A.O. Smith VW-500, VW-750, VW-1000, VW-1500 User Manual

Domestic Hot Water Boilers
®
HOT WATER SUPPLY BOILERS
FEATURES
The VF™ Boiler is capable of fi ring from 100% to 25% or a 4:1 turndown ratio of rated input based on the current system demand. The VF’s modulating capability is virtually limitless, and the boiler’s output is based strictly on the current system demand and the required BTUs needed to maintain the desired system set point temperature.
ADVANCED HIGH EFFICIENCY, LOW NOx COMBUSTION TECHNOLOGY
Venturi-mixing gas/air ratio system - Works with variable speed blower to precisely mix
gas and air throughout fi ring range.
4:1 Turndown - Fully modulating capability prevents energy-stealing short cycling and
provides smooth system operation with higher overall system effi ciencies
VW-500
through
VW-2000
LOW NOx OPERATION
Complies with SCAQMD Rule 1146.2 and other Air Quality Management Districts with
similar requirements for low NOx emissions
ADVANCED MODULATING CONTROL
Includes remote tank temperature control to adjust tank temperature at the boiler -
Modulates the boiler to maintain tank set point temperature within +/-1 degree
Infi nite boiler output control between 25% and 100% fi re
LED read out - Provides current boiler status in plain English with help screens
to assist should a fault occur
Controls every electrical boiler function and provides on board diagnostics
iCOMM™ Compatible and can be monitored from remote locations.
Call 1.888.WATER02 for more information.
ALL BRONZE FACTORY MOUNTED PUMP
Integrally mounted, wired, and controlled by the boiler control
Factory-sized for proper fl ow between boiler and storage tank
Allows 50 equivalent feet of piping between boiler and tank
HIGH EFFICIENCY COPPER FIN TUBE HEAT EXCHANGER
Vertical straight tube 2 or 4 pass heat exchanger design encircles the
burner with a combustion chamber that is a 360° wall of copper fi n tubes
Rust-resistant operation - All internal heat exchanger non-copper surfaces are glasslined with A. O. Smith’s proprietary porcelain glass coating, which far exceeds competitive coatings
Impervious to thermal shock
COMPACT, LOW-PROFILE DESIGN
Zero clearance on sides for 500-1000 models, 4 inches on sides for 1500-2000 models
Ideal for multiple boiler installations
STANDARD VENT OR DIRECT VENT FLEXIBILITY
Standard vent confi guration, vertical or horizontal sidewall
Two-pipe direct venting vertical and/or horizontal sidewall, with all combustion makeup air drawn from outside the building
FACTORY START-UP INCLUDED
Required for activating warranty and assuring maximum operating performance. Contact your local sales representative or Authorized Start-Up Agent to arrange a FREE Certifi ed Start-Up.
Revised September 2010
Page 1 of 4
AOSDG25000
®
CATEGORY IV LISTED
Requires AL29-4C gas tight rust resistant
venting material
PROFESSIONAL START-UP SERVICE INCLUDED
Assures optimum performance for each
installation
MEETS THE THERMAL EFFICIENCY AND STANDBY LOSS REQUIREMENTS OF THE U. S. DEPARTMENT OF ENERGY AND CURRENT EDITION ASHRAE/ IESNA 90.1
5-YEAR HEAT EXCHANGER WARRANTY
For complete information, consult written
warranty or contact A. O. Smith
OTHER VF™ BOILER FEATURES:
ASME 160# W.P.
ASME RATED PRESSURE RELIEF VALVE, 125 PSI.
FACTORY MOUNTED FLOW SWITCH
MEETS CSD-1 CODE-–FACTORY STANDARD
BRASS DRAIN VALVE
LOW GAS PRESSURE SWITCH
DIGITAL INLET/OUTLET
TEMPERATURE READOUT
MANUAL RESET HI-LIMIT
ALL BRONZE FACTORY MOUNTED PUMP
Domestic Hot Water Boilers
VF™ BOILER APPROVED OPTIONS:
SEQUENCING PANEL ALARM BUZZER SIDEWALL VENT KITS VERTICAL AND HORIZONTAL
DIRECT VENT KITS
SKID-MOUNTED SYSTEMS DRY CONTACTS FOR ANY
BOILER FAILURE
LOW WATER CUTOFF LP GAS
CUPRO-NICKEL HEAT EXCHANGER TUBES ENERGY MANAGEMENT INTERFACE ADAPTER (BacNet, Lowworks, for other contact Factory)
For Technical Information and Automated Fax Service, call 800-527-1953. A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Model
VW-500 500,000
VW-750 750,000
VW-1000 1,000,000
VW-1500 1,500,000
VW-2000 2,000,000
Note: Maximum gas supply pressure: 13.8˝ W.C. natural gas, 13.8˝ propane Minimum gas supply pressure: 4˝ W.C. natural gas, 8˝ propane Electrical Power: 120 Volts, 60 Hertz, 30 Amps..
Input
Rating
BTU/Hr.
Water
Flow
GPH
LPH
GPH
LPH
GPH
LPH
GPH
LPH
GPH
LPH
40 60 80 90
(22) (33) (44) (90) (56) (67) (78) 1,268 845 634 563 507 423 362 4,797 3,198 2,399 2,132 1,919 1,599 1,371 1,901 1,268 951 845 761 634 543 7,196 4,797 3,598 3,198 2,878 2,399 2,056 2,535 1,690 1,268 1,127 1,014 845 724 9,595 6,397 4,797 4,264 3,838 3,198 2,741 3,780
14,307
5,040
19,076
Temperature Rise - °F (°C)
100 120 140
2,520 1,890 1,680 1,512 1,260 1,080 9,538 7,154 6,359 5,723 4,769 4,088 3,360 2,520 2,240 2,016 1,680 1,440
12,718 9,538 8,478 7,631 6,359 5,450
Revised September 2010
www.hotwater.com
Page 2 of 4
AOSDG25000
Loading...