*Figured at 1 KW (3413 Btu) = 4.1 gallons at 100°F temperature rise.
To determine recovery rate per minute, divide recovery rate per hour by 60.
Approvals
All models bear theAll models are listed
National Sanitationby Underwriters
Foundation seal ofLaboratories Inc.
approval.
3
Model and Rating
Foreword
Detailed installation diagrams are in this manual. These diagrams
will serve to provide the installer with a reference for the materials
and method of piping suggested. IT IS NECESSARY THAT ALL
WA TER PIPING AND THE ELECTRICAL WIRING BE INST ALLED
AND CONNECTED AS SHOWN IN THE DIAGRAMS.
Particular attention should be given to the installation of
thermometers at the locations indicated in the diagrams as these
are necessary for checking the operation of the heater.
In addition to these instructions, the equipment shall be installed
in accordance with those installation regulations in force in the
local area where the installation is to be made. Authorities having
General Safety Information
PRECAUTIONS
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN
UNDER WATER. Immediately call a qualified service technician
to inspect the appliance and to replace any part of the control
system and any gas control which has been under water.
IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT
OPERATE HEATER UNTIL ALL CORRECTIVE STEPS HAVE
BEEN MADE BY A QUALIFIED SERVICEMAN.
1. EXTERNAL FIRE.
2. DAMAGE.
3. FIRING WITHOUT WATER.
GROUNDING INSTRUCTIONS
This water heater must be grounded in accordance with the
National Electric Code and/or local codes. These must be followed
in all cases.
This water heater must be connected to a grounded metal,
permanent wiring system; or an equipment grounding conductor
must be run with the circuit conductors and connected to the
equipment grounding terminal or lead on the water heater.
HYDROGEN GAS (FLAMMABLE)
CAUTION
HYDROGEN GAS CAN BE PRODUCED IN A HOT WATER
SYSTEM SERVED BY THIS HEA TER THA T HAS NOT BEEN USED
FOR A LONG PERIOD OF TIME (GENERALLY TWO WEEKS OR
MORE).
reduce the risk of injury under these conditions, it is recommended
HYDROGEN GAS IS EXTREMELY FLAMMABLE. To
jurisdiction shall be consulted before installations are made.
BE SURE TO TURN OFF POWER WHEN WORKING ON OR
NEAR THE ELECTRICAL SYSTEM OF THE HEATER. NEVER
TOUCH ELECTRICAL COMPONENTS WITH WET HANDS OR
WHEN STANDING IN WATER.
ALWAYS USE THE CORRECT SIZE FOR THE CIRCUIT. SEE
P AGE 16 THROUGH 21.
The principal components of the heater are identified on page 2.
The model and rating plate on page 4 interprets cert ain markings
into useful information. Both of these references should be used
to identify the heater, its components and optional equipment.
that the hot water faucet be opened for several minutes at the kitchen
sink before using any electrical appliance connected to the hot water
system. If hydrogen is present there will probably be an unusual
sound such as air escaping through the pipe as the water begins to
flow.
THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR
THE F AUCET AT THE TIME IT IS OPEN.
WHEN REPLACING FUSES
INSULA TION BLANKETS
Insulation blankets available to the general public for external
use on water heaters are not approved for use on your A.O.
Smith water heater. The purpose of an insulation blanket is to
reduce the standby heat loss encountered with storage tank
water heaters. Your A.O. Smith water heater meets or exceeds
the ASHRAE/IES 90.1b 1992 standards with respect to insulation
and standby loss requirements, making an insulation blanket
unnecessary.
WARNING
Should you choose to apply an insulation blanket to this heater,
you should follow these instructions (See "Getting to know your
water heater" on page 2 for identification of components mentioned
below). Failure to follow these instructions can result in fire,
asphyxiation, serious personal injury or death.
Do not cover the temperature & pressure relief valve.
•
• Do not cover the instruction manual. Keep it on the side of
the water heater or nearby for future reference.
• Do obtain new labels from A.O. Smith for placement on the
blanket directly over the existing labels.
WARNING
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT
IN SERIOUS PERSONAL INJUR Y OR DEATH.
4
Installation
REQUIRED ABILITY
INSTALLATION OR SERVICE OF THIS WATER HEATER
REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED
TRADESMAN IN THE FIELD INVOLVED. PLUMBING AND
ELECTRICAL WORK ARE INVOLVED.
GENERAL
The installation must conform to these instructions and the local
code authority having jurisdiction. Grounding and electrical wiring
connected to the water heater must also conform to the current
version of the
requirements the current version of the
CAN/CSA-C22.2 No. M91. These codes may be obtained from
the following institutes; The NFP A-70 is available from the National
Fire Protection Association, 1 Batterymarch Park, Quincy, MA
02269. The CAN/CSA C22.2 No. M91 is available from the
Canadian Standards Association, 178 Rexdale Blvd., Toronto
Ontario, Canada M9W 1R3.
If your location requires the installation of the water heater to
comply with National Sanitation Foundation requirements, the
heater must be sealed to the floor so as to prevent seepage
underneath the heater. The following are recommended sealants
that may be used on all types of flooring except concrete GE
Silicone Seal RTV-120, 103, 108, and 109.
National Electrical Code NFPA-70 or for Canadian
Canadian Electric Code,
LOCATION
For proper installation, the heater should be installed on a level
surface.
LOCATE THE WATER HEATER NEAR A FLOOR DRAIN. THE
HEATER SHOULD BE LOCATED IN AN AREA WHERE
LEAKAGE FROM THE HEA TER OR CONNECTIONS WILL NOT
RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER
FLOORS OF THE STRUCTURE.
WHEN SUCH LOCATIONS CANNOT BE A VOIDED, A SUITABLE
DRAIN PAN SHOULD BE INSTALLED UNDER THE HEATER.
Such pans should be fabricated with sides at least 2" deep, with
length and width at least 2" greater than the diameter of the heater
and must be piped to an adequate drain. Drain pans suitable for
these heaters are available from your distributor or Product Service
Division, A.O. Smith W ater Heater Parts Fulfillment, 125 Southeast
Parkway, Franklin, TN 37068.
Water heater life depends upon water quality , water pressure and
the environment in which the water heater is installed. Water
heaters are sometimes installed in locations where leakage may
result in property damage, even with the use of a drain pan piped
to a drain. However, unanticipated damage can be reduced or
prevented by a leak detector or water shut-off device used in
conjunction with a piped drain pan. These devices are available
from some plumbing supply wholesalers and retailers, and detect
and react to leakage in various ways:
• Sensors mounted in the drain pan that trigger an alarm or turn
off the incoming water to the water heater when leakage is
detected.
• Sensors mounted in the drain pan that turn off the water supply
to the entire home when water is detected in the drain pan.
• Water supply shut-off devices that activate based on the water
pressure differential between the cold water and hot water pipes
connected to the water heater.
• Devices that will turn off the gas supply to a gas water heater
while at the same time shutting off its water supply.
Locate the heater close to the point of major hot water usage and
the power supply.
•Try to make hot water piping and branch circuit wiring as short
as possible.
•Insulate hot and cold water piping where heat loss and
condensation may be a problem.
THE HEATER SHOULD NOT BE LOCA TED IN AN AREA WHERE
IT WILL BE SUBJECT TO FREEZING.
Suggested clearances from adjacent surfaces are 18 inches in
front for access to the controls and elements and 12 inches from
top. The heater may be installed on or against combustible
surfaces.
W ATER LINE CONNECTIONS
This manual provides detailed installation diagrams (see back
section of this manual) for typical methods of application for the
water heaters. The water heater may be installed by itself, or with
a separate storage tank, on both single and two-temperature
systems. When used with a separate storage tank, the circulation
may be either by gravity or by means of a circulating pump. When
a circulating pump is used it is important to note that the flow rate
should be slow so that there will be a minimum of turbulence
inside the heater.
CAUTION
A closed system will exist if a check valve, pressure reducing
valve, or a water meter is installed in the cold water line between
the water heater and street main (or well).
Excessive pressure may develop causing premature tank failure
or intermittent relief valve operation. This type of failure is notcovered by the limited warranty. An expansion tank may be
required in the inlet supply line between the appliance and the
meter or valve to compensate for the thermal expansion of water.
If a water heater is installed in a closed water system, contact the
water supplier or local plumbing inspector on how to control this
situation.
RELIEF DEVICES
CAUTION
TO REDUCE THE RISK OF EXCESSIVE PRESSURES AND
TEMPERATURE IN THIS WATER HEATER, INSTALL
TEMPERATURE AND PRESSURE PROTECTIVE EQUIPMENT
REQUIRED BY LOCAL CODES but not less than a combination
temperature and pressure relief valve certified by a nationally
recognized testing laboratory that maintains periodic inspection
of production of listed equipment or materials, as meeting the
requirements for Relief Valves for Hot Water Supply Systems,
ANSI Z21.22 /CSA 4.4 (current version).
This valve must be marked with a maximum set pressure not to
exceed the marked maximum working pressure of the water heater.
INSTALL THE VALVE INTO AN OPENING PROVIDED AND
MARKED FOR THIS PURPOSE IN THE WATER HEATER, AND
ORIENT IT OR PROVIDE TUBING SO THAT ANY DISCHARGE
FROM THE VAL VE WILL EXIST ONL Y WITHIN 6 INCHES ABOVE,
OR A T ANY DISTANCE BELOW THE STRUCTURAL FLOOR AND
CANNOT CONTACT ANY LIVE ELECTRICAL PART. THIS
DISCHARGE OPENING MUST NOT BE BLOCKED OR REDUCED
IN SIZE UNDER ANY CIRCUMST ANCES.
5
The pressure setting of the relief valve should not exceed the
pressure capacity of any component in the system. The
temperature setting of the relief valve should not exceed 210°F.
SMALL CHILDREN TO USE A HOT WATER TAP, OR TO DRAW
THEIR OWN BATH WATER. NEVER LEAVE A CHILD OR
DISABLED PERSON UNA TTENDED IN A BATHTUB OR SHOWER.
An unplugged 3/4" relief valve opening is provided for installing
temperature and pressure relief valve.
TEMPERA TURE LIMITING CONTROL(S)
Both the DVE and DRE model water heaters incorporate high
temperature cutoffs. In the event of high temperature cutoff
operation, the reason for the operation of the high temperature
cutoff operation must be determined and corrected. Once the
situation has been corrected the high temperature cutoff(s) may
be reset in the following manner:
DVE Models
The DVE models have a single immersion-type high temperature
cutoff control in the control circuit, see DVE CONTROL CIRCUIT
DIAGRAMS. This high temperature cutoff is factory set to open at
190°F (88°C). To manually reset the control you must:
1. Disconnect the power to the heater.
2. Allow the tank to cool to approximately 120°F.
3. Remove the front control cover.
4. Press the manual reset button. The control will not
reset until it has cooled approximately 50°F (28°C).
DRE Models
The DRE models have multiple surface mounted combination high
temperature cutoff and thermostat controls. There is one of these
combination high temperature cutoff and thermostat controls for
each element in a DRE model, see DRE CIRCUIT DIAGRAMS.
Each of the high temperature controls is of the manual reset type.
To manually reset the controls:
THE WATER HEATER SHOULD BE LOCATED IN AN AREA
WHERE THE GENERAL PUBLIC DOES NOT HAVE ACCESS
TO SET TEMPERATURES.
SETTING THE WATER HEATER TEMPERATURES AT 120°F
WILL REDUCE THE RISK OF SCALDS. Some states require
settings at specific lower temperatures.
The water temperature is controlled in the DVE models with a
single thermostat located on the right front of the heater, just inside
the control cabinet. This control is set at 140°F at the factory and
has a fixed 5°F differential. The DRE models have multiple
thermostats depending on the configuration purchased. These
thermostats are also set at 140°F and have a 5-15°F differential.
A.O. Smith recommends setting the dial at the lowest setting which
produces an acceptable hot water supply. This will always give
the most energy efficient operation.
Figure 1 shows the approximate time-to-burn relationship for
normal adult skin.
Valves for reducing point-of-use temperature by mixing cold and
hot water are available. Also available are inexpensive devices
that attach to faucets to limit hot water temperatures.
licensed plumber or the local plumbing authority.
Contact a
1. Disconnect the power to the heater.
2. Allow the tank to cool approximately 160°F.
3. Remove the front control cover.
4. Press the manual reset button on each of the effected
controls. The control will not reset until it has cooled
approximately 30°F (17°C).
Once the control(s) has been reset the control cover should be
replaced prior to operating the heater.
TEMPERA TURE REGULA TION
DANGER
THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE
THERMOSTAT TO CONTROL WATER TEMPERATURE. HOT
WATER TEMPERATURES REQUIRED FOR AUTOMATIC
DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS
RESULTING IN SERIOUS PERSONAL INJURY AND/OR DEATH.
THE TEMPERA TURE A T WHICH INJURY OCCURS V ARIES WITH
THE PERSONS AGE AND TIME OF EXPOSURE. THE SLOWER
RESPONSE TIME OF CHILDREN, AGED, OR DISABLED
PERSONS INCREASES THE HAZARDS TO THEM. NEVER ALLOW
DRE MODELS DVE MODELS
TemperatureTime to produce 2nd & 3rd
SettingDegree burns on adult skin
180°FNearly instantaneous
170°FNearly instantaneous
160°FAbout 1/2 second
150°FAbout 1-1/2 seconds
140°FLess than 5 seconds
130°FAbout 30 seconds
120°FMore than 5 minutes
FIGURE 1
6
Piping Diagrams
ONE TEMPERA TURE WITH CIRCULATING LOOP
INSERT B
VACUUM RELIEF
VALVE. INSTALL PER
LOCAL CODES.
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE
TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 6. IF HIGHER PREHEAT
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT
WATER SUPPLIED TO FIXTURES.
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTER, CHECK VALVE OR WATER METER WITH
CHECK VALVE. PROVISIONS FOR THERMAL EXPANSION OF
WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED.
*PIPE TO OPEN DRAIN
INSTALL IN ACCORDANCE WITH A LL LOCAL CODES.
7
INSERT B
V ACUUM RELIEF
V ALVE. INSTALL PER
LOCAL CODES.
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE A T FIXTURES.
SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 6. IF HIGHER PREHEAT
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD
AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
8
INSERT B
V ACUUM RELIEF
V ALVE. INSTALL PER
LOCAL CODES.
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE
TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 6. IF HIGHER PREHEAT
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WA TER
SUPPLIED TO FIXTURES.
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.