Boiler/Building Management Interface (BMI) For  
Hydronic and Domestic Hot Water Heating Boilers
FEATURES
NEW BOILER/BUILDING MANAGEMENT INTERFACE (BMI) - Provides 
connections for energy management systems and/or boiler sequencing controls and 
allows these systems to control the firing rate of all Genesis and VF Boiler models.
WORKS WITH GENESIS STAGE FIRED MODELS AND MODULATING 
VF BOILER MODELS - 
systems or boiler sequencers to control the stage firing of 2, 3, and 4 stage Genesis 
Boilers. When used with modulating VF Boilers the BMI accepts a 0 to 10 volt signal 
from energy management systems or boiler sequencers for a fully modulating 
system with optimum temperature control and maximum system efficiency.
PROVIDES SMOOTH SYSTEM OPERATION AND PREVENTS BOILER 
SHORT CYCLING 
systems and/or boiler sequencing controls are used to control the firing rate to 
match the heat demand of the facility. By providing access to the firing rate of 
the boiler, the energy management systems and/or boiler sequencing controls can 
better control the system temperature which helps to prevent boiler short cycling 
and provides smoother overall system operation.
Note - Can be ordered with the boiler and factory installed or ordered as a kit for 
field upgrade.
Provides contacts and allows energy management 
- The BMI is recommended wherever energy management 
A. O. Smith
Part 
# 9007866005
RECOMMENDED FOR USE WITH A. O. SMITH PROVIDED TEKMAR 
CONTROLS 
9005409105 - tekmar 274 Control - Can manage 4 - on/off boilers, 2 - 2-stage boilers,  
 1 - 3-stage boilers, or 1 - 4-Stage boiler (Has set point for domestic hot water and 
 outdoor reset for hydronic heating systems)
 9005408105 - tekmar 268 Control - Can manage 9 - on/off boilers, 4 - 2-stage boilers, 
 3 - 3-stage boilers, or 2 - 4-Stage boilers (Has set point for domestic hot water and 
 outdoor reset for hydronic heating systems)
 9007563005 - tekmar 275 Control - Can manage 1 to 4 modulating boilers with 0 to 
 10 Volt Signal (Has set point for domestic hot water and outdoor reset for hydronic 
 heating systems)
Please note that the above listed tekmar controls can all be used for both hydronic heating 
and/or domestic hot water heating systems. All three controls include a remote 1/2” tank 
temperature probe well to be installed in the hot water storage tank or hydronic heating 
return loop for optimum temperature sensing.
- 
Page 1 of 2
AOSBG25150
 

Boiler/Building Management Interface (BMI) For  
Hydronic and Domestic Hot Water Heating Boilers
Factory Mounting Location
VF 500, 750, 1000
5.5"
5"
12"
1.5"
2.25"
VF 1500 and 2000
6.75"
1.5"
1.5"
Genesis 300 to 750
Genesis 1000 to 2500
For Technical Information and Automated Fax Service, call 800-527-1953. A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
July 2011R
www.hotwater.com 
Page 2 of 2
AOSBG25150