American Power Conversion 420-620 User Manual

Installation and Initial Start-Up
To obtain warranty coverage, please fill out and return the warranty registration card now.
Inspection
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly.
Placement
APC Smart-UPS 420/620
User’s Manual
990-7041 Revision 1 9/97
Connect Telephone/Network Surge Suppression (Optional)
Connect a single line telephone or a 10Base-T/ 100Base-Tx network cable into the RJ-45/RJ-11 telephone/network surge protection IN jack on the back of the UPS. Connect from the OUT jack with telephone cable (supplied) or network cabling (not supplied) to a fax modem or network port.
Install the UPS in a protected area that is free of excessive dust and has adequate air flow. Do not operate the UPS where the temperature and humidity is outside the specified limits.
Warning: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the warranty.
Connect to Utility
Check the Site Wiring Fault Indicator
Caution: If the site wiring fault indicator lights, get a qualified electrician to correct the building wiring.
Connect the Loads
Plug the loads into the output connectors on the rear of the UPS. To use the UPS as a master on/off switch, make sure that all of the loads are switched on.
Caution: Do not connect a laser printer to the UPS.
Connect Computer Interface Port (Optional)
plus
PowerChute® is included with this UPS. Connect the supplied interface cable to the 9-pin computer interface port on the back panel of the UPS. Connect to the computer. See software documentation for installation instructions.
Charge the battery
The UPS charges its battery whenever it is
connected to utility power. The battery will charge fully during the first 4 hours of normal operation. Do not expect full runtime during this initial charge period.
power management software
Operating Instructions
Switch On — Switch Off
With the UPS plugged in, press and release the on/off/test button to supply power to the loads.
The loads are immediately powered while the UPS performs a self-test. Press and release the button again to turn off power to the loads. It may be convenient to use the UPS as a master on/off switch for the protected equipment.
The on-line LED illuminates when the UPS is supplying utility power to the loads.
Self-test
The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by default). Automatic self-test eases maintenance requirements by eliminating the need for periodic manual self-tests.
During the self-test, the UPS briefly operates the loads on-battery. If the UPS passes the self-test, it returns to on-line operation.
If the UPS fails the self-test it immediately returns to on-line operation and lights the replace battery LED.
The loads are not affected by a failed test. Recharge the battery overnight and perform the self-test again. If the replace battery LED is still on, replace the battery using the
Battery
procedure.
Replacing the
On Battery
During on-battery operation, the on­battery LED illuminates and the UPS
sounds an audible alarm consisting of 4 beeps every 30 seconds. The alarm stops when the UPS returns to on-line operation.
Low Battery
When the UPS is operating on-battery and the energy reserve of the battery runs low, the UPS beeps continuously until the UPS shuts down from battery exhaustion or returns to on-line operation.
Overload
When loads exceed the UPS’s capacity, the overload LED illuminates and the
UPS emits a sustained tone. The alarm remains on until the overload is removed. Disconnect nonessential load equipment from the UPS to eliminate the overload.
If the overload is severe, the input circuit breaker may trip (the resettable center plunger of the circuit breaker pops out). Disconnect nonessential load equipment from the UPS to eliminate the overload and press the plunger back in.
If there is AC power and the circuit breaker does not trip during overload, the loads are still powered. If the circuit breaker trips or the UPS attempts to transfer to battery, the loads’ power will be shut off. Turn the UPS off then back on to power the loads.
Replace Battery
If the battery fails a self-test, the UPS emits short beeps for one minute and the replace battery LED illuminates.
The UPS repeats the alarm every five hours. Perform the self-test procedure to confirm replace battery conditions. The alarm stops when the battery passes the self-test.
Shutdown Mode
If there is no power, the host connected to the computer interface port can command the UPS to shut down. This is normally done to preserve battery capacity after a controlled shutdown of the protected system. In shutdown mode the UPS stops supplying power to the load. The online and overload LED indicators flash alternately or, if the UPS has shutdown due to a low battery, the UPS will beep once every 4 seconds for approximately 16 seconds. When line power is restored, the UPS will return to on­line operation.
Cold Start Note: Cold start is not a normal operating
condition.
When the UPS is off and there is no utility power, it is possible to cold start the UPS to power the loads from the UPS’s battery.
Press and hold the on/off/test button until the UPS begins beeping.
Release the on/off/test button beeping to start the UPS.
during
the
Storage
Storage Conditions
Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for at least 4 hours. Disconnect any cables connected to the computer interface port to avoid unnecessarily draining the battery.
Extended storage
At -15 to +30 At +30 to +45
°C (+5 to +86 °F), charge the UPS’s battery every 6 months
°C (+86 to +113 °F), charge the UPS’s battery every 3 months.
Replacing the Battery
This UPS has an easy to replace hot-swappable battery.
Note: Please read the cautions in the
APC Safety Guide
.
Replacement Batteries
See your dealer or call the number in this manual for information on replacement battery kits. For 420 models, order RBC 2. For 620 models, order RBC 4.
Battery Replacement Procedure
Battery replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and loads on for the following procedure.
Note: Once the battery is disconnected, the loads are not protected from power outages.
1. Lay the UPS on its left side. Remove the two screws holding on the battery door and open the door.
Note: It may be necessary to pull the battery door slightly toward the front of the unit in order to open the door fully.
2. Gently pull out the battery by grasping the white tab.
3. Disconnect the two wires connecting the battery to the UPS. Loosen the wires by wiggling them while pulling straight back from the battery connector.
4. Connect the new battery in place of the old.
Note: Small sparks at the battery connections are normal during connection.
5. Place the new battery in the UPS. Use care to avoid pinching the wires.
6. Close the battery compartment door and replace the screws.
7. Dispose of the old battery properly at an appropriate recycling facility or return it to the supplier in the packing material for the new battery. See the new battery instructions for more information.
Troubleshooting
Problem Possible Cause Solution
UPS will not turn on. On/off/test button not
pushed. UPS input circuit breaker
tripped.
UPS will not turn on or off. Computer interface
problem.
UPS operates on-battery even though normal line voltage is thought to exist.
UPS beeps occasionally. Normal UPS operation. None. The UPS is UPS does not provide
expected back up time.
On-line and overload indicators are flashing alternately.
All indicators are flashing. Internal UPS fault. Do not attempt to use the
The UPS operates normally, but the site wiring fault indicator is lit. On-line and on-battery indicators only are flashing
All indicators are off and the UPS is not operating.
The replace battery light is illuminated.
The overload light is illuminated or flashing
UPS’s input circuit breaker tripped.
The UPS’s battery is weak due to recent outage or is near the end of its service life.
The UPS was shutdown
by PowerChute® software.
Building wiring error such as missing ground or hot to neutral wire reversal. Internal UPS fault. Do not attempt to use the
The UPS is shutdown and the battery is discharged from an extended power outage.
Weak batteries. Allow the batteries to
Replacement batteries not connected properly. The UPS is overloaded. Reduce the load on the
plus
For Computer Interface Port Specifications, see the APC Website.
Press the on/off/test button to power the UPS and the loads. Reduce the load on the UPS by unplugging equipment and reset the circuit breaker by pressing the plunger back in. Disconnect the computer interface. If the UPS now works normally, check the interface cable and the attached computer. Reduce the load on the UPS by unplugging equipment and reset the circuit breaker by pushing the plunger back in.
protecting the load. Charge the battery. The UPS’s batteries require recharging after an extended outage. Batteries age faster when put into service often and when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet lit.
None. The UPS will restart automatically when utility power returns.
UPS. Turn the UPS off and have it serviced immediately. Have a qualified electrician correct the building wiring.
UPS. Turn the UPS off and have it serviced immediately. None. The UPS will return to normal operation when the power is restored and the battery has a sufficient charge.
recharge for at least 4 hours. If the problem persists after recharging, replace the batteries. Confirm the battery connections.
UPS by unplugging equipment.
Service
If the UPS requires service
Follow these steps:
1. Use the
2. Verify that no circuit breakers are tripped. A tripped circuit breaker is the most common UPS problem!
3. If the problem persists, call customer service or visit the APC Internet Website (www.apcc.com).
Note the model number of the UPS, the serial number, and the date purchased. A technician will ask you to describe the problem and try to solve it over the phone, if possible. If this is not possible the technician will issue a Return Merchandise Authorization Number (RMA#).
If the UPS is under warranty, repairs are free. If not, there is a repair charge.
4. Pack the UPS in its original packaging. If the original packing is not available, ask customer service about obtaining a new set.
Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging. Damage sustained in transit is not covered under warranty.
Include a letter with your name, RMA#, address, copy of the sales receipt, description of the trouble, your daytime phone number, and a check (if necessary).
5. Mark the RMA# on the outside of the package
6. Return the UPS by insured, prepaid carrier to the address below.
APC APC 132 Fairgrounds Road Ballybritt Business Park West Kingston, Rhode Island 02892 USA Galway, Ireland 10800-702000 1-800-800-4APC/1-401-789-5735 353-91-702020
Troubleshooting
North & South America Europe
Internet E-Mail
http://www.apcc.com apctech@apcc.com
do not return it to the dealer!
section to eliminate common problems.
Specifications
Acceptable input voltage 0 - 160 VAC Input voltage (on-line operation)* 81-143 VAC Output voltage * 106-127 VAC Input Over Current Protection Resettable circuit breaker Frequency limits (on-line operation) 47 - 63 Hz Transfer time 4 ms typical, blackout response time Maximum load 420 VA 260 W 620 VA 390 W On-battery output voltage 115 VAC On-battery frequency 50 or 60 Hz, ±0.1 Hz; unless synchronized to
On-battery waveshape Stepped sine-wave Output Over Current Protection Overcurrent and short-circuit protected,
Battery type Spill proof, maintenance free, sealed lead-acid Typical battery life 3 to 6 years, depending on number of
Typical recharge time 2 to 5 hours from total discharge Operating temperature
Storage temperature Operating and storage relative humidity 0 to 95%, non-condensing
Operating elevation 0 to +3,000 m (0 to +10,000 ft) Storage elevation 0 to +15,000 m (0 to +50,000 ft) Audible noise at 1 m (3 ft) <45 dBA Size (H x W x D) 16.8 x 11.9 x 36.8 cm
Weight - net (shipping) 10.0 (10.9) kg Safety and approvals UL 1778, UL 497A, CSA 107.1, FCC part 68
EMC verification FCC/DOC Class B certified Electromagnetic immunity IEC 801-4 level IV, 801-5 level III
* User-adjustable through PowerChute®
420 VA 620 VA
utility during brownout
latching shutdown on overload
discharge cycles and ambient temperature
0 to +40 °C (+32 to +104 °F)
-15 to +45 °C (+5 to +113 °F)
(6.6 x 4.7 x 14.5 in)
22.0 (24.0) lb.
plus
(see software documentation).
12.3 (13.2) kg
27.0 (29.0) lb.