Commercial Gas Water Heaters
The A. O. Smith BTPD Models Feature All Stainless Steel Tank
Construction And Are Designed For Heating Deionized Water.
The Tank And Other Wetted Components Are Suitable For
Deionized Water.
These units are designed for industrial and process water applications and are not
recommend normal potable water heating applications. For potable water heating applications
A. O. Smith designs and builds a long list of other models to choose from.
water heater producing non-potable water, and therefore does not need to meet
current edition ASHRAE/IESNA 90.1 or C.E.C. energy guidelines.
FEATURES
POWERED GAS BURNER
Suitable for natural or propane gas (specify when ordering). Powered burner
has electronic fl ame safeguard control with intermittent spark ignition. Also
included are main and pilot automatic gas valves, plus gas pressure regulators.
FULLY AUTOMATIC CONTROLS WITH SAFETY SHUTOFF
High temperature limit control (manual reset). CSA/ASME Certified T&P relief valve.
Hinged door control compartment for ease of access. Two thermostats, upper and
lower, for accurate temperature control.
Entire unit UL listed (File No. MH11631).
This is a process
BTPD-140
through
BTPD-199
STAINLESS STEEL TANK
Tank and wetted components suitable for deionized water
STANDARD DESIGN PRESSURE
160 PSI working pressure on all models
JACKET
Is of heavy gauge steel with premium powder coat baked
enamel fi nish
OTHER FEATURES
Two layers of high temperature ceramic fi ber insulation in
combustion chamber
Flame inspection port opening
Mounted on rugged channel iron skids
Barometric draft regulator
120 volt control circuit
Redundant solenoid gas valve
THREE-YEAR LIMITED TANK WARRANTY
Factory Start-Up included - Required for activating warranty and assuring
maximum operating performance. Contact your local sales representative or
Authorized Start-Up Agent to arrange a FREE Certifi ed Start-Up.
For complete warranty information, consult written warranty shipped with
water heater or contact A. O. Smith
GAS FIRED
December 2012R
Page 1 of 2
AOSCG11100
Commercial Gas Water Heaters
DIMENSIONS FOR NATURAL AND POPANE GAS
SHIPPING WT. 615 LBS.
Storage
Models
BTPD-85-140
BTPD-85-199
Maximum supply gas pressure 14” W.C. A negative draft of —.02” to —.07” W.C. is required in vent piping.
Capacity
U.S. Gallons
85
85
Input Rating
BTU/HR.
140,000
199,000
Recovery
Capacity
GPH
80°F Rise
168
239
Recovery
Capacity
GPH
100°F Rise
134
191
Recovery
Capacity
GPH
140°F Rise
96
137
Motor HP
120V60Hz1 0
1/12 HP/2.2 Amps
SUGGESTED SPECIFICATION
Water heater(s) shall be Model ______________ as manufactured by A. O. SMITH or equal. Water heater(s) shall be type 316L stainless steel and
include a powered gas burner with electronic flame safeguard, intermittent ignition, redundant automatic gas valve, gas pressure regulator and
flame inspection port. Maximum supply gas pressure to heater 14” W.C. Heater(s) shall have an input rating of _______and a recovery rating of
_________GPH at a temperature rise of 100°F with a minimum actual storage capacity of 85 gallons. Heater(s) shall be equipped with 1 1/4” NPT
wat
er inlet and outlet openings, shall have a working pressure of 160 PSI, and listed by Underwriters Laboratories. Controls shall include: high
temperature limit control (manual reset), upper and lower thermostats, CSA/ASME Certified T&P Relief Valve, and draft regulator. Control
compartment door shall be hinged for easy access. The heater(s) shall be insulated with a vermin-proof glass fiber insulation or equal. This is a
proces water heater producing non-potable water, and therefore does not need to meet current edition ASHRAE/IESNA 90.1 or C.E.C. energy
guidelines. The outer jacket shall have a premium powder coat baked enamel finish. Heater(s) tank shall have a 3 year limited warranty against
corrosion as outlined in the written warrany.
For Technical Information and Automated Fax Service, call 800-527-1953. A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
December 2012R
www.hotwater.com
Page 2 of 2
AOSCG11100