A.O. Smith HD-20-80 Technical Documents

Page 1
Commercial Storage Tanks
HEAVY-DUTY LARGE VOLUME STORAGE TANKS MODEL HD CUSTOM BUILT
Large volume tanks are designed for storing potable water. Fitting locations of these custom-line tanks match the needs of normal installations plus those for the A. O. Smith Cer -Temp 80 Shure-Temp™ systems.
FEATURES
®
and
MODELS
HD-20-80
THROUGH
HD
-96-12,500
SIZES FROM 80 TO 12,500 GALLONS
All tanks are constructed to the requirements of the ASME Code. These ASME Code tanks are available at 125,150 &160 PSI working pressure. Consult factory for ASME Code tanks that have greater or lesser working pressures with special configurations or materials.
LINING AND COATINGS
Each lining and coating has particular capabilities and limitations. Thorough investigation on the service life of steel tanks with protective coatings or linings has led to the recommendation of the following linings:
n
Glass Lined — All internal surfaces
exposed to water are glass lined per
ASME HLW Code procedures.
n
Cement Lined — Cement lining
consists of a specially formulated cement applied over the interior of the vessel. Cement lined tanks are recommended when storing water at 180°F or higher.
n
Epoxy Lined — The application of
specially formulated epoxy makes this lining suitable for cold or hot water storage.
Please consult the factory for recommendations on the uses of linings for
specific applications. All tanks receive one prime coat of paint on external surface. A. O. Smith representative for severe or unusual applications that may require other materials.
Contact your local
CATHODIC PROTECTION
Glass lined, cement and epoxy tanks are furnished with anodes designed for maximum protection.
CUSTOM TANK OPENINGS
All tanks will be supplied with the fittings located as indicated on the drawings unless specified otherwise. Custom tank opening sizes and locations can be provided as per your specification.
INSPECTION OPENINGS
n
11”x15” manhole or 4”x 6” handhole
are available as options on diameters 36” and below.
n
2 each 2” ASME inspection openings
are standard on tanks 36” diameter and below.
n
12”x16” ASME inspection openings
are standard on tanks with 42” diameters and above.
TANK OPTIONS
n
Manholes • Handholes
n
Additional/Custom Tank Openings
n
Lifting Lugs
n
Angle Legs
n
Ring Base
n
Horizontal Tank Saddles
n
Factory Jacketing and Insulation
n
Tank Heaters - Cement and
Epoxy Linings
U
OPTIONAL
December 2013
Page 1 of 4
AOSTT35400
Page 2
Commercial Storage Tanks
STORAGE TANK SELECTION
Model
Number
HD20-80 20” 60” 80 HD54-650 54” 71” 650
HD20-100 20” 72” 100 HD54-750 54” 81” 750
HD24-125 24” 66” 125 HD54-900 54” 95” 900
HD24-140 24” 75” 150 HD54-1,000 54” 105” 1,000
*HD24-175 24” 90” 175 *HD54-1,250 54” 129” 1,250
HD30-175 30” 60” 175 *HD54-1,500 54” 153” 1,500
HD30-200 30” 71” 200 *HD54-1,800 54” 181” 1,800
HD30-250 30” 84” 250 *HD60-800 60” 72” 800
*HD30-300 30” 99” 300 *HD60-1,000 60” 88” 1,000
HD36-250 36” 60” 250 *HD60-1,250 60” 107” 1,250
HD36-300 36” 71” 300 *HD60-1,500 60” 126” 1,500
HD36-350 36” 86” 350 *HD60-1,750 60” 146” 1,750
HD36-400 36” 93” 400 *HD60-2,000 60” 165” 2,000
*HD36-500 36” 122” 500 HD66-1,000 66” 75” 1,000
HD42-375 42” 67 375 *HD66-1,500 66” 107” 1,500
HD42-450 42” 79” 450 *HD66-2,000 66” 139” 2,000
HD42-500 42” 88” 500 *HD66-2,500 66” 171” 2,500
HD42-600 42” 103” 600 *HD72-2,500 72” 147” 2,500
HD42-700 42” 119” 700 *HD72-3,000 72” 174” 3,000
HD42-800 42” 134” 800 *HD72-3,500 72” 201” 3,500
HD48-500 48” 73” 500 *HD72-4,000 72” 228” 4,500
HD48-600 48” 81” 600 *HD84-4,000 84” 173” 4,000
HD48-700 48” 93” 700 *HD84-5,000 84” 212” 5,000
HD48-750 48” 105” 750 *HD84-6,000 84” 252” 6,000
HD48-900 48” 117” 900 *HD84-8,000 84” 330” 8,000
HD48-1,000 48” 137” 1,000 *HD96-7,500 96” 244” 7,500
*HD48-1250 48” 159” 1,250 *HD96-10,000 96” 319” 10,000
*HD48-1,500 48” 190” 1,500 *HD96-12,500 96” 395” 12,500
Diameter
Nominal
Approximate
O. A. Length
Gallon
Capacity
Model
Number
Diameter
Nominal
Approximate
O. A. Length
Gallon
Capacity
NOTE: Above listed tanks are standard sizes only. Other capacity tanks are available. Custom tanks built to your specifications are also available. Consult factory representative.
* Vertical installation requires addition of angle iron legs or ring base.
Page 2 of 4
www.hotwater.com
AOSTT35400
Page 3
Commercial Storage Tanks
CUSTOM-LINE STORAGE TANKS (20” THRU 96” DIA. TANKS)
AA
A
A
OVERALL
ASME PLATE
B
E
A
B
AA
THREADED LEG SOCKET
A
"C"
A
A
A
B
A
NOTE:
1) 54” DIAMETER AND LARGER TANKS MUST BE ORDERED WITH ANGLE LEGS RATHER THAN THREADED LEG SOCKETS FOR VERTICAL INSTALLATIONS.
2) SPECIFY FOR HORIZONTAL OR VERTICAL INSTALLATION.
3) NO LEG SOCKETS PROVIDED ON HORIZONTAL TANKS.
2 each 2” ASME inspection openings are standard on tanks 36” diameter and below.
12”x16” ASME inspection openings are standard on tanks with 42” diameters and above.
CUSTOM-LINE STORAGE TANKS (20” THRU 96” DIA. TANKS)
OVERALL
AA
E
B
1-1/4" CONTROL OPENING
ASME PLATE
A
AA
A
A
B
A
A
B
NOTE:
1) ADD SUFFIX “ES” FOR SINGLE - WALL OR “ED” FOR DOUBLE - WALL TO MODEL NUMBER WHEN EQUIPPED WITH A TUBE TANK HEATER (i.e.: HD-36-350ES).
2) SPECIFY FOR HORIZONTAL OR VERTICAL INSTALLATION.
3) NO LEG SOCKETS PROVIDED ON HORIZONTAL TANKS.
ALL DIMENSIONS IN INCHES
DIMENSION CHART
DIMENSION A B C D E
20 2 3/4 1 1/2 6 3/4
24 THRU 36
2 1/2 3/4 2 1/2 8 1
42 AND 48 3 3/4 3 10 1
54 THRU 96 3
3/4
3101
B
A
B
AA
AA
A
A
A
ASME PLATE
B
E
A
THREADED LEG SOCKET
"C"
T&P VALVE
A
OPENING
OVERALL
D
www.hotwater.com
Page 3 of 4
AOSTT35400
Page 4
Commercial Storage Tanks
TANK SADDLES
B
5’
(NOM.)
A
FACTORY INSULATION OPTIONS
Factory Jacketed and Insulation
n
INSULATION — Entire tank is surrounded with high-density fiberglass insulation to reduce costly heat loss; non-sagging and vermin-
proof. To meet or exceed the thermal efficiency and/or standby loss requirements of the U.S. Department of Energy and current edition of ASHRAE/IESNA 90.1, depth of insulation cavity requires use of remote bulb-type tank temperature control and thermometer.
n
CABINET — Heavy gauge steel with high quality powder coat paint provides additional insulating qualities for greater energy savings.
n
Adds 6˝ to the diameter of the tank.
A.O. SMITH
PART NO.
TANK DIA. A
P2-2600-20 20 22 P2-2600-24 24 26 P2-2600-30 30 32 P2-2600-36 36 38 P2-2600-42 42 44 P2-2600-48 48 50 P2-2600-54 54 56 P2-2600-60 60 62 P2-2600-66 66 58 P2-2600-72 72 74 P2-2600-84 84 86 P2-2600-96 96 98
B
6 6 6 6 6 6 8 8
8 10 10 10
OUTDOOR FOAM INSULATION
n
INSULATION — Entire tank is sprayed with minimum of 2˝ high-density polyurethane foam insulation that forms
a watertight jacket that is approved for outdoor use. Meets or exceeds the thermal efficiency and standby loss requirements of the U.S. Department of Energy and Current Edition of the ASHARAE/IESNA 90.1.
n
Adds 6˝ to the diameter of the tank.
Note: Minimum foa m insula tion thi cknes s is 2˝ ; h owever, since tank is hand sprayed , insula tion thicknes ses may be greater in som e areas giving th e finishe d tank an uneven b ut watertight surface.
HIGH EFFICIENCY (R-16) FACTORY JACKET AND INSULATION
n
INSULATION — Meets or exceeds the thermal efficiency and/or standby loss requirements of the U.S. Department of Energy and Current
Edition of the ASHARAE/IESNA 90.1. For Green building jobs where maximum energy efficiency is required. Entire tank is surrounded with high-density fiberglass insulation to reduce costly heat loss and save additional energy; non-sagging and vermin-proof. The increased depth of the insulation cavity requires use of remote bulb-type tank temperature control and thermometer.
n
CABINET — Heavy gauge steel with high quality powder coat paint provides additional insulating qualities for greater energy savings.
n
Adds 10˝ to the diameter of the tank.
SUGGESTED SPECIFICATION
SAMPLE SPECIFICATION FOR CUSTOM-LINE STORAGE TANKS
When jacketed or insulated these models meet or exceed the thermal efficiency and standby loss requirements of ASHRAE 90.1b (current standard).
ASME storage tank to be A. O. Smith Custom-Line model ______________. Capacity to be ___________gallons with a diameter of _______ inches. Tank(s) shall be constructed and stamped according to ASME specifications for __________psi working pressure. Manhole (12”x16”), handhole (4x6) or inspection openings (2-2˝) shall be installed in accordance with ASME code requirements and manufacturer(s) standard practice. Tank to be constructed of (carbon steel) _________. Lining shall be (glass, epoxy, cement) ______________. Tank(s) lined with (glass, cement, epoxy) _____________lining shall be equipped with the number and size of magnesium anode rod(s) sufficient to provide adequate protection for the tank lining. Tank shall be (vertical, horizontal) _______________ design and provided with (four) ___________ (angle iron legs, threaded leg socket(s)) _____________ ring base, ___________ saddles.
SAMPLE SPECIFICATION FOR TANK HEATERS
Tank heaters shall be Model No. ____________ 3/4˝ OD 20 gauge copper “U” tubes. Heater to have ________ square feet of heating surface to heat ____________ gallons per hour from_____________ degrees F to ____________ degrees F with heating media of ____________psi steam (or _________ degrees F boiler water). The element shall be constructed so that the entire section can be removed from the tank for cleaning and inspection.
For Technical Information and Automated Fax Service, call 800-527-1953. A.O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Page 4 of 4
www.hotwater.com
AOSTT35400