A. O. Smith VF1500 User Manual

Boiler/Building Management Interface (BMI) For Hydronic and Domestic Hot Water Heating Boilers
FEATURES
NEW BOILER/BUILDING MANAGEMENT INTERFACE (BMI) - Provides
connections for energy management systems and/or boiler sequencing controls and
allows these systems to control the firing rate of all Genesis and VF Boiler models.
WORKS WITH GENESIS STAGE FIRED MODELS AND MODULATING VF BOILER MODELS -
systems or boiler sequencers to control the stage firing of 2, 3, and 4 stage Genesis
Boilers. When used with modulating VF Boilers the BMI accepts a 0 to 10 volt signal
from energy management systems or boiler sequencers for a fully modulating
system with optimum temperature control and maximum system efficiency.
PROVIDES SMOOTH SYSTEM OPERATION AND PREVENTS BOILER SHORT CYCLING
systems and/or boiler sequencing controls are used to control the firing rate to
match the heat demand of the facility. By providing access to the firing rate of
the boiler, the energy management systems and/or boiler sequencing controls can
better control the system temperature which helps to prevent boiler short cycling
and provides smoother overall system operation.
Note - Can be ordered with the boiler and factory installed or ordered as a kit for
field upgrade.
Provides contacts and allows energy management
- The BMI is recommended wherever energy management
A. O. Smith
Part
RECOMMENDED FOR USE WITH A. O. SMITH PROVIDED TEKMAR CONTROLS
9005409105 - tekmar 274 Control - Can manage 4 - on/off boilers, 2 - 2-stage boilers, 1 - 3-stage boilers, or 1 - 4-Stage boiler (Has set point for domestic hot water and outdoor reset for hydronic heating systems)
9005408105 - tekmar 268 Control - Can manage 9 - on/off boilers, 4 - 2-stage boilers, 3 - 3-stage boilers, or 2 - 4-Stage boilers (Has set point for domestic hot water and outdoor reset for hydronic heating systems)
9007563005 - tekmar 275 Control - Can manage 1 to 4 modulating boilers with 0 to 10 Volt Signal (Has set point for domestic hot water and outdoor reset for hydronic heating systems)
Please note that the above listed tekmar controls can all be used for both hydronic heating
and/or domestic hot water heating systems. All three controls include a remote 1/2” tank
temperature probe well to be installed in the hot water storage tank or hydronic heating
return loop for optimum temperature sensing.
-
Page 1 of 2
AOSBG25150
Boiler/Building Management Interface (BMI) For Hydronic and Domestic Hot Water Heating Boilers
Factory Mounting Location
VF 500, 750, 1000
5.5"
5"
12"
1.5"
2.25"
VF 1500 and 2000
6.75"
1.5"
1.5"
Genesis 300 to 750
Genesis 1000 to 2500
For Technical Information and Automated Fax Service, call 800-527-1953. A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.