A. O. Smith VB-1500 Service Manual

500 Tennessee Waltz Parkway
Ashland City, TN 37015
Service Handbook
COMMERCIAL GAS FIRED BOILER
FOR MODELS:
VW/VB 1500, VW/VB 2000
HYDRONIC HEATING
SERIES 100, 101
INSTALLATION CONSIDERATIONS - PRE SERVICE
CHECKS - WATER HEATER CONSTRUCTION -
OPERATION & SERVICE - TROUBLESHOOTING
SERVICING SHOULD ONLY BE PERFORMED BY A QUALIFIED SERVICE AGENT
PRINTED IN THE U.S.A. 0910 318149-000

TABLE OF CONTENTS

TABLE OF CONTENTS .......................................................................... 1
INTRODUCTION .................................................................................... 2
Model Numbers And Factory Congurations ..................................... 2
Qualications ..................................................................................... 2
Qualied Installer or Service Agency .......................................... 2
Service Warning ................................................................................2
Service Reminder .............................................................................. 3
Tools Required ................................................................................... 3
INSTALLATION CONSIDERATIONS ..................................................... 4
Instruction Manual .............................................................................4
Closed Water Systems ...................................................................... 4
Thermal Expansion ............................................................................ 4
Air Requirements ............................................................................... 4
Contaminated Air ............................................................................... 4
Venting ............................................................................................... 5
Water Piping ...................................................................................... 5
Temperature Rise & Flow Rate .......................................................... 5
Bypass Lines .....................................................................................5
Boiler Controls ................................................................................... 6
The Heating Cycle ....................................................................... 6
Primary System Control .............................................................. 6
Remote Temperature Probe Installation ...................................... 7
The Controlling Probe ................................................................. 7
FEATURES AND COMPONENTS ......................................................... 8
Front, Back & Side Views .................................................................. 8
How It Works .....................................................................................9
OPERATION AND SERVICE ............................................................... 10
Modulating Fire Operation ............................................................... 10
Combustion Blower ......................................................................... 10
Burner Assembly ..............................................................................11
Venturi & Gas Train ......................................................................... 12
Cong Key ....................................................................................... 13
Combustion Blower Speed Data ..................................................... 14
Temperature Probes ........................................................................ 15
Inlet and Outlet Temperature Probes ........................................ 15
Remote Temperature Probe ...................................................... 15
Quad Thermistor Probe ............................................................. 15
Control Panel ................................................................................... 17
Pressure Switches ........................................................................... 18
MCB - Modulation Control Board ..................................................... 19
PDB - Power Distribution Board ...................................................... 28
Power Supply Test ........................................................................... 33
START UP ............................................................................................ 34
Prior To Start Up .............................................................................. 34
Modulate Mode ............................................................................... 34
Modulate Mode Adjustment ....................................................... 34
Turning The Boiler Off......................................................................34
Start Up Procedure .......................................................................... 35
Manifold Gas Pressure Test............................................................. 38
CONTROL SYSTEM OPERATION ...................................................... 39
EMC 5000 Modulation Control ........................................................ 39
Control System Features: ......................................................... 39
Control System Navigation .............................................................. 40
UIM - User Interface Module ..................................................... 40
Status Lights ............................................................................. 41
Firing Rate Status ..................................................................... 41
User Input Buttons .................................................................... 42
Adjusting User Settings ...................................................................43
Operating Setpoint Adjustment ................................................. 43
Control System Menus ....................................................................44
Sequence Of Operation ................................................................... 45
TROUBLESHOOTING ......................................................................... 46
Poor Combustion - Ignition Failure - Rough Start/Operation ........... 46
Verify Correct Cong Key Is Installed ........................................ 46
Adequate Combustion Air - Proper Venting .............................. 46
Vent Gas Recirculation .............................................................. 46
Restore Gas Flow Settings To Default ...................................... 47
Firing Rate - Modulation Performance ...................................... 47
Burner Inspection ...................................................................... 47
Error Messages ...............................................................................48
LCD Display Is Blank ................................................................ 49
Display Fail ................................................................................ 50
No Cong Key ........................................................................... 50
Cong Key CRC ........................................................................ 50
Cong Key Part ......................................................................... 51
Low AC Voltage ......................................................................... 51
Low 24 VAC .............................................................................. 51
Low Water ................................................................................. 52
MRHiLimit .................................................................................. 52
Low Gas .................................................................................... 53
No Flow ..................................................................................... 54
Inlet Probe ................................................................................. 56
Tank Probe ................................................................................ 57
Outlet Probe .............................................................................. 58
Igniter ........................................................................................ 58
Blower Prover ............................................................................ 59
Blocked Inlet .............................................................................. 61
Blocked Flue ............................................................................. 62
Flame ........................................................................................ 63
PIPING DIAGRAMS ............................................................................. 65
Temperature Probe and Bypass Line Location ......................... 65
BOILER TEMPERATURE LOGS ......................................................... 69
Scheduling Deliming Maintenance ............................................ 69
Servicing should only be performed by a Qualied Service Agent
1

INTRODUCTION

This Service Manual covers VF Boiler models VW/VB 1500 and VW/VB 2000 - Series 100/101 Boilers. The instructions and illustrations contained in this Service Manual will provide you with troubleshooting procedures to diagnose and repair common service problems and verify proper operation.

MODEL NUMBERS AND FACTORY CONFIGURATIONS

See the rating plate afxed to the Boiler for Model, Series and Serial numbers. The VF product name stands
for Variable Fire. The VF Boiler model numbers are expressed on the boiler rating plates as: VW 1500, VW 2000, VB 1500, and VB 2000. The 1500 models are rated at 1,500,000 Btu/hr and the 2000 models are rated
at 2,000,000 Btu/hr. The two different model number prexes, VW and VB, are used to indicate the factory congurations as follows:
• VW model Boilers are factory congured for domestic hot water system requirements.
• VB model Boilers are factory congured for hydronic heating system requirements.
VW and VB factory congurations differ in three respects:
1. Factory installed all bronze Boiler Circulation Pump:
VW Models standard.
VB Models optional.
2. Factory installed pressure only relief valve:
VW Models 125 PSI valve standard.
VB Models 50 PSI valve standard.
3. Temperature Setting Range:
VW Models
Operating Setpoint: 105°F to 190°F (41°C to 88°C).
Automatic Reset High Limit: 135°F to 210°F (57°C to 99°C).
VB Models
Operating Setpoint: 105°F to 215°F ((41°C to 102°C).
Automatic Reset High Limit: 135°F to 235°F (57°C to 113°C).
Note: VW models can be special ordered without the factory installed pump and VB models can be special
ordered with a factory installed pump. These factory congurations can also be changed in the eld by
installing circulation pumps, changing pressure relief valves and dip switch settings on Control System circuit boards to accommodate domestic and hydronic hot water system requirements, see MCB - Section D on page 23 and Field Supplied Boiler Circulation Pumps on page 30.

QUALIFICATIONS

QUALIFIED INSTALLER OR SERVICE AGENCY

Service of VF Boilers requires ability equivalent to that of a Qualied Service Agent (dened by ANSI below) in the eld involved. Installation skills such as plumbing, air supply, venting, gas supply and electrical supply are
required in addition to electrical testing skills. Start up and servicing of VF Boilers also requires combustion analysis skills and test equipment.
ANSI Z223.1 2006 Sec. 3.3.83: “Qualied Agency” - “Any individual, rm, corporation or company that either
in person or through a representative is engaged in and is responsible for (a) the installation, testing or replacement of gas piping or (b) the connection, installation, testing, repair or servicing of appliances and equipment; that is experienced in such work; that is familiar with all precautions required; and that has
complied with all the requirements of the authority having jurisdiction.”

SERVICE WARNING

If you are not qualied (as dened by ANSI above) and licensed or certied as required by the authority
having jurisdiction to perform a given task do not attempt to perform any of the procedures described in this manual. If you do not understand the instructions given in this manual do not attempt to perform any procedures outlined in this manual.
2
Servicing should only be performed by a Qualied Service Agent

SERVICE REMINDER

When performing any troubleshooting step outlined in this Service Manual, always consider the wiring and connectors between components. Perform a close visual inspection of all wiring and connectors to and from a given component before replacing components. Ensure wires were stripped before being crimped in a wire connector, ensure wires are crimped tightly in their connectors, ensure connection pins in sockets and plugs are not damaged or worn, ensure plugs and sockets are mating properly and providing good contact.
Failure to perform this critical step or failing to perform this step thoroughly often results in needless down time, unnecessary parts replacement, and customer dissatisfaction.

TOOLS REQUIRED

Instruction Manual that came with the Boiler.
Hand tools common to installation and service of commercial water heaters and boilers.
TORX® T40 or 5 mm hex wrench - for setting gas mixture at gas valve.
3 mm or 7/64 inch hex (Allen) wrench - for setting gas mixture at gas valve.
Two Manometers or Pressure Gauges
One - U tube manometer or gauge for measuring supply gas pressure.
One (optionally two) digital Manometer(s) range -15.00 to +15.00" W.C., resolution 0.01" W.C.
Recommend UEI model EM200, TPI model 620 or equivalent. Used to measure manifold gas pressures and to test performance of pressure switches. Optional second digital manometer can be used in place of U tube manometer for measuring supply gas pressures.
• 1/4" and 3/8" plastic/silicone/rubber exible tubing - used to connect manometers to pressure sensing
ports on Boiler during start up and service.
• 1/4" and 3/8" plastic barbed Tee tting - standard automotive emission grade ttings - used to connect
manometers to pressure sensing ports on Boiler during start up and service.
True RMS Digital Multi Meter DMM, recommend UEI model DL289 or Fluke equivalent. Capable of measuring:
AC/DC Voltage
Ohms
• DC micro amps μA (ame sensing current)
AC amp meter- recommend UEI model DL289 or equivalent.
Combustion analyzer capable of measuring:
CO2 (carbon dioxide)
CO (carbon monoxide)
Draft Pressure
Exhaust Temperature (vent gases)
Servicing should only be performed by a Qualied Service Agent
3

INSTALLATION CONSIDERATIONS

This section of the Service Manual covers some of the critical installation requirements that, when overlooked, often result in operational problems, down time and needless parts replacement. Costs to correct installation errors are not covered under the limited warranty. Ensure all installation requirements and instructions contained in the Instruction Manual that came with the Boiler have been followed prior to performing any service procedures.

INSTRUCTION MANUAL

Have a copy of the Instruction Manual that came with the Boiler on hand for the Model and Series number being serviced. Installation information given in this Service Manual is not a complete installation instruction. Installation information given in this manual has a limited focus as it applies to servicing the Boiler. This Service Manual does not replace or supersede the Instruction Manual that came with the Boiler. Always refer to the Instruction Manual for complete installation instructions. If the Instruction Manual is not on hand, copies can be obtained from the manufacturers web site or by calling the toll free support phone number shown on the back cover of this manual.

CLOSED WATER SYSTEMS

Water supply systems may, because of code requirements or such conditions as high line pressure, among
others, have installed devices such as pressure reducing valves, check valves, and back ow preventers.
Devices such as these cause the water system to be a closed system.

THERMAL EXPANSION

As water is heated, it expands (thermal expansion). In a closed system the volume of water will grow when it is heated. As the volume of water grows there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent Temperature-Pressure Relief Valve operation; water discharged from the valve due to excessive pressure build up. This condition is not covered under the limited warranty. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion.
A properly sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal expansion. Contact a local plumbing service agency to have a thermal expansion tank installed.

AIR REQUIREMENTS

Carefully review the requirements for combustion and ventilation air in the Instruction Manual that came with the Boiler. Failure to meet these requirements when the Boiler is installed or overlooking their importance when servicing the Boiler often results in needless down time, unnecessary parts replacement, and customer dissatisfaction.
An inadequate supply of air for combustion and ventilation often causes operational problems. A lack of combustion and ventilation air can create a negative ambient air pressure in the installed space which can lead to improper combustion and operational problems with pressure switches.

CONTAMINATED AIR

Combustion air that is contaminated can greatly diminish the life span of the Boiler and its components such as Igniters and Burners. Propellants of aerosol sprays, beauty shop supplies, water softener chemicals and chemicals used in dry cleaning processes that are present in the combustion, ventilation or ambient air can cause such damage.
Vapors from volatile compounds such as solvents, cleaners, chlorine based chemicals and refrigerants in
addition to being highly ammable in many cases, can also react to form highly corrosive substances such as
hydrochloric acid inside the combustion chamber. The results can be hazardous and cause product failure.
If the Boiler is installed in laundries with dry cleaning equipment, it is imperative the Boiler be installed in a
Direct Vent conguration so that air for combustion is derived directly from the outdoor atmosphere through a
sealed intake air pipe. See the venting installation section in the Instruction Manual that came with the Boiler for more information on Direct Vent installations.
4
Servicing should only be performed by a Qualied Service Agent

VENTING

Ensure all venting requirements and venting installation instructions contained in the Instruction Manual that
came with the Boiler have been observed and followed. Failing to install the required Boot Tee tting at the
Boiler's vent connection, not installing the factory provided vent and/or intake air terminations, exceeding the maximum equivalent vent and/or intake air piping lengths, adding too many elbows to the intake air and/or vent pipes, installing the wrong vent/intake air pipe size, will cause operational problems, improper combustion, rough starting/operation and Control System lock outs.

WATER PIPING

Ensure all water piping requirements, diagrams and piping installation instructions contained in the Instruction Manual that came with the Boiler have been observed and followed. Factory installed pumps on VF Boilers are sized for up to a maximum of 25 equivalent feet of outlet (supply) and inlet (return) piping; 50 equivalent feet total. Exceeding these limitations will lead to Control System lock outs and can permanently damage the Boiler's Heat Exchanger. A bypass line must be installed between the outlet and inlet piping of the Boiler on the "system side" of the Boiler's Circulation Pump to prevent condensation on the copper Heat Exchanger, see the Piping Diagrams beginning on page 65.

TEMPERATURE RISE & FLOW RATE

Water ow rates through the Boiler are critical, ow rates
Ou t let In l et
­De l ta T
=
Tank
in the eld. Because the temperature rise through the Boiler is directly linked to the ow rate and is simple to measure, temperature rise is commonly used to conrm proper ow rates.
Temperature rise is calculated by subtracting the inlet water temperature from the outlet water temperature.
Temperature rise is commonly referred to as the "Delta T" and expressed as ΔT. The temperature rise through the Boiler should be set between 20° F and 30°F. Temperature rise (ow rate) is set by throttling a ow control valve installed in the Boiler's outlet (supply) water line with the boiler ring at 100%, see Figure 33 on page
65. Never attempt to throttle the outlet valve unless the Boiler is ring at 100%. Valves on the Boiler's inlet
(return) water line must never be throttled and left fully open at all times except when servicing the Boiler.
The Outlet, Inlet and Delta T (ΔT) are all displayed on the Control System's default Temperatures Menu. The
Control System is programmed to warn the end user whenever the temperature rise is below 20° F by slowly
ashing on and off "< 20" to the right of Delta T on the default Temperatures Menu. See the illustration above.
14 0 °F 12 5 °F
15 ° F
11 5 °F
<2 0 << < <
that are too low may cause excessive lime/calcium
accumulation inside the Heat Exchanger while ow rates
that are too high can lead to velocity erosion that can
eventually cause water leaks. Boiler efciency is also affected by ow rates. Measuring the actual water ow rate
(gallons per minute) through the Boiler is often impractical

BYPASS LINES

Bypass lines are required on all VF Boiler installations to
Ou t let In l et
­De l ta T
=
Tank
outlet (supply) and inlet (return) water lines, see Figure 33 on page 65. After the temperature rise through the
Boiler has been set the ow control valve in the bypass line is throttled to ensure a minimum 120° F inlet water temperature with the Boiler ring at 100%. Never attempt to throttle the bypass valve unless the Boiler is ring at 100%.
Some condensate formation on a cold start up is normal. However, if condensate formation is not prevented during normal operating conditions, copper oxide will form on the Heat Exchanger and will eventually block
the ow of ue gases through the Heat Exchanger. The Control System is programmed to warn the end user whenever the inlet water temperature is below 120° F by slowly ashing on and off "< 120" to the right of Inlet
water temperature on the default Temperatures Menu. See the illustration above.
14 0 °F
11 5 °F
<1 2 0
25 ° F
11 5 °F
Servicing should only be performed by a Qualied Service Agent
<< < <
maintain a minimum inlet water temperature of 120°F. Bypass lines feed a portion of the outlet water back to the inlet of the Boiler which raises the inlet water temperature and helps prevent condensate formation on the copper Heat Exchanger, see Figure 3 on page 9. Bypass lines are
installed with a ow control valve between the Boiler's
5

BOILER CONTROLS

Boiler controls that are improperly installed or congured can cause serious operational and service related
problems such as short cycling. This section provides information for how various controls can work together or independently to provide proper boiler and system control.

THE HEATING CYCLE

Two conditions must be met before the VF Boiler can start a heating cycle:
1. The actual temperature sensed by the Control System from the designated "Controlling Probe" (page 7) must be lower than the Operating Setpoint minus the Setpoint Differential, see Adjusting User Settings on page 43.
2. The Enable/Disable circuit must be a closed circuit. There are two wires provided in the wiring junction box on the back of the Boiler for this circuit, see Figure 1.
NOTE: See the Sequence Of Operation on page 45.

PRIMARY SYSTEM CONTROL

All VF Boiler installations require a “Primary System Control” that senses and reacts to water temperature
inside the storage tank on domestic water applications or in the return line on primary/secondary hydronic
heating systems. When installed and congured properly the Primary System Control will activate and
deactivate boiler heating cycles based on its setpoint compared to current system water temperature. There
are three suitable methods to congure a Primary System Control. One of the following three methods MUST BE used.
POWER SUPPLY AND SYSTEM CONTROL - FIELD WIRING
120 VAC INPUT POWER SUPPLY
FACTORY SUPPLIED REMOTE TEMPERATURE PROBE OR QUAD THERMISTOR PROBE
FIELD SUPPLIED EXTERNAL CONTROL
120 VAC HOT
120 VAC NEUTRAL
GND - EARTH GROUND
COM
NO
JUNCTION BOX
BACK OF BOILER
HIGH VOLTAGE
WIRING
LOW VOLTAGE
CONTROL WIRING
Figure 1
FACTORY INSTALLED WIRING
FIELD INSTALLED WIRING
BLACK - 120 VAC HOT
WHITE - 120 VAC NEUTRAL
GREEN - GROUND
YELLOW - 5 VDC
YELLOW - 5 VDC
BLACK/WHITE STRIPE - 24 VAC
YELLOW/VIOLET STRIPE - 24 VAC
REMOTE TEMP PROBE
ENABLE DISABLE CIRCUIT
1. The Primary System Control can be the Boiler’s EMC 5000 Control System working with the factory supplied Remote Temperature Probe or the optional Quad Thermistor Probe installed inside the storage tank on domestic water applications or in the return line on primary/secondary hydronic heating systems.
This application ensures the Boiler’s ability to fully modulate its ring rate. See Temperature Probes on
page 15 and Figure 33 on page 65.
2. Alternatively, the iCOMM™ system hardware working with an onsite BACnet compliant BMS (Building Management System) can be used as a Primary System Control. This application ensures the Boiler’s
ability to fully modulate its ring rate and allows BACnet compliant controls to utilize outdoor temperature
6
Servicing should only be performed by a Qualied Service Agent
reset schedules to maximize energy savings on hydronic heating applications during medium and low load conditions. The onsite BACnet compliant BMS must have its own temperature sensor installed in the storage tank for domestic water applications or in the return line on primary/secondary hydronic heating systems or it must monitor the factory supplied Remote Temperature Probe or Quad Thermistor Probe
as described in the rst method to initiate boiler heating cycles. iCOMM™ system hardware is purchased
separately from the manufacturer. For more information call 888 928-3702.
3. The Primary System Control may also be a eld supplied external control such as a storage tank
thermostat or boiler sequencing panel. Field supplied external controls must meet three requirements to be a suitable Primary System Control:
A. The eld supplied control must be able to sense water temperature inside the storage tank on
domestic water applications or in the return loop on primary/secondary hydronic heating systems.
B. The eld supplied control must function as a thermostat with a set of “dry” (no voltage or load)
control contacts to use with the Boiler’s Enable/Disable circuit, see Figure 1 on page 6 for wiring.
C. The eld supplied control must open/close its control contacts based on actual system
temperature AND its own system temperature setpoint.
FIELD SUPPLIED CONTROL NOTES: If the eld supplied external control does not meet all three of the requirements listed above it MUST NOT be used as the required Primary System Control.
When using a eld supplied external control as the Primary System Control the Operating Setpoint of Boiler Control System must be set at least 5° higher than the system setpoint of the eld supplied
control. This is done to ensure the Boiler’s setpoint does not deactivate the current heating cycle before
the external control’s setting has been satised. This also prevents the Boiler from short cycling. See
Adjusting User Settings on page 43.
When a eld supplied external control is used as the Primary System Control it activates and deactivates boiler operation based on the temperature it senses in the system. It cannot control the Boiler’s ring rate.
The Boiler is not able to modulate its ring rate when using this type of Primary System Control.

REMOTE TEMPERATURE PROBE INSTALLATION

All VF Boilers are supplied from the factory with a Remote Temperature Probe which is suitable for all single boiler applications, see Figure 8 on page 15. When connecting up to 4 boilers to a single storage tank or one primary/secondary hydronic heating system the optional Quad Thermistor Probe should be used, see Figure 9 on page 16. Call the toll free parts department phone number on the back of this manual to order the Quad Thermistor Probe.
On domestic hot water applications the Remote Temperature Probe or the optional Quad Thermistor Probe MUST BE installed in the designated temperature control opening on the storage tank, typically a 3/4 inch NPT opening in the lower portion of the tank. On hydronic heating applications the probe being used MUST
BE installed in the return line of the primary hydronic heating loop before (upstream) the rst boiler. A eld supplied Tee tting with a 3/4 inch NPT branch is installed in the return line for this purpose. See Figure 33
on page 65 and the piping diagrams in the back of this manual for probe location.
Once the probe has been installed in the system, see the Field Wiring section in the Installation Manual that came with the Boiler and Figure 1 on page 6 in this manual for wiring instructions.

THE CONTROLLING PROBE

When the Remote Temperature Probe or the optional Quad Thermistor Probe and the eld wiring has been
installed the probe being used must be designated as the “Controlling Probe." To do this turn off power to the Boiler and locate the SW1 dipswitch array on the MCB circuit board, see Figure 12 on page 19 and Figure 16 on page 23.
SW1 dipswitch #4 must be set to the “On” position to congure the Remote Temperature Probe or the optional Quad Thermistor Probe as the Controlling Probe. The SW1 dipswitch #4 is set to “Off” from the
factory so this change must be performed on all installations. When power to the Boiler is turned back on the Boiler’s Control System will now monitor the remote probe that was installed and use temperature data from
that probe to activate and deactivate heating cycles and to modulate the ring rate of the Boiler. See Table 4 on page 23 to congure the SW1 dipswitches.
Servicing should only be performed by a Qualied Service Agent
7

FEATURES AND COMPONENTS

FRONT, BACK & SIDE VIEWS

FRONT VIEW
TOP FRONT PANEL
OPENS FOR SERVICE
Outlet
155°F
Inlet
125°F
-
Delta T
30°F
=
Tank
120°F <<<<
Select
Up
Menu
25% Firing Rate 100%
Down
Help
UIM (User Interface Module)
Service Standby Running
BACK VIEW
1 1/4 INCH NPT SUPPLY GAS CONNECTION WITH FACTORY INSTALLED SHUTOFF VALVE WITH SUPPLY GAS TEST PORT
VF
WIRING/ELECTRICAL JUNCTION BOX
PRESSURE ONLY RELIEF VALVE VW MODELS - 125 PSI VB MODELS - 50 PSI
2 1/2 INCH NPT OUTLET WATER CONNECTION WITH OEM TEE FITTING INSTALLED WITH PRESSURE RELIEF VALVE AND FLOW SWITCH
VENT (EXHAUST) CONNECTION 7 INCH - AL29-4C STAINLESS STEEL
FLOW SWITCH
VENTILATION AIR OPENINGS
INTAKE AIR CONNECTION 6 INCH PVC
2 1/2 INCH NPT INLET WATER CONNECTION
VENTILATION AIR OPENINGS
CONDENSATE DRAIN HOSE OPENING
SIDE VIEW
1 1/4 INCH NPT SUPPLY GAS CONNECTION WITH FACTORY INSTALLED SHUTOFF VALVE WITH SUPPLY GAS TEST PORT
PRESSURE ONLY RELIEF VALVE 125 PSI ON VW MODELS 50 PSI ON VB MODELS
ALL BRONZE BOILER CIRCULATION PUMP FACTORY INSTALLED AT INLET WATER CONNECTION: VW MODELS - STANDARD VB MODELS - OPTIONAL
VENT (EXHAUST) CONNECTION 7 INCH - AL29-4C STAINLESS STEEL
Figure 2
8
Servicing should only be performed by a Qualied Service Agent

HOW IT WORKS

L
L
VF Boiler Heat Exchangers are ASME constructed and rated at 160 PSI. All VF Boilers are SCAQMD Rule
1146.2 low NOx compliant and are equipped with CSD-1 compliant controls. The Heat Exchanger is a circular
shaped vertical tube 4 pass Heat Exchanger constructed from 30 extruded copper tubes roll tted into two
ASME grade steel multiple pass headers that are glass lined.
Water enters the upper header through the inlet water connection and travels down and up a total of 4 times
through the copper tubes and headers. Steel vertical ue bafes are secured to the copper tubes to regulate the ow of ue gases.
The Heat Exchanger is housed in a sealed stainless steel combustion chamber to contain the products of
combustion and properly convey ue gases to the vent/exhaust connection on the back of the boiler. This combustion chamber design prevents critical boiler components from being exposed to high temperature ue
gases. The boiler cabinet is constructed with multiple panels that can be removed during operation for inspection.
HEAT EXCHANGER / COMBUSTION BLOWER & BURNER VIEWS
COMBUSTION BLOWER
DRAIN VALVE
COMPLETE ASSEMBLY HEAT EXCHANGER
COMBUSTION
GAS VALVE
VENTURI
CONDENSATE TRAY
ASME GRADE
AIR INTAKE
STAINLESS STEEL
HEAT EXCHANGER
ENCLOSURE
VENT/EXHAUST CONNECTION
7 INCH AL29-4C STAINLESS STEEL
STEEL GLASS LINED HEADERS
DRAIN VALVE
COMBUSTION
STEEL RADIAL
FIRE BURNER
BLOWER ADAPTER
INLET WATER
CONNECTION
OUTLET WATER
CONNECTION
30 EXTRUDED
COPPER FIN
VERTICA
WATER TUBES
WITH STEE
FLUE BAFFLES
BLOWER
BLOWER
ADAPTER
STAINLESS
BLOWER/BURNER ASSEMBLY
Figure 3
Servicing should only be performed by a Qualied Service Agent
9

OPERATION AND SERVICE

MODULATING FIRE OPERATION

VF Boilers are modulating re boilers, the Control Systems modulates the ring rate of the Burner between 25% and 100% to match system load by controlling the speed of the Combustion Bower, see Figure 4.
VF Boilers do not have a gas orice. The Combustion Blower "pulls" fuel gas from the outlet of the 120 VAC
Gas Valve (when energized) into a Venturi that is connected to the inlet of the Combustion Blower, see Figure
6 on page 12. The ring rate of the Boiler is directly proportional to the speed of the Combustion Blower motor.
As the blower speed increases, the pressure inside the Venturi falls creating a stronger vacuum which pulls
more fuel gas into the blower/burner assembly which increases the ring rate.
The Control System controls the speed of the Combustion Blower in response to system temperature. As the system temperature falls blower speed is increased to provide more heating capacity. The Control System sends digital speed instructions to the electronic speed control which is part of the Combustion Blower assembly, see Figure 4 on page 10.

COMBUSTION BLOWER

The Combustion Blower is an assembly that includes the blower motor, housing and an integral electronic speed control. The PDB (Power Distribution Board - see page 28) sends 120 VAC and an earth ground from its J3 socket to the 120 VAC 3 pin socket on the Combustion Blower assembly to power the electronic speed control. The MCB (Modulation Control Board - see Figure 12 on page 19) sends an instruction to start, stop and control the blower motor speed. Four wires from the J24 socket on the MCB (see page 27) carry this instruction to the 5 pin socket on the Combustion Blower assembly, see Figure 4 below.
LIFT HANDLE
BLOWER MOTOR WITH INTEGRATED ELECTRONIC SPEED CONTROL
COMBUSTION BLOWER
BLOWER
HOUSING
120 VAC POWER
3 PIN SOCKET
MCB SPEED INSTRUCTION 5 PIN SOCKET
10
BLOWER OUTLET FLANGE
Figure 4
Servicing should only be performed by a Qualied Service Agent

BURNER ASSEMBLY

The Burner on the VF Boiler is a stainless steel radial re burner with a woven steel ber surface. It is installed
in the center of the vertical tube Heat Exchanger, see Figure 3 on page 9. The Burner is mounted inside the recess of the top header on the Heat Exchanger. A Blower Adapter is installed between the Combustion Blower's condensate tray and the Burner, see Figure 5 below.
The Igniter on the VF Boiler is a 120 VAC hot surface igniter. The Igniter receives power from the J18 socket on the MCB (Modulation Control Board - see page 22). Normal resistance of the Igniter is 40-70 ohms @ 77° F (25° C). The Control System monitors current through the Igniter and must sense a minimum of 2.7 AC amps before it will energize the 120 VAC Gas Valve.
A Low Gas Pressure Switch is installed in the body of the 120 VAC Gas Valve. This is a normally open switch that closes on a rise in pressure. Switch contacts close at +4.0" W.C. on natural gas models and +6.4" W.C. on propane gas models.
VF Boilers have two Flame Sensors. One Flame Sensor is mounted close to the Burner to sense ame at lower ring rates; the second Flame Sensor is mounted further away to sense ame at higher ring rates,
see Figure 5 below. A single wire, connected the J16 spade connector (see page 22) on the MCB, is bifurcated (divided) into two wires, each end then connects to one of the two Flame Sensors. The Control System must
sense a minimum of 2.5 DC micro amps (2.5 µA) to prove ame at the Burner.
COMBUSTION BLOWER
NOTE: BLOWER ASSEMBLY INCLUDES INTEGRATED ELECTRONIC SPEED CONTROL.
120 VAC
GAS VALVE
CONDENSATE TRAY
BLOWER ADAPTER
TWO FLAME SENSORS
FIRST FLAME SENSOR MOUNTED CLOSE TO BURNER TO SENSE FLAME DURING LOW FIRE.
SECOND FLAME SENSOR MOUNTED FURTHER FROM BURNER TO SENSE FLAME DURING HIGH FIRE.
GASKETS
NOTE: 40-70 OHMS @ 77° F
(25°C). CONTROL SYSTEM
MUST SENSE A MINIMUM OF 2.7 AC AMPS BEFORE
ENERGIZING GAS VALVE
VF BOILER STAINLESS STEEL BURNER
LOW GAS
PRESSURE
SWITCH
NOTE: N.O. SWITCH
CLOSE ON RISE
+4.0” W.C. NATURAL
+6.4” W.C. PROPANE
120 VAC
HOT SURFACE
IGNITER
RADIAL FIRE
STAINLESS
STEEL BURNER
NOTE: CONTROL SYSTEM MUST SENSE A MINIMUM OF 2.5 DC MICRO AMPS (2.5 µA) TO PROVE FLAME AT BURNER
Servicing should only be performed by a Qualied Service Agent
WOVEN STEEL
FIBER SURFACE
Figure 5
11

VENTURI & GAS TRAIN

The gas train includes a Venturi connected to the inlet of the Combustion Blower. The outlet of the 120 Volt Gas Valve is also connected to the Venturi by a manifold gas line. There is a shutoff valve installed in the manifold gas line for start up and service procedures. The Venturi contains a convergent/divergent nozzle (cone shaped restrictor) that constricts the air passage to the blower. As air enters the constriction point its velocity increases. A pressure drop occurs at this point and creates a negative (vacuum) pressure in the
cavity between the nozzle and the Venturi housing. This negative pressure “pulls” gas from the outlet of the
120 Volt Gas Valve into the blower where it is mixed with combustion air and then supplied to the burner, see Figure 6.
As the Combustion Blower speed is increased (page 10) the velocity of air owing through the Venturi is also
increased. This increases the vacuum created by the Venturi and more fuel gas is pulled from the 120 Volt
Gas Valve and supplied to the Burner. This increases the ring rate (input Btu/hr) of the VF Boiler. As the blower speed is decreased less fuel gas is supplied to the Burner and the ring rate is reduced.
The MCB controls blower speed according to system temperature. When system temperature sensed at the Controlling Probe (page 7) is well below the Operating Set Point the MCB will run the blower at maximum
speed = 100% ring rate. As system temperature rises closer to the Operating Set Point the MCB will reduce blower speed which reduces (modulates) the ring rate. VF Boilers are designed to modulate between 25% and 100%; a 4 to 1 turn down rate.
VENTURI OPERATION
COMBUSTION
BLOWER
VENTURI
Negative Pressure
Velocity Increases
At Constriction Point.
Pressure Drops
Negative Pressure
COMBUSTION
AIR INTAKE
NOZZLE
COMBUSTION
BLOWER
BURNER
GAS TRAIN TOP VIEW
VENTURI
MANIFOLD
GAS LINE
120 VAC
GAS VALVE
MANIFOLD GAS
FUEL GAS
120 VAC
GAS VALVE
COMBUSTION AIR INTAKE
MANIFOLD PRESSURE SENSING PORT
MANIFOLD GAS SHUTOFF VALVE
SUPPLY GAS TEST PORT 1/8” NPT
SUPPLY
GAS
SUPPLY GAS
SHUTOFF VALVE
12
Figure 6
Servicing should only be performed by a Qualied Service Agent

CONFIG KEY

The Cong Key is an 18” long cable with a plug on one end and an EEPROM memory chip sealed at the other. The Cong Key plugs into the J23 socket on the MCB, see MCB - Section H on page 27. The memory chip contains blower speed programming data specic to the input Btu/hr and fuel type for each VF Boiler. VF Boilers are available in natural and propane gas and in ve input Btu/hr models ranging from 500,000 to
2,000,000. This Service Manual covers the 1,500,000 and 2,000,000 Btu/hr models only.
Each time the Boiler is powered up the MCB reads and then stores the blower speed programming data
from the Cong Key into it’s own internal memory. The MCB then uses the data to modulate the Combustion
Blower speed by sending instructions from the MCB J24 socket to the 5 pin socket on the Combustion Blower Assembly, see Figure 4 on page 10 and MCB - Section H on page 27. Modulating the Combustion Blower speed
also modulates the ring rate on VF Boilers, see Venturi & Gas Train on page 12.
There is a label at the end of the Cong Key cable near the memory chip that identies which boiler model it is
used for. This end of the cable is threaded into the wiring chase during manufacturing. The software revision
for the Cong Key can be viewed in the Log & System Info menu, see Control System Menus on page 44.
WARNING:
Cong Keys are manufactured for a particular fuel type and input Btu/hr rating as described above. Cong Keys MUST NOT be interchanged in the eld for any reason. Doing so can cause ignition failure, rough starting/operation and poor combustion. Changing a Cong Key can permanently damage the Boiler, cause property damage, personal injury or death. Damage to the Boiler caused by interchanging Cong Keys in the eld is not covered under the limited warranty as this would be considered a eld alteration of the Boiler's
design.
If it is suspected the Cong Key is defective or the Boiler is experiencing ignition failure, rough starting/ operation and/or poor combustion, ensure the proper Cong Key is installed. Navigate to the Log & System Info menu in the control system and record the kBTU Rating, Fuel Type and Cong Key Rev number, see
Control System Navigation on page 40 and Control System Menus on page 44. If the Fuel Type and/or kBTU rating listed in the Log & System Info menu does not match the rating plate on the Boiler, turn the Boiler off and disable Boiler operation. Call the toll free support phone number on the back cover of this manual for further assistance.
Figure 7
Servicing should only be performed by a Qualied Service Agent
13

COMBUSTION BLOWER SPEED DATA

Nominal Combustion Blower speeds during various operating states for natural gas models are shown in Table 1 below. Combustion Blower speeds for propane models are shown in Table 2. Due to slip in the Combustion Blower and manufacturing tolerances in the electronic speed control these numbers will vary.
When combustion is poor, the ring rate of the Boiler or the Combustion Blower speed is in question, or the
Boiler is experiencing rough starting/operation or ignition failure compare the values given here to actual blower speeds shown in the Control States menu. The current blower speed (RPM) and operating state can be viewed in real time in the Control States menu, see Control System Navigation on page 40 and Control System Menus on page 44.
Viewing the Combustion Blower speed data can also be useful if the Cong Key (see page 13) is suspected as
being defective. Actual blower speeds will vary somewhat but should be relatively close to what is shown in
the tables below. If Combustion Blower speeds vary greatly, 25% or more, or if the Cong Key is suspected
as being defective call the toll free support phone number on the back cover of this manual for further assistance.
TABLE 1
NATURAL GAS MODELS
OPERATING STATE VW/VB 1500
NOMINAL BLOWER SPEED
Pre/Post Purge Periods 4950 RPM 4950 RPM
Ignition Trial Period 1800 RPM 1800 RPM
Forced Maximum Firing Rate 100% 3700 RPM 4650 RPM
Forced Minimum Firing Rate 25% 920 RPM 1225 RPM
NOMINAL BLOWER SPEED
VW/VB 2000
TABLE 2
PROPANE GAS MODELS
OPERATING STATE VW/VB 1500
NOMINAL BLOWER SPEED
Pre/Post Purge Periods 4950 RPM 4950 RPM
Ignition Trial Period 1800 RPM 1800 RPM
Forced Maximum Firing Rate 100% 3700 RPM 4415 RPM
Forced Minimum Firing Rate 25% 900 RPM 1170 RPM
NOMINAL BLOWER SPEED
VW/VB 2000
14
Servicing should only be performed by a Qualied Service Agent

TEMPERATURE PROBES

Temperature probes are 3/4 inch male NPT threaded immersion probes, see Figure 8. Temperature probes have embedded temperature sensors (thermistors). Thermistors are thermally sensitive resistors; as the surrounding temperature rises the resistance of the thermistor (measured in ohms) will decrease and as the surrounding temperature falls the resistance of the thermistor increases, see Table 3 on page 16. The Boiler’s Control System monitors these sensors to determine water temperature at various points in the system.
INLET / REMOTE TEMPERATURE PROBE
OUTLET TEMPERATURE PROBE
Figure 8

INLET AND OUTLET TEMPERATURE PROBES

All VF Boilers have one Inlet and one Outlet Temperature Probe factory installed in the top of the Heat Exchanger to monitor the water temperature entering and leaving the Boiler. The Inlet Probe is a temperature sensor only and has two wiring leads. The Outlet probe also contains the manual reset high temperature limit switch and has four wiring leads. The Control System displays the Inlet and Outlet water temperatures sensed from these two probes on the default Temperatures Menu. The Control System also displays the temperature difference between the Inlet and Outlet Temperature Probes on the Temperatures Menu as the "Delta T" value. See Figure 29 on page 40.

REMOTE TEMPERATURE PROBE

All VF Boilers are supplied from the factory with a Remote Temperature Probe. The supplied Remote Temperature Probe is used to control system water temperature for a single boiler in a domestic hot water storage tank or in the return line from a primary/secondary hydronic heating system. Use of the Remote Temperature Probe allows a boiler to sense the actual water temperature inside the storage tank or hydronic
heating loop. The Boiler will modulate its ring rate in response to the actual system temperature and load
conditions. The Control System displays the temperature sensed from the Remote Temperature Probe as the
“Tank” temperature on the default Temperatures Menu. See Figure 29 on page 40.

QUAD THERMISTOR PROBE

When connecting up to 4 boilers to a single storage tank or one primary/secondary hydronic heating system the optional Quad Thermistor Probe should be used. The Quad Thermistor Probe is a remote temperature probe with four temperature sensors embedded in one device. The Quad Thermistor Probe allows up to 4 boilers to sense system temperature from the same point in the system. Use of the Quad Thermistor Probe will allow each connected boiler to individually sense the actual water temperature in the storage tank or the hydronic heating loop. The temperatures sensed from each of the four temperature sensor circuits in a Quad
Thermistor Probe are shown as the “Tank” temperature on each Boiler’s default Temperatures Menu. See
Figure 29 on page 40.
Servicing should only be performed by a Qualied Service Agent
15
QUAD THERMISTOR PROBE
FOUR (2 WIRE - COLOR CODED) TEMPERATURE SENSOR CIRCUITS FOR USE WITH MULTIPLE BOILERS.
FACTORY EQUIPPED WITH 6 x 1/2 INCH NPT PIPE NIPPLE TO ACCOMMODATE STORAGE TANK INSULATION THICKNESS. THIS CAN BE FIELD REPLACED WITH A SHORTER NIPPLE TO ACCOMMODATE VARIOUS TANKS AND HEATING LOOPS.
EIGHT WIRE TERMINAL STRIP FOR CONNECTIONS MOUNTED INSIDE THE PROBE COVER
SIDE VIEW
REMOVE 1/8 INCH ALLEN SET SCREW IN PROBE END TO REPLACE FACTORY NIPPLE WITH FIELD SUPPLIED NIPPLE.
Figure 9
OPERATIONAL NOTES: When using multiple boilers with the Quad Thermistor Probe staggering each
Boiler's Operating Setpoint by 1° to 3° will achieve greater system energy savings. The Boiler(s) with the
lower Operating Setpoint will reduce their ring rate rst and cycle off before the boiler(s) with higher settings.
Setting up a monthly maintenance schedule to rotate which boiler(s) has the higher Operating Setpoint will also provide a means for lead/lag control which will maintain even wear/operating time for each boiler.
TABLE 3
WATER TEMPERATURE TEMPERATURE SENSOR
RESISTANCE IN OHMS
16
CELSIUS FAHRENHEIT
40° 26,435
21° 70° 11,974
38° 100° 5,862
49° 120° 3,780
55° 130° 3,066
60° 140° 2,503
71° 160° 1,698
82° 180° 1,177
Servicing should only be performed by a Qualied Service Agent

CONTROL PANEL

Figure 10 shows the Control Panel layout inside the VF Boiler. Three pressure switches are located in the upper right corner. Directly beneath the pressure switches is the Pump Relay that energizes factory
installed Boiler Circulation Pumps or eld supplied 120 VAC pumps up to 1 horsepower. For higher voltage/ horsepower pumps a eld supplied starter must be used. The black and white 120 VAC pump wiring in the junction box on the back of the Boiler would be used to power the eld supplied starter coil in this case. The
MCB (Modulation Control Board) and the PDB (Power Distribution Board are also located on the Control Panel. The optional LWCO (Low Water Cut Off) circuit board is mounted on the Control Panel on models so equipped.
PRESSURE SWITCHES
BLOCKED FLUE
(EXHAUST)
BLOCKED
INTAKE AIR
BLOWER PROVER
MCB
(Modulation Control Board)
BOILER
CIRCULATION
PUMP RELAY
(Power Distribution Board)
LWCO CIRCUIT BOARD
(Low Water Cut Off)
PDB
ON/OFF
POWER RELAY
Figure 10
Servicing should only be performed by a Qualied Service Agent
17

PRESSURE SWITCHES

Blocked Flue (Exhaust) Switch
Normally Closed, Opens On Pressure Rise
Natural Gas
Propane Gas
Single Pressure Sensing
Blocked Intake Air Switch
Normally Closed, Opens On Pressure Fall
Single Pressure Sensing
-4.0" W.C. ± 0.18
-5.7" W.C. ± 0.18
Blower Prover Switch
Normally Open, Closes On Differential
Natural Gas
Propane Gas
There are three pressure switches installed on all VF Boilers to verify the venting (exhaust) and the intake air
are not restricted and to conrm the Combustion Blower is operating properly when energized, see Figure 10
on page 17 and Figure 11 below.
The sensing tubes must be routed to the correct sensing ports and they must be properly connected at all times. Improper routing, kinks and disconnected sensing tubes will cause improper operation and associated Control System lock outs. The Blower Prover switch is a dual pressure switch, when testing performance two pressure readings are necessary. If the two sensing tubes connected to the Blower Prover switch are reversed, the Control System will lock out and display the "Blower Prover" error message on the LCD.
Figure 11 below illustrates the proper routing for the pressure switches and provides the operating parameters for each switch. Refer to this illustration when testing pressure switch performance or verifying proper sensing tube routing.
PRESSURE SWITCHES
OPERATIONAL
PARAMETERS
+3.5" W.C. ± 0.18 +4.0" W.C. ± 0.18
Natural Gas Propane Gas
Dual Pressure Sensing
-4.0" W.C. ± 0.18 -4.0" W.C. ± 0.18
WIRING TERMINALS
TO ALUMINUM CONNECTING TUBE FROM COMBUSTION CHAMBER
BLOCKED FLUE
(EXHAUST)
PRESSURE SWITCH
SENSING TUBES
BLOCKED
INTAKE AIR
TO INTAKE AIR
SENSING PORT
BLOWER PROVER
P1P1 P2P2
B
TO MANIFOLD PRESSURE
A
SENSING PORT
18
Servicing should only be performed by a Qualied Service Agent
INTAKE AIR SENSING PORT
MANIFOLD PRESSURE SENSING PORT
B
Figure 11
A

MCB - MODULATION CONTROL BOARD

The MCB circuit board is the main controller and is located on the Control Panel, see Figure 10 on page 17. All instructions for Burner modulation and temperature control originate from this circuit board. Diagnostic and operational messages are generated by the MCB and sent to the UIM. Most of the Boiler’s components, such as the Igniter, Combustion Blower, 120 VAC Gas Valve, and Temperature Probes are directly connected to one of the MCB’s socket connectors. The UIM (User Interface Module, see page 40) is also connected to one of the internal communication ports on the MCB. The Flame Sensors (see Figure 5 on page 11) are connected to the J16 spade connector on the MCB. Optional iCOMM™ system hardware, when used, is connected to one of the external communication ports on the MCB. The MCB circuit board has been divided into sections in the illustration below, each section will be covered in the pages that follow.
DE
J7J8
J6
F
G
J9
ICSP
EXT COMM
EXT COMM
INT COMM
INT COMM
SW2
SW1
J23
J24
H
MCB
(Modulation Control Board)
RED LED
F1 FUSE
J3
J4
J11
J5
J17
J19
A
B
J2
J15
J1
J16
Figure 12
Servicing should only be performed by a Qualied Service Agent
J18
C
19
MCB - SECTION A
See Figure 12 on page 19 for location of this section on the MCB.
RED LED
F1 FUSE
A
J3
1 2 3
Figure 13
The upper right corner of the MCB contains the following sockets/components:
Red LED (illuminated when the F1 fuse is open or not installed)
F1 Fuse (7.5 amp automotive fuse - transformer secondary [24 VAC] winding protection)
J3 Socket (24 VAC power supply from transformer)
Pin 1 - 24 VAC from PDB J2 Socket Pin 1
Pin 2 - 24 VAC from PDB J2 Socket Pin 2
Pin 3 - Ground from PDB J2 Socket Pin 3
20
Servicing should only be performed by a Qualied Service Agent
MCB - SECTION B
See Figure 12 on page 19 for location of this section on the MCB.
5
4 3
2 1
J4
10
9 8 7 6
J11
1 2
3
10
9 8 7 6
J5
J17
J19
J4 Socket (Outputs/Inputs)
Pin 1 - Power Accessory 24 VAC
Pin 2 - Power Accessory Prover
Pin 3 - Power Accessory 24 VAC RTN
Pin 4 - 24 VAC line low water cut off (optional)
Pin 5 - Low water cut off proving signal
Pin 6 - 24 VAC line low water cut off (optional)
Pin 7 - 24 VAC alarm bell circuit (optional)
Pin 8 - 24 VAC alarm bell circuit (optional)
Pin 9 - Spare - not used
Pin 10 - Spare - not used
J11 Socket (Enable/Disable Circuit)
Pin 1 - 24 VAC to dry control contacts
Pin 2 - 24 VAC to dry control contacts
Pin 3 - Spare - not used
J19 Socket
Pin 1 - 120 VAC - Gas Valve solenoid
Pin 2 - 120 VAC - Gas Valve solenoid
5
4 3 2 1
4 5 6
1 2
Figure 14
B
1 2 3
J5 Socket (Inputs)
Pin 1 - 24 VAC Flow Switch
Pin 2 - 24 VAC Flow Switch
Pin 3 - 24 VAC Low Gas Pressure Switch
Pin 4 - 24 VAC Low Gas Pressure Switch
Pin 5 - 24 VAC Blocked Flue (Exhaust) Switch
Pin 6 - 24 VAC Blocked Flue (Exhaust) Switch
Pin 7 - Spare - Not used
Pin 8 - Spare - Not used
Pin 9 - Spare - Not used
Pin 10 - Spare - Not used
J17 Socket (Blower Prover/Hi Gas Press Switch)
Pin 1 - 24 VAC Blower Prover Switch
Pin 2 - 24 VAC Blower Prover Switch
Pin 3 - 24 VAC High gas press switch (optional)
Pin 4 - 24 VAC High gas press switch (optional)
Pin 5 - 24 VAC Blocked Intake Air Switch
Pin 6 - 24 VAC Blocked Intake Air Switch
J4 Socket Pins 7 & 8 provide 24 VAC for an optional alarm bell that will sound whenever the Boiler Control System declares a fault condition. This is a switched 24 VAC control circuit with a maximum amp rating of 1 AC amp @ 24 VAC.
‡ The enable/disable circuit is provided for use with external supervisory controls. Field wring is installed between this circuit and a set of "dry contacts" on the external control, see Figure 1 on page 6. This is a switching circuit only: Do not apply any external voltage or connect any load (IE: relay coil) to this circuit. This will permanently damage the MCB circuit board and is not covered under the limited warranty.
Servicing should only be performed by a Qualied Service Agent
21
Loading...
+ 53 hidden pages