WARNING: If the information in this
manual is not followed exactly, a fire or
explosion may result causing property
damage, personal injury or loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
— WHA T TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the fire department.
MODELS:
VB/VW-500, 750 AND 1000
SERIES 100/101
— Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
MC BEE, SC., RENTON, WA.,
STRATFORD-ONTARIO, VELDHOVEN-THE NETHERLANDS,
NANJING, CHINA
www.hotwater.com / email: parts@hotwater.com
PRINTED 0207212800-000
1
SAFE INSTALLATION, USE AND SERVICE
Your safety and the safety of others is extremely important in the installation, use, and servicing of this boiler.
Many safety-related messages and instructions have been provided in this manual and on your own boiler to warn you and
others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very
important that the meaning of each safety message is understood by you and others who install, use, or service this boiler.
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message
and how to avoid the risk of injury.
IMPORT ANT DEFINITIONS
• Qualified Installer: A qualified installer must have ability equivalent to a licensed tradesman in the fields of plumbing,
air supply , venting and gas supply, including a thorough understanding of the requirement s of the National Fuel Gas
Code as it relates to the installation of gas fired boilers. The qualified installer must have a thorough understanding of
this instruction manual.
• Service Agency: A service agency also must have ability equivalent to a licensed tradesman in the fields of plumbing,
air supply , venting and gas supply, including a thorough understanding of the requirement s of the National Fuel Gas
Code as it relates to the installation of gas fired boilers. The service agency must also have a thorough
understanding of this instruction manual, and be able to perform repairs strictly in accordance with the service guidelines
provided by the manufacturer .
• Gas Supplier: The Natural Gas or Propane Utility or service who supplies gas for utilization by the gas burning
appliances within this application. The gas supplier typically has responsibility for the inspection and code approval of
gas piping up to and including the Natural Gas meter or Propane storage tank of a building. Many gas suppliers also
offer service and inspection of appliances within the building.
This design complies with the current edition of the ANSI
Z21.13 low-pressure boiler standard.
Compliance under this standard implies that when the boiler
underwent test, the gas manifold and control assembly provided
on the boiler met safe lighting and other performance criteria.
Detailed installation diagrams are found in this manual. These
diagrams will serve to provide the installer a reference for the
materials and methods of piping necessary. It is essential that
all water, gas piping and wiring be installed as shown on the
diagrams. You should thoroughly read and understand this
manual before installation and/or operation of this boiler.
The factory warranty will be
improperly installed or operated.
void if the boiler(s) have been
AL 29-4C® is a registered trademark of Allegheny Ludlum
Corporation.
In addition to these instructions, the boiler(s) shall be installed in
accordance with those installation regulations in force in the local
area where the installation is to be made. These shall be carefully
followed in all cases. Authorities having jurisdiction should be
consulted before installations are made.
In the absence of local codes, the installation must comply with
the current editions, as follows:
In the United States:
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the
National Electric Code, NFPA 70.
6
GROUNDING INSTRUCTIONS
This boiler must be grounded in accordance with the National
Electrical Code and/or local codes. Boiler is polarity sensitive;
correct wiring is imperative for proper operation.
LP gas is present or even suspected, do not attempt to
find the cause yourself. Leave the building, leaving doors
open to ventilate, then call your gas supplier or service
agent. Keep area clear until a service call has been
made.
This boiler must be connected to a grounded metal, permanent
wiring system, or an equipment grounding conductor must be run
with the circuit conductors and connected to the equipment
grounding terminal or lead on the boiler.
INLET W A TER CONSIDERA TIONS
To minimize the amount of condensate, a minimum inlet
water temperature to the heat exchanger of 120°F (49°C)
shall be maintained. This temperature can be acquired by
returning 120°F (49°C) water from the remote storage tank
to the boiler or by installing a by-pass loop between the
boiler’s inlet and outlet connections. When installing a bypass loop, a remote probe MUST be used, see SYSTEM
INSTALLATION.
Circulating water through the boiler and to the remote storage
tank (if applicable) is accomplished by a pump on VW models
only. For hot water heating systems using the VB model, the
circulating pump is NOT provided on standard models (optional)
and must be field installed.
CORRECT GAS
MAKE SURE THE GAS ON WHICH THE BOILER WILL
OPERATE IS THE SAME AS THAT SPECIFIED ON THE
BOILER RATING PLATE. DO NOT INSTALL THE BOILER
IF EQUIPPED FOR A DIFFERENT TYPE OF GAS —
CONSULT YOUR SUPPLIER.
At times you may not be able to smell an LP gas leak.
One cause is odor fade, which is a loss of the chemical
odorant that gives LP gas its distinctive smell. Another
cause can be your physical condition, such as having a
cold or diminishing sense of smell with age. For these
reasons, the use of a propane gas detector is
recommended.
IF YOU EXPERIENCE AN OUT OF GAS SITUATION, DO
NOT TRY TO RELIGHT APPLIANCES YOURSELF. Call
your local service agent. Only trained LP professionals
should conduct the required safety checks in accordance
with industry standards.
HIGH ALTITUDE INSTALLATIONS
PRECAUTIONS
IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO
NOT OPERATE UNTIL ALL CORRECTIVE STEPS HAVE
BEEN MADE BY A QUALIFIED SERVICEMAN:
1. EXPOSURE TO FIRE.
2. IF DAMAGED.
3. FIRING WITHOUT WATER.
4. SOOTING.
IF THE BOILER HAS BEEN EXPOSED TO FLOODING,
IT MUST BE REPLACED.
LIQUEFIED PETROLEUM GAS MODELS
Boilers for propane or liquefied petroleum gas (LPG) are different
from natural gas models. A natural gas boiler will not function
safely on LP gas and no attempt should be made to convert
a boiler from natural gas to LP gas.
LP gas must be used with great caution. It is highly
explosive and heavier than air. It collects first in the low
areas making its odor difficult to detect at nose level. If
Rated inputs are suitable up to 6000 feet (1829m)
elevation. Consult the factory for installation at altitudes
over 6000 feet (1829m).
FIELD INSTALLED COMPONENTS
When installing the boiler, the following components MUST
be installed:
1) Circulating Pump (Hydronic)
2) Tank Temperature Control Probe (Hot Water Supply)
3) Remote Temperature Control Probe (Hydronic)
4) Storage Tank T&P Relief Valve
5) Manual Gas Shutoff Valve (Supply)
Check the FEATURES AND CONTROLS section for further
information.
7
FEATURES
THE CONTROL SYSTEM
The control system consists of four basic components:
1) Modulation Control Board (MCB); 2) Power Distribution Board
(PDB); 3) Variable Frequency Drive (VFD), see Figure 2; 4)
User Interface Module, see Figure 19. The Modulation Control
Board and the Power Distribution Board are located in the control
box and can be accessed by opening the front door of the
unit. The User Interface Module is attached to the front door
panel. Every system will have one Modulation Control Board
(MCB), one Power Distribution Board (PDB), and one User Interface
Module (UIM).
The MCB contains dipswitches which are used to configure
the boiler for several different control options, see the Control
System Section.
FIGURE 2.
HOT SURF ACE IGNITER
The Hot Surface Igniter is a device that ignites the main burner by high
temperature (>1800°F) [982°C], see Figure 3. The igniter is made of
recrystallized silicon carbide, and when 120 V AC is applied to the igniter,
sufficient heat is generated to ignite the main burner. Although
improvements have been made to strengthen the igniter , it is still fragile
and care must be taken in handling the igniter to prevent breakage.
The high BPS closes only when the blower is in pre and post purge.
If the high BPS closes at any time during the heating cycle, the
boiler will shut off.
OPTIONAL LOW/HIGH GAS SWITCH
This VF boiler is available with optional low and high gas pressure
switches which meet the CSD-1 code requirements, see Figure 5.
The low gas switch is normally closed and remains closed unless
pressure falls below the preset pressure. The high gas switch is
normally closed and remains closed unless pressure exceeds the
preset pressure.
FIGURE 5. LOW/HIGH GAS PRESSURE SWITCH.
W ATER FLOW SWITCH
The water flow switch is installed at the boiler outlet to
prevent burner operation in the event of inadequate water
flow through the boiler. It is a normally open switch that will
close its contacts when increasing water flow rate is detected.
The water flow switch is factory-set. The contacts will open
when the flow rate drops below the factory setting causing
the gas valve to close which will turn off the gas to the
burner, see Figure 6. Under no circumstances shall the
flow switch be tampered with or bypassed. Doing so may
cause damage to the heat exchanger not covered under
the warranty.
FIGURE 3.
FIGURE 4.
BLOCKED EXHAUST SWITCH
The Blocked Exhaust Switch, see Figure 4, ensures that the vent
system is clear. This exhaust switch is normally closed and only
opens on fault conditions.
BLOWER PROVER SWITCH
This VF boiler has two blower prover switches (BPS). The low
blower prover switch is a single-pole, normally open pressure switch
that closes on increased negative pressure. The low BPS closes
when the blower starts and remains closed during the operation of
the heating cycle.
The second BPS is the high BPS. It is also a single-pole, normally
open pressure switch that closes on increased negative pressure.
FIGURE 6. WATER FLOW SWITCH.
FLAME SENSOR
Each Boiler is equipped with two flame senors coupled together
to detect the presence of the burner flames at high and low
fire conditions. These flame rods work together as one to
sense the flame. If no flame is sensed, the gas valve(s) will close
automatically . If no flame is sensed on three ignition trials, the boiler
will lock out. In the event of a lockout, depress the SELECT button
on the display board to restart the boiler.
8
WATER TEMPERATURE LIMIT CONTROLS
FOR HOT WATER HEATING BOILERS-VB models, a remote
probe is supplied due to the various types of systems and operating
conditions. A remote probe can be used as an option to control
loop temperature and unit staging. Additionally, the inlet
temperature probe can be used as the loop thermostat in some
heating applications. The remote probe connects to designated
wires in the junction box at the rear of the boiler, refer to the PROBE
INSTALLATION section. Do not operate this boiler using the
internal high limits only; use a remote probe or operating
thermostat to control system temperatures.
The “V(B/W)” models incorporate an outlet water probe consisting
of two limit controls:
1. An adjustable automatic high limit control that can be set as
high as either 210°F (99°C) or 235°F (113°C), depending on
the application.
2. A fixed manual high limit (ECO), factory set at 244°F (118°C). If
the manual reset should open due to high temperature, the
gas valves will close and the unit will go into lockout. If lockout
occurs, push the SELECTION button on the UIM to restart the boiler.
ON/OFF SWITCH
The ON/OFF Switch is a single-pole, single-throw rocker switch.
This switch provides 120V from the line source to the boiler.
CIRCULA TING PUMP
HOT WATER SUPPLY BOILER-VW, the circulating pump is
integral to the VW models. This pump has been lubricated at
the factory, and future lubrication should be in accordance
with the motor manufacturer’s instructions provided as a
supplement to this manual.
FOR HOT WATER HEATING BOILERS-VB MODELS, the
circulating pump is NOT provided on standard models (optional)
and must be obtained and installed in the field.
LOW WATER CUTOFF (Optional)
If low water detection is required by the authorities having
jurisdiction, a low water cutoff switch should be installed next to
the boiler in the outlet water line as shown in Figure 13. The switch
should receive periodic (every six months) inspection to assure
proper operation. A Low Water Cutoff device of the float type should
be flushed every six months.
SAFETY RELIEF V AL VE
NOTE: If a system pump is to be installed on a VB
model, the maximum rating of the pump motor must
not exceed 1 hp.
REMOTE PROBE
FOR HOT WATER SUPPLY BOILERS-VW models, a remote
probe is supplied with each hot water supply boiler. The inlet water
temperature and the tank temperature are displayed separately
on the default menu screen.
Note: The remote probe must be designated as the controlling probe
using dipswitch “4” on MCB before it can be used for VW hot water
supply applications, see page 29 (MCB -T en Position Dip Switch).
“Pigtails” of field-supplied yellow wires located in the rear of
the unit in the junction box should be spliced to “pigtails” of
remote probe and connected in the junction box. See Figure 7
for probe installation.
Encase field-supplied wires between remote probe and junction box with
1/2" field supplied conduit. "Pigtails" of field-supplied wires should be
spliced to "pigtails" of remote probe. This conduit and wiring should be
separate from any other conduit/wiring to guard against EMI
(electromagnetic interference).
The purpose of a safety relief valve is to avoid excessive pressure
or temperature into the steam range which may cause scalding at
fixtures, tank explosion, system damage, or boiler damage.
To avoid scalding or water damage, a drain line must be
connected to a safety relief valve to direct discharge to a safe
FIGURE 7. REMOTE PROBE INSTALLATION.
9
location. A drain line must not contain any valves between the
boiler and the relief valve, or the relief valve and the drain exit. In
addition, there should not be any restrictions in a drain line nor
should it be routed through areas where freezing conditions might
occur. Do not thread or cap the drain line exit. Restricting or
blocking a drain line will defeat the purpose of the safety relief
valve and may create an unsafe condition. Install a drain line
with a downward slope such that it will naturally drain itself.
Your local code authority may have other specific safety relief
valve requirements not covered below. If any pressure relief valve
is replaced, the replacement valve must comply with the current
version of the ASME Boiler and Pressure Vessel Code, Section
IV (“HEATING BOILERS”).
Select a relief valve with a discharge rating NOTLESS than the
boiler input, and a set pressure NOT EXCEEDING the working
pressure of any component in the system.
FOR VW HOT WATER SUPPLY BOILERS, the units are shipped
with a 125 psi (860kPa) pressure relief valve that must be installed
in the water outlet as near to the boiler as possible.
In addition, a CSA design-certified and ASME-rated temperature
and pressure (T&P) relief valve must be installed on each and
every water storage tank in the hot water supply system. The T& P
relief valve must comply with the applicable construction provisions
of the
Devices for Hot Water Supply Systems, ANSI Z21.22 or CAN/
CSA-B149.1-00, or current edition. The T&P relief valve must be
of the automatic reset type and not embody a single-use type
fusible plug, cartridge or linkage.
The T&P relief valve should have a temperature rating of 210°F
(99°C), a pressure rating NOT exceeding the lowest rated working
pressure of any system component, and a discharge capacity
exceeding the total input of the water boilers supplying water to the
storage tank.
Locate the T&P relief valve (a) in the top of the tank, or (b) in the side
of the tank on a centerline within the upper 6 inches (152mm) of the
top of the tank, see Figures 13 and 14. The tapping shall be threaded
in accordance with the current edition of the Standard for Pipe Threads,
General Purpose (inch), ANSI/ASME B1.20.1. The location of, or
intended location for, the T&P relief valve shall be readily accessible
for servicing or replacement.
Standard for Relief Valves and Automatic Gas Shutoff
This ASME-rated valve has a discharge capacity that exceeds the
maximum boiler input rating and a pressure rating that does not
exceed the maximum working pressure shown on the boiler rating plate.
GENERAL
REQUIRED ABILITY
INSTALLATION OR SERVICE OF THIS BOILER REQUIRES
ABILITY EQUIV ALENT TO THAT OF A LICENSED TRADESMAN
IN THE FIELD INVOLVED. PLUMBING , AIR SUPPLY, VENTING,
GAS SUPPLY, AND ELECTRICAL WORK ARE REQUIRED.
LOCATION
When installing the boiler, consideration must be given to proper
location. The location selected should provide adequate air supply
and be as centralized with the piping system as possible.
FOR VB HOT WATER HEATING BOILERS, the units are shipped
with a 50 psi (345kPa) pressure relief valve. This relief valve must
be installed in the water outlet as near to the boiler as possible.
If the boiler is installed above radiation level, a Low Water Cutoff
Device must be installed in the boiler outlet at the time of installation.
PANELS AND COVERS
All panels and covers (e.g. control and junction box covers;
front, side and rear panels of boiler, see Figure 8) MUST be in
place after service and/or before operation of the boiler. This
will ensure that all gas ignition components will be protected
from water.
The VF is a low-pressure boiler (Category IV) to be used as either
hot water supply (domestic/commercial water heating) or hot water
heating (hydronic) application. Category IV boilers operate with a
positive vent pressure and with a vent gas temperature less than
120°F (49°C) above its dew point. Category IV appliances are
often termed “High Efficiency” appliances.
10
FIGURE 8.
CHEMICAL VAPOR CORROSION
Boiler corrosion and component failure can be caused by the
heating and breakdown of airborne chemical vapors. Spray can
propellants, cleaning solvents, refrigerator and air conditioning
refrigerants, swimming pool chemicals, calcium and sodium
chloride (water softener salt), waxes, and process chemicals are
typical compounds which are potentially corrosive. These materials
are corrosive at very low concentration levels with little or no odor
to reveal their presence.
Products of this sort should not be stored near the boiler . Also, air
which is brought in contact with the boiler should not contain any
of these chemicals. If necessary, uncontaminated air should be
obtained from remote or outside sources. Failure to observe this
requirement will void the warranty.
shall be wide enough to allow the boiler to enter or to permit the
replacement of another appliance such as a boiler.
LEVELING
Each unit should be checked after installat ion to be cer tain
that it is level.
If the unit is not level, obtain and insert shims under the feet at the
frame base to correct this condition.
AIR REQUIREMENTS
INST ALLA TION CLEARANCES
This boiler MUST NOT be installed on carpeted floors. This boiler is
approved for installation on combustible flooring in an alcove with
minimum clearances to combustibles of:
4" (1 02mm) Rear; 0" (0mm) T op and Sides; 6" (152mm) Vent. 2” (51mm)
clearance is allowable from combustible construction for hot water pipes.
Sufficient area should be provided at the front and rear of the unit for
proper servicing. Service clearances of 24" (610mm) in front, rear, top
and sides are recommended. In a utility room installation, the door opening
UNCONFINED SPACE
In buildings of conventional frame, brick or stone construction,
unconfined spaces may provide adequate air for combustion.
If the unconfined space is within a building of tight construction
(buildings using the following construction: weather stripping, heavy
insulation, caulking, vapor barrier, etc.), air for combustion, ventilation,
and draft hood dilution must be obtained from outdoors or spaces freely
FIGURE 9. SIDEWALL EXHAUST VENTING
11
communicating with the outdoors. The installation instructions for
confined spaces in tightly constructed buildings must be followed to
ensure adequate air supply .
CONFINED SPACE
When drawing combustion and dilution air from inside a conventionally
constructed building to a confined space, such a space shall be provided
with two permanent openings, ONE IN OR WITHIN 12 INCHES
(305mm) OF THE ENCLOSURE TOP AND ONE IN OR WITHIN 12
INCHES (305mm) OF THE ENCLOSURE BOTTOM. Each opening
shall have a free area of at least one square inch per 1000 Btu/hr
(2,225mm
2
per kw) of the total input of all appliances in the enclosure,
but not less than 100 square inches (645cm2).
If the confined space is within a building of tight construction, air for
combustion, ventilation and draft hood dilution must be obtained
from outdoors. When directly communicating with the outdoors or
communicating with the outdoors through vertical ducts, two
VENTING
permanent openings, located in the aforementioned manner, shall
be provided. Each opening shall have a free area of not less than
one square inch per 4000 Btu/hr (551mm
2
per kw) of the total input
of all appliances in the enclosure. If horizontal ducts are used, each
opening shall have a free area of not less than one square inch per
2000 Btu/hr (1,101mm
2
per kw) of the total input of all appliances in
the enclosure.
Where power vented equipment is used in the same room as the
boiler, sufficient air openings must be supplied.
UNDERSIZED OPENINGS MAY RESULT IN INSUFFICIENT AIR FOR
COMBUSTION.
Where an exhaust fan is installed in the same room with the
boiler, sufficient openings for air must be provided in the walls.
UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN
INTO THE ROOM THROUGH THE CHIMNEY OR OTHER
OPENINGS, CAUSING POOR COMBUSTION. SOOTING MAY
RESULT WITH AN INCREASED RISK OF ASPHYXIATION.
Special consideration is recommended, before locating the vent
termination near walkways, windows and building entrances.
Direct venting into dead spaces such as alleys, atriums, and inside
corners can cause recirculation of flue gases. Recirculation of
flue gases will cause sooting, premature failure of the heat
exchanger, and icing of the combustion air intake during severe
cold weather. To prevent the recirculation of flue gases, maintain
as much distance as possible between the combustion air intake
and the exhaust vent terminal. Due to large volumes of flue gases,
multiple boiler applications also require additional distance between
the intake and exhaust terminals.
Additional care must be exercised to assure proper draft. For proper
operation, a minimum draft of -0.02” W .C. and a maximum draft of
-0.04” W.C. is recommended when vertically vented. Draft should
be measured 2 feet (0.6m) above the boiler vent collar.
VENT SIZING, INSTALLATION AND TERMINATION SHALL
BE IN ACCORDANCE WITH THIS INSTALLATION MANUAL.
ALL ELECTRICAL POWER AND GAS MUST BE TURNED OFF
PRIOR TO ANY INSTALLATION OF THE VENTING SYSTEM.
SPECIAL INST ALLA TION CONSIDERA TIONS
This boiler is a category IV appliance that can be vented using room
air for intake combustion air, or direct vented so that all intake air for
combustion comes from the outside through a sealed pipe. When
installing this appliance as direct vent, special vent kits are required.
In cold climates any water vapor remaining in the flue gases will condense
into a cloud of vapor at the point where the vent system exits the building.
VENTING SYSTEM USING AL 29-4C
®
This boiler may be installed in four separate orientations depending
on the requirements of the building and the appliance. The inst aller
must decide which method is most appropriate for each installation.
These orientations are:
1. Vertical Termination - vertical vent termination through un-
enclosed or enclosed areas with roof penetration, see Figure 11.
termination directly through an outside wall, see Figure 11A.
3. Horizontal Direct Vent - using TWT to exhaust flue products
and PVC piping to bring combustion air to the boiler from the
outside, see Figures 12 and 12C.
4. Vertical Direct V ent - using a vertical vent termination to exhaust
flue products and PVC piping to bring combustion air to the
boiler from outside, see Figures 12A and 12B.
GENERAL EXHAUST VENT INSTALLATION PROCEDURE
Prior to beginning the installation of the vent system, determine and
obtain all part s required for the installation. IF THIS INSTALLA TION IS
A DIRECT VENT INSTALLA TION A DIRECT VENT KIT IS REQUIRED.
REFER TO THE P ARTS LIST FOR KIT NUMBER.
Proper operation of the boiler and venting system is dependent
upon use of all specified parts and installation techniques; both
safety and proper performance of the system may suffer if
instructions are not followed.
CONNECTING VENT TO BOILER
At the outlet of the boiler vent, see Figure 10, the AL 29-4C® Vent
Boot-T ee and Boot-T ee Drain Cover must be used as the transition
12
from the horizontal to vertical run. This is where the bottom most
support bracket should be located.
The Boot-Tee Drain Cover is required in order to dispose of
the condensate from the venting system. The plastic tube
(3/8 [9mm] ID, 10 feet [3m] long) needed to route the condensate
to a suitable drain is provided with the boiler.
1. Attach the Boot Tee Drain Cover to the appropriate leg of the
Boot-Tee, see Figure 10.
2. A trap loop must be formed into the drain tube simply by looping
the tube to a minimum 3 inch (76mm) diameter and secure the
loop with a cable tie, see Figure 10.
3. Prior to final assembly the trap loop must be “primed” by pouring
a small quantity of water into the drain hose.
4. Connect the Boot-Tee and Drain Tee assembly to the boiler
vent connector, see Figure 10.
5. Attach the hose to the drain fitting and run the hose to a sanitary
sewer drain maintaining the proper trap loop and following all
local, state and federal codes and regulations for draining of
acidic effluent (condensate).
Figure 10.
VENTING SUPPORTS
Care must be taken in the installation of the venting system that
adequate support is maintained throughout the installation process.
When extending more than 10 feet (3.0m) vertically, vertical support
kits are required once every 10 feet (3.0m) of vertical run. Vertical
support is also required immediately after any transition (elbow,
tee, etc.) to vertical of over 10 feet (3.0m) of run and after any
offset in the vertical run.
The support brackets (supplied in the Vertical Support Kit) are to be
securely fastened to a solid vertical member of the building using the
appropriate fasteners; i.e., wood screws for wood framing, machine or
tapping screws for structural steel or masonry anchors for solid masonry .
The bracket should be located so that it will not interfere with any joints
of the venting system. The bottom most support bracket should be
located directly above the first transition from horizontal to vertical, see
Figure 10. Refer to Figures 12, 12A, 12B and 12C.
If a means of support for the brackets are not available and
horizontal vent sections are present, install hanger straps
(made from non-combustible material) as close to the points of
transition as possible. If the horizontal portions of the vent and/or
vent connector are longer than 6 feet (2.0m), then install hanger
straps every 6 feet (2.0m) to support the connector.
DO NOT rivet or screw the straps to the conduit or otherwise
puncture the conduit wall. Instead, wrap an extra loop of strap
around the conduit to hold it in position, or attach the strap to the
center screw of the double wall AL 29-4C
®
vent coupling, if applicable.
VERTICAL INST ALLA TION REQUIREMENTS
1. The vent system must terminate at least 3 feet (1.0m) and
no more than 6 feet (2.0m) above the roof line and no
closer than 10 feet (3.0m) from any wall or vertical
structure. If the exhaust vent terminal is within 10 feet
(3.0m) of a wall or parapet, it must extend a minimum of
2 feet (610mm) above the wall or parapet, see Figures 11
and 12A.
2. For direct vent installations, the total distance of the vent system
from the boiler vent connector to the vertical vent termination shall
not exceed 70 equivalent feet (21.3m). A maximum of three 90°
elbows can be used. Minimum vertical vent is 7 equivalent feet (2.1m)
for direct vent installations. Standard minimum vertical vent length is
7 feet (2.1m), plus Boot-T ee. See Figures 1 1, 12A, 12B, and 12C for
differences between standard and direct vent installations.
®
3. An AL 29 -C
Vent Vertical Vent Terminal must be used at
the termination.
4. Maintain a minimum of 6 feet (2.0m) separation between
the air intake and the exhaust terminals.
HORIZONTAL INSTALLATION REQUIREMENTS
1. The vent system must terminate with a AL 29-4C® Vent
Through-the-Wall Termination (TWT). Plan the terminal
location based on the dimensions shown in Figure 9. Do
not locate the terminal within 8 feet (2.5m) of an inside
corner of a building or adjacent to outside walls, shrubs or
other such objects that may cause adverse wind conditions
in the immediate area.
2. The TWT shall be located not less than 12 inches (305mm)
above grade or, in geographical areas where snow
accumulates, no less than 12 inches (305mm) above the
anticipated snow line. Ensure that the TWT is protected
against blockage which may occur during ice buildup or
snowstorms.
The TWT shall terminate at least 3 feet (1.0m) above any
forced air inlet within 10 feet (3.0m), except when the
forced air inlet is the combustion air intake of a direct vent
appliance. The TWT shall terminate at least 4 feet (1.2m)
below, 4 feet (1.2m) horizontally from or 1 foot (305mm)
above any door, window or gravity air inlet into any building
as provided in the current edition of the NATIONAL FUEL
GAS CODE ANSI Z223.1, see Figure 9.
In addition, a minimum clearance of 4 feet (1.2m)
horizontally from, and in NO CASE ABOVE OR BELOW,
unless the 4 feet (1.2m) of horizontal distance is maintained
from electric meters, gas meters, regulators and relief
equipment.
3. This horizontal exhaust vent system must pitch upward toward
the termination at 1/4 inch per foot (21mm per meter).
4. The TWT is designed such that the building is protected
from degradation by flue gas and condensate. However, if
additional protection is desired, install against the wall a
non-corrosive metal sheet under the TWT.
5. Due to the normal formation of water vapor in the combustion
process, horizontal terminations must not be located over
areas of pedestrian or vehicular traffic, (i.e., public walkways
or over areas where condensate could create a nuisance or
hazard). This is especially true in colder climates where ice
buildup is likely to occur. A.O. Smith Corporation will not be
held liable for any personal injury or property damage due
to any dislodging of ice.
13
NOTES: If the exhaust vent terminal is
within 10’ (3.0m) of a wall or parapet, it
must extend a minimum of 2’ (610mm)
above the wall or parapet.
Joints are not joined to show vent pipe
orientation.
NOTES: Joints are not joined to
show vent pipe orientation.
FIGURE 11. VERTICAL TERMINATION.
FIGURE 11A. HORIZONTAL THROUGH THE WALL TERMINATION (TWT).
14
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.