WARNING: If the information in these
instructions is not followed exactly, a fire
or explosion may result causing property
damage, personal injury or death.
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
•
Do not touch any electrical switch; do
•
not use any phone in your building.
Immediately call your gas supplier
•
from a neighbor’s phone. Follow the
gas supplier’s instructions.
If you cannot reach your gas supplier,
•
call the fire department.
Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
Thank you for buying this energy efcient water heater.
We appreciate your condence in our products.
Read and understand this instruction
manual and the safety messages
herein before installing, operating or
servicing this water heater.
Failure to follow these instructions and
safety messages could result in death
or serious injury.
This manual must remain with the
water heater.
PLACE THESE INSTRUCTIONS ADJACENT TO HEATER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
PRINTED 0115 197288-004
TABLE OF CONTENTS
SAFE INSTALLATION, USE AND SERVICE ........................................ 3
The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others.
Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and
others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important
that the meaning of each safety message is understood by you and others who install, use, or service this water heater.
This is the safety alert symbol. It is used to alert you to
potential personal injury hazards. Obey all safety
messages that follow this symbol to avoid possible
injury or death.
DANGER indicates an imminently
DANGER
WARNING
CAUTION
hazardous situation which, if not avoided,
will result in injury or death.
WARNING indicates a potentially hazardous
situation which, if not avoided, could result
in injury or death.
CAUTION indicates a potentially hazardous
situation which, if not avoided, could result in
minor or moderate injury.
CAUTION used without the safety alert
CAUTION
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message, and
how to avoid the risk of injury.
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances
known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of
potential exposure to such substances.
This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm. This
water heater can cause low level exposure to some of the substances listed in the Act.
symbol indicates a potentially hazardous
situation which, if not avoided, could result in
property damage.
APPROVALS
LOW LEAD
Note: ASME construction is optional on the water heaters covered in this manual.
3
GENERAL SAFETY INFORMATION
Fire or Explosion Hazard
Read instruction manual before
installing, using or servicing
water heater.
Avoid all ignition sources if you smell gas.
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
Use only the gas shown on the water heater rating label.
Keep ignition sources away from faucets after extended
periods of non-use.
Maintain required clearances to combustibles.
Do not expose water heater controls to excessive gas
pressure.
Property Damage Hazard
All water heaters eventually leak.
•
Do not install without adequate drainage.
•
CAUTION
Fire and Explosion Hazard
Leak test before placing the
water heater in operation.
Disconnect gas piping and main
gas shutoff valve before leak
testing.
Install sediment trap in
accordance with NFPA 54.
Use joint compound or Teflon tape
compatible with propane gas.
For continued protection against
•
•
Fire Hazard
risk of fire:
Do not install water heater on
carpeted floor.
Do not operate water heater if
any part has been exposed to
flooding or water damage.
Electrical Shock Hazard
Turn off power to the water heater
•
before performing any service.
Label all wires prior to disconnecting
•
when performing service. Wiring errors
can cause improper and dangerous
operation.
Verify proper operation after servicing.
•
Failure to follow these instructions can
•
result in personal injury or death.
Fire and Explosion Hazard
Do not use water heater with any gas
other than the gas shown on the rating
label.
Excessive gas pressure to gas valve can
cause serious injury or death.
Turn off gas lines during installation.
Contact a qualified installer or service
technician for installation and service.
Jumping out control circuits or components can
result in property damage, personal injury or death.
Service should only be performed by a qualified service
•
technician using proper test equipment.
Altering the water heater controls and/or wiring in any way
•
could result in permanent damage to the controls or water
heater and is not covered under the limited warranty.
Altering the water heater controls and/or wiring in any way
•
could result in altering the ignition sequence allowing gas to
flow to the main burner before the hot surface igniter is at
ignition temperature causing delayed ignition which can
cause a fire or explosion.
Any bypass or alteration of the water
heater controls and/or wiring will result
in voiding the water heater warranty.
4
GENERAL SAFETY INFORMATION
Improper installation, use and service may result
in property damage.
•
Do not operate water heater if any part has been exposed
to flooding or water damage.
•
Inspect anode rods regularly, replace if damaged.
•
Install in location with drainage.
•
Fill tank with water before operation.
•
Properly sized thermal expansion tanks are required on all
closed water systems.
Refer to this manual for installation and service.
CAUTION
Read and understand this instruction
manual and the safety messages
herein before installing, operating or
servicing this water heater.
Failure to follow these instructions and
safety messages could result in death
or serious injury.
This manual must remain with the
water heater.
Water temperature over 125°F (52°C)
can cause severe burns instantly
resulting in severe injury or death.
Children, the elderly and the
physically or mentally disabled are at
highest risk for scald injury.
Feel water before bathing or
showering.
Temperature limiting devices such as
mixing valves must be installed
when required by codes and to
ensure safe temperatures at fixtures.
Explosion Hazard
Overheated water can cause
water tank explosion.
Properly sized temperature and
pressure relief valve must be
installed in the opening provided.
Verify the power to the water heater is turned off before performing any service procedures.
GENERAL SAFETY INFORMATION
PRECAUTIONS
DO NOT USE THIS WATER HEATER IF ANY PART HAS
BEEN EXPOSED TO FLOODING OR WATER DAMAGE.
Immediately call a qualified service technician to inspect the
water heater and to make a determination on what steps
should be taken next.
If the unit is exposed to the following, do not operate heater
until all corrective steps have been made by a qualified
service technician.
1. External re.
2. Damage.
3. Firing without water.
GROUNDING INSTRUCTIONS
This water heater must be grounded in accordance with the
National Electrical Code and/or local codes. These must be
followed in all cases.
This water heater must be connected to a grounded, permanent
wiring system; or an equipment grounding conductor must be
run with the circuit conductors and connected to the equipment
grounding terminal or lead on the water heater, see Figure 20.
HYDROGEN GAS FLAMMABLE
Explosion Hazard
Flammable hydrogen gases
may be present.
Keep all ignition sources away
from faucet when turning on
hot water.
Hydrogen gas can be produced in a hot water system served
by this water heater that has not been used for a long period of
time (generally two weeks or more). Hydrogen gas is extremely
ammable. To reduce the risk of injury under these conditions,
it is recommended that a hot water faucet served by this water
heater be opened for several minutes before using any electrical
appliance connected to the hot water system. If hydrogen is
present there will probably be an unusual sound such as air
escaping through the pipe as the water begins to ow. THERE
SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE
FAUCET AT THE TIME IT IS OPEN.
5
INTRODUCTION
Thank You for purchasing this water heater. Properly installed
and maintained, it should give you years of trouble free service.
ABBREVIATIONS USED
Abbreviations found in this Instruction Manual include :
• ANSI - American National Standards Institute
• ASME - American Society of Mechanical Engineers
• AHRI - Air-Conditioning, Heating and Refrigeration Institute
• NEC - National Electrical Code
• NFPA - National Fire Protection Association
• UL - Underwriters Laboratory
• CSA - Canadian Standards Association
QUALIFICATIONS
QUALIFIED INSTALLER OR SERVICE AGENCY
Installation and service of this water heater requires ability
equivalent to that of a Qualied Agency (as dened by ANSI
below) in the eld involved. Installation skills such as plumbing,
air supply, venting, gas supply and electrical supply are required
in addition to electrical testing skills when performing service.
ANSI Z223.1 2006 Sec. 3.3.83: “Qualied Agency” - “Any
individual, rm, corporation or company that either in person or
through a representative is engaged in and is responsible for (a)
the installation, testing or replacement of gas piping or (b) the
connection, installation, testing, repair or servicing of appliances
and equipment; that is experienced in such work; that is familiar
with all precautions required; and that has complied with all the
requirements of the authority having jurisdiction.”
If you are not qualied (as dened by ANSI above) and licensed
or certied as required by the authority having jurisdiction
to perform a given task do not attempt to perform any of the
procedures described in this manual. If you do not understand
the instructions given in this manual do not attempt to perform
any procedures outlined in this manual.
PREPARING FOR THE INSTALLATION
1. Read the “General Safety” section, page 4-5 of this manual
first and then the entire manual carefully. If you don’t follow
the safety rules, the water heater will not operate properly.
It could cause DEATH, SERIOUS BODILY INJURY AND/OR
PROPERTY DAMAGE.
This manual contains instructions for the installation, operation,
and maintenance of the gas-red water heater. It also contains
warnings throughout the manual that you must read and be
aware of. All warnings and all instructions are essential to the
proper operation of the water heater and your safety. Since we
cannot put everything on the rst few pages, READ THE ENTIRE
MANUAL BEFORE ATTEMPTING TO INSTALL OR OPERATE
THE WATER HEATER.
2. The installation must conform with these instructions and the
local code authority having jurisdiction. In the absence of local
codes, the installation must comply with the current editions
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or CAN/
CSA-B149.1 the Natural Gas and Propane Installation Code.
All documents are available from the Canadian Standards
Association, 8501 East Pleasant Valley Road, Cleveland, OH
44131. NFPA documents are also available from the National
Fire Protection Association, 1 Batterymarch Park, Quincy, MA
02269.
3. If after reading this manual you have any questions or do
not understand any portion of the instructions, call the local
gas utility or the manufacturer whose name appears on the
rating plate.
4. Carefully plan the place where you are going to put the
water heater. Correct combustion, vent action, and vent pipe
installation are very important in preventing death from possible
carbon monoxide poisoning and res.
Examine the lo c a t i o n to ensure the water he ater co m p l i e s with
the “Locating the New Water Heater” section in this manual.
5. For California installation this water heater must be braced,
anchored, or strapped to avoid falling or moving during
an earthquake. See instructions for correct installation
procedures. Instructions may be obtained from California
Office of the State Architect, 400 P Street, Sacramento,
CA 95814.
6. Massachusetts Code requires this water heater to be installed in
accordance with Massachusetts 248-CMR 2.00: State Plumbing
Code and 248-CMR 5.00.
6
FEATURES AND COMPONENTS
THE ELIMINATOR (SELF-CLEANING SYSTEM)
These units include The Eliminator (Self-Cleaning System) installed
in the front water inlet, See Figure 1. The Eliminator inlet tube can
only be used in the front water inlet connection. Do not install the
Eliminator inlet tube in either the top or back inlet water connection.
The Eliminator must be oriented correctly for proper function. There
is a marked range on pipe nipple portion of the Eliminator, that
must be aligned with top of inlet spud. A label above the jacket hole
has an arrow that will point to marked portion of pipe nipple if the
orientation is correct. If the arrow does not point within the marked
range on pipe nipple, adjust the pipe nipple to correct. A pipe union
is supplied with the Eliminator to reduce probability of misaligning
the Eliminator accidentally while tightening the connection to inlet
water supply line. Improper orientation of the Eliminator can cause
poor performance of heater and can signicantly reduce outlet water
temperatures during heavy draws.
Note: The Eliminator may have 1, 3 or 7 cross tubes.
FIGURE 1.
HIGH LIMIT SWITCH
The digital thermostat (Figure 2) contains the high limit (energy
cutout) switch. The high limit switch interrupts main burner gas ow
should the water temperature reach 203°F (95°C).
In the event of high limit switch operation, the water heater cannot be
restarted unless the water temperature is reduced to approximately
120°F (49°C). The high limit reset button on the front of the control
then needs to be depressed.
Continued manual resetting of high limit control, preceded by higher
than usual water temperature is evidence of high limit switch operation.
The following is a possible reason for high limit switch operation:
• A malfunction in the thermostatic controls would allow the gas
control valve to remain open causing water temperature to
exceed the thermostat setting. The water temperature would
continue to rise until high limit switch operation.
Contact your dealer or service agent if continued high limit switch
operation occurs.
bur ns dur ing each running cyc le. Th e ma i n bu r n e r an d pi l o t ga s e s
are cut off during the OFF cycle. Pilot gas ignition is proven by the
pilot sensor. Main burner ignition will not occur if the pilot sensor
does not rst sense pilot ignition.
IGNITION MODULE
FIGURE 3.
AUTOMATIC FLUE DAMPER
All units are equipped with an automatic ue damper that reduces
heat loss during the OFF cycles. The automatic ue damper
drive assembly is a eld replaceable part and may be obtained
by contacting A. O. Smith Corporation at 500 Tennessee Waltz
Parkway, Ashland City, TN 37015, 1-800-433-2545. In Canada,
contact A.O. Smith Enterprises LTD., P.O. Box, 310 - 768 Erie
Street, Stratford, Ontario, Canada N5A 6T3, 1-800-265-8520.
Each automatic ue damper drive assembly is equipped with a
“Service Switch”, as shown in Figure 4
The “Service Switch” has 2 positions: AUTOMATIC OPERATION
and HOLD OPEN DAMPER. For normal operation the switch
should be in the AUTOMATIC OPERATION position.
If there is a problem with the damper the “Service Switch” can be
placed in the HOLD OPEN DAMPER position. When the switch
is placed in the HOLD OPEN DAMPER position the damper disc
will rotate to the open position and the heater may be used until
vent assembly is repaired or replaced. DO NOT turn the damper
disc manually; damage will occur to the drive assembly if operated
manually. Refer to TESTING DAMPER OPERATION section of
this manual for additional information.
DIGITAL THERMOSTAT
FIGURE 2.
ELECTRONIC IGNITION CONTROL
Each heater is equipped with a Honeywell ignition module. The
solid state ignition control ignites the pilot burner gas by creating a
spark at the pilot assembly. See Figure 3. Pilot gas is ignited and
FLUE DAMPER
FIGURE 4.
UNCRATING
The heater is shipped with the ue damper already installed. The
wiring conduit runs from the thermostat to the damper drive cover.
Before turning unit on, check to make sure the wiring conduit is
securely plugged into damper drive.
7
INSTALLATION CONSIDERATIONS
ROUGH IN DIMENSIONS
MODELS BTR(C) 120 THROUGH 400
See Models Below
* BTR(C) - 120 Models are approved for 5” (13 cm) venting using a 6” (15 cm) to 5” (13 cm) reducer.
ModelType of Gas
All ModelsNatural4.5" W.C. (1.12 kPa)14" W.C. (3.48 kPa)3.5" W.C. (0.87 kPa)120/60<5
All ModelsPropane11.0" W.C. (2.74kPa)14" W.C. (3.48kPa)10.0" W.C. (2.49 kPa)120/60<5
9
Gas Manifold PressureVolts/HzAmperesMinimumMaximum
CAUTION
INSTALLATION CONSIDERATIONS
LOCATING THE WATER HEATER
Property Damage Hazard
All water heaters eventually leak.
•
Do not install without adequate drainage.
•
When installing the heater, consideration must be given to proper
location. Location selected should be as close to the stack or chimney
as practicable, with adequate air supply and as centralized with the
piping system as possible.
Fire or Explosion Hazard
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
Avoid all ignition sources if you smell gas.
Do not expose water heater controls to excessive gas
pressure.
Use only the gas shown on the water heater rating label.
Maintain required clearances to combustibles.
Keep ignition sources away from faucets after extended
periods of non-use.
Flammable items, pressurized containers or any other potential
re hazardous articles must never be placed on or adjacent to
the heater. Open containers or ammable material should not be
stored or used in the same room with the heater.
The heater must not be located in an area where it will be subject
to freezing.
Locate it near a oor drain. The heater should be located in an
area where leakage from heater or connections will not result
in damage to adjacent area or to lower oors of the structure.
When such locations cannot be avoided, a suitable metal drain
pan should be installed under heater. Such pans should be
fabricated with sides at least 2” deep, with length and width at
least 2” greater than diameter of heater and must be piped to
an adequate drain. Pan must not restrict combustion air ow.
CLEARANCES
These heaters are approved for installation on combustible ooring
in an alcove when the minimum clearance from combustion or
non-combustible construction are followed as indicated in Figure 6
and Table 5.
In all installations the minimum combustible clearances from draft
hood surface or vent piping shall be 6” (152mm). Vent piping passing
through a combustible wall or ceiling must be a continuous run
(no joints) and retain 6” (152mm) clearance unless an approved
reducing thimble is used.
A service clearance of 24” (610mm) should be maintained from
serviceable parts, such as relief valves, bafes, thermostats, cleanout
openings or drain valves.
Read instruction manual before
installing, using or servicing
water heater.
There is a risk in using fuel burning appliances such as gas water
heaters in rooms, garages or other areas where gasoline, other
ammable liquids or engine driven equipment or vehicles are stored,
operated or repaired. Flammable vapors are heavy and travel along
the oor and may be ignited by the heater’s igniter or main burner
ames causing re or explosion. Some local codes permit operation
of gas appliances in such areas if they are installed 18” or more
above the oor. This may reduce the risk if location in such an area
cannot be avoided.
Do not install this water heater directly on a carpeted oor. A re
hazard may result. Instead the water heater must be placed on a
metal or wood panel extending beyond the full width and depth by at
least 3 inches in any direction. If the heater is installed in a carpeted
alcove, the entire oor shall be covered by the panel. Also, see the
DRAINING requirements in MAINTENANCE Section.
The heater shall be located or protected so it is not subject to physical
damage by a moving vehicle.
* The BTRC version has a 2” (5.08cm) to sides and rear clearance.
** The BTRC version has a 4” (10.16cm) to sides and rear clearance.
C
(BACK)
D
(CEILING)
10
FIGURE 6.
NSF LEG KIT
The NSF Leg Kit (part number 9003425205) is needed only
for applications that must conform to NSF/ANSI Standard 5.
Installation of the NSF leg kit will increase the height of the unit
and all connection points by 3 inches. See Figure 7.
Follow these steps to install the Leg Kit:
1. Unit needs to be lifted in a way not to damage unit or laid on
it’s side to access the bottom of the legs.
2. Slide leg extension under leg and the bolt up through the
bottom hole located in the bottom of the leg.
3. Once in place, screw nut down and secure.
4. Front of leg should line up with front of leg extension as
shown to make sure weight of unit is distributed through the
leg extension.
FIGURE 7.
INSULATION BLANKET
Breathing Hazard - Carbon Monoxide Gas
Do not obstruct water heater air intake
with insulating blanket.
Gas and carbon monoxide detectors
are available.
Install water heater in accordance with
the instruction manual.
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual.
Insulation blankets are available to the general public for external
use on gas water heaters but are not necessary with these
products. The purpose of an insulation blanket is to reduce the
standby heat loss encountered with storage tank heaters. The
water heaters covered by this manual meet or exceed the Energy
Policy Act standards with respect to insulation and standby heat
loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this
heater, you should follow these instructions. See the Features
and Components section of this manual for identication of
components mentioned below. Failure to follow these instructions
can restrict the air ow required for proper combustion, potentially
resulting in re, asphyxiation, serious personal injury or death.
• DO NOT apply insulation to the top of the water heater, as
this will interfere with safe operation of the draft hood.
• DO NOT cover the gas control valve, thermostat or the
Temperature-Pressure Relief Valve.
• DO NOT allow insulation to come within 2” (5 cm) of the
burners, to prevent blockage of combustion air ow to the
burners.
• DO NOT allow insulation to come within 9 inches (23 cm)
of oor, (within 2 inches (5 cm) of bottom cover) to prevent
blockage of combustion air ow to the burners..
• DO NOT cover the instruction manual. Keep it on the side of
the water heater or nearby for future reference.
• DO obtain new warning and instruction labels from the
manufacturer for placement on the blanket directly over the
existing labels.
• DO inspect the insulation blanket frequently to make certain
it does not sag, thereby obstructing combustion air ow.
HARD WATER
Where hard water conditions exist, water softening or the
threshold type of water treatment is recommended. This will
protect the dishwashers, coffee urns, water heaters, water piping
and other equipment.
See the Maintenance Section in this manual for sediment and
lime scale removal procedures.
CIRCULATION PUMPS
A circulating pump is used when a system requires a circulating
loop or there is a storage tank used in conjunction with the water
heater. See Water Piping Diagrams in this manual for installation
location of circulating pumps.
See the Circulation Pump Wiring Diagrams in this manual for
electrical hookup information. Install in accordance with the
current edition of the National Electrical Code, NFPA 70 or the
Canadian Electrical Code, CSA C22.1.
All-bronze circulating pumps are recommended for used with
commercial water heaters.
Some circulating pumps are manufactured with sealed bearings
and do not require further lubrication. Some circulating pumps
11
must be periodically oiled. Refer to the pump manufacturer’s
CIRCULATING PUMPWIRING DIAGRAM
DISHWASHER LOOP WITH TOGGLE SWITCH
FIELD SUPPLIED TEMPERATURECONTROL INSTALLED IN THECIRCULATING LOOP RETURN LINE
DISHWASHERTOGGLESWITCH
CIRC
PUMP
MOTOR
L1 HOT
L2 NEUTRAL
120 VAC
POWER
NOTE: USE SEPARATE 120 VAC POWERSUPPLY FOR PUMP CIRCUIT. DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION.
instructions for lubrication requirements.
CIRCULATING PUMP WIRING DIAGRAM
STORAGE TANK OR BUILDING RECIRCULATION
FIELD SUPPLIED TEMPERATURE CONTROL
INSTALLED IN THE STORAGE TANK
NOTE: USE SEPARATE 120 VAC POWER
SUPPLY FOR PUMP CIRCUIT. DO NOT
SHARE POWER WITH WATER HEATER AS THIS
MAY CAUSE ELECTRICAL LINE NOISE AND
LEAD TO ERRATIC CONTROL SYSTEM
OPERATION.
L1 HOT
L2 NEUTRAL
120 VAC
POWER
OR CIRCULATING LOOP RETURN LINE
CIRC
PUMP
MOTOR
Breathing Hazard - Carbon Monoxide Gas
Under no circumstances should
the input exceed the rate shown
on the water heater’s rating label.
Overfiring could result in damage to
the water heater and sooting.
Gas and carbon monoxide detectors
are available.
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual.
FIGURE 8.
CIRCULATING PUMP WIRING DIAGRAM
DISHWASHER LOOP WITH TOGGLE SWITCH
DISHWASHER
TOGGLE
SWITCH
NOTE: USE SEPARATE 120 VAC POWER
SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE
POWER WITH WATER HEATER AS THIS MAY
CAUSE ELECTRICAL LINE NOISE AND LEAD
TO ERRATIC CONTROL SYSTEM OPERATION.
L1 HOT
120 VAC
POWER
L2 NEUTRAL
FIELD SUPPLIED TEMPERATURE
CONTROL INSTALLED IN THE
CIRCULATING LOOP RETURN LINE
FIGURE 9.
HIGH ALTITUDE INSTALLATIONS
Fire and Explosion Hazard
Under no circumstances should the
input exceed the rate shown on the
water heater’s rating label.
Overfiring could result in fire or
explosion.
Gas and carbon monoxide detectors are
available.
CIRC
PUMP
MOTOR
Installations above 2000 feet (610 meters) require
replacement of burner orifices in accordance with current
edition of the National Fuel Gas Code (ANSI Z223.1). For
Canadian installations consult Canadian Installations Code
CAN/CSA B149.1. Failure to replace orifices will result in
improper and inefficient operation of the water heater resulting
in the production of increased levels of carbon monoxide gas
in excess of safe limits which could result in serious personal
injury or death.
You sho u l d cont a ct your gas su pp l i er for any sp e c i f i c ch a ng e s
which may be required in your area.
As the elevation above sea level is increased, there is less
oxygen per cubic foot of air. Therefore, the heater input rate
should be reduced at high altitudes for satisfactory operation
w i t h th e r e d u c e d ox yg e n su p p l y. Fa i l u r e to ma k e th i s re d u c t i o n
would result in an over firing of the heater causing sooting,
poor combustion and/or unsatisfactory heater performance.
Ratings specied by manufacturers for most appliances apply
for elevations up to 2000 feet (610m). For elevations above
2000 feet (610), ratings must be reduced at the rate of 4%
for each 1000 feet (305m) above sea level. For example, if a
heater is rated at 78,000 Btuh (22.9 Kwh) at sea level, to rate
the heater at 4000 feet (1219m), you subtract 4 (once for each
thousand feet) x.04 (4% input reduction) x 78,000 (original
rating) from the original rating.
Therefore, to calculate the input rating at 4,000 feet (1219m):
4 x .04 x 78,000 = 12,480 Btuh (3.7 Kwh), 78,000 (22.9 Kwh) 12,480 (3.7 Kwh) = 65,520 Btuh (19. 2 Kwh). At 60 0 0 fe e t (1829 m)
the correct input rating should be 59,280 Btuh (17.4 Kwh).
12
INSTALLATION REQUIREMENTS
GAS SUPPLY SYSTEMS
Low pressure building gas supply systems are defined as those
systems that cannot under any circumstances exceed 14”
W.C. (1/2 PSI Gauge). These systems do not require pressure
regulation. Measurements should be taken to insure that gas
pressures are stable and fall within the requirements stated on
the water heater rating plate. Readings should be taken with
all gas burning equipment off (static pressure) and with all gas
burning equipment running at maximum rate (dynamic pressure).
The gas supply pressure must be stable within 1.5” W.C.
from static to dynamic pressure to provide good performance.
Pressure drops that exceed 1.5” W.C. may cause rough starting,
noisy combustion or nuisance outages. Increases or spikes
in static pressure during off cycles may cause failure to ignite
or in severe cases damage to appliance gas valves. If your
low pressure system does NOT meet these requirements, the
installer is responsible for the corrections.
High Pressure building supply systems use pressures that
exceed 14” W.C. (1/2 PSI Gauge). These systems must use eld
supplied regulators to lower the gas pressure to less than 14”
W.C. (1/2 PSI Gauge). Water heaters require gas regulators that
are properly sized for the water heater input and deliver the rating
plate specied pressures. Gas supply systems where pressure
exceeds 5 PSI often require multiple regulators to achieve desired
pressures. Systems in excess of 5 PSI building pressure should
be designed by gas delivery professionals for best performance.
Water heaters connected to gas supply systems that exceed 14”
W.C. (1/2 PSI Gauge) at any time must be equipped with a gas
supply regulator.
All models require a minimum gas supply pressure of 4.5" W.C. for
natural gas and 11.0" W.C. for propane gas. The minimum supply
pressure is measured while gas is owing (dynamic pressure).
The supply pressure should never fall below 4.5" W.C. for natural
gas and 11.0" W.C. for propane gas. The supply pressure should
be measured with all gas red appliances connected to the
common main ring at full capacity. If the supply pressure drops
more than 1.5” W.C. as gas begins to ow to the water heater
then the supply gas system including the gas line and/or the
gas regulator may be restricted or undersized. See Supply Gas
Regulator section and Gas Piping section of this manual. The gas
valve on all models has a maximum gas supply pressure limit of
14” W.C. The maximum supply pressure is measured while gas is
not owing (static pressure).
SUPPLY GAS REGULATOR
The maximum allowable gas supply pressure for this water heater
is 14 inches W.C. (3.48 kPa). Install a positive lock-up gas pressure
regulator in the gas supply line if inlet gas pressure can exceed 14
inches W.C. (3.48 kPa) at any time. Regulators must be sized/used
according to manufacturer’s specications.
If a positive lock-up regulator is required follow these instructions:
1. Positive lock-up gas pressure regulators must be rated at or above
the input Btu/hr rating of the water heater they supply.
2. Positive lock-up gas pressure regulator(s) should be installed no closer
than 3 equivalent feet (1 meter) and no farther than 8 equivalent
feet (2.4 meters) from water heater’s inlet gas connection.
3. After installing the positive lock-up gas pressure regulator(s) an
initial nominal supply pressure setting of 7.0” W.C. while the water
heater is operating is recommended and will generally provide good
water heater operation. Some addition adjustment maybe required
later to maintain a steady gas supply pressure.
4. When installing multiple water heaters in the same gas supply
system it is recommended that individual positive lock-up gas
pressure regulators be installed at each unit.
POWER SUPPLY
The water heaters covered in this manual require a 120 VAC,
1Ø (single phase), 60Hz, 15 amp power supply and must also
be electrically grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical Code, ANSI/
NFPA 70 or the Canadian Electrical Code, CSA C22.1.
WATER TEMPERATURE CONTROL AND MIXING VALVES
Water temperature over 125°F (52°C)
can cause severe burns instantly
resulting in severe injury or death.
Children, the elderly and the
physically or mentally disabled are at
highest risk for scald injury.
Feel water before bathing or showering.
Temperature limiting devices such as
mixing valves must be installed
when required by codes and to
ensure safe temperatures at fixtures.
Water heated to a temperature which will satisfy clothes washing, dish
washing, and other sanitizing needs can scald and cause permanent
injury upon contact. Short repeated heating cycles caused by small
hot water uses can cause temperatures at the point of use to exceed
the water heater’s temperature setting by up to 20°F (11°C).
Some people are more likely to be permanently injured by hot water
than others. These include the elderly, children, the inrm and the
physically/mentally disabled. Table 6 shows approximate time-to-burn
relationship for normal adult skin. If anyone using hot water provided
by the water heater being installed ts into one of these groups or if
there is a local code or state law requiring a certain water temperature
at the point of use, then special precautions must be taken.
In addition to using the lowest possible temperature setting that
satises the demand of the application a Mixing Valve should be
installed at the water heater (see Figure 10) or at the hot water taps
to further reduce system water temperature.
Mixing valves are available at plumbing supply stores. Consult a
Qualied Installer or Service Agency. Follow mixing valve manufacturer’s
instructions for installation of the valves.
(U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15,1978)
Time for 1st Degree Burn
(Less Severe Burns)
(normal shower temp.)
Time for Permanent Burns
2nd & 3rd Degree
(Most Severe Burns)
13
HOT WATER
OUTLET
TEMPERED WATER
OUTLET
12” TO 15”
(30-38 cm)
A properly sized thermal expansion tank must be installed on
all closed systems to control the harmful effects of thermal
expansion. Contact a local plumbing service technician to have a
thermal expansion tank installed.
See Water Line Connections on page 21 and the Water Piping
Diagrams beginning on page 40.
TEMPERATURE-PRESSURE RELIEF VALVE
COLD
WATER
INLET
CHECK
VALV E
TO TANK
INLET
CHECK
VALV E
MIXING
VALV E
FIGURE 10.
DISHWASHING MACHINES
All dishwashing machines meeting the National Sanitation
Foundation requirements are designed to operate with water ow
pressures between 15 and 25 pounds per square inch (103 kPa
and 173 kPa). Flow pressures above 25 pounds per square inch
(173 kPa), or below 15 pounds per square inch (103 kPa), will
result in improperly sanitized dishes. Where pressures are high,
a water pressure reducing or ow regulating control valve should
be used in the 180°F (82°C) line to the dishwashing machine and
should be adjusted to deliver water pressure between these limits.
The National Sanitation Foundation also recommends circulation
of 180°F (82°C) water. The circulation ow rate should be just
enough to provide 180°F (82°C) water at the point of take-off to
the dishwashing machine.
Adjust ow by throttling a full port ball valve installed in the
circulating line on the outlet side of the pump. Never throttle ow
on the suction side of a pump. See Water Piping Diagrams in
this manual.
NOTE: These water heaters meet the NSF Standard 5 for
sanitary installations when used with the leg kit part number
9003425205.
CLOSED WATER SYSTEMS
Water supply systems may, because of code requirements
or such conditions as high line pressure, among others, have
installed devices such as pressure reducing valves, check
valves, and back ow preventers. Devices such as these cause
the water system to be a closed system.
THERMAL EXPANSION
As water is heated, it expands (thermal expansion). In a closed
system the volume of water will grow when it is heated. As the
volume of water grows there will be a corresponding increase
in water pressure due to thermal expansion. Thermal expansion
can cause premature tank failure (leakage). This type of failure
is not covered under the limited warranty. Thermal expansion
can also cause intermittent Temperature-Pressure Relief Valve
operation: water discharged from the valve due to excessive
pressure build up. This condition is not covered under the limited
warranty. The Temperature-Pressure Relief Valve is not intended
for the constant relief of thermal expansion.
Explosion Hazard
Temperature-Pressure Relief Valve
must comply with ANSI Z21.22CSA 4.4 and ASME code.
Properly sized temperaturepressure relief valve must be
installed in opening provided.
Can result in overheating and
excessive tank pressure.
Can cause serious injury or death.
This water heater is provided with a properly rated/sized and certied
combination Temperature-Pressure Relief Valve (T&P valve) by
the manufacturer. The valve is certied by a nationally recognized
testing laboratory that maintains periodic inspection of production
of listed equipment of materials as meeting the requirements for
Pressure Relief Valves for Hot Water Supply Systems, ANSI Z21.22
• CSA 4.4, and the code requirements of ASME.
If replaced, the new T&P valve must meet the requirements
of local codes, but not less than a combination TemperaturePressure Relief Valve rated/sized and certied as indicated in
the above paragraph. The new valve must be marked with a
maximum set pressure not to exceed the marked hydrostatic
working pressure of the water heater (150 psi = 1,035 kPa) and
a discharge capacity not less than the water heater Btu/hr or kW
input rate as shown on the water heater’s model rating label.
NOTE: In addition to the factory installed Temperature-Pressure
Relief Valve on the water heater, each remote storage tank that
may be installed and piped to a water heating appliance must also
have its own properly sized, rated and approved TemperaturePressure Relief Valve installed. Call the toll free technical
support phone number listed on the back cover of this manual
for technical assistance in sizing a Temperature-Pressure Relief
Valve for remote storage tanks.
For safe operation of the water heater, the Temperature-Pressure
Relief Valve must not be removed from its designated opening
nor plugged. The Temperature-Pressure Relief Valve must be
installed directly into the tting of the water heater designed for
the pressure relief valve . Install discharge piping so that any
discharge will exit the pipe within 6 inches (15.2 cm) above an
adequate oor drain, or external to the building. In cold climates
it is recommended that it be terminated at an adequate drain
inside the building. Be certain that no contact is made with any
live electrical part. The discharge opening must not be blocked
or reduced in size under any circumstances. Excessive length,
over 30 feet (9.14 m), or use of more than four elbows can cause
restriction and reduce the discharge capacity of the valve.
14
No valve or other obstruction is to be placed between the
CAUTION
Temperature-Pressure Relief Valve and the tank. Do not connect
discharge piping directly to the drain unless a 6” (15.2 cm)
air gap is provided. To prevent bodily injury, hazard to life, or
property damage, the relief valve must be allowed to discharge
water in adequate quantities should circumstances demand. If
the discharge pipe is not connected to a drain or other suitable
means, the water ow may cause property damage.
Water Damage Hazard
CONTAMINATED AIR
Breathing Hazard - Carbon Monoxide Gas
Install water heater in accordance with
the Instruction Manual and NFPA 54 or
CAN/CSA-B149.1.
To avoid injury, combustion and ventilation
air must be taken from outdoors.
Do not place chemical vapor emitting
products near water heater.
Temperature-Pressure Relief Valve discharge
•
pipe must terminate at adequate drain.
T&P Valve Discharge Pipe Requirements:
• Shall not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions.
• Shall not be plugged or blocked.
• Shall not be exposed to freezing temperatures.
• Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both
the Temperature-Pressure Relief Valve and the discharge
pipe.
• Must terminate a maximum of six inches above a oor
drain or external to the building. In cold climates, it is
recommended that the discharge pipe be terminated at an
adequate drain inside the building.
• Shall not have any valve or other obstruction between the
pressure relief valve and the drain.
Burn hazard.
Hot water discharge.
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual.
Corrosion of the ue ways and vent system may occur if air for
combustion contains certain chemical vapors. Such corrosion
may result in failure and risk of asphyxiation.
Combustion air that is contaminated can greatly diminish the life
span of the water heater and water heater components such as
hot surface igniters and burners. Propellants of aerosol sprays,
beauty shop supplies, water softener chemicals and chemicals
used in dry cleaning processes that are present in the combustion,
ventilation or ambient air can cause such damage.
Do not store products of this sort near the water heater. Air which
is brought in contact with the water heater should not contain any
of these chemicals. If necessary, uncontaminated air should be
obtained from remote or outdoor sources. The limited warranty
is voided when failure of water heater is due to a corrosive
atmosphere. (See limited warranty for complete terms and
conditions).
AIR REQUIREMENTS
Breathing Hazard - Carbon Monoxide Gas
Keep clear of TemperaturePressure Relief Valve
discharge outlet.
The Temperature-Pressure Relief Valve must be manually operated
at least twice a year. Caution should be taken to ensure that (1) no
one is in front of or around the outlet of the Temperature-Pressure
Relief Valve discharge line, and (2) the water manually discharged
will not cause any bodily injury or property damage because
the water may be extremely hot. If after manually operating the
valve, it fails to completely reset and continues to release water,
immediately close the cold water inlet to the water heater, follow the
draining instructions in this manual, and replace the TemperaturePressure Relief Valve with a properly rated/sized new one.
NOTE: The purpose of a Temperature-Pressure Relief Valve is to
prevent excessive temperatures and pressures in the storage tank.
The T&P valve is not intended for the constant relief of thermal
expansion. A properly sized thermal expansion tank must be
installed on all closed systems to control thermal expansion, see
Closed Water Systems and Thermal Expansion on page 14.
If you do not understand these instructions or have any questions
regarding the Temperature-Pressure Relief Valve call the toll
free number listed on the back cover of this manual for technical
assistance.
Install water heater in accordance with
the Instruction Manual and NFPA 54 or
CAN/CSA-B149.1.
To avoid injury, combustion and ventilation
air must be taken from outdoors.
Do not place chemical vapor emitting
products near water heater.
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual.
For safe operation an adequate supply of fresh uncontaminated
air for combustion and ventilation must be provided.
An insufcient supply of air can cause recirculation of combustion
products resulting in contamination that may be hazardous to
life. Such a condition often will result in a yellow, luminous burner
ame, causing sooting of the combustion chamber, burners and
ue tubes and creates a risk of asphyxiation.
Do not install the water heater in a conned space unless an
adequate supply of air for combustion and ventilation is brought
in to that space using the methods described in the Conned
Space section that follows.
Never obstruct the ow of ventilation air. If you have any doubts
or questions at all, call your gas supplier. Failure to provide the
proper amount of combustion air can result in a re or explosion
and cause property damage, serious bodily injury or death.
15
UNCONFINED SPACE
An Unconned Space is one whose volume IS NOT LESS THAN
50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the
total input rating of all appliances installed in the space. Rooms
communicating directly with the space, in which the appliances
are installed, through openings not furnished with doors, are
considered a part of the unconned space.
Makeup air requirements for the operation of exhaust fans,
kitchen ventilation systems, clothes dryers and replaces shall
also be considered in determining the adequacy of a space to
provide combustion, ventilation and dilution air.
UNUSUALLY TIGHT CONSTRUCTION
In unconned spaces in buildings, inltration may be adequate
to provide air for combustion, ventilation and dilution of ue
gases. However, in buildings of unusually tight construction (for
example, weather stripping, heavily insulated, caulked, vapor
barrier, etc.) additional air must be provided using the methods
described in the Conned Space section that follows.
CONFINED SPACE
A Conned Space is one whose volume is less than 50 cubic
feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input
rating of all appliances installed in the space.
Openings must be installed to provide fresh air for combustion,
ventilation and dilution in conned spaces. The required size for
the openings is dependent on the method used to provide fresh
air to the conned space and the total Btu/hr input rating of all
appliances installed in the space.
DIRECT VENT APPLIANCES
Appliances installed in a Direct Vent conguration that derive all
air for combustion from the outdoor atmosphere through sealed
intake air piping are not factored in the total appliance input Btu/
hr calculations used to determine the size of openings providing
fresh air into conned spaces.
EXHAUST FANS
Where exhaust fans are installed, additional air shall be provided
to replace the exhausted air. When an exhaust fan is installed
in the same space with a water heater, sufcient openings to
provide fresh air must be provided that accommodate the
requirements for all appliances in the room and the exhaust fan.
Undersized openings will cause air to be drawn into the room
through the water heater’s vent system causing poor combustion.
Sooting, serious damage to the water heater and the risk of re
or explosion may result. It can also create a risk of asphyxiation.
LOUVERS AND GRILLES
The free areas of the fresh air openings in the instructions that
follow do not take in to account the presence of louvers, grilles or
screens in the openings.
The required size of openings for combustion, ventilation and
dilution air shall be based on the “net free area” of each opening.
Where the free area through a design of louver or grille or screen
is known, it shall be used in calculating the size of opening
required to provide the free area specied. Where the louver and
grille design and free area are not known, it shall be assumed
that wood louvers will have 25% free area and metal louvers and
grilles will have 75% free area. Non motorized louvers and grilles
shall be xed in the open position.
VENTING INSTALLATION
VENTING
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST
BE FOLLOWED TO AVOID CHOKED COMBUSTION OR
RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE
SOOTING OR RISKS OF FIRE AND ASPHYXIATION.
Heater must be protected from freezing downdrafts.
Remove all soot or other obstructions from the chimney that will retard
a free draft.
Type B venting is recommended with these heaters. For typical venting
application see TECHNICAL DATA VENTING on pages 19 and 20.
This water heater must be vented in compliance with all local codes,
the current revision of the National Fuel Gas Code (ANSI-Z223.1) and
with the Category I Venting Tables.
If any part of the vent system are exposed to ambient temperatures
below 40°F it must be insulated to prevent condensation.
• Do not connect the heater to a common vent or chimney with solid
fuel burning equipment. This practice is prohibited by many local
building codes as is the practice of venting gas red equipment to
the duct work of ventilation systems.
• Where a separate vent connection is not available and the vent pipe
from the heater must be connected to a common vent with an oil
burning furnace, the vent pipe should enter the smaller common
vent or chimney at a point above the large vent pipe.
Each adapter ts on top of the installed ue damper. Use only vent
reducers supplied with the unit. The venting must comply with the
current editions of the NATIONAL FUEL GAS CODE, ANSI Z223.1/
NFPA 54 or NATURAL GAS AND PROPANE INSTALLATION CODE
CAN/CSA-B149.1
FIGURE 11.
VENT REDUCER
Model BTR 120 is shipped with a 6" to 5" ue outlet adapter. Models
BTR 250, 251 and 275 are shipped with a 8" to 6" ue outlet adapter.
FIGURE 12.
16
MULTIPLE HEATER MANIFOLD
Figure 13 and tables on pages 19 and 20 should be used for
horizontally manifolding two or more heaters.
FIGURE 13.
FRESH AIR OPENINGS FOR CONFINED SPACES
The following instructions shall be used to calculate the size,
number and placement of openings providing fresh air for
combustion, ventilation and dilution in conned spaces. The
illustrations shown in this section of the manual are a reference
for the openings that provide fresh air into conned spaces
only. DO NOT refer to these illustrations for the purpose of vent
installation. See Venting Installation on page 16 for complete
venting installation instructions.
OUTDOOR AIR THROUGH ONE OPENING
FIGURE 15.
Alternatively a single permanent opening, commencing within 12
inches (300 mm) of the top of the enclosure, shall be provided.
See Figure 14. The water heater shall have clearances of at
least 1 inch (25 mm) from the sides and back and 6 inches (l50
mm) from the front of the water heater. The opening shall directly
communicate with the outdoors or shall communicate through a
vertical or horizontal duct to the outdoors or spaces that freely
communicate with the outdoors and shall have a minimum free
area of the following:
1. 1 square inch per 3000 Btu/hr (733 mm2 per kW) of the total input
rating of all appliances located in the enclosure, and
2. Not less than the sum of the areas of all vent connectors in the space.
OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS
OUTDOOR AIR THROUGH TWO OPENINGS
FIGURE 14.
The conned space shall be provided with two permanent
openings, one commencing within 12 inches (300 mm) of the top
and one commencing within 12 inches (300 mm) of the bottom of
the enclosure. The openings shall communicate directly with the
outdoors. See Figure 14.
Each opening shall have a minimum free area of 1 square inch
per 4,000 Btu/hr (550 mm
of all appliances installed in the enclosure. Each opening shall
not be less than 100 square inches (645 cm
2
per kW) of the aggregate input rating
2
).
FIGURE 16.
The conned space shall be provided with two permanent
horizontal ducts, one commencing within 12 inches (300 mm) of
the top and one commencing within 12 inches (300 mm) of the
bottom of the enclosure. The horizontal ducts shall communicate
directly with the outdoors. See Figure 16.
Each duct opening shall have a minimum free area of 1 square
inch per 2,000 Btu/hr (1100 mm
2
per kW) of the aggregate input
rating of all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional
area as the free area of the openings to which they connect.
The minimum dimension of rectangular air ducts shall be not less
than 3 inches.
17
OUTDOOR AIR THROUGH TWO VERTICAL DUCTS
The illustrations shown in this section of the manual are a
reference for the openings that provide fresh air into conned
spaces only.
DO NOT refer to these illustrations for the purpose of vent
installation. See Venting Installation on page 14 for complete
venting installation instructions.
When ducts are used, they shall be of the same cross sectional
area as the free area of the openings to which they connect.
The minimum dimension of rectangular air ducts shall be not less
than 3 inches.
AIR FROM OTHER INDOOR SPACES
FIGURE 18.
FIGURE 17.
The conned space shall be provided with two permanent vertical
ducts, one commencing within 12 inches (300 mm) of the top and
one commencing within 12 inches (300 mm) of the bottom of the
enclosure. The vertical ducts shall communicate directly with the
outdoors. See Figure 17.
Each duct opening shall have a minimum free area of 1 square
inch per 4,000 Btu/hr (550 mm
2
per kW) of the aggregate input
rating of all appliances installed in the enclosure.
The conned space shall be provided with two permanent
openings, one commencing within 12 inches (300 mm) of the top
and one commencing within 12 inches (300 mm) of the bottom of
the enclosure. See Figure 18.
Each opening shall communicate directly with an additional
room(s) of sufcient volume so that the combined volume of all
spaces meets the criteria for an Unconned Space.
Each opening shall have a minimum free area of 1 square inch
per 1,000 Btu/hr (2200 mm2 per kW) of the aggregate input rating
of all appliances installed in the enclosure. Each opening shall
not be less than 100 square inches (645 cm
2
).
18
TABLE 7. TECHNICAL DATA VENTING
TYPE B GAS VENT
Multiple Gas Fired Tank-Type Heaters
When venting multiple tank type heaters using Type B vent
pipe, follow the installation diagram (gure 13) and tables
below which give sizing and data based upon NFPA 54/ANSI
Z223. 1992.
MODEL BTR(C)-120
Input: 120,000 Btuh Total Vent Height (Feet)
Draft Hood: 5”681015203050100
Number of
Heaters
2
3
448012121210101088
MODEL BTR(C)-154
Input: 154,000 Btuh Total Vent Height (Feet)
Draft Hood: 6”681015203050100
When mechanical venting of these heaters is desired, the
following kits are available.
Models 120 through the 200/A
A. O. Smith part number 9005381205
Models 250/A through the 400/A
A. O. Smith part number 9003434205
Where an approved power venter is to be installed to operate
in conjunction with the water heater thermostat, the following
codes must be adhered to. Field wiring should conform to
the current edition of the National Electrical Code NFPA 70.
For Canadian installations the electrical connections and
grounding shall be done in accordance with the current edition
of the Canadian Electrical Code CSA C22.1 and/or local codes.
WATER HEATER INSTALLATION
VENT INSTALLATION
Seal all joints between the power venter and the vent
termination. This is to prevent leakage of exhaust products
into the room(s) due to positive pressure of blower.
The “Sequence of Operation” description will be the same with
mechanical venting except;
When the water heater thermostat calls for heat:
Thermostat contacts “Close” and the power venter blower
(120 VAC) is energized. Sufficient draft must be established
for the “Draft Prover Switch (N.O.)” to “Close”. When the
draft prover switch “Closes” the relay coil of the flue damper
is energized.
MULTIPLE UNIT INSTALLATION
For multiple unit installations, contact A. O. Smith, Technical
Support Center at 1-800-527-1953.
WATER LINE CONNECTIONS
The water piping installation must conform to these instructions
and to all local code authority having jurisdiction. Good practice
requires that all heavy piping be supported.
Read and observe all requirements in the following sections
before installation of the water piping begins:
1. Water Temperature Control and Mixing Valves on page 13.
2. Dishwashing Machines on page 14.
3. Temperature-Pressure Relief Valve on page 14-15.
4. Closed Systems and Thermal Expansion on page 14.
5. For multiple water heater installations see Water Piping
Diagrams beginning on page 40.
WATER (POTABLE) HEATING AND SPACE HEATING
1. All piping components connected to this unit for space
heating applications shall be suitable for use with potable
water.
2. Toxic chemicals, such as those used for boiler treatment,
shall NEVER be introduced into this system.
3. This unit may NEVER be connected to any existing heating
system or component(s) previously used with a non-potable
water heating appliance.
4. When the system requires water for space heating at
temperatures higher than required for domestic water
purposes, a tempering valve must be installed. Please
refer to installation diagrams beginning on page 40 of this
manual for suggested piping arrangements.
5. These water heaters cannot be used in space heating
applications only
THERMOMETERS (NOT SUPPLIED)
Thermometers should be obtained and eld installed as shown
in the installation diagrams.
Thermometers are installed in the system as a means of
detecting the temperature of the outlet water supply.
WATER PIPING DIAGRAMS
This manual provides detailed water piping diagrams for typical
methods of application for the water heaters, see Water Piping
Diagrams beginning on page 40.
The water heater may be installed by itself, or with a separate
storage tank. When used with a separate storage tank, the
circulation may be either by gravity or by means of circulating
pump. Adjust ow by throttling a full port ball valve installed in the
circulating line on the outlet side of the pump. Never throttle ow
on the suction side of a pump. See the Water Piping Diagrams
beginning on page 40.
NOTE: In addition to the factory installed Temperature-Pressure
Relief Valve (T&P valve) on the water heater, each remote
storage tank that may be installed and piped to a water heating
appliance must also have its own properly sized, rated and
approved Temperature-Pressure Relief Valve installed.
Call the toll free technical support phone number listed on the
back cover of this manual for further assistance in sizing a T&P
valve for remote storage tanks.
T&P VALVE DISCHARGE PIPE
Explosion Hazard
Temperature-Pressure Relief Valve
must comply with ANSI Z21.22CSA 4.4 and ASME code.
Properly sized temperaturepressure relief valve must be
installed in opening provided.
Can result in overheating and
excessive tank pressure.
Can cause serious injury or death.
21
This water heater is provided with a properly rated/sized and
certied combination temperature - pressure (T&P) relief valve by
the manufacturer. See Temperature-Pressure Relief Valve on pages
14-15 for information on replacement and other requirements.
CAUTION
Water Damage Hazard
Temperature-Pressure Relief Valve discharge
•
pipe must terminate at adequate drain.
Install a discharge pipe between the T&P valve discharge
opening and a suitable oor drain. Do not connect discharge
piping directly to the drain unless a 6” (15.2 cm) air gap is
provided. To prevent bodily injury, hazard to life, or property
damage, the relief valve must be allowed to discharge water
in adequate quantities should circumstances demand. If the
discharge pipe is not connected to a drain or other suitable
means, the water ow may cause property damage.
T&P VALVE DISCHARGE PIPE REQUIREMENTS:
• Shall not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions.
• Shall not be plugged or blocked.
• Shall not be exposed to freezing temperatures.
• Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both
Temperature-Pressure Relief Valve and the discharge pipe.
• Must terminate a maximum of six inches above a oor
drain or external to the building. In cold climates, it is
recommended that the discharge pipe be terminated at an
adequate drain inside the building.
• Shall not have any valve or other obstruction between the
relief valve and the drain.
INSTALLATION DIAGRAMS - TOP INLET/OUTLET USAGE
Use of the top inlet water connection requires an inlet dip tube
(refer to gure 19). The tube is supplied in the heater. Follow
caution labels if applying heat to this tting. Do not allow pipe
dope to contact the plastic tube during installation.
TUBE INLET INSTALLATION
FIGURE 19.
22
HEATER WIRING
All electrical work must be installed in accordance with the current edition of the National Electrical Code ANSI/NFPA No. 70 or Canadian Electrical
Code CSA C22.1 and must conform to all local code authority having jurisdiction. AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF
ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION.
0
If any of the original wire as supplied with the water heater must be replaced, use only type 105°C thermoplastic or equivalent 250
used for the ame sensor and igniter leads.
The controls of this water heater are polarity sensitive. Be certain to properly wire the hot and neutral connections.
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED MUST BE REPLACED, USE ONLY TYPE 105O C
THERMOPLASTIC OR EQUIVALENT. FLAME SENSOR IGNITION CABLE MUST BE 250O C TYPE F.
197287-000 REV 02
FIGURE 20.
23
GAS PIPING
Contact your local gas service company to ensure that adequate
gas service is available and to review applicable installation codes
for your area.
Size the main gas line in accordance with Table 8. The gures shown
are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is
considered normal for low pressure systems. Note: Fittings such as
elbows, tees and line regulators will add to the pipe pressure drop.
Also refer to the latest version of the National Fuel Gas Code.
Schedule 40 Steel or Wrought Iron Pipe is the preferred material
for the gas line of this water heater. It is imperative to follow the
sizing recommendations in the latest version of the National Fuel
Gas Code if Corrugated Stainless Steel Tubing (CSST) is used as
the gas line for this water heater.
The heater is not intended for operation at higher than 14.0" W.C.natural gas, (1/2 pound per square inch gage) supply gas pressure.
Exposure to higher supply pressure may cause damage to the
gas valve which could result in re or explosion. If overpressure
has occurred such as through improper testing of gas lines or
emergency malfunction of the supply system, the gas valve must be
checked for safe operation. Make sure that the outside vents on the
supply regulators and the safety vent valves are protected against
blockage. These are parts of the gas supply system, not the heater.
Vent blockage may occur during ice storms.
Natural Gas 0.60 Specic Gravity, 0.50" W.C. Pressure Drop
It is important to guard against gas valve fouling from contaminants in
gas ways. Such fouling may cause improper operation, re or explosion.
If copper supply lines are used they must be internally tinned and
certied for gas service. Before attaching the gas line, be sure that
all gas pipe is clean on the inside.
To trap any dirt or foreign material in the gas supply line, a sediment
trap must be incorporated in the piping (see Figure 21). The sediment
trap must be readily accessible and not subject to freezing conditions.
Install in accordance with recommendations of serving gas suppliers.
Refer to the latest version of the National Fuel Gas Code.
To prevent damage, care must be taken not to apply too much torque
when attaching gas supply pipe to gas valve inlet.
Apply joint compounds (pipe dope) sparingly and only to the male
threads of pipe joints. Do not apply compounds to the rst two threads.
Use compounds resistant to the action of liqueed petroleum gases.
Schedule 40 Steel or Wrought Iron Pipe
1/2"3/4"1"1 1/4"1 1/2"
GAS METER SIZE – NATURAL GASES ONLY
Be sure the gas meter has sufcient capacity to supply the full rated
gas input of the water heater as well as the requirements of all other
gas red equipment supplied by the meter. If gas meter is too small, ask
the gas company to install a larger meter having adequate capacity.
GAS PIPING AND SEDIMENT TRAP INSTALLATION
FIGURE 21.
GAS LINE LEAK TESTING
Fire and Explosion Hazard
Use joint compound or Teflon tape
compatible with propane gas.
Leak test before placing the water
heater in operation.
Disconnect gas piping and main gas
shutoff valve before leak testing.
Install sediment trap in accordance
with NFPA 54.
Any time work is done on the gas supply system perform a leak test
to avoid the possibility of re or explosion.
1. For test pressures exceeding 1/2 psi (3.45 kPa) disconnect the
water heater and its Main Gas Shutoff Valve from the gas supply
piping system during testing, see Figure 21. The gas supply line
must be capped when disconnected from the water heater.
2. For test pressures of 1/2 psi (3.45 kpa) or less, the water heater
need not be disconnected, but must be isolated from the supply
gas line by closing the Main Gas Shutoff Valve during testing.
3. Coat all supply gas line joints and connections upstream of the
water heater with a non-corrosive soap and water solution to
test for leaks. Bubbles indicate a gas leak. Do not use matches,
candles, ame or other sources of ignition for this purpose.
4. Repair any leaks before placing the water heater in operation.
PURGING
Gas line purging is required with new piping or systems in which air
has entered.
Purging should be performed per the current edition of NFPA 54 the
National Fuel Gas Code.
24
OPERATION
Fire or Explosion Hazard
Gas line purging is required with new piping or systems in
which air has entered.
To avoid risk of fire or explosion purge discharge must not
enter into confined areas or spaces where ignition can occur.
The area must be well ventilated and all sources of ignition
must be deactivated or removed.
Light the water heater in accordance with the Lighting and
Operation Instruction label on the water heater and in this manual
on pages 27 and 28.
The water heaters covered by this manual are equipped with
an electronic control system that automatically sequences
the Igniter, the 24 VAC Gas Valve, the Burner ignition, and
flame sensing.
Before attempting start up, thoroughly study and know the exact
Sequence Of Operation. See written Sequence Of Operation on
page 25 and Sequence Of Operation Flow Chart on page 26.
Be cer tain that the water heater is full of water, that air is purged
from the gas and water lines and that there are no leaks in the
gas and water lines. Ensure all inlet water valves are open.
Read instruction manual before
installing, using or servicing
water heater.
PRIOR TO START UP
Installation and start up of this water heater requires abilities and
skills equivalent to that of a licensed tradesman in the eld involved,
see Qualications on page 6.
Do not place the water heater in operation if any part has been under
water. Immediately call a qualied service technician to inspect the
water heater and to replace any part of the control system and any
gas control which has been under water.
SEQUENCE OF OPERATION
The following information will describe the Sequence of Operation
for this water heater.
1. Switch power on to unit.
2. Thermostat calls for heat.
3. Ignition Control performs diagnostic self check on system
components.
4. The Ignition Control begins the trial for ignition.
5. The Ignition Control turns on the Spark Igniter and opens the Pilot
Gas Valve.
6. The Ignition Control monitors the Flame Sensor during the ignition
trial period.
7. If the Ignition Control does not sense the pilot ame during the
ignition trial period, the Ignition Control shuts the Pilot Gas
Valve and turns off the Spark Igniter. Depending on the water
heater model, the Ignition Control will either retry the ignition trial
at step 4 or lockout the ignition sequence. If the ignition sequence
FILLING THE WATER HEATER
Follow these steps to ll the water heater prior to start up.
1. Close the heater drain valve.
2. Open a nearby hot water faucet to permit air in system to escape.
3. Fully open the cold water inlet valve allowing the piping and
water heater to ll with water.
4. Close hot water faucet opened in Step 2 as water starts to ow.
Read SEQUENCE OF OPER ATION section of this manual prior
to lighting and operating this water heater.
With above conditions satisfied, start the unit in accordance with
the instructions on the operating label attached to the heater.
For your convenience a copy of the instructions are shown on
pages 27 and 28.
is locked out, the power to the unit must be cycled to restart the
Ignition Control.
8. If the pilot ame is proved during the ignition trial period, the
Ignition Control turns off the Spark Ignitor and opens the Main
Gas Valve.
9. The Ignition Control allows a 2 second pilot ame stabilization
period to insure that the pilot ame is not extinguished by the
main burner light-off process.
10. The Ignition Control monitors the Flame Sensor during the
heating cycle. If the ame signal is lost, the Ignition Control shuts
the Main Gas Valve and Pilot Gas Valve and re-starts the ignition
process at step 4.
11. Once the unit is satised, the Ignition Control will shut off the
Main Gas Valve and the Pilot Gas Valve and the unit will be in
standby mode until another call for heat is initiated by
the thermostat.
See the ow chart on page 26 for more information.
25
Description of this ow chart can be found in the “SEQUENCE OF OPERATION” section found on page 25.
IDLE
(NOT POWERED)
SEQUENCE OF OPERATION FLOW CHART
“CALL FOR HEAT”
RECEIVED FROM
THERMOSTAT
POWER TO
MODULE AND
SELF CHECK
TRIAL FOR
IGNITION
(TIMER STARTED)
FLAME
PROVED?
(BEFORE TRIAL FOR IGNITION TIMER EXPIRES)
YES
NO
A
SPARK ON
CLOSE PILOT
GAS VALV E
OPEN PILOT GAS
VALV E
SPARK OFF
RETRY DELAY
(5 MINUTES)
RETRY
RETRY OR
LOCKOUT
MODEL?
WAIT FOR
“CALL FOR HEAT”
TO BE REMOVED
ACTIVATE ALARM
CONTACT(S)
(OPTIONAL)
LOCKOUT
SPARK OFF
OPEN MAIN GAS
VALV E
FLAME
STABILIZATION
(2 SECONDS)
RUN
“CALL
FOR HEAT”
ENDS?
YES
CLOSE MAIN GAS
VALVE AND PILOT
GAS VALV E
NO
NO
FLAME
LOST?
YES
FLOW CHART 1.
CLOSE MAIN GAS
VALV E AND PILOT
GAS VALV E
A
26
LIGHTING & OPERATION LABEL
FOR YOUR SAFETY READ BEFORE OPERATING
OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING
FIGURE 22. LABEL FOR NATURAL GAS MODELS
27
FOR YOUR SAFETY READ BEFORE OPERATING
OPERATING INSTRUCTIONS
TO TURN OFF GAS TO APPLIANCE
FIGURE 23. LABEL FOR PROPANE GAS MODELS
28
ADJUSTMENTS
ON INITIAL STARTUP SOME ADJUSTMENTS MAY BE NECESSARY.
Check Manifold and inlet gas pressures (see GAS SUPPLY
SYSTEMS on page 13 and CHECKING THE INPUT on page 29-30.)
Check Pilot Burner (See Pilot Burner section on page 34.)
TESTING DAMPER OPERATION
With the Service Switch in the AUTOMATIC OPERATION
position, check the operation of the ue damper three (3) times
with the water operating controls for proper operating sequence:
• The damper disc must be open (in the vertical position) before
the ignition and combustion process begins.
• The damper disc must be in the open position when the main
burner is ring.
• The gas control valve must close and the main burner must
have ceased ring before the damper disc begins its return to
the closed (horizontal) position.
If during testing of the operation of the damper you nd that
there is a problem with the operation of the water heater when
the Service Switch is in the AUTOMATIC OPERATION position:
Reset the Service Switch to the HOLD OPEN DAMPER position
and check operation again.
If the water heater does operate when placed in the HOLD OPEN
DAMPER position:
• Refer to the EFFIKAL RVGP-FSF-SERIES TROUBLESHOOTING
GUIDE on page 37.
If the water heater does not operate with the Service Switch in
either position:
• Refer to the Troubleshooting Sections and Troubleshooting
Checklist.
CHECKING VENTING
FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR
CONTAMINATION AND UNSAFE CONDITIONS.
• If the back draft cannot be corrected by the normal method or
if a suitable draft cannot be obtained, a blower type ue gas
exhauster must be employed to assure proper venting and
correct combustion.
CHECKING THE INPUT
For installation locations with elevations above 2000 feet, refer
to HIGH ALTITUDE INSTALLATIONS section of this manual for
input reduction procedure.
1. Attach a pressure gauge or a manometer to the manifold
pressure tap on the gas control valve and refer to Table
9, for correct manifold pressure.
2. Use this formula to “clock” the meter. Be sure that other
gas consuming appliances are not operating during this
interval.
(3600/T) x H = Btuh
T = Time in seconds to burn one cubic foot of gas.
H = Btu’s per cubic foot of gas.
Btuh = Actual heater input.
Example: (Using BTR-250 heater)
T = 15.1 seconds
H = 1050 Btu
Btuh = ?
(3600/15.1) x 1050 = 250,000 (Compare with BTR-250 model
and rating.)
The following steps shall be followed with each appliance connected
to the venting system placed in operation, while any other appliances
connected to the venting system are not in operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as
required in the National Fuel Gas Code, ANSI Z223.1or the CAN/
CGA B149 Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage, corrosion and
other deciencies which could cause an unsafe condition.
3. So far as is practical, close all building doors and windows
and all doors between the space in which the water heater(s)
connected to the venting system are located and other spaces
of the building. Turn on all appliances not connected to the
venting system. Turn on all exhaust fans, such as range hoods
and bathroom exhausts, so they shall operate at maximum
speed. Close replace dampers.
4. Follow the lighting instruction. Place the water heater being
inspected in operation. Adjust thermostat so water heater shall
operate continuously.
5. Test for draft hood spillage at the relief opening after 5 minutes
of main burner operation.
6. After it has been determined that each appliance connected to
the venting system properly vents when tested as outlined above,
return doors, windows, exhaust fans, replace dampers and any
other gas burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests,
the venting system must be corrected.
29
TABLE 9.
APPROXIMATE TIME REQUIRED TO CONSUME
1 CU. FT. OF GAS AT FULL CAPACITY
INPUT
RATE
(BTUH)
120,000
154,000
180,000
199,000
250,000
251,000
275,000
305,000
365,000
390,000
TYPE
OF
GAS
NATURAL
PROPANE
NATURAL
PROPANE
NATURAL
PROPANE
NATURAL
PROPANE
NATURAL
PROPANE
NATURAL
PROPANE
NATURAL
PROPANE
NATURAL
PROPANE
NATURAL
PROPANE
NATURAL
PROPANE
BTUH
PER
CU. FT.
1050
2500
1050
2500
1050
2500
1050
2500
1050
2500
1050
2500
1050
2500
1050
2500
1050
2500
1050
2500
TIME REQ’D TO
CONSUME 1 CU.
FT. OF GAS
31. 5 SEC.
75.0 SEC.
24.5 SEC.
58.4 SEC.
21.0 SEC.
50.0 SEC.
19.0 SEC.
45.2 SEC.
15.1 SEC.
36.0 SEC.
15.1 SEC.
35.9 SEC.
13.7 SEC.
32.7 SEC.
12.4 SEC.
29.5 SEC.
10.4 SEC.
24.7 SEC.
9.7 SEC.
23.1 SEC.
Should it be necessary to adjust the gas pressure to the burners
to obtain the full input rate, the steps below should be followed:
3. Remove the regulator adjustment sealing cap and adjust the pressure
by turning the adjusting screw with a screwdriver. See Figure 24.
Clockwise to increase gas pressure and input rate.
Counterclockwise to decrease gas pressure and input rate.
4. “Clock” the meter as in step 2 above.
5. Repeat steps 3 and 4 until the specied input rate is achieved.
6. Turn the gas control knob to PILOT. Remove the pressure
gauge and replace the sealing cap and the Allen wrench set
screw in the pressure tap opening.
FIGURE 24.
UNDER NO CIRCUMSTANCES SHOULD THE GAS INPUT EXCEED
THE INPUT SHOWN ON THE HEATER MODEL AND RATING
PLATE. OVERFIRING COULD RESULT IN DAMAGE OR SOOTING
OF THE HEATER.
30
Loading...
+ 90 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.