A.O. Smith VWT-500, VWT-1000 User Manual

Page 1
Commercial Gas Boilers
ACMSS00507
TOTAL HOT WATER SUPPLY SYSTEM USING VF™BOILERS
With Ac-U-Temp, A. O. Smith makes it as easy as possible to install a complete packaged hot water supply system, combining high-efficiency VF™boilers with storage tanks up to 10,000 gallons. Each Ac-U-Temp system is custom-made to your specifications for each application and shipped fully assembled, pre-piped and pre-wired. All the installer has to do is make the flue, gas, electrical and water connections, so installations are easy.
Consult your A. O. Smith representative for more information on the wide range of available boiler/storage tank combinations using the Ac-U-Temp system.
VF MODULATING BOILERS UP TO 88% THERMAL EFFICIENCY
• A. O. Smith’s most efficient hot water supply boilers
• Available inputs: 500,000, 750,000, 1,000,000 BTUs
• Flexible conventional-vent or sealed-combustion direct-vent options
• For complete information on VF Hot Water Supply Boilers, consult VF Specification Sheet
GLASS-LINED STORAGE TANKS
• Standard capacities up to 1,000 gallons
• Custom tanks available up to 10,000 gallons
• Standard tanks are factory jacketed and insulated – bare uninsulated tanks also available
• Optional cement or epoxy-lined tanks available
• For complete information on standard and optional tanks, consult tank Specification Sheet
MULTIPLE BOILER SYSTEMS
• Ac-U-Temp systems can be designed with multiple boilers to provide 50% to 100% back-up
• Multi-boiler systems can be sequenced to meet changing system demands
• Sequenced multi-boiler systems with small storage tanks are ideal for applications with relatively constant hot water demands
• Optional sequenced control panel available
MULTIPLE TANK SYSTEMS
• Ac-U-Temp systems can be designed with multiple tanks for applications with low ceiling heights or other unique installation challenges
VWT-500
through
VWT-1000
July 2007R
Page 1 of 4
Page 2
ACMSS00507
Page 2 of 4
MODEL
NUMBER
INCHES
OR
CM
DIMENSIONS
LENGTH
(C2)
WIDTH
(C1)
HEIGHT
(D)
INLET SIZE GAS INLET
VW-500
Inches
30 30 60 2 1
CM
76.2 76.2 152.4 5.1 2.5
VW-750
Inches
30 30 66 2 1
CM
76.2 76.2 167.6 5.1 2.5
VW-1000
Inches
30 30 75 2 1
CM
76.2 76.2 190.5 5.1 2.5
MODEL
NUMBER
INCHES
OR
CM
DIMENSIONS
HEIGHT
(A)
WIDTH
(B1)
INLET
HEIGHT (B2)
INLET SIZE OUTLET SIZE
AJ-80A
Inches
66-1/4 28 15 2 2
CM
168.3 71.1 38.1 5.1 5.1
AJV-120A
Inches
66 28 15 2 2
CM
167.6 76.2 167.6 5.1 2.5
AJV-140A
Inches
88 30 19-1/2 2-1/2 2-1/2
CM
223.5 76.2 49.5 6.4 6.4
AJV-200A
Inches
84 36 21 2-1/2 2-1/2
CM
213.4 91.4 53.3 6.4 6.4
AJV-250A
Inches
96 36 21 2-1/2 2-1/2
CM
243.8 91.4 53.3 6.4 6.4
AJV-350A
Inches
99 42 22-1/2 2-1/2 2-1/2
CM
251.5 106.7 57.2 6.4 6.4
AJV-400A
Inches
105 42 22-1/2 2-1/2 2-1/2
CM
233.7 106.7 57.2 6.4 6.4
AJV-500TA
Inches
101 48 24 3 3
CM
256.5 121.9 61 6.4 6.4
AJV-500A
Inches
86 54 25-1/5 3 3
CM
218.4 137.2 64.8 6.4 6.4
AJV-750A
Inches
118 54 24-1/2 3 3
CM
299.7 137.2 62.2 6.4 6.4
AJV-1000A
Inches
150 54 25-1/2 3 3
CM
381 137.2 64.8 6.4 6.4
BOILER DATA
VERTICAL STORAGE VESSEL DATA
MODEL
NUMBER
INCHES
OR
CM
DIMENSIONS
LENGTH
(A1)
OUTLET DIM
(A2)
WIDTH
(B1)
HEIGHT
(B2)
INLET
HEIGHT (B3)
INLET
SIZE
OUTLET
SIZE
AJH-200
Inches
77 59 36 41 11 2-1/2 2-1/2
CM
195.6 149.9 91.4 104.1 27.9 6.4 6.4
AJH-350
Inches
93 72-1/2 42 47 14 2-1/2 2-1/2
CM
236.2 184.2 106.7 119.4 35.6 6.4 6.4
AJH-350
Inches
99 72-1/2 42 47 14 3 3
CM
251.5 184.2 106.7 119.4 35.6 7.6 7.6
AJH-350
Inches
94 73 48 53 14 3 3
CM
238.8 185.4 121.9 134.6 35.6 7.6 7.6
AJH-350
Inches
79 56-1/2 54 59 14 3 3
CM
200.7 143.5 137.2 149.9 35.6 7.6 7.6
AJH-350
Inches
111 88-1/2 54 59 14 3 3
CM
281.9 224.8 137.2 149.9 35.6 7.6 7.6
AJH-350
Inches
143 120-1/2 54 59 14 3 3
CM
363.2 306.1 137.2 149.9 35.6 7.6 7.6
HORIZONTAL STORAGE VESSEL DATA
Page 3
Commercial Gas Boilers
ACMSS00507
Page 3 of 4
The above are standard available configurations. Custom configurations designed to your specifications are available.Contact your local A. O. Smith Sales Representative for assistance.
TOTAL HOT WATER SUPPLY SYSTEM USING VF™BOILERS
Configuration H
Configuration P
Configuration V
Page 4
Commercial Gas Boilers
ACMSS00507
Page 4 of 4
DUAL-ENERGY SOURCE OPTION
• Storage tanks can be specified with an optional heat exchanger for winter heating using on-site hydronic heating boiler(s), switching to domestic hot water boiler(s) for summertime operation
• Water-to-water or steam-to-water heat exchangers available in single-wall or double-wall design
• Complete control packages can be factory-installed for “hook up and run” simplicity
PROFESSIONAL START-UP SERVICE FURNISHED
Assures optimum performance for each installation
MEETS ASHRAE/IESNA 90.1-1999
5 YEAR VF BOILER HEAT EXCHANGER WARRANTY
5 YEAR STORAGE TANK WARRANTY
For complete information, consult written warranty or
contact A. O. Smith
OTHER FEATURES:
ASME TEMPERATURE AND PRESSURE RELIEF VALVE #125
TANK TEMPERATURE SENSOR AND THERMOMETER
ISOLATION VALVES (BALL VALVES)
125 PSI TANK WORKING PRESSURE
ALL-BRONZE CIRCULATING PUMP LARGE SYSTEMS SHIPPED WITH SPLIT/
BOLT TOGETHER SKIDS FOR EASE OF SHIPPING AND INSTALLATION
OTHER OPTIONS:
150 AND 160 PSI TANK WORKING PRESSURES 11˝ X 15˝ MANHOLES
Tank Type (A=Skid Mounted, J=Jacketed, V=Vertical, H= Horizontal)
TOTAL HOT WATER SUPPLY SYSTEM USING VF™BOILERS
SUGGESTED SPECIFICATION
Hot Water Supply System - shall consist of A. O. SMITH Ac-U-Temp factory assembled unit Model No. __________. System shall be completely factory assembled and shall include the A.O. SMITH VF hot water supply boiler(s), with input of ____ BTU/H for (natural/propane) ____ gas and recovery capacity of _______ gph, and the A.O. SMITH glass-lined (cement/epoxy) hot water storage tank with ____ gallons capacity for ________ mounting (vertical-horizontal). System shall include properly sized circulator, inlet and outlet thermometers, tank temperature thermometer, relief valve, and tank temperature control. Entire system shall be rigidly mounted on welded steel skid base and shipped assembled to job site (Ac-U-Temp systems employing tanks too large for shipping as an assembled unit, will be shipped with the tank mounted on a split bolt-together skid). See VF Boiler Specification Sheet for boiler details. See A.O.Smith Storage Specification sheets for storage tank details.
Hot water supply boiler(s) and storage tank(s) shall have a 5 year limited warranty against corrosion as outlined in the written warranty
500 Tennessee Waltz Pkwy, Ashland City, TN 37015
For Technical Information and Automated Fax Service, call 800-527-1953.
A. O. Smith reserves the right to make product changes or improvements without prior notice.
©2007 A. O. Smith Corporation Printed in U.S.A.
www.hotwater.com
Loading...