, could result in injury or death.
CAUTION! Indicates a hazard which, if not avoided, could result in damage to the
product or other property.
NOTICE!
WARNING!
This UPS unit contains hazardous AC and DC voltages. Only qualified electricians should install the UPS, AC line and external batteries, and must be familiar with batteries and battery installation. Before installing, maintaining or servicing the UPS, shut off the UPS and disconnect all sources of AC and DC power. As the UPS has no built-in disconnection devices to switch off external AC and DC input power, ensure that disconnection devices are provided as separate parts in connection with the installation! The installer must provide each external disconnecting device for this UPS system with labels with the following text: “Isolate the Uninterruptible Power Supply (UPS) as instructed in this guide before working on circuit”
AC and/or DC voltage will always involve a potential risk of AC voltage at UPS output generated from either batteries or utility. To avoid equipment damage or personal injury, always assume that there may be voltage at UPS output. This system is equipped with an auto-start function. If activated, the system may start without warning. Refer to the “Programming” section of this guide for information on de-activation.
TEST BEFORE YOU TOUCH!
To reduce the risk of fire or electric shocks, install the UPS and external batteries in a temperature and humidity controlled indoor area, free of conductive contaminants. UPS batteries are high-current sources. Shorting battery terminals or DC terminals, DC busbars can cause severe arcing, equipment damage and injury. A short circuit can cause a battery to explode. Always wear protective clothing and eye protection and use insulated tools when working on batteries.
Read and pay attention to this important information.
CAUTION!
This unit contains components sensitive to electrostatic discharge (ESD). If you do not follow the ESD procedures, you may cause severe damage to electronic components.
990-4059
2 Installation Guide APC Silcon 480kW 400V UPS
Introduction
1.0 Introduction
Power regulation varies from area to area, and information given in this installation guide can therefore only be of a general nature. Electricians should therefore always refer to national and local electrical codes prior to installing the UPS system.
1.1 Tools and Equipment
CAUTION!
Heavy equipment. To prevent personal injury or equipment damage, take extreme care when handling and transporting UPS cabinet and equipment.
CAUTION!
Ensure that front doors are in place and that internal front cover is fastened by screws before attempting to lift or transport the system.
This section lists all tools and equipment required to install all UPS configurations. See also section 4.0 of this guide for further details on connection.
Tools:
• 10mm socket
• 13mm socket-deep
• 17mm socket
• 19mm socket-deep
• 19mm combo wrench
• Small flat head/regular screwdriver
• #3 philips screwdriver
• Compression lug crimping tool
• Knock-out set (for glands)
Equipment:
• Compression lugs for cable terminations
• Cable to Service Bypass Panel from system feeder
• Cable to UPS input from Service Bypass Panel
• Cable to Service Bypass Panel from UPS output
• Cable from Service Bypass Panel to customer distribution
• Cable to UPS input from external batteries/external Battery Breaker Box (systems with external battery)
• Solid core, control cable to UPS from Service Bypass Panel
• Solid core, control cable to UPS from external batteries/external Battery Breaker Box
990-4059
Installation Guide APC Silcon 480kW 400V UPS 3
Unpacking
2.0 Unpacking
NOTICE!
Unless otherwise specified by the shipping company use a fork lift to unload equipment from pallet
1. To unpack UPS unit, remove top and bottom screws from side plates of packaging and lift up side plates
2. Verify compliance between type label on reverse side of front door and system ordered. Check input and output voltage
3. Copy type label data to label copy below for easy identification of system
4. Use fork lift to transport system to installation site
SKU SKU
Copy of type label
PLEASE RECYCLE
The shipping materials for the APC Silcon UPS are recyclable. Please save them for later use or dispose of them appropriately.
990-4059
4 Installation Guide APC Silcon 480kW 400V UPS
480kW
1900 mm wide
1800 mm
APC Isolation
Transformer Module
420kW
1600 mm wide
1800 mm
?
Installation
3.0 Installation
3.1 Requirements on Site
All system parts are accessible from front or top of UPS. Cable entries are accessible from bottom. A 1-metre free space on all sides should be allowed during installation. After installation of the UPS, leave a free space of 600 mm to the right for system access. (As per applicable national and/or local codes.)
For ventilation and service purposes allow for free space of minimum 1m above the unit or per national and/or local codes and in front of UPS. Never install systems in direct sunlight.
NOTICE!
For reliability reasons do not stand on the UPS. Keep the UPS cabinet surface free of any objects.
3.1.1 Cabinet Dimensions
UPS Height [mm] Width [mm] Depth [mm]
480kW 1800 1900 800
Cabinet
Installation Guide APC Silcon 480kW 400V UPS 5
990-4059
Installation
Rear
Front
Com. cable entry
Power cable entry
Rear
Power cable entry
Front
?
3.2 Footprint
3.2.1 1900mm Cabinet for 480kW UPS
3.2.2 1600mm Cabinet for 480kW Isolation Transformer
990-4059
6 Installation Guide APC Silcon 480kW 400V UPS
2 1
2 1
X005 X001
X004:- X003:+
X004:+ X003:-
Right side view
Relay board Please refer
Battery
Front view
System Integration Interface
Communication Interface
Parallel Controller
to “Relay Board” section
4.0 External Connection
4.1 Connecting the UPS
External Connection
NOTICE!
Check correct phase rotation of mains input voltage!! Max. input/output cables: 3//300 mm If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required.
CAUTION!
This UPS unit is an EN 50091-2 product and may cause radio interference in a domestic environment. Take preventive measures in necessary.
Installation Guide APC Silcon 480kW 400V UPS 7
CAUTION!
At a switch mode load of 100% the neutral must be rated for 200% output phase current.
2
.
990-4059
External Connection
UPS External
Input
Fuses* FM
[A]
380-415V
480kW 1000 3//200 200 800 3//150
* DIN gL types
NOTICE!
All cable dimensions are recommended sizes only. Refer to local legal regulations.
UPS External Alarm
Cable max.
[mm2]
480kW 2 30 800 3//150
PVC cables insulated to withstand ambient temperature of max. 30°C ** Must be rated as external PE cable if mains system is not supplying PE
NOTICE!
Install gland plate in bottom of unit.
External
Input Cable
[mm2]
380-415V
External System
External PE
Cable
[mm2]
Earth Cable
[mm2]**
Maximum
External
Output Fuses*
[A]
External Battery
Breaker
[A]
Output Cable
External Battery
Cable [mm2]
External
[mm2]
990-4059
4.2 System Integration Interface
8 Installation Guide APC Silcon 480kW 400V UPS
External Connection
NOTICE!
Consistent use of designations (Q001, Q002, Q003, H002, H003) in diagrams simplifies information exchange.
System Integration Interface (SII) is the control link between UPS and system main switches as shown in above diagram. The purpose of the SII is to ensure correct operation of switches without losing system output power.
Auxiliary contacts on the main switches transmit the SII board inputs. Lamps on Service Bypass Panel and Battery Breaker Box/Battery Cabinet indicate “green light” for operation of output switches.
SII board also integrates input facilities for emergency shut-down and temperature compensation of charge voltage for external battery (use with battery monitor). “Battery operation” and “Common fault” are two main SII board status relay signals.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 9
External Connection
Blue Brown
4.2.1 Connections
990-4059
10 Installation Guide APC Silcon 480kW 400V UPS
External Connection
Terminal Blocks: X003/X004 (Anxiliary Contacts)
When switching Q001, Q002, Battery Breaker 1 or Battery Breaker 2 from “ON or 1” to “OFF or 0”, the anxiliary contact has to be open BEFORE the corresponding main contacts are opened. When switching Q001, Q002, Battery Breaker 1 or Battery Breaker 2 the opposite way from “OFF or 0” to “ON or 1”, the anxiliary contact has to close with a maximum delay of 0.5 seconds from the time the corresponding main contacts are closed.
• This type of auxillary contact is called a “late make” contact. (This also means that it will
“break early” when activated in opposite direction.)
• This auxillary contact is also called “NORMALLY OPEN” (NO), because the auxillary
contact will be open when the main contacts are open.
• Please note that the above term “NORMALLY” has nothing to do with NORMAL UPS
OPERATION MODE.
When switching Q003 from “OFF or 0” to “ON or 1”, the anxiliary contact has to open BEFORE the corresponding main contacts are closed. When switching Q003 the opposite way from “ON or 1” to “OFF or 0”, the auxillary contact has to close with a maximum delay of 0.5 seconds from the time when the corresponding main contacts are opened.
• This type of anxiliary contact is called an “early break” contact. (This also means that it will
“make late” when activated in the opposite direction.)
• The auxiliary contact is also called “NORMALLY CLOSED” (NC), because the auxiliary
contact will be closed when the main contacts are open.
• Please note that the above term “NORMALLY” has nothing to do with NORMAL UPS
OPERATION.
X005 (Output Relays)
Battery operation signals are received with a 30-second delay. This function is inactive during battery test. Common fault relay facility is programmable (standard factory setting: 10 sec.) See APC Silcon User Guide for details. Maximum nominal voltage on contact circuits is 277VAC. If two different phases are involved, maximum phase to neutral voltage should be below 160VAC. Please note that phase L1 is already present on the System Integration Interface board, supplied from the Service Bypass Panel. Therefore, if a phase is needed for alarm or signal purposes, Phase L1 should be used.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 11
External Connection
Parallel Board
4.3 Parallel Board
CAUTION!
Control cables must be separated from AC and DC power cables.
The built-in parallel board connects two or more UPS systems in parallel, either to obtain increased system reliability or to obtain higher output power. The parallel board also ensures correct load-sharing between paralled systems.
NOTICE!
For reliability reasons, APC recommends separate battery packs in redundant/parallel conigurations.
To prepare the UPS for parallel/redundant mode, disconnect all sources of AC and DC power supply to the UPS and connect the ribbon cable from the parallel board to the main controller board (the ribbon cable is delivered with the UPS).
CAUTION! DO NOT connect ribbon cable between controller and parallel card in single configurations.
Ribbon cable is for parallel operation only.
Complete the parallel system set-up by connecting the external control cables (see below). Follow the instructions in the “Programming Parameters for Advanced Parallel” section of this guide to execute necessary re-programming.
990-4059
12 Installation Guide APC Silcon 480kW 400V UPS
to other parallel units
UPS 1
UPS 2
UPS 3
X020:15-pin SUB-D female
X021:15-pin SUB-D female
Parallel Board
External multicore cable with 14 wires + shield
External Connection
External Control Cables
External multicore cable is equipped with 15-pin SUB-D plug at either end. Connect pin 1 to pin 1, and pin 2 to pin 2 etc. up to pin 15 - with the exception of pin 8, which is not to be connected. Shield is connected to plug cover at both ends. Terminals X020 and X021 for control cables located on parallel board. Connect X020 in UPS1 to X021 in UPS2, and connect X020 in UPS2 to X021 in UPS3 etc. Connect X020 in last UPS to X021 in UPS1.
Cable is delivered with the UPS.
Power Cables
To optimize load-sharing in parallel operation, external power circuits must be “symmetrical”: Power input and output cables to have same length and identical cross-sections.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 13
External Connection
Maximum load: 8.0A – 250VAC
Minimum load: 0.05A – 6VAC
1
2
3
0.3A – 60VDC
0.05A – 6VDC
4.4 Relay Board
Relays
All relays are “fail safe”: In alarm modes, relay coil will be de-energized.
990-4059
14 Installation Guide APC Silcon 480kW 400V UPS
External Connection
4.4.1 Relay Board/Relay Functions
NOTICE
If alarm mode Communication to controller lost is active, ALL relays will indicate failure
Relay Number Message Alarm-trigging Events
1 ## (X002) Mains outside limits Mains voltage RMS outside limits
2 ## (X003) Bypass outside limits Bypass voltage RMS outside limits
3 ## (X004) Output outside limits Output voltage RMS value outside limits
4 (X005) System overload Output load exceeding 100%
5 (X006) Fan fault Blocked or faulty fan
6 (X007) High Equipment
Temperature or
Inverter Fuse Blown
7 (X008) MCCB battery off Battery MCCB/Fuse not closed or released
8 (X009) Normal operation UPS running in normal operation mode
9 ## (X010) Battery operation UPS running in battery operation mode
10 ## (X011) Bypass operation UPS running in bypass operation mode
11 ## (X012) Stand-by operation UPS in stand-by mode
12 (X013) Service bypass
operation
13 ## (X014) Boost charge
operation
14 (X015) Battery voltage
outside limits
15 (X016) Battery condition
fault
16 ## (X017) Common fault All alarms as mentioned above
Mains wave form (fast detector) outside limits
Mains frequency outside limits
Bypass wave form (fast detector) outside limits
Bypass frequency outside limits
Output wave form (fast detector) outside limits
Output frequency outside limits
Delta inverter current limiter active Main inverter current limiter active
Static switch temperature too high
Main inverter failure (temperature too high or fuse blown)
Delta inverter temperature too high
Magnetic temperature too high
Isolation transformer (option) temperature too high
Battery temperature too high
(status)
(status)
(status)
(Hot stand-by - parallel systems only)
Service bypass switch active
UPS boost-charging on battery
DC voltage too high (shut down)
DC voltage below warning level DC voltage too low (shut down)
ABM has detected weak battery condition
ABM has detected defect battery
(ABM = Advanced Battery Monitor)
(except relays 8+9+10+11)
Internal power supply fault
System locked in operation mode
Internal memory fault
Internal communication fault
## Delay programmable in configuration stack : Common fault delay. Settings 0,10,20,30 seconds.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 15
External Connection
See section 5.2: System configuration
NOTICE!
Alarm Trigging Events 1-2-3-9-10-11-13 activates the corresponding alarm relay after the delay.
Alarm Trigging Events 4-5-6-7-8-12-14-15 activates the corresponding alarm relay momentarily.
Common fault relay 16 is activated at the same time as relay 1-2-3-4-5-6-7-12-13-14-15, or in any of the below situations.:
Internal power supply fault
System locked in operation mode
Internal memory fault
Internal communication fault
990-4059
16 Installation Guide APC Silcon 480kW 400V UPS
.
.
External Connection
4.5 Communication Interface Board
The 3-port ComInterface is used to establish an interaction between UPS and e.g. a computer system. Main purpose: To ensure a controlled computer shut-down in case of a mains supply failure.
4.5.1 Connections
990-4059
Installation Guide APC Silcon 480kW 400V UPS 17
External Connection
Part of UPS Cabinet
X50 is a 24V supply for Triple Chassis.
Only to be used for this purpose.
Not suitable for telephone equipment.
Triple Chassis must be connected to both
X50 and a serial port.
Serial ports
X50
X008X007
APC Silcon Triple Chassis
4.6 Connecting of APC Silcon Tripel Chassis
The enclosed Triple Chassis must be connected to the serial port on the Communication Interface Board, and to the 24V supply (cables included). Terminal locations shown below.
For more information please refer to the following section.
990-4059
18 Installation Guide APC Silcon 480kW 400V UPS
External Connection
4.7 APC Silcon Triple Chassis
The APC Silcon Triple Chassis (AP9604S) is an American Power Conversion (APC) external management peripheral that allows you to use monitoring and control management peripherals with your APC Silcon series UPS. The retrofit model (AP9604SR) is for use with Silcon series UPSs that are not equipped with a 24 VDC power port.
4.7.1 Safety Warnings
Use the APC Silcon Triple Chassis only in conjunction with an APC Silcon UPS.
Do not connect a computer to any APC Silcon Triple Chassis port using a straight-through extension cable. Use the communications cable provided with the APC Silcon Triple Chassis.
Connections using a cable made by any other manufacturer may cause damage or improper operation of the APC Silcon Triple Chassis, the UPS, or the computer.
4.7.2 Product Description
u
x
v
w
Monitoring port
1
To UPS port
2
4.7.2.1 Monitoring Port
The Monitoring port has two functions:
• Connecting to a terminal for configuration of the chassis. For direct connection to the Monitoring port, you must use the Monitoring cable supplied with the chassis (APC P/N 940-0024C).
• Connecting to other APC external management peripherals in a daisy chain.
Status LED
3
Optional Power port
4
4.7.2.2 To UPS Port
The “To UPS” port connects the chassis to the UPS, using the Silcon UPS cable (APC P/N 940-
0071). The cable connector plugs into a communications port on an APC Silcon UPS.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 19
External Connection
4.7.2.3 LEDs
The APC Silcon Triple Chassis status LED provides important information concerning operation of the chassis. Refer to the table below for a description of the conditions indicated by the LED.
IF the LED is… THEN the Silcon Triple Chassis…
off is not receiving power.
flashing quickly (5 times per second)
has not been configured. See the APC Silcon Management Quick Start Guide provided with your chassis or the Web/SNMP Management Card Installation Guide on the CD for more information.
flashing slowly (1 time per second)
on is operating normally.
4.7.2.4 Optional Power Input
With the Optional Power input, you can power the APC Silcon Triple Chassis from an external source, using a 24 VDC power adapter. A universal adapter (AP9505i) or a standard adapter (AP9505) can be purchased separately from APC.
4.7.3 Installing Management Peripherals
There are two basic types of APC management peripherals that work with the APC Silcon Triple Chassis:
• Management peripheral cards, which fit into external management peripherals that are equipped with a card slot.
• External management peripherals, which connect to the Monitoring (or Advanced) port of other external management peripherals.
NOTICE!
The name “Monitoring” port varies from product to product, but its purpose is the same – to replicate the UPS communications port.
is powered on but is not communicating with the UPS.
990-4059
20 Installation Guide APC Silcon 480kW 400V UPS
External Connection
4.7.3.1 Order of Management Peripheral Cards
Because UPS signals are passed between management peripherals, you must install management peripheral cards in the correct order for them to work together properly. The card slots are numbered 1 to 3, from left to right, as viewed from the rear of the chassis. The following table lists the management peripheral cards, their priority, and proper position.
Management Peripheral Card
Web/
SNMP Management
Card
Out-of-Band Management Card (Call-
UPS®II)
Interface Expander AP9607 Second lowest
Environmental Monitoring Card (Measure-
4.7.3.2 Installing Management Peripheral Cards
To install management peripherals, perform the following steps.
1) Make sure that the chassis is powered off.
2) Install management peripheral cards into the housings on the rear of the chassis. See the instructions supplied with the cards and the table above.
3) If you are daisy-chaining other APC external management peripherals to the APC Silcon Triple Chassis: Connect the UPS cable (supplied with the management peripheral) to the Monitoring port of the chassis and to the “To UPS” port of the other management peripheral (Share-UPS, MasterSwitch, etc.). See “Daisy-chaining the APC Silcon Triple Chassis”.
4) Power the APC Silcon Triple Chassis and all external management peripherals.
UPS
P/N Priority Position
AP9606 Highest
AP9608 Second-highest
®
II)
AP9612T AP9612TH
Lowest
High-numbered slot
Low-numbered slot
NOTICE!
If your configuration requires additional power, connect a 24V AC/DC power adapter available from APC (part number AP9505 or AP9505i) for all models of Triple Chassis.
4.7.3.3 Daisy-chaining the APC Silcon Triple Chassis
If you need more than the three card slots available with the APC Silcon Triple Chassis, or if you want to use other external management peripherals, you can daisy-chain external management peripherals together, provided that the total amperage of all installed management peripherals — cards and external — does not exceed the supplied amperage. (See “Determining Power Requirements:”).
NOTICE!
When daisy-chaining Triple Chassis units, you may need to use a power adapter.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 21
External Connection
To add card slots, you can daisy-chain the APC Silcon Triple Chassis with the standard Triple Chassis (AP9604) management peripheral, installing the APC Silcon Triple Chassis closer to the UPS.
4.7.4 Powering the APC Silcon Triple Chassis
The APC Silcon Triple Chassis supplies power to the installed management peripheral cards and to the Monitoring port, allowing you to power multiple management peripherals.
4.7.4.1 AP9604S Power Considerations
The AP9604S model of the APC Silcon Triple Chassis receives its power from the UPS through the power connector of the Silcon UPS cable. If the total current required by all the installed management peripherals exceeds 500 mA, you must use a 24 VDC power adapter. To find out whether you need additional power, see “Determining power requirements”.
4.7.4.2 Power Adapters
APC offers two models of 24 VDC power adapter.
• The standard adapter (AP9505) can provide an additional 400 mA.
• The universal adapter (AP9505i) can provide 850 mA.
4.7.4.3 Using a Power Adapter
To use the adapter, plug it into a protected power outlet and into the Optional Power port of the APC Silcon Triple Chassis.
NOTICE!
If the power adapter loses power because of a UPS shutdown, its attached management peripherals may not operate properly, thus adversely affecting the UPS and its protected equipment.
4.7.4.4 AP9604SR Power Considerations
The AP9604SR model receives its power from the UPS through the supplied 24 VDC universal adapter. The total current required by your management peripherals must not exceed the 850 mA limit of the power adapter. See ““Determining power requirements”.
4.7.4.5 Determining Power Requirements:
To determine the total amount of current required by your management peripherals, add the individual current requirements for each management peripheral to be installed with the APC Silcon Triple Chassis to the current requirements of the chassis itself. Refer to this table
Part # Management Peripheral Draw (mA)
AP9207 Share-UPS 8-port Interface Expander 65
AP9600 Expansion Chassis 30
AP9604 Triple Chassis 20
990-4059
22 Installation Guide APC Silcon 480kW 400V UPS
External Connection
AP9604S[R] APC Silcon Triple Chassis 90
AP9606 Web/SNMP Management Card 110
AP9607 Interface Expander 45
AP9608 Out-of-Band Management Card
(Call-
UPS II)
AP9612 Environmental Monitoring Card (Measure-UPSII) 60
AP9825i Isolated Extension Cable 50
AP9830 Remote Power-Off Device 35
4.7.5 Troubleshooting
The following table shows the solution to common problems with the operation of the Triple Chassis
Problem Possible Cause Solution
See Powering the APC Silcon Triple Chassis, and verify that you are not exceeding current requirements.
Configure the Silcon Triple Chassis. See the APC Silcon Management Quick Start Guide provided with your chassis or the Web/SNMP Management Card Installation Guide on the CD for more information.
Verify that the supplied UPS cable is properly connected to the Triple Chassis and to a communications port on the UPS.
Status LED is off
Status LED is flashing quickly
Status LED is flashing slowly
The chassis is not receiving adequate power.
The chassis has not been configured.
The chassis is not communicating with the UPS.
35
Attached management peripheral cannot identify UPS model or nominal output voltage.
4.7.5.1 If Problems Persist
For problems not covered in the troubleshooting chart or for persistent problems, follow this procedure:
1) Note the serial number and date of purchase of the APC Silcon Triple Chassis. Contact APC Customer Support at the phone number or address that is listed in this manual.
2) Be prepared to provide a description of the problem. A technician will help solve the problem over the phone, if possible, or will give you a return material authorization (RMA) number.
3) If the APC Silcon Triple Chassis is under warranty, repairs are free of charge. If the warranty has expired, there will be a nominal charge for repair.
The management peripheral firmware does not support 3-phase UPSs.
You may be able to upgrade the firmware of the management peripheral. Call APC Customer Support.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 23
External Connection
4) Pack the APC Silcon Triple Chassis carefully in its original packaging, if possible. Do not use polystyrene beads for packing. Damage sustained in transit is not covered under the warranty. Enclose a letter in the package with your name, address, RMA number, a copy of the sales receipt, daytime phone number, and payment (if applicable).
5) Mark the RMA number clearly on the outside of the shipping carton. The factory will not accept any materials without this marking.
6) Return the Triple Chassis by insured, prepaid carrier to the address given to you by APC Customer Support.
4.7.6 Product Specifications
4.7.6.1 Monitoring Port Pin Assignments
The Monitoring port is a 9-pin communications port. The port operates with no flow control at a rate of 2400 baud. The data format is 8 data bits with 1 start bit, 1 stop bit, and no parity. When the Triple Chassis operates with simple signalling, the following limitations and capabilities apply to the Monitoring port:
• Pins 3, 5, and 6 are open collector outputs which must be pulled up to a common referenced supply no greater than +40 VDC. The transistors are capable of a non­inductive load of 25 mA. Use only Pin 4 as the common.
• The output at Pin 2 generates a low-to-high RS-232 level when the device is signalling an On Battery condition. The pin is normally at a low RS-232 level.
• The UPS is signalled to shut down when a high RS-232 level is applied to Pin 1 for
4.5 seconds. Shutdown is also dependent on the UPS status.
When the Triple Chassis operates with advanced signalling, the following limitations and capabilities apply to the Monitoring port:
• Pin 7 is unassigned.
• DC operating voltage is available on Pin 8. This voltage may be from the UPS or from an external adapter, whichever is greater.
990-4059
24 Installation Guide APC Silcon 480kW 400V UPS
External Connection
UPS Shut Down RS-232 Input or
Advanced Mode RS-232 Data RX In
Line Fail RS-232 Output or
Advanced Mode RS-232 Data TX Out
Unregulated
+24 VDC Output
Normally Open
Line Fail Signal
Normally Open Low Battery Signal
Normally Closed Line Fail Signal
Common
Chassis
Installation Guide APC Silcon 480kW 400V UPS 25
990-4059
External Connection
4.7.6.2 Power, Physical, and Environmental Specifications.
Item Specification
Power
Turn on voltage: > 22 VDC
Turn off voltage: < 16 VDC
Current draw (normal operation): 90 mADC
Current draw (voltage <
Physical
Size (H xW x D): 44 x 432 x 127 mm
Weight: 1.81 kg
Shipping weight: 3.65 kg
Environmental
16 VDC): < 1 mADC
Elevation (above
Operating Storage
Temperature:
Operating Storage
Relative humidity:
Operating Storage
Electromagnetic immunity:
MSL):
0 to 3000 m 0 to 15 000 m
0 to 45˚C
-20 to 70˚C
0 to 95%, non-condensing 0 to 95%, non-condensing
FCC Class A EN50082-1 verified
990-4059
26 Installation Guide APC Silcon 480kW 400V UPS
External Connection
4.8 APC Silcon Battery Cabinets
IMPORTANT SAFETY INSTRUCTIONS
a The installation of battery drawers in UPS cabinets requires battery knowledge and should be
made or supervised by qualified personnel only. Keep unauthorized personnel away from batteries.
b Use identical battery types and numbers when replacing batteries. See battery supplier
manual for further details.
c CAUTION - Do not dispose of batteries in a fire. Battery may explode.
d CAUTION - Batteries are fully charged on delivery. Do not short battery terminals or DC
terminals.
e CAUTION - Avoid rough treatment and opening of batteries. Released electrolyte is harmful
to skin and eyes and may be toxic.
f CAUTION - Batteries may cause electric shocks and high voltage short-circuit current. Follow
below precautions when working with batteries:
1 Remove watches, rings and other metal objects.
2 Use tools with insulated handles.
3 Wear rubber gloves and boots.
4 Do not leave tools or metal parts on top of batteries.
5 Disconnect charging source prior to connecting batteries.
Installation and use of this product must comply with all national, federal, state, municipal or local codes. If you need assistance, please have your UPS model and serial number ready and call APC, see “How to Contact APC” in this guide.
For more information on the APC World Wide Web site at http://www.apc.com or www.apc.co.jp.
WARNING!
The entire system contains HAZARDOUS AC/DC VOLTAGES from several power sources. Some terminals and components are live even with the system being switched off!
ONLY qualified electricians should carry out installations according to national and local codes.
NO UPS types may have built-in batteries when connected to external batteries!
NEVER install batteries not complying with APC specifications. Failing that, the installer takes
over full responsibility!
NEVER lift or transport connected or installed batteries.
NOTICE!
For reliability reasons do not stand on the UPS. keep the UPS cabinet surface free of any objects.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 27
External Connection
System Integration Interface
Battery Breaker trip for EPO
APC UPS Silcon
Diagram - UPS with Battery Cabinet
(Emergency Power Off)
Battery Cabinet
4.8.0.6 Installation of Batteries
See Installation Guide for Battery Cabinet for:
• Preparing Batteries and UPS
• Dimensions and Weight
• Connecting Batteries
WARNING!
Before proceding, ensure that power supplies have been disconnected from UPS for a minimum of 5 minutes.
CAUTION!
Follow Start-up Procedure in APC Silcon User Guide.
990-4059
28 Installation Guide APC Silcon 480kW 400V UPS
4.9 Battery Breaker Box/Fuse-box
CAUTION!
Batteries connected to a UPS out of service for a period exceeding 8 days may be damaged. Refer to Section 7.0 Power Disconnection in this guide.
Battery Breaker Box/Fuse-box provides overcurrent and short-circuit protection for UPS installations with external batteries.
NOTICE!
If battery has been disconnected, refer to Section: - UPS Start Up in the APC Silcon User Guide.
4.9.1 Battery Breaker Box
Battery Breaker Box/
Fuse-box
Battery
APC Silcon UPS
?
External Connection
Installation Guide APC Silcon 480kW 400V UPS 29
990-4059
External Connection
Battery 1
Battery 2
Battery 1
Battery 2
UPS
UPS
Main cables are connected directly to component terminals
?
UPS Ampere
Rating
[A]
480kW 800 3//150 40 1035x835x300 100
4.9.2 APC Battery Breaker Box Connection Diagram (120-480kW)
Connection
Cable
[mm2]
Max. short­circuit
current [kA]
Dimensions
HxWxD [mm]
Weight
[kg]
X009 LED signal from UPS OK to operate corresponding MCCB X010 MCCB position signals for UPS X011 Trip for emergency stop (220-240V AC)
4.9.3 UPS with External Battery in Battery Breaker Box/Fuse-box Configuration
990-4059
30 Installation Guide APC Silcon 480kW 400V UPS
External Connection
?
990-4059
Installation Guide APC Silcon 480kW 400V UPS 31
Programming Parameters
5.0 Programming Parameters
Below table shows operating parameters programmable from keyboard. Only qualified users should re-set programming parameters.
5.1 Parameters
Parameter Setting* Comments
Bypass operation YES, NO YES will switch the system into bypass mode
GB, D, F
Language
Autostart YES, NO
Remote shutdown active YES, NO
Remote shutdown HIGH, LOW Nature of remote shutdown signal level
Remote shutdown time
Battery capacity test ---
Battery monitor test** ---
Automatic battery test** OFF, 3, 6 months
Battery monitor reset** ---
Boost charge YES, NO YES results in boost charge (10 hours)
Autoboost charge YES, NO
Enter new date YYMMDD Set tolocal date
Enter new time HHMMSS Set to local time (24 hour clock)
DK, S, SF NL, PL, CZ E, P, SK, H
0, 1, 2, 3, 4 5, 6, 7, 8, 9 10 min.
Language of text in display
Automatic restart by mains return (1 min.delay). Ensures quick battery recharge
Shutdown of UPS by remote signal when in battery operation. Saves battery energy
Time delay on remote shutdown of UPS
Initiates back-up time check. Time measured from start until it reaches low DC warning level. (See User Guide section 6 )
Initiates checks of battery condition by 25% discharging
Activates the battery monitor test in cyclic intervals
Press the and key
to resets alarm (flashing light)!
YES results in boost charge after battery operation. (10 hours)
* Factory settings in bold
** Only for systems with Battery Monitor active
*** Do not leave system running in bypass mode (Static bypass) for extended periodes of time, as batteries are not recharged in bypass mode.
990-4059
32 Installation Guide APC Silcon 480kW 400V UPS
5.1.1 Programming Keys
Scrolls up through list
Scrolls down through list
Stores
parameters/ enter parameter stack
Silences the audible alarm
Chooses parameters
Displays time
Exits a mode
Accesses alarm stack
NOTICE!
Display accuracy is + 1%, + digit.
Programming Parameters
990-4059
Installation Guide APC Silcon 480kW 400V UPS 33
Programming Parameters
5.1.2 Programming Example - Switch to Bypass Operation
NOTICE!
Do not leave in by-pass mode for extended periods in order not to affect battery capacity.
Return to normal operation
Follow same procedure to program other parameters.
5.2 System Configuration
System configuration parameters are vital for correct system operation and are password­protected.
CAUTION!
Incorrect programming may damage battery or cause output voltage to be lost during operation!
990-4059
34 Installation Guide APC Silcon 480kW 400V UPS
Programming Parameters
System Configuration Parameters (password protected)
Parameter Setting* Comments
Enter System no. Voltage L-L
System Frequency 50/60 Optional selection of frequency
Isolation Transformer Input YES, NO YES if optional input isolation transformer is available
IsolationTransformer Output
Delta Soft Start Time 1, 10, 20, 40 sec. Input current switching in ramp function. Use higher
External SSW present YES, NO YES for systems with external static bypass switch
Normal Charge Voltage 410-460V
Boost Charge Voltage 438-460V
Low Battery warning 336-384V
Low Battery shut-down 310-336V
Synchronization 0.25, 0.5, 1, 2, 4
High Battery Temperature 15-40°C
Common fault delay 0, 10, 20,
Reset operation mode lock YES, NO YES resets system locked in bypass or battery
Expected back-up time (min.)
Battery Capacity in (Ah) 0.1-999.9
Highest Station Address 2-9 Highest station address in parallel system
Station Address 1-9 Station address in parallel system
APM Mode Active (Advanced Power Management)
APM Test Mode Active YES, NO YES, if APM test mode is active
Battery Connection Common,
380, 400, 415 Optional selection of voltage
YES, NO YES if optional output isolation transformer is available
438V
438V
336V
326V
Hz/sec.
35°C
30 sec.
0.1-999.9
5.0
7.0
Disabled Redundant +1 Parallel +1
Separate
values for smaller/unstable diesel generators
Setting of float charge voltage at 20°C (Automatic compensation for temperature deviations)
Setting of boost charge voltage at 20°C (Automatic compensation for temperature deviations)
Discharged Battery warning
Switches off system at min. permissible battery voltage
Syncronization speed.
Alarm - Ambient temperature for battery too high
Delay before common fault alarm relay is activated
operation mode caused by system failures (only applicable for service personnel)
Expected UPS back-up time in minutes when running at 100% ohmic load. Time used by ABM**
Total Battery capacity in Ah. Setting used by ABM**.
Use only in parallel systems. Disabled: Advanced power management off. Redundant +1: Redundant operation with one unit being inactive in parallel system Parallel +1: Redundant operation with all units in operation.
Common: if common battery is used in parallel system. Separate: if separate battery is used
* Bold text refers to factory standard setting **Advanced Battery Monitor
990-4059
Installation Guide APC Silcon 480kW 400V UPS 35
Programming Parameters
*** If voltage or frequency settings is changed, unit needs to be powered down for the new settings to take effect.
5.2.1 Programming Example - Change Charge Voltage to 446
NOTICE!
Change charge voltages, battery warning limit, shut down voltage and high battery temperature limit by entering the actual value. See example above.
990-4059
36 Installation Guide APC Silcon 480kW 400V UPS
Programming Parameters
5.2.2 Programming Example - Change to Output Isolation Transformer available
NOTICE!
Change parameters by pressing the key once or several times. See example above.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 37
Programming Parameters
5.3 Programming Parameters for Advanced Parallel Operation
To use the advanced parallel functions, the following parameters must be programmed:
1. “Station number”
2. “Highest station address”
3. “Advanced power management”
4. “APM test mode active”
5. “Battery connection”
5.3.1 Description of Settings
1. “Station number”
• Valid station numbers: 1-9 stating the UPS parallel address in system.
2. “Highest station number”
• Valid station numbers: 2-9 stating the number of UPSs in system.
3. “Advanced power management”
• “Disabled”: Advanced Power Management is inactive.
• “PARALLEL+1”: Advanced Power Management is activated when the system operates as PARALLEL N+1, meaning that one system can be isolated without overloading the remaining systems (N systems/UPSs).
• “REDUNDANT+1”: Advanced power management is activated when the system operates as REDUNDANT N+1, meaning that one system can be isolated without overloading the remaining systems (N systems/UPSs) with one spare system.
4. “APM test mode active”
• “No”: Stand-by-time will be 24 hours - on-line time will be 48 hours (xN systems).
• “Yes”: Stand-by-time will be 1 min. - on-line time will be 2 min (xN systems).
5. “Battery connection”
• “Separate”: Separate battery for this UPS.
• “Common”: Common battery in a parallel system.
NOTICE!
Common: Common battery in a parallel system. When this setting is chosen, the highest battery temperature that can be found in the parallelled systems (for charge voltage compensation).
NOTICE!
Common battery pack is a technical possibility. However, APC recommend separate battery pack due to a higher safety degree in connection with redundant/parallel operation. The UPS system is designed for both situations.
990-4059
38 Installation Guide APC Silcon 480kW 400V UPS
Programming Parameters
5.3.2 Programming example
Example with four systems in parallel with separate batteries.
• Programme the station addresses 1-4: 1 for UPS 1, 2 for UPS 2, 3 for UPS 3, and 4 for UPS 4.
• All UPS systems have to be programmed to “Highest station address”:4.
• If APM is not to be tested, “APM test mode active” must be “NO”.
• If a system is isolated due to service, the station numbers must be reprogrammed for the remaining active systems starting with number 1 and ending with maximum. number of active systems. No number must be left in this sequence. Furthermore, “Highest station address” must be changed to number of active UPSs in parallel.
5.4 Battery Monitor
990-4059
Installation Guide APC Silcon 480kW 400V UPS 39
Programming Parameters
5.4.1 Installation of new batteries
To avoid false alarms, the above procedure MUST be followed.
NOTICE!
Contact your local dealer if you have any questions regarding changing parameters.
990-4059
40 Installation Guide APC Silcon 480kW 400V UPS
Options/Accessories
6.0 Options/Accessories
Please contact your local APC representative for information on options/accessories available in your region. See “How to Contact APC” in this guide.
6.1 Service Bypass Panel for Single Operation
UPS Exter-nal
System Input Fuse [A]
Max. Prospec­tive Short­Circuit Current [kA]
System Input/ UPS Input Cable [mm2] **
System Output/ UPS Output Cable [mm2] **
Max. External System Output Fuse [A]***
Max. Cable Size/ Stud Size
Dimensions HxWxD [mm]
Weight [kg]
480kW 1000 45 3x200 3x150 800 M12 ? ? ?
*** If no external System Output fuses are available or if it has a higher value than
indicated above, System Output and UPS Output cables should be dimensioned as System Input and UPS Input cables.
** Sizes according to IEC 364-5-532 for PVC insulated copper cables (max. ambient
temperature: 30
o
C). Installation method B: Insulated conductors in wall conduit.
Also refer to local legal regulations.
Beware that single-phase Switch Mode Power supply loads will increase neutral current! At a 100% SMPS load, neutral cable should be dimensioned for 200% of phase current.
* Depth of enclosure includes switch handles
Fixing Cen­tres AxB [mm]
990-4059
Installation Guide APC Silcon 480kW 400V UPS 41
Options/Accessories
?
?
6.1.1 Wiring up UPS with SBP in TN-C-S Network
6.1.2 Wiring up UPS with SBP in TN-S Network
990-4059
42 Installation Guide APC Silcon 480kW 400V UPS
Action
1. Press on the keyboard
2. Press or on the keyboard until
3. Press on the keyboard
4. Press on the keyboard
5. Check lamp indication on the Service Bypass Panel
6. Turn the external bypass switch (Q003) to position 1
7. Turn the output switch (Q002) to position 0
8. Open the front door and press both the green ON and the red OFF keys simultaneously
The acoustic alarm sounds for 30 sec.*
9. Turn the input switch to position 0
The red alarm LED below the display lights and the acoustic alarm sounds for 30 sec.
* The acoustic alarm can be reset by the key
Bypass operation :NO
Bypass operation :YES
Display shows
Lamp indication on Service Bypass Panel
The Green lamp (H003) above the bypass switch handle (Q003) lights
The Green lamp (H002) above the output switch handle (Q002) lights
Only the lamp (H002) above the output switch handle (Q002) lights now
** System OFF **
Display shows
EMERGENCY (UPS not alive)
1. Turn the input switch (Q001) to position 0.
2. Turn the output switch (Q002) to position 0.
3. Change any released system input fuse(s).
4. Turn the bypass switch (Q003) to position 1.
Options/Accessories
6.1.3 Operating The External Service Bypass Switch
Installation Guide APC Silcon 480kW 400V UPS 43
990-4059
Options/Accessories
** System OFF **
Normal operation load power %
Display shows
Lamp indication on Servive Bypass Panel
The Green lamp (H002) above the output switch handle (Q002) lights
Now also the green lamp (H003) above the bypass switch handle (Q003) lights
Only the Green lamp (H003) above the bypass switch handle (Q003) lights
Display shows
Bypass operation :NO
Bypass operation :YES
:
Bypass operation :YES
:
Bypass operation :NO
Normal operation load power xx %
No lamps on the Service Bypass Panel light any longer
10. Press on the keyboard
11. Press or on the keyboard until
12. Press on the keyboard
11. Press on the keyboard
11. Press on the keyboard
Action
1. Turn the input switch (Q002) to position 0
2. Open the UPS front door and press the green "ON key
3. Press on the keyboard
4. Press or on the keyboard until
5. Press on the keyboard
6. Press on the keyboard
7. Check lamp indication on the bypass panel
8. Turn the output switch (Q002) to position 1
9. Turn the bypass switch (Q003) to position 0
6.1.3.1 Switching from External Bypass to Normal UPS Operation
990-4059
44 Installation Guide APC Silcon 480kW 400V UPS
Options/Accessories
Service Bypass Panel (SBP)
Mains Supply System Output
Control cables
Q003
Q004
Q001bQ001a
Q002b
Q002a
APC Silcon 400V UPS
X020 X021
X020 X021
APC Silcon 400V UPS
Battery
Battery Breaker/
Fuse Box
6.2 Service Bypass Panel for Parallel Redundant Operation
Installation Guide APC Silcon 480kW 400V UPS 45
990-4059
Options/Accessories
?
6.2.1 Two Parallel Systems with Service Bypass Panel
990-4059
46 Installation Guide APC Silcon 480kW 400V UPS
Options/Accessories
?
6.2.2 Parallel/Redundant Operation with Service Bypass Panel and External Battery via MCCB
990-4059
Installation Guide APC Silcon 480kW 400V UPS 47
Options/Accessories
H002a
6.2.3 Operating External Service Bypass Switch for Parallel Systems
6.2.3.1 Bypassing Parallel UPS Systems
990-4059
CAUTION!
Batteries connected to a UPS out of service for a period exceeding 8 days may be damaged.
48 Installation Guide APC Silcon 480kW 400V UPS
Step 1-4 can be carried out with any of the parallel systems, however this will switch all systems into bypass operation.
1. Press on the keyboard
2. Press or on the keyboard until
3. Press on the keyboard
4. Press on the keyboard
All systems will transfer to bypass operation
Do not switch off any of the UPS systems until step 5-8 has been completed.
5. Check lamp indication on the Service Bypass Panel
6. Turn the external bypass switch (Q003) to position ”1“
7. Turn the output isolator (Q004) to position ”0“
8. Turn the output switches (Q002) to position ”0“
9. Open the front door and press both the green ON and the red OFF keys simultaneously in any of the systems The acoustic alarm sounds for 30 sec.* Repeat for (all) other system(s).
10. Turn all input switches (Q001) to position ”0“ The red alarm LED below the display lights and the acoustic alarm sounds for 30 sec.
* The acoustic alarm can be reset by the key
Bypass operation :NO
Bypass operation :YES
Display shows
Lamp indication on bypass panel
The green lamp (H003) above the bypass switch handle (Q003) lights
The green lamp (H004) above the output isolator (Q004 and the green lamps (H002) above the output switch handles (Q002) lights
The green lamps (H002) above the output switch (Q002) light and the green lamp (H004) above the output switch (Q004) lights
Now the lamps (H002) above the output switch handles (Q002) light and the green lamp (H004) above the output switch (Q004) lights
** System OFF **
Display shows
Action
Bypass operation
Options/Accessories
Installation Guide APC Silcon 480kW 400V UPS 49
990-4059
Options/Accessories
H002a
6.2.3.2 Switching Parallel System from External Bypass into Normal UPS Operation
990-4059
50 Installation Guide APC Silcon 480kW 400V UPS
Options/Accessories
Action
1. Check that output switch (Q004) is in position 0
2. Check that all output switches (Q002) are in position 0
3. Turn input switches (Q001) to position “1”
4. Open the UPS front door and press the green ON” push-botton
5. Press on the keyboard
6. Press or on the keyboard until
7. Press on the keyboard
8. Press on the keyboard
All systems will transfer to bypass operation
9. Check that all output switches (Q002) are in position 0
10. Turn all output switches (Q002) to position 1
11. Turn the output switch (Q004) to position 1
12. Turn the bypass switch (Q003) to position 0
** System OFF **
Normal operation load power 0%
Display shows
Lamp indication on Service Bypass Panel
The green lamps (H002) above all the output switch handles (Q002) lights. The green lamp (H004) above the output switch (Q004) handle also lights.
The green lamps (H002) above all the output switch handles (Q002) light. The green lamp (H004) above the output switch (Q004) handle and the green lamp (H003) above the bypass switch light.
The green lamps (H002) and (H004) do not light any longer. (H003) will light until normal operation.
Bypass operation :NO
Bypass operation :YES
Bypass operation
Installation Guide APC Silcon 480kW 400V UPS 51
990-4059
Options/Accessories
The following can be carried out on any UPS
13. Press on the keyboard
14 Press or on the keyboard until
15. Press on the keyboard
16. Press on the keyboard
All the systems will transfer to normal operation.
Normal operation load power xx%
Display shows
Bypass operation :NO
Bypass operation :YES
No lamps on the bypass panel lights any longer
990-4059
52 Installation Guide APC Silcon 480kW 400V UPS
Options/Accessories
H002a
6.2.4 Isolating One UPS for Service/Maintenance
In a redundant system, one UPS may be isolated for service/maintenance without affecting other UPSs.
1. Check that remaining UPS(s) is capable of carrying the load in the event that one UPS is
isolated
2. Switch off system to be isolated for maintenance purposes by pushing green “ON” and red
“OFF” buttons simultaneously
3. To disconnect battery, mains and output, open battery MCCB/fuse and set input switch
(Q001) and output switch (Q002) to position “0”
With Q002 in position “0”, UPS will be operational and may be tested as a single system without affecting other parallel UPS(s).
6.2.5 Switching Back to Normal Parallel/Redundant Operation
1. Turn input switch (Q001) and output switch (Q002) to position “1”
2. Charge capacitor, connect battery and start up UPS
UPS will automatically switch to normal operation and start load-sharing with other parallelled UPS(s).
WARNING!
System will discharge built-in capacitors, but check terminal voltage before proceding.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 53
Options/Accessories
ISU System
Parallel Operation System 3
Parallel Operation System 2
Parallel Operation System 1
Ext. sync Source
UPS 2C
UPS 2B
UPS 2A
UPS 1C
UPS 1A
UPS 1B
UPS 3C
UPS 3A
UPS 3B
UPS 4
ISU
5
ISU
4
ISU
2
ISU
1
ISU
3
6.3 Intersystem Synchronization Unit
Intersystem Synchronization Unit System (ISU System)
The ISU system consists of inter-connected ISUs. One ISU system may consist of up to 5 ISUs, regardles of ISU configuration. The ISU system synchronizes the voltage of parallel operation systems running in battery operation.
The ISU system may also include one or more external synchronization sources, e.g. a gen-set or a non-APC Silcon UPS system.
Synchronization accuracy of the ISU is better than 2
Schematic overview of ISU system (example):
o
.
Intersystem Synchronization Unit (ISU)
The ISU is an active part of an ISU system, serving as the interface to the sources and the ISU system.
The ISU can be connected to a parallel UPS configuration, using the standard parallel communication controller in the parallel operation system.
(See Intersystem Synchronization Unit User’s Manual for further details.)
6.4
990-4059
54 Installation Guide APC Silcon 480kW 400V UPS
Options/Accessories
6.5 Remote Display
With the remote display unit data may be displayed at distances of up to 25 m from UPS. For extended communication distance, see section below.
Remote display may easily be connected to UPS via one of the two serial communication ports on the communication interface board.
To obtain a transmission distance of up to 3.2 km normal RS232C signal levels must be converted to a long distance communication standard. The converter must be placed outside the UPS cabinet.
6.5.1 Extension of Remote Display Communication Distance
Remote display communicates with the UPS through a 3-wire RS232 interface. Remote display is a DTE (Data Terminal Equipment) employing a SUB-D 9-pin female connector. Communication speed: 9600 bps.
For communication distances, see Table 1. Insert converters if longer distances are necessary, or if communication cables are led through magnetically noisy areas. Converters must comply with local regulations
Table 1: Remote Display Communication Extensions
Standard (RS232)
Max. distance 80/25 ft/m 10000/3200 ft/m
Converter Manufacture Art. Code
RS232 BLACK BOX connector Sub-D 25-pin female
BLACK BOX interconnector 4-screw terminal
Two converter boxes are required for a communication distance extension: One box near the UPS for the conversion from RS232C to a long distance communication standard, and another box at the other end to convert back to RS232C, which is to be connected to the
No converter BLACK BOX
Short-haul Modem Async
ME800A-R2
990-4059
Installation Guide APC Silcon 480kW 400V UPS 55
Options/Accessories
Remote Display. The converter provides optical signal insulation. Both converter boxes must be supplied by an uninterruptible power source.
6.5.1.1 Connections Without Converter
Connect a 25-pin female Sub-D and a 9-pin male Sub-D connector with a 3-wire shielded cable, as shown in the table below. Connect shield at one end only.
Pin Connection for Interconnection Cable (without converter):
Host (DTE) Remote Display (DTE)
25-pin female pin No.
2 (TXD) 2 (RXD)
3 (RXD) 3 (TXD)
7 (GND) 5 (GND)
House (shield) No Connection
6.5.1.2 Connections With Converter
Connections to be made according to converter manual.
Pinconnection example only:
Pin Connections for cable from host to ME800A-R2.
Host (DTE)
25-pin female pin No.
ME800A-R2 (DCE)
25-pin male pin No.
9-pin male pin No.
Pin connection for cable from ME800A-R2 to Remote Display
ME800A-R2 (DCE)
25-pin male pin No.
Remote Display (DTE)
9-pin male pin No.
2 (TXD) 3 3 2 (RXD)
3 (RXD) 2 2 3 (TXD)
7 (GND) 7 7 5 (GND)
House (Shield) No connection No connection House (Shield)
The ME800A-R2 must be set up as a DCE with no RTS/DTR control.
The interconnection cable between the two ME800A-R2 boxes is a 4-wire twisted pair telephone cable with or without shield. The shield improves noise immunity but reduces maximum communication distance.
990-4059
56 Installation Guide APC Silcon 480kW 400V UPS
Options/Accessories
Rear view
Cable entry from bottom and rear
Rear view Front view
3. Mont back plate
4. Connect cables
1. Turn 180° to loosen
2. Remove front cover
Mains adapter
DP9-F
the 4 screws
X
APC Silcon, DB25-F
Remote Display, DB9-M
6.5.2 Remote Display Installation
6.5.2.1 Connecting RS232C and Mains Adapter
CAUTION!
Wiring for alarm and signal circuit field to be rated 300V (minimum).
6.5.2.2 Remote Display Power Supply
The remote display is supplied by normal AC power with no battery back-up. For UPS data transmission to remote display to remain unaffected during power failure, the remote display must be supplied from an uninterruptible power source.
Converters used to extend communication distance must also be supplied from uninterruptible power sources.
6.5.2.3 Remote Display Cables
RS232C to RS232C cable:
Connect shield at one end only! Rating: Refer to Local/National electrical codes. Communication voltage +
15VDC
Installation Guide APC Silcon 480kW 400V UPS 57
990-4059
Options/Accessories
6.5.3 Remote Display Use
The remote display is an inactive unit unable to influence the operation of the UPS: Some of the alarms visible on the internal display are also available on the remote display (See the Alarm section in the APC Silcon User Guide).
6.5.3.1 Initiating the Remote Display
After having connected the supply the display will show:
Remote Display: “APC Silcon UPS”
6.5.3.2 Communication Fault
Communication fault between UPS and remote display will appear in the display as follows:
“Data transmission interrupted”
6.5.3.3 Remote Display Setting
Use # Stack to select language and type of UPS connected to remote display.
Parameter Setting Comments
Language GB,D,F,DK, S, SF,NL, PL, CZ,
E, P, SK, H, I
Host SDC charger, DP300E, 300E Type of UPS connected to remote
6.5.3.4 Operation
See the Operation section in the APC Silcon User Guide.
6.5.3.5 Display of Measured Value
See Display of Measured Value in the APC Silcon User Guide. Time reading not visible from the remote display.
6.5.3.6 Alarms
See Alarms section in the APC Silcon User Guide.
Language
display
990-4059
58 Installation Guide APC Silcon 480kW 400V UPS
6.6 Isolation Transformer
1600 mm wide
1800mm
?
APC Isolation
Transformer Module
480kW
Options/Accessories
Isolation
Transformer
540kVA 480kW 1800 1400 800 2550
*Actual dimensions may vary
UPS Height
[mm]*
Width [mm]*
Depth [mm]*
Weight
[kg]
990-4059
Installation Guide APC Silcon 480kW 400V UPS 59
Options/Accessories
Input
Output
E
G
G
Example of Transformer Configuration (Yyno)
NOTICE!
APC isolation transformers are available in various configuration. Contact your local APC representative for further information. See How to Contact APC in this guide.
990-4059
60 Installation Guide APC Silcon 480kW 400V UPS
6.6.1 Connecting Isolation Transformer
?
Options/Accessories
Isolation
Transformer
540kW 480kVA 1000 3//200 200 3//200 2
*DIN gL types PVC cables insulated to withstand a maximum ambient temperature of 30°C
NOTICE!
If an MCCB is used in stead of external input fuses, the MCCB load capacity must be 8xIn (nominal current) for minimum 10 ms.
NOTICE!
Check correct phase rotation of mains input voltage! Maximum input/output cables: 3//300 mm If input neutral is not available, an optional Dzn0 or Dyn11 input isolation transformer must be used.
NOTICE!
All external cable dimensions are recommended sizes only. Refer to local legal regulations.
UPS External
Input
Fuses* FM
[A]
380-415V
External
Input Cable
2
]
[mm
380-415V
External PE
Cable
2
]
[mm
External
Output
Cable
2
]
[mm
External
Temp. Signal
Cable
[mm
2
]
2
.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 61
Options/Accessories
NOTICE!
Make sure that gland plate is installed in bottom of cabinet.
CAUTION!
At 100% switch mode load, neutral must be rated for 200% phase current.
990-4059
62 Installation Guide APC Silcon 480kW 400V UPS
Options/Accessories
6.6.2 Wiring up UPS with External Yyn0 Isolation Transformer at Output
WARNING!
Isolation transformer provides galvanic isolation between mains supply and load. Load will loose galvanic isolation if isolation transformer is bypassed
NOTICE!
Refer to local legal regulation for wiring information.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 63
Options/Accessories
6.6.3 Wiring up UPS with External Yyn0 ?????? Isolation Transformer at Input
WARNING!
Isolation transformer provides galvanic isolation between mains supply and load. Load will loose galvanic isolation if isolation transformer is bypassed.
NOTICE!
Refer to local legal regulation for wiring information.
990-4059
64 Installation Guide APC Silcon 480kW 400V UPS
Options/Accessories
6.6.4 Wiring up UPS with External Optional Dzn0 Isolation Transformer at Input
WARNING!
Isolation transformer provides galvanic isolation between mains supply and load. Load will loose galvanic isolation if isolation transformer is bypassed.
NOTICE!
Refer to local legal regulation for wiring information.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 65
Options/Accessories
6.6.5 Wiring up UPS with External Optional Dzn0 Isolation Transformer at Output
WARNING!
Isolation transformer provides galvanic isolation between mains supply and load. Do not bypass isolation transformer in order to avoid damaging circulation currents and to prevent load from loosing galvanic isolation.
NOTICE!
Refer to local legal regulation for wiring information.
990-4059
66 Installation Guide APC Silcon 480kW 400V UPS
Options/Accessories
6.6.6 Wiring up UPS with External Optional Dyn11 Isolation Transformer at Input
WARNING!
Isolation transformer provides galvanic isolation between mains supply and load. Do not bypass isolation transformer in order to avoid damaging circulation currents and to prevent load from loosing galvanic isolation.
NOTICE!
Refer to local legal regulation for wiring information.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 67
System Specifications
7.0 System Specifications
7.1 Technical Data
Input Voltage tolerance
Normal operation Bypass operation
Frequency 50Hz/60Hz
Input power factor load 25% minimum 0.97
Current distortion Max. 5%
Output Voltage 3x380/400/415V
Voltage tolerance ±1% static symmetrical load±
Voltage distortion max. 3% linear load
Load power factor 0.9 lead to 0.8 lag
Frequency 50Hz/60Hz (mains synchronized)
Overload capacity Mains operation Mains operation Battery operation Bypass operation
General Ambient temperature 0-40°C (Temperatures above 25°C will
Humidity Protection class Safety
Emission and Immunity Static bypass switch Auto restart Economy mode
Voltage 3x380/400/415V
±15% ±10% (standard) ±4, 6, 8% (programmable)
±6 standard ±0.5-8% (programmable)
load 100% minimum 0.99
±3% static symmetrical load ±5% 0-100% load step
max. 6% non-linear load
0.1% free-running
+
200% - 60 seconds 125% - 10 minutes 150% - 30 seconds 125% - continuous
reduce battery lifetime)
Max. 95% non-condensing IP30 EN 50091-1 CE Mark EN 50091-2 Built-in Programmable Programmable
7.2 Dimensions / Weight
Type Height [mm] Width [mm] Depth [mm] Weight [kg]
480kW 1800 1900 800 1800
990-4059
68 Installation Guide APC Silcon 480kW 400V UPS
Warranty
8.0 Warranty
8.1 APC Silcon Series Limited Factory Warranty
APC warrants that the unit, when properly installed and commissioned by APC or APC authorized service personnel, shall be free from defects in materials and workmanship for a period of (1) year from the date of installation or maximum 18 months after manufacturing. In the event that the unit fails to meet the foregoing warranty, APC shall for a period of one (1) year repair or replace any defective parts, without charge for on-site labor and travel if trained & authorized APC personnel has conducted start-up of the unit.
An APC Start-Up Service must be performed/completed by APC or APC authorized service personnel or the on-site factory warranty will be voided and replacement of defective parts only will be covered. APC shall have no liability and no obligation to repair the installed unit if non-authorized APC personnel performed the start-up and such start-up caused the unit to be defective.
APC SHALL NOT BE LIABLE UNDER THE WARRANTY IF ITS TESTING AND EXAMINATION DISCLOSE THAT THE ALLEGED DEFECT IN THE PRODUCT DOES NOT EXIST OR WAS CAUSED BY PURCHASERS OR ANY THIRD PERSONS MISUSE, NEGLIGENCE, IMPROPER INSTALLATION OR TESTING, UNAUTHORIZED ATTEMPTS TO REPAIR OR MODIFY, OR ANY OTHER CAUSE BEYOND THE RANGE OF THE INTENDED USE, OR BY ACCIDENT, FIRE, LIGHTNING OR OTHER HAZARD.
THERE ARE NO WARRANTIES, EXPRESSED OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITHIN. APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. APCS EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, APCS RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE, CONSTITUTE APCS SOLE LIABILITY AND PURCHASERS EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APCS WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 69
Appendix
Main Input Breaker
Field Wiring*
Battery Bank**
UPS Module
Service Bypass Panel
Field Wiring
Output Breaker
*
** Internal Batteries available for 40kW units and smaller
*
*
Q1
Q2
Q3
* Not supplied by APC
9.0 Appendix
9.1 Table 1. Installation Planning Data
Installation Planning Data
APC Silcon Series
AC Input Battery System DC AC Output
Min. Input Input Full I
Power rating Source P (kW) I (A) Cable Overcurrent V
kW kVA Pf V Hz Nom. Max. Nom. Max. (per phase) Protection* (Vdc) P(kW) (A) (A) (A) Protection* (kW)
480 480 1 380
COLUMN 1a 1b 1c 1d 1e 1f 1g 1h 2a 2b 2c 2d 3a 3b 4a
NOTES 3 4 1 2 9 5, 6, 13 8 12 10 11 6, 7 13
* Provided by others
50/60 491.8 569.5 838.3 400 415
747.3
768.4
922.1
822.0
845.2
3//200mm
2
1000 A 2x384 505.3 658 775 727.3
n
NomIMax
load Disch Disch InOvercurrent Dissipation
Load side Heat
695.7
666.7
800 A 15.9
990-4059
70 Installation Guide APC Silcon 480kW 400V UPS
Notes:
1. Nominal input current based on rated load.
2. Maximum input current based on rated load + full battery recharge. Full battery recharge assumed to increase input current with 10%.
3. Nominal power consumption (column 1c) based on nominal input current (1e) and the corresponding input voltage (1a).
4. Maximum power consumption (1d) based on maximum input current (1f) and the corresponding
input voltage (1a).
5. Suggested input overcurrent protection (1h) based on continous full load maximum input current
(1f). MCCB breaker selection based on continous full load nominal input current (1e) is acceptable, provided battery recharge time is short.
6. Fuses according to DIN LV HRC type gL, 500V assumed. MCCB load capacity must be 8xIn
(nominal current) for minimum 10ms.
Appendix
7. Suggested load side overcurrent protection (3b) based on nominal output current (3a).
8. Nominal battery voltage assumed to be 2V/cell (Lead technologi).
9. Recommended cable sizes, see "External Connection" section of this guide.
CAUTION! Cable sizes must comply with national and/or local legal regulations.
10. Nominal battery discharge current (2c) based on full rated load and nominal battery
voltage (2V/cell).
11. Maximum battery discharge current (2d) based on full rated load and battery voltage at end of discharge (1.7V/cell).
12. Full load discharge power from battery based on nominal battery discharge current
(2c) x nominal battery voltage (2x192cells x 2V/cell), or maximum battery discharge current (2d) x battery voltage at end of discharge (2x192cells x 1.7 V/cell).
13. Heat dissipation based on nominal full load capacity and linear load.
990-4059
Installation Guide APC Silcon 480kW 400V UPS 71
How to Contact APC
10.0 How to Contact APC
APC Corporate
132 Fairgrounds Road West Kingston, RI 02892 USA
Telephone: 401 789-5735 Fax: 401 789-3710
PowerFax™: 800 347-FAXX
Pre-sales Technical Support 877-474-5266 (1-877-4Silcon)
Post-sales Technical Support 877-287-7835 (1-877-2UPS-TEK)
E-mail: apcinfo@apc.com Web: www.apc.com/support/contact/contact_support.cfm
APC Denmark
Silcon Allé DK-6000 Kolding Denmark
Telephone: + 45 75 54 22 55 Fax: + 45 72 19 03 50
Pre-sales Technical Support + 45 72 19 04 90
Post-sales Technical Support + 353 91 70 2000
APC Japan Inc. BR Gotanda Building, 7F 2-30-4 Nishi-Gotanda, Shinagawa-ku Tokyo 141-0031 Japan
Telephone: (03) 5434-2021 Fax: (03) 5434-2122
990-4059
72 Installation Guide APC Silcon 480kW 400V UPS
Loading...