A.O. Smith VW-500, VW-750, VW-1000, VW-1500 User Manual

Page 1
Domestic Hot Water Boilers
®
HOT WATER SUPPLY BOILERS
FEATURES
The VF™ Boiler is capable of fi ring from 100% to 25% or a 4:1 turndown ratio of rated input based on the current system demand. The VF’s modulating capability is virtually limitless, and the boiler’s output is based strictly on the current system demand and the required BTUs needed to maintain the desired system set point temperature.
ADVANCED HIGH EFFICIENCY, LOW NOx COMBUSTION TECHNOLOGY
Venturi-mixing gas/air ratio system - Works with variable speed blower to precisely mix
gas and air throughout fi ring range.
4:1 Turndown - Fully modulating capability prevents energy-stealing short cycling and
provides smooth system operation with higher overall system effi ciencies
VW-500
through
VW-2000
LOW NOx OPERATION
Complies with SCAQMD Rule 1146.2 and other Air Quality Management Districts with
similar requirements for low NOx emissions
ADVANCED MODULATING CONTROL
Includes remote tank temperature control to adjust tank temperature at the boiler -
Modulates the boiler to maintain tank set point temperature within +/-1 degree
Infi nite boiler output control between 25% and 100% fi re
LED read out - Provides current boiler status in plain English with help screens
to assist should a fault occur
Controls every electrical boiler function and provides on board diagnostics
iCOMM™ Compatible and can be monitored from remote locations.
Call 1.888.WATER02 for more information.
ALL BRONZE FACTORY MOUNTED PUMP
Integrally mounted, wired, and controlled by the boiler control
Factory-sized for proper fl ow between boiler and storage tank
Allows 50 equivalent feet of piping between boiler and tank
HIGH EFFICIENCY COPPER FIN TUBE HEAT EXCHANGER
Vertical straight tube 2 or 4 pass heat exchanger design encircles the
burner with a combustion chamber that is a 360° wall of copper fi n tubes
Rust-resistant operation - All internal heat exchanger non-copper surfaces are glasslined with A. O. Smith’s proprietary porcelain glass coating, which far exceeds competitive coatings
Impervious to thermal shock
COMPACT, LOW-PROFILE DESIGN
Zero clearance on sides for 500-1000 models, 4 inches on sides for 1500-2000 models
Ideal for multiple boiler installations
STANDARD VENT OR DIRECT VENT FLEXIBILITY
Standard vent confi guration, vertical or horizontal sidewall
Two-pipe direct venting vertical and/or horizontal sidewall, with all combustion makeup air drawn from outside the building
FACTORY START-UP INCLUDED
Required for activating warranty and assuring maximum operating performance. Contact your local sales representative or Authorized Start-Up Agent to arrange a FREE Certifi ed Start-Up.
Revised September 2010
Page 1 of 4
AOSDG25000
Page 2
®
CATEGORY IV LISTED
Requires AL29-4C gas tight rust resistant
venting material
PROFESSIONAL START-UP SERVICE INCLUDED
Assures optimum performance for each
installation
MEETS THE THERMAL EFFICIENCY AND STANDBY LOSS REQUIREMENTS OF THE U. S. DEPARTMENT OF ENERGY AND CURRENT EDITION ASHRAE/ IESNA 90.1
5-YEAR HEAT EXCHANGER WARRANTY
For complete information, consult written
warranty or contact A. O. Smith
OTHER VF™ BOILER FEATURES:
ASME 160# W.P.
ASME RATED PRESSURE RELIEF VALVE, 125 PSI.
FACTORY MOUNTED FLOW SWITCH
MEETS CSD-1 CODE-–FACTORY STANDARD
BRASS DRAIN VALVE
LOW GAS PRESSURE SWITCH
DIGITAL INLET/OUTLET
TEMPERATURE READOUT
MANUAL RESET HI-LIMIT
ALL BRONZE FACTORY MOUNTED PUMP
Domestic Hot Water Boilers
VF™ BOILER APPROVED OPTIONS:
SEQUENCING PANEL ALARM BUZZER SIDEWALL VENT KITS VERTICAL AND HORIZONTAL
DIRECT VENT KITS
SKID-MOUNTED SYSTEMS DRY CONTACTS FOR ANY
BOILER FAILURE
LOW WATER CUTOFF LP GAS
CUPRO-NICKEL HEAT EXCHANGER TUBES ENERGY MANAGEMENT INTERFACE ADAPTER (BacNet, Lowworks, for other contact Factory)
For Technical Information and Automated Fax Service, call 800-527-1953. A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Model
VW-500 500,000
VW-750 750,000
VW-1000 1,000,000
VW-1500 1,500,000
VW-2000 2,000,000
Note: Maximum gas supply pressure: 13.8˝ W.C. natural gas, 13.8˝ propane Minimum gas supply pressure: 4˝ W.C. natural gas, 8˝ propane Electrical Power: 120 Volts, 60 Hertz, 30 Amps..
Input
Rating
BTU/Hr.
Water
Flow
GPH
LPH
GPH
LPH
GPH
LPH
GPH
LPH
GPH
LPH
40 60 80 90
(22) (33) (44) (90) (56) (67) (78) 1,268 845 634 563 507 423 362 4,797 3,198 2,399 2,132 1,919 1,599 1,371 1,901 1,268 951 845 761 634 543 7,196 4,797 3,598 3,198 2,878 2,399 2,056 2,535 1,690 1,268 1,127 1,014 845 724 9,595 6,397 4,797 4,264 3,838 3,198 2,741 3,780
14,307
5,040
19,076
Temperature Rise - °F (°C)
100 120 140
2,520 1,890 1,680 1,512 1,260 1,080 9,538 7,154 6,359 5,723 4,769 4,088 3,360 2,520 2,240 2,016 1,680 1,440
12,718 9,538 8,478 7,631 6,359 5,450
Revised September 2010
www.hotwater.com
Page 2 of 4
AOSDG25000
Page 3
Domestic Hot Water Boilers
®
Model
Number
Input Output
20°F (11°C) t 30°F (17°C) ∆t
Maximum Flow Rate
Rating Rating GPM LPM P FT Pm GPM LPM P FT Pm GPM LPM P FT Pm GPM LPM P P m
Minimum Flow Rate
FT
Btu/hr Btu/hr
VW-500 500,000 421,500 42 159 1.8 0.5 28 106 1.3 0.4 42 159 1.8 0.5 28 106 1.3 0.4
VW-750 750,000 633,750 63 238 2.9 0.9 42 159 2.1 0.6 63 238 2.9 0.9 42 159 2.1 0.6
VW-1000 1,000,000 845,000 85 322 3.9 1.2 56 212 2.8 0.9 85 322 3.9 1.2 56 212 2.8 0.9
VW-1500 1,500,000 1,260,000 126 477 13 4 84 318 7 2 126 477 13 4 84 318 7 2
VW-2000 2,000,000 1,680,000 168 636 44 13 112 424 18 5 168 636 44 13 112 424 18 5
Notes: Head loss shown is through boiler only and allows for no additional piping
Dimensions and Shipping Weights
Model
Number
B
30.5
VW-500
VW-750
VW-1000
VW-1500
67
A
VW-2000
Water Inlet/
Outlet
Connections
2” 6” 4” 1” 56 30 37.5 22 30 31 36 45 450
2” 6” 4” 1” 62 30 37.5 28 30 31 42 51 575
2” 6” 4” 1” 71 30 37.5 34 30 31 48 59 750
2.5” 7” 6” 1.25” 67 30.5 61 23.5 37 40 43 56.5 1275
2.5” 7” 6” 1.25” 72 30.5 61 29.5 37 40 48 62 1380
Flue
Outlet
Diameter
Air Intake
Diameter
Gas
A B C D E F G H
Inlet
Approx.
Shipping
Weight
(Lbs.)
VF FRONT
VW-500 thru VW-1000
60.19
C
22.38
D
16.5
E
37.0
40.0
F
VF SIDE
Please note this product specification sheet is intended to assist with product selection. For the most current product installation and design instructions, please see the latest edition of the Instruction Manual available at www.hotwater.com or call your local A. O. Smith Sales Representative for assistance.
For Technical Information and Automated Fax Service, call 800-527-1953. A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Revised September 2010
VF BACK
G
www.hotwater.com
VW-1500 thru VW-2000
VF BACK
Gas
Inlet
³
Water Outlet
³
H
Flue
Outlet
³
³
³
Water Inlet
Air Intake
H
G
Page 3 of 4
AOSDG25000
Page 4
Domestic Hot Water Boilers
®
SUGGESTED SPECIFICATION
The gas-fired hot water supply boiler(s) shall be A. O. Smith VF Boiler model VW______ having an input rating of _______ BTU/hr and capable of supplying no less than ______
GPH at a 100°F temperature rise when fired with (Natural/Propane) gas. 1) The boiler shall bear the ASME “H” stamp and shall be National Board registered (CRN in Canada) for
160 PSI working pressure. 2) The boiler(s) shall be equipped with a factory-installed 125# PSIG ASME Pressure Relief Valve. 3) The boiler(s) shall be design-tested and certified
to the ANSIZ21.13 - CSA 4.9 Standards and approved by CSA International. 4) Complies with SCAQMD Rule 1146.2 and other Air Quality Management Districts with similar
requirements for low NOx emmissions.The heat exchanger shall: 1) Incorporate a vertical straight tube 2 or 4 multi-pass copper fin tube heat exchanger design. 2) Be circular,
encompassing the entire burner and forming the combustion chamber. 3) The tubes shall be rolled into ASME grade steel glass lined tube sheets. 4) The headers shall be ASME
160 psi welded glass lined steel. 5) For ease of service and access, headers shall be bolted and sealed to the tube sheets with silicone “O” rings, having a temperature rating of
over 400°F. Tube access plugs are not acceptable. 6) To provide rust-resistant operation, all internal heat exchanger water contact surfaces shall be copper or glass lined steel. 7)
The heat exchanger shall be immune to thermal shock. 8) All non-heating surface heat exchanger components (headers, tube sheets, header bolts and gaskets) shall be outside
and away from the combustion and flue collection areas, only the copper fin tubes shall be exposed to the products of combustion. 9) The sealed heat exchanger flue collection
system shall be constructed of stainless steel. 10) The heat exchanger shall be approved for inlet water temperatures down to 120°F. 10) The entire heat exchanger shall carry a
five (5) year warranty. Boiler Pump: 1) The hot water supply boiler(s) shall be supplied with a factory sized and wired all bronze circulating pump. 2) The pump shall be interfaced
with and managed by the boiler’s control and cycled as needed for most efficient operation. Burner: 1)The gas burner shall be constructed of high temperature stainless steel
and utilize a woven metal fiber mesh covering, be warranted for 5 years, and fire in a radial 360-degree flame pattern. 2) The burner shall be capable of infinitely modulating
between 25% and 100% fire (4:1 turndown) with smooth starts and clean combustion. Boiler Controls: 1) All electrical boiler functions shall be controlled, operated, and monitored
by a microprocessor-based control. 2) The microprocessor shall control and modulate the burner based on current system output requirements to maintain the boiler set point
temperature and be accurate to within plus or minus 1°F. 3) The hot surface ignition system shall employ a separate flame sensor for maximum reliability. 4) The boiler control shall
provide on board diagnostics with digital singular fault code read outs in plain English and help screens for additional trouble shooting assistance if needed. 5) The boiler shall be
supplied with a remote tank thermistor for sensing and controlling the hot water storage tank temperature upto 1,000 feet away. 6) Provisions for connecting a remote thermistor,
alarm bell, and alternate temperature controller must be provided. 7) Factory mounted and wired flow switch, blower prover, and blocked flue switches shall be provided. 8)
The gastrain shall meet or exceed the requirements of ANSIZ21.13 - CSA 4.9 and include gas pressure regulator, manual gas cock, redundant safety gas valve, operating control
valve, and plugged pressure test tapings. Venting: 1) The boiler shall be certified for direct horizontal through-the-wall venting or direct vertical venting; in addition to sidewall or
conventional vertical venting. 2) The boiler shall be capable of horizontal sidewall or direct venting up to 70 equivalent feet without the aid of any optional sidewalll vent fans or
blowers. Factory Start-Up Included-Required for activating warranty and assuring maximum operating performance. 1) The boiler shall meet the thermal efficiency and standby
loss requirements of the U. S. Department of Energy and current edition ASHRAE/IESNA 90.1. 2) Boiler should incorporate the iCOMM™ system connection for remote monitoring,
leak detection and fault alert.
For Technical Information and Automated Fax Service, call 800-527-1953. A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Revised September 2010