A. O. Smith GB-1300 Installation Manual

Genesis Engineering and Design Manual
Introduction
Engineering and Design Manual
Dear A. O. Smith Customer,
This Engineering and Design Manual has been written to aid in designing and specifying
A. O. Smith Genesis hydronic heating boilers. This manual is intended to quickly and easily
answer the most frequently asked questions regarding the Genesis product line.
to be all inclusive. Reference should be made to the instruction manual accompanying the
product. This Engineering and Design Manual contains supplemental information to the
Genesis Instruction and User’s Information Manual. A copy of the complete instruction manual
can be obtained from the A. O. Smith website (www.hotwater.com), from the A. O. Smith
Customer Care Center at 1-800-527-1953, or from your local A. O. Smith Representative.
A. O. Smith is proud of our quality products, and we appreciate your interest in our
products. We hope to be working with you soon.
Sincerely yours,
A. O. Smith Water Heaters
1
Table of Contents
CHAPTER 1 - BASICS OF INSTALLATION .............................................................................5-6
Code Compliance............................................................................................................5
Location...........................................................................................................................5
Installation Clearances....................................................................................................5
CHAPTER 2 - SPECIAL SITUATIONS......................................................................................7-8
Installation on Combustible Flooring...............................................................................7
Outdoor Units ..................................................................................................................7
CHAPTER 3 - COMBUSTION AIR..........................................................................................9-12
Sizing Combustion Air Louvers.......................................................................................9
Combustion Air and the Genesis Boiler..........................................................................9
or Combustion (Through the Wall)..........................................................................10
Air f
Air for Combustion (Vertical Ducts)...............................................................................10
Air for Combustion (Horizontal Ducts) ..........................................................................11
Alternate Air f
or Comb
ustion.........................................................................................11
CHAPTER 4 - SPECIAL PROBLEMS - COMBUSTION AIR ...............................................13-14
Boiler Room Exhaust Fans ...........................................................................................13
Contaminated Combustion Air ......................................................................................13
Flammable Items...........................................................................................................14
CHAPTER 5 - VENTING SECTION.......................................................................................15-36
General Venting Information..........................................................................................15
enting Categor
Genesis
Genesis Boiler Category I Venting ................................................................................16
Natural Draft Vertical Venting Using Boiler Room Air for Combustion (Category I)......17
Masonr
Category I Common Venting Multiple Units ..................................................................18
Common Venting Genesis Boilers When Using A Stack-Rack.....................................19
Categor
Category I Vertical Direct Venting (Two Pipe System Using Outdoor Air) ....................21
Meeting Special State and Local Codes Requiring Direct Vent Sealed Combustion ...23
Category III One Pipe Sidewall Venting Using Boiler Room Air ...................................24
Category III Horizontal Two Pipe Direct Vent Using Outdoor Air ..................................25
Category III Extended Horizontal Sidewall And Direct Venting (Power Assist) ............27
Locating Exhaust and Comb Special
Category III - Genesis Venting ......................................................................................29
Termination Considerations...........................................................................................30
Type “B” Double Wall Vent Sizing Tables .................................................................31-35
V
y Chimne
y I Natural Draft Vertical Vent Termination........................................................20
ent Terminal Location Considerations ............................................................29
V
ys - Atmospher
ies and Venting Materials......................................................15
ic Dr
ustion Air
.......................................................................
aft
erminations ....................................................29
T
18
2
Genesis Engineering and Design Manual
Table of Contents
CHAPTER 6 - GAS SUPPLY......................................................................................................37
General Genesis Gas Supply Considerations .........................................................37-40
Single Boiler Gas Pipe Sizing .......................................................................................38
Gas System Sizing........................................................................................................38
Multiple Appliance Gas System Sizing - Natural Gas...................................................38
Multiple Appliance Gas System Sizing - Propane Gas.................................................39
High Altitude Installations..............................................................................................39
General Altitude Information .........................................................................................39
High Altitude Sizing Considerations..............................................................................40
Genesis Pre-Jet Orifices ...............................................................................................40
CHAPTER 7 - GENESIS ELECTRICAL REQUIREMENTS.......................................................41
CHAPTER 8 - HYDRONIC HEATING SYSTEMS & COMPONENTS...................................43-45
Genesis Boilers .............................................................................................................43
Boiler & System Water Flo
Boiler Temperature Settings ..........................................................................................44
Hydronic Heating System Components
w Requirements..................................................................43
........................................................................44
CHAPTER 9 - HYDRONIC HEATING SYSTEM PIPING ......................................................47-57
Primary/Secondary Piping ............................................................................................47
Primary/Secondary Piping Multiple Boilers...................................................................48
Boiler Oper
Minimum System/Boiler Temperature ...........................................................................49
Locating the System Temperature Sensor ....................................................................49
imar
Pr
For Design Temperatures of 180°F or Less..................................................................50
For Design Temperatures Over 180°F ..........................................................................51
or Design
F
Understanding Cast Iron and Steel Boiler Systems with Three-Way Mixing Valves.....53
Efficiency of Low Mass vs. High Mass Boilers..............................................................53
Retrofitting A Cast Iron Boiler
Boiler System ................................................................................................................54
Special Cases - Piping Low or Varied Flow Systems ...................................................56
INDEX OF FIGURES ..................................................................................................................58
ABLES
INDEX OF
T
ating Temperature Controls.........................................................................48
y/Secondar
T
.....................................................................................................................59
y - Multiple Boiler Piping Configurations.....................................50-52
F ........................................................................52
°
emper
atures Belo
w 120
With Three-Way Mixing Valve To A Copper
3
Basics of Installation
Air Inlet
Alternate Air Inlet
xhaust Vent
E
Alternate Exhaust Vent
Gas Connection
odels 200 thru 500
M
Gas Connection Models 650 & 750
Control Board Access Door
On/Off
witch
S
Flow Switch Factory Mounted
Factory Sized and Mounted Pump (Standard GW Water Heaters, Optional GB Boiler Models)
Control Box Access Door
Genesis Boiler Points of Reference
Exhaust Vent
Alternate Exhaust Vent
Pressure Relief Valve
Water Outlet
Dia-Scan II User Interface & Digital Readout
Control Board Access Door
Genesis Models GB-300 thru 750
Control Board Access Door
Air Inlet
Water Inlet
View Port
On/Off Switch
Electrical Connection Boxes
al Boiler Mounted Pump
r
Integ (Standard GW Water Heaters, Optional GB Boiler Models)
Control Box Access Door
Pressure Relief Valve
Water Outlet
Dia-Scan II User Interface
Digital Readout
&
Exhaust Vent
Left or Right Hand Gas Connections
Genesis Models GB-1000 thru 2500
Figure 1-1
Water Inlet
View Port
Integral Boiler Mounted Pump (Standard GW Water Heaters, Optional GB Boiler Models)
4
Genesis Engineering and Design Manual
CHAPTER 1. BASICS OF INSTALLATION
Code Compliance
The Genesis boiler design complies with the
latest edition of the American National Standards
Institute for gas-fired, low-pressure steam and hot
water boilers, ANSI Z21.13 and CSA 4.9.
In addition to the information in the instruction
manual, the boiler(s) shall be installed in strict
accordance with those installation regulations in
force in the local area where the installation is to
be made
consulted bef
absence of local codes
comply with the latest editions of:
. Author
ities having jurisdiction should be
ore installations begin. In the
, the installation m
ust
the piping system as possible. This location
should also be such that the gas ignition system
components are protected from external dripping
and spraying of water during appliance operation
and service.
Additional boiler location considerations:
• The boiler must not be installed on carpeting
(See Chapter 2).
• The boiler should not be located in an area
where it will be subject to freezing.
• The boiler should be located near a floor drain.
• The boiler should be located in an area where
leakage from the boiler or connections will not
result in damage to the adjacent area or to
lower floors of the structure.
In the United States:
The National Fuel Gas Code, ANSI
Z223.1/NFP
Electr
The installation Code CAN/CSA B149.1-00
Electric Code, CSA C22.1.
A 54 and the National
ic Code, NFPA 70.
In Canada:
and the Canadian
Location
Before installing any boiler, careful
consideration must be given to proper location.
The location selected should be as close to the
stack or chimney as practical, offer adequate
make-up air supply, and be as centralized within
Note: When such locations cannot be avoided,
a suitable drain pan should be installed under
the boiler. Drain pans should be fabricated with
sides at least 2
width at least 2 inches greater than the
dimensions of the boiler. The drain pan must be
piped to an adequate drain and must not restrict
combustion air flow.
1
2 inches deep, with length and
Installation Clearances
Sufficient area should be provided at the front
and sides of the unit for proper servicing. For ease
of service, minimum clearances of 24 inches in
the front and 18 inches on the water connection
side are recommended.
5
Basics of Installation
Please note that the minimum clearances
shown are the certified minimum clearances.
Whenever possible, additional space is
recommended. Genesis boilers are approved for
installation on noncombustible flooring in an
alcove with minimum clearance to combustibles.
For installation on combustible flooring, see
Chapter 2 Special Situations.
Figure 1-2 Figure 1-3
(Table A) Minimum Clearances to Combustibles
Clearances
Left Side A
Rear B 3" 3"
Right Side C 3" 3"
Top D 3" 6"
Front
Vent 6" 6"
Hot Water Pipes 2" 2"
Location
Figure 2 & 3
Models GB/GW-400 - 750
3" 12"
(18" for Service) (18" for Service)
Alcove Alcove
(24" for Service) (24" for Service)
Models GB/GW-1000 -
2500
6
Genesis Engineering and Design Manual
CHAPTER 2. SPECIAL SITUATIONS
Installation on Combustible Flooring
For installation on combustible flooring, use
the Combustible Floor Shield Kit.The combustible
floor kit base adds 4˝ to the overall height of the
boiler. See Figure 2-1. (See Table B for kit part #).
Genesis on
Combustible Floor Shield
concrete pad. The concrete pad must be at least
12 inches larger than the boiler footprint on all four
sides of the boiler.
For rooftop installations use the combustible
floor base (see Figure 2-1 and Table B for kit part #).
• An outdoor model Genesis boiler should not
be located in an area where high winds can
cause a down draft by rolling off walls,
buildings, shrubbery, inside corners, or roof
overhangs. The boiler should be a minimum
of 6 feet away from such structures if high
winds are prevalent in the area.
Table B - Combustible Floor Shield Kit #
Outdoor Units
or
ed f
Smith Genesis boilers are appro
.
O
A.
outdoor installation ONL
Outdoor units require additional
.
kits
consider
this engineer
the Instr
ations that will not be fully discussed in
ing and design man
uction Man
issues are addressed belo
Y with appro
or full details
ual f
ual.
.
.
w
Primary Outdoor Issues:
The outdoor boiler cannot be installed directly on
the ground.
The boiler m
ust be installed on a
v
ed outdoor
v
Please see
Only pr
imar
Model # A.O. Smith Part #
GB-300 9500007275
GB-400 210202-002
GB-500 9003670001
GB-650 210202-004
GB-750 9500007276
GB-1000 21
y
GB-1300 211093-001
GB-1500 21
GB-1850 211093-003
GB-2100 211093-004
GB-2500 211093-005
1093-000
1093-002
7
Special Situations
• Outdoor units should never be installed
under roof overhangs where water from the
roof can fall directly on the unit. Install at least
3 feet away from the drip line of the roof
overhang.
• Special considerations apply in areas where
freezing temperatures are encountered.
Genesis boilers in hydronic heating
applications must use a glycol mixture. In
addition, for Genesis boilers used in a potable
domestic hot water application, the boiler pump
delay setting must be set to “constant run.”
Note: If any potable domestic hot water heating
system must be shut down for service during cold
weather, shut off the water supply, then drain the
boiler, piping, and pump. Additional freeze
protection measures such as automatic drain
systems should also be considered.
8
Genesis Engineering and Design Manual
CHAPTER 3. COMBUSTION AIR
Figure 3-1 Combustion Air
Combustion Air
Complete combustion requires 10 cubic f
of air per 1000 BTU per hour gas input. The
National Fuel Gas Code also recommends an
“excess”
additional 2.5 cubic f
cubic f
gas input is the recommended minimum
combustion air supply required to ensure
complete combustion for natural and propane gas
equipment. (See Figure 3-1).
minimum make-up air opening sizes for various
building installations. (Ref: NFPA 54/ANSI
Z223.1, sec. 5.3 or CAN/CSA B149.1-00).
eet of make-up air per 1000 BTU per hour
The National Fuel Gas Code specifies
eet of
air. This 12.5
eet
should be considered.
mesh smaller than 1/4-inch square
area is not kno
National Fuel Gas Code ANSI Z223.1
recommends using figures of 20-25 percent free
area for wood louvers, or 60-75 percent for metal
illes or louv
r
g
wn, the current edition of the
.
ers
Screens shall not be of
. If the free
Combustion Air and the Genesis Boiler
When installing the Genesis in an area of tight
uction or within a
constr
than 50 cubic f
the total input r
that space), adequate comb
eet of volume per 1,000 BTU/H of
ating of all appliances installed in
“confined” air space (less
ustion air must be
Sizing Combustion Air Louvers
To calculate the free area of a vent opening,
the blocking effect of screens, louvers, and grilles
supplied to the boiler
from NFP
explains various methods of meeting the
minimum air requirements for these installations.
9
A 54, ANSI Z223.1, 1996, Sec., 5.3
. The following information
Combustion Air
Air for Combustion (Through the Wall)
The Genesis is installed as a Category I
appliance when it is vented vertically and is using
boiler room air for combustion. (Can use standard
type “B” vent material when installed in this
configuration.) A fresh supply of make-up air for
combustion can be supplied to the boiler through
make-up air ducts which directly communicate
with the outdoors. Two openings are required: one
Figure 3-2 Air for Combustion
(Through the Wall)
within 12 inches of the top of the enclosure and
one within 12 inches of the bottom of the
enclosure. Each opening shall have a free area
of not less than 1 square inch per 4000 BTUH of
the total input of all appliances within the enclosure.
Air for Combustion (Vertical Ducts)
The lower opening is primarily providing
combustion air. The upper opening is providing
vent dilution air and acts as a relief opening f
flue gases in the event that the vent becomes
obstructed or a do
wndraft condition occurs.
or
Figure 3-3 Air for Combustion (Vertical Ducts)
Often it is more practical to install vertical
make-up air ducts, as shown in Figure 3-3, to the
outdoors. Again, two openings are required: one
within 12 inches of the top of the enclosure and
one within 12 inches of the bottom of the
enclosure. Each opening shall have a free area
of not less than 1 square inch per 4000 BTUH of
the total input of all appliances within the
enclosure.
10
Figure 3-4 Air for Combustion (Horizontal Ducts)
Air for Combustion (Horizontal Ducts)
Genesis Engineering and Design Manual
When the boiler is installed in an inter
ertical ducts, horizontal
with no roof access f
make-up air ducts should be installed.
using horizontal ducts, two openings are required:
one within 12 inches of the top of the enclosure
or v
ior room
When
Alternate Air for Combustion
and one within 12 inches of the bottom of the
enclosure
of not less than 1 square inch per 2000 BTUH of
the total input of all appliances within the
enclosure.
. Each opening shall have a free area
Figure 3-5 Alternate Air f
Since the release of the 1996 edition, the
National Fuel Gas Code has allo
method of supplying air f
or combustion using a
wed a second
(Thr
ough the
single opening.
opening and is intended to help pre
damage to boiler room piping.
11
or Combustion
all)
W
This method uses a smaller
vent freeze
Combustion Air
Alternate Air for Combustion (continued)
Figure 3-6 Alternate Air for Combustion (Vertical Duct)
One permanent opening, commencing within
12 inches (30 cm) of the top of the enclosure,
shall be permitted where the equipment has
clearances of at least 1 inch (2.5 cm) from the
sides and back and 6 inches (16 cm) from the
front of the appliance. The opening shall directly
comm
unicate with the outdoors or shall
communicate through a vertical or horizontal duct
to the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors, and shall
have a minimum free area of:
• 1 square inch per 3000 BTU/H (7cm
2
per kW)
of the total input rating of all equipment located
in the enclosure, and
• not less than the sum of the cross sectional
areas of all v
ent connectors in the confined
space.
Figure 3-7 Alternate Air for Combustion (Horizontal Duct)
12
CHAPTER 4. SPECIAL PROBLEMS –
COMBUSTION AIR
Boiler Room Exhaust Fans
Genesis Engineering and Design Manual
Insufficient make-up air is a major cause of
combustion problems. One common example is a
mechanical room where exhaust vent equipment
was not considered in sizing make-up air
requirements. This may result in air being pulled
down the exhaust vent of the Genesis causing flue
gas spillage, flame roll out, improper combustion
(sooting), and/or erratic boiler shut down.
Figure 4-1 Boiler Room Exhaust F
Contaminated Combustion Air
The quality of the combustion air is important
in all applications, including those involving direct
venting. Contaminants in combustion air can lead
to premature boiler failure. Vapors from
bleaches, soaps, waxes, salts, freon, (See
Figure 4-2) etc. are drawn into the combustion
chamber with the make-up air and, once fired,
mix with water vapor in the gases to form
extremely corrosive hydrochloric or hydrofluoric
acid and other corrosive by-products.
ans
Figure 4-2
13
Special Problems - Combustion Air
Flammable Items
Flammable items, pressurized containers or
any other potentially hazardous articles must not
be placed on or adjacent to the boiler. Open
containers of flammable material should not be
stored or used in the same room with the boiler.
14
Genesis Engineering and Design Manual
CHAPTER 5. VENTING SECTION
General Venting Information
The Genesis boiler is a fan-assisted
appliance, that offers many different venting and
combustion make-up air options and methods. It
has a sealed combustion chamber and can be
installed as a true Category III Direct Vent
Appliance. However, the Genesis unit can also be
installed in less stringent Category I
configurations. Whatever the configuration, you
must understand the following definitions in order
to proper
mak
application.
ly specify the venting and combustion
e-up air requirements for a particular
Definitions:
Fan Assisted Combustion
• A fan-assisted comb
ustion appliance is one
• Category III - A non-condensing gas
appliance that operates with a positive vent
pressure.
• Category IV - A condensing gas appliance
that operates with a positive vent pressure.
Genesis Venting Categories and Venting Materials
The Genesis boiler operates at an efficiency
of 83.7% (rounded to 84%), the highest efficiency
possible in a non-condensing boiler. At 83.7%, the
Genesis is operating near the threshold of
condensing. When vented vertically, the natural
draft and natural buoyancy of the hot flue gases
move the flue gases up the vent rapidly before the
gases can condense in the vent. This allows the
use of standard Type “B” venting material.
which has a f
A fan-assisted burner is defined as: “a burner
which uses either induced or forced draft.”
• A draft hood appliance can only be a
Category I appliance, while an appliance with
a fan-assisted burner may fall into any of the
four categories.
Gas Appliance Venting Categories Defined:
• Category I - A non-condensing gas appliance
that operates with a non-positive vent
pressure.
• Category II - A condensing gas appliance
that operates with a non-positive vent
pressure.
an-assisted burner.
However, when venting the unit horizontally,
and without the aid of a natural draft, the flue
gases move more slowly providing additional time
for the flue gases to cool, increasing the likelihood
of flue gases condensing in the vent. Therefore,
when venting mid-efficiency boilers, (such as the
Genesis) horizontally, AL29-4C stainless steel
venting material must be used to prevent damage
from corrosive condensate building up in the
vent. Such buildup in non-approved vent piping
will potentially result in deadly flue gases leaking
into the building or facility.
15
Venting Section
Genesis venting will fall into one of the four configurations as shown on Table C.
(Table C) Genesis Vent Categories and Materials
Source of Combustion
Air
Using Boiler Room Air
(Non - Direct Vent)
Using Outdoor Air Piped
Directly to the Boiler
(Dirct Vent)
Venting
Configuration
Vertical Venting
Natural Draft
Horizontal
Sidewall Venting
ertical Venting Category I
V
Horizontal
Sidewall Venting
Certified Venting
Genesis Boiler Category I Venting
Single Unit
The Genesis boiler uses fan assisted
ustion. When sizing the vent for a Genesis
comb
boiler in a natur
the “Fan” columns in the venting tables (see pages
al draft vertical vent system, use
Category
Category I
Category III
Category III
Approved Venting
Meterial
Type "B" or
Equivalent
AL29-4C
Stainless Steel
(Gas Tight)
Type "B" or
Equivalent
AL29-4C
Stainless Steel
(Gas Tight)
Approved
Combustion Air
None
PVC, ABS, CPVC,
Galvanized Steel
31-35). A single Genesis boiler may be vented
vertically up to 35 feet without a barometric
damper. Over 35 vertical feet a barometric
damper is required. A barometric damper is also
required if the dr
aft in the vent exceeds negative
0.05 inches water column (W.C.). Adjust the
barometric damper to maintain between negative
0.02 inches and negative 0.05 inches water
column (W.C.). See Figure 5-1.
When retrofitting and venting the Genesis
boiler through an oversize metal or masonry
chimney, additional care must be exercised. As
always, a minimum draft of negative 0.02 inches
W.C. and a maximum draft of negative 0.05 inches
W.C. must be maintained. This draft should be
measured 2 feet above the boiler vent collar.
16
Genesis Engineering and Design Manual
Natural Draft Vertical Venting Using Boiler Room Air for Combustion (Category I)
Genesis is using
Boiler Room Air For Combustion
Figure 5-2 - Natural Draft Vertical Venting
(Table D) Genesis Natural Draft Vertical Vent
Model #
GB/GW
GB/GW-400 thru
GB/GW-500
GB/GW-650 thru
GB/GW-750
GB/GW-1000 10 Category I
GB/GW-1300 thru
GB/GW-1500
GB/GW-1850 thru
GB/GW-2100
GB/GW
-300
-2500
Vent Size
(Inch)
5 Category I
6 Category I
8 Category I
12 Category I
14 Category I
16 Category I
Certified Venting
Category
Approved Venting
Material
Type "B" or
Equivalent
Type "B" or
Equivalent
Type "B" or
Equivalent
ype "B" or
T
Equivalent
Type "B" or
Equivalent
Type "B" or
Equivalent
Type "B" or
Equivalent
Max. Distance W/O
Barometric Damper /
With Barometric
o Roof
35' / T
35' / To Roof
35' / To Roof
35' / To Roof
o Roof
35' / T
35' / To Roof
o Roof
35' / T
17
Venting Section
Carefully inspect all chimney systems during
the project design phase. If there is any doubt
about the sizing or condition of a masonry
chimney, reline the chimney with a properly sized
and approved chimney liner system. Metal liner
systems Type "B" double wall or flexible metallic
liners are recommended. Consult with local code
officials to determine code requirements.
Category I Common Venting
Figure 5-3 - Masonry Chimney
Masonry Chimneys - Atmospheric Draft
A masonry chimney must be properly sized
for the installation of any gas fired appliance.
Exterior masonry chimneys with one or more
sides exposed to cold outdoor temperatures are
more likely to have venting problems. The
temperature of the flue products from a mid
efficiency appliance may not be able to sufficiently
ucture of the chimney to
heat the masonr
ate proper dr
gener
condensing of flue products
masonr
y flue tile
y str
This will result in
aft.
, insufficient dr
, damage of the
aft, and possib
Multiple Units
When common venting multiple Genesis
boilers, barometric dampers will be required at
each unit to regulate the draft. The negative draft
must be within the range of negative 0.02 inches
W.C. to negative 0.05 inches of W.C. to ensure
le
spillage of flue products into an occupied living
.
space
Very tall and or large chimneys may have
excessively high and hard to control draft,
resulting in poor combustion, nuisance control
lockouts, overheating of the combustion chamber,
and premature boiler failure.
Figure 5-4 - Multiple Units Preferred
Method
proper draft and good boiler operation. It is
recommended that a barometric damper be
installed in the vent connector between the boiler
vent outlet and the main breeching. (See Figure 5-4).
18
Loading...
+ 43 hidden pages