1. After the points of termination have been determined, use the cover
plates as templates to mark the holes for the vent pipes to be inserted
through the wall. BEWARE OF CONCEALED WIRING AND PIPING INSIDE
OF WALL.
2. If the vent terminals are being installed on the outside of a finished wall,
it may be easier to mark both the inside and outside wall. Align the holes
by drilling a hole through the center of the template from the inside
through to the outside. The template can now be positioned on the
outside wall using the drilled holes as a centering point for the template.
3. A) MASONRY SIDE WALLS
Chisel an opening approximately one half inch larger than the marked
circle.
B) WOODEN SIDE WALLS
Drill a pilot hole approximately one quarter inch outside of the marked
circle. This pilot hole is used as a starting point for a saws-all or sabre
saw blade. Cut around the marked circle staying approximately one
quarter inch outside of the line. (This will allow the vent pipe to easily
slide through the opening. The resulting gap will be covered by the vent
terminal cover plates.) Repeat this step on the inside wall if necessary.
4. Cut a length of 3 inch PVC pipe about 3.5 inches longer than the wall
thickness at the opening.
5. Glue the intake vent terminal to the section of the pipe.
6. Slide the wall plate over the pipe to stop against intake vent terminal.
7. Place a bead of caulking (not supplied) around the gap between the
pipe and the wall. Place some of the caulking on the back of the plate to
hold it against the wall after installation.
8. If the vent pipe is installed up to the wall, with a coupling on the end
against the wall opening, the pipe with the vent terminal can be prepared
for gluing before inserting through the wall. Slide the pipe through the
wall and insert into coupling on the other side of the wall, making sure
that the vent terminal ends up pointed in the correct position (Figure 10).
FIGURE 10
9
Page 10
FIGURE 11
VERTICAL VENT TERMINAL INSTALLATION
IMPORT ANT
WHEN TERMINATING THROUGH A ROOF, THE FOLLOWING
SPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BE
FOLLOWED.
1. Proper support must be provided for all pipe protruding through the
roof.
2. The vertical roof terminations should be sealed with a plumbing roof
boot or equivalent flashing.
3. The intake vent termination and the exhaust vent termination must
penetrate the same side of roof.
4. The center line of the intake vent termination and the center line of the
exhaust vent termination must be no closer than 24" (inches).
5. The intake vent terminal and the exhaust vent terminal must be oriented
facing downward and the same direction.
The specifications are displayed in Figure 11 & 12.
NOTE: Exhaust vent terminal is installed using the same procedure.
INST ALLA TION SEQUENCE
NOTE: BEFORE BEGINNING INSTALLATION OF ANY VENT PIPE, READ
“VENT PIPE PREPARATION” SECTION ON PAGE 11.
1. After the points of termination have been determined, use the cover
plates as templates to mark the holes for the vent pipes to be inserted
through the roof.
2. Drill a pilot hole approximately one quarter inch outside of the marked
circle. This pilot hole is used as a star ting point for a saws-all or sabre
saw blade. Cut around the marked circle staying approximately one
quarter inch outside the line. (This will allow the vent pipe to easily slide
through the opening). The resulting gap will be covered by the roof boot/
flashing.
3. Suspend the pipe through the center of the hole using proper support.
4. Slide roof boot or equivalent flashing over pipe and secure roof boot
equivalent flashing to roof.
5. Seal around flashing.
6. Terminate intake terminal and exhaust vent terminal facing down as
shown in Figure 12.
FIGURE 12
INSTALLATION OF VENT SYSTEM
WARNING
THE OPTIONAL INTAKE VENTING ARRANGEMENT AND THE EXHAUST
VENTING ARRANGEMENT MUST BE INSTALLED TO RUN DIRECTLY TO THE
OUTDOORS AND NOT IN ANY WAY BE CONNECTED TO ANOTHER
VENTING SYSTEM (I.E. FURNACE, DRYERS OR SPACE HEATERS). IT IS
CRUCIAL THAT THE VENTING ARRANGEMENT BE KEPT SEPARATE FROM
OTHER VENTING SYSTEMS. IF THIS WARNING IS IGNORED, AND THE
SYSTEM IS VENTED INCORRECTLY, IT MAY CAUSE IMPROPER OPERATION,
FIRE, EXPLOSION, OR ASPHYXIATION.
1. Plan the route of the vent system from the vent termination to the planned
location of the appliance. Layout the total vent system to use the minimum
of vent pipe and elbows possible.
2. The installer may add up to a MAXIMUM OF FIFTY (50) EQUIVALENT
feet of pipe to the exhaust venting arrangement. This addition of FIFTY
(50) EQUIVALENT feet of pipe on both the intake venting arrangement
and exhaust venting arrangement must include any 3 inch PVC elbows
which equals (5) EQUIVALENT feet of pipe.
10
Page 11
Table 2. VENT LENGTH TABLE
Number of3" Minimum 3" Maximum 4" Maximum
90° ElbowsPipe (Feet)Pipe (Feet)Pipe (Feet)
ONE (1)745115
TWO (2)740110
THREE (3)735105
FOUR (4)730100
FIVE (5)7-- -95
SIX (6)7-- -90
4-inch PVC may be used for a MAXIMUM intake of ONE HUNDRED TWENTY
(120) EQUIVALENT FEET and a MAXIMUM exhaust of ONE HUNDRED
TWENTY (120) EQUIVALENT FEET. The maximum number of 90° elbows
with the 4-inch venting is six (6) on the intake and six (6) on the exhaust.
A 90° elbow is equal to five (5) equivalent feet of pipe. One (1) 90° elbow
is equal to two (2) 45° elbows. Any venting configuration using less than
50 equivalent feet should use 3-inch venting. See Table 2.
The 3-inch venting terminals (provided) must be used with the 4-inch
venting by adding 4x3 reducing couplings at the venting terminals. A
reducing coupling is also needed immediately after the condensate elbow
(exhaust) and immediately before the 3-inch blower adapter (intake) if
direct venting is installed. See Table 2.
IMPORTANT
When multiple units are direct vented through a wall (3-inch or 4-inch
venting), all intake vent terminals should be no lower than the highest
exhaust vent terminal.
NOTE: This unit can be vented using only PVC (Class 160, ASTM D-2241
FOR SAFE OPERATION OF THE WATER HEATER, THE RELIEF VALVE(S)
MUST NOT BE REMOVED OR PLUGGED.
In addition to the appliance relief valve, each remote storage tank which
may be used in conjunction with this appliance shall also be installed with
a properly sized, rated and approved temperature (ANSI) and pressure
(ASME) relief valve(s). This relief valve shall comply with the standard for
relief valves and automatic gas shutoff devices for hot water supply
systems. ANSI Z21.22
Your local code authority may have other specific relief valve requirements.
WARNING
THE PURPOSE OF A RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE
OR TEMPERATURE INTO THE STEAM RANGE, WHICH MAY CAUSE
SCALDING AT FIXTURES, TANK EXPLOSION, SYSTEM OR HEATER
DAMAGE. NO VALVE IS TO BE PLACED BETWEEN THE RELIEF VALVE AND
THE TANK.
A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO DIRECT
DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR WATER
DAMAGE. THIS LINE MUST NOT BE REDUCED FROM THE SIZE OF THE
VALVE OUTLET AND MUST NOT CONTAIN VALVES OR RESTRICTIONS,
NOR SHOULD IT BE LOCATED IN FREEZING AREAS. DO NOT THREAD OR
CAP THE END OF THIS LINE. RESTRICTED OR BLOCKED DISCHARGE WILL
DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE. THE DISCHARGE
LINE SHALL BE INSTALLED TO ALLOW COMPLETE DRAINAGE OF BOTH
THE VALVE AND LINE.
13
Page 14
WATER LINE CONNECTIONS
HEATER WIRING
This manual provides detailed installation diagrams (see back section of
this manual) for typical methods of application for the water heaters.
The water heater may be installed by itself, or with a separate storage
tank. When used with a separate storage tank, the circulation may be
either by gravity or by means of circulating pump. When a circulating pump
is used, it is important to note that the flow rate should be slow so that there
will be a minimum of turbulence inside the heater.
CLOSED SYSTEM
A closed system will exist if a check valve (without bypass), pressure
reducing valve (without bypass), or a water meter (without bypass) is
installed in the cold water line between the water heater and street main
(or well).
Excessive pressure may develop causing premature tank failure or
intermittent relief valve operation. This type of failure is not covered by the
limited warranty. An expansion tank or a similar device may be required in
the inlet supply line between the appliance and the meter or valve to
compensate for the thermal expansion of water under supply pressure.
If a water heater is installed in a closed water system, check local codes
or contact the water supplier or local plumbing inspector on how to control
this situation.
CAUTION
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE
MUST BE REPLACED, IT MUST BE REPLACED WITH 105°C WIRE OR ITS
EQUIVALENT, EXCEPT IN THE BURNER HOUSING. IN THIS CASE USE
200°C WIRE.
THE COMPUTER CONTROL REQUIRES A SOURCE OF STABLE CLEAN
ELECTRICITY FOR PROPER OPERATION. INSTALLING THE HEATER ON
A BRANCH CIRCUIT THAT HAS ELECTRONIC NOISE, IS SUBJECT TO
FLUCTUATIONS IN VOLTAGE LEVEL OR HAS AN APPLIANCE WHICH
GENERATES EMF OF RFI INTERFERENCE CAN CAUSE THE
CONTROLLER TO MALFUNCTION. A HIGH QUALITY POWER
CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST.
MALFUNCTIONS CAUSED BY A POOR ELECTRICAL SUPPLY ARE NOT
COVERED UNDER YOUR WARRANTY.
The controller is wired to the heater as shown in figures 16 & 17. The
model and rating plate provides the electrical information needed to
size the complete heater branch supply.
All electrical work must be installed in accordance with the National
Electrical Code and local requirements.
When installed, the appliance must be electrically grounded in
accordance with local codes or, in the absence of local codes, with
the National Electrical Code, ANSI/NFPA 70.
DO NOT ENERGIZE THE BRANCH CIRCUIT BEFORE THE HEATER TANK
IS FILLED WITH WATER.
NOTE: This controller is Polarity Sensitive. If the Hot and Neutral Supply
Voltage is reversed, the controller will not sense flame. Verify polarity
before connecting the unit.
BSR BOARD (BTH - 250 ONLY)
FIGURE 16
14
Page 15
8. After an additional 2 seconds, the control will monitor the flame sense
probe to confirm a flame is present. If a flame is not verified within this
time period, the gas valve will immediately be closed, and the blower will
continue to run for approximately 10 seconds. The control will then
return to step 2.
9. If a flame is confirmed, the control will enter the heating mode where it
will continue heating the tank water until the setpoint temperature plus
differential is reached. At this point, the gas valve is closed and the
control enters the post-purge cycle.
10.The combustion blower will run for the duration of the post purge cycle
to purge the system of all combustion gases. When the post purge
cycle is complete, the blower is de-energized and will coast to a stop.
11. The control will now enter the idle state while continuing to monitor the
internal tank water temperature and the state of other system devices.
If the temperature drops below the setpoint value less differential, the
control will automatically return to step 2 and repeat the entire operating
cycle. During this idle state, if the control detects an improper operating
state for external devices such as the ECO switch, vent switch, pressure
switch, etc., the appropriate LED(s) on the Display Board will be
illuminated indicating the nature of the fault.
SELF DIAGNOSTIC CONTROLLER
ITEM DESCRIPTION
1. Transformer
2. Control Board
3. E.C.O./Temperature Probe
4. Blower Proving Air Switch
5. Low Voltage Cable Assembly
6. Line Voltage Cable Assembly
7. Blower/Motor Assembly
8. Igniter Assembly
9. Cable To Control Display Board
10. Control Display Board
11. Blocked Outlet Exhaust Switch
12. Lower Temperature Probe
13. Wire Assembly-Gas Pressure
Switch
FIGURE 17
14. Tubing-Pressure
15. Tubing-Pressure
16. Connector-Tubing
17. Switch-On/Off
18. Low Gas Pressure
Switch
19. Bocked Inlet Switch
20. Wire Assembly-Air
Flow Switch
OPERATION
SEQUENCE OF OPERATION
Typical Control/Appliance Operating Sequence
1. When the control is powered, it should first display 0, then the input
line voltage (120), the calibration setting (12), then the actual water
temperature in the tank.
2. If the control determines that the actual water temperature inside the
tank is below the programmed temperature setpoint less the differential,
a call for heat is activated.
3. The control then performs selected system diagnostic checks. This
includes confirming the proper state of the air switch and ECO limit
device.
4. If all checks are successfully passed, the combustion blower is
energized for the pre-purge cycle.
5. When the pre-purge cycle is complete, power is applied to the ignitor
element for the ignitor warm-up period.
6. At the conclusion of the igniter warm-up period, the gas valve will open,
allowing gas to enter the burner chamber.
7. The igniter will remain on for a short predetermined time period, then will
be turned off.
This controller is designed for ignition lockout after three consecutive failed
attempts to light. If lockout occurs, the display lights will match Figure 18.
Along with this, a numeric message will appear in the display. The following
list of ERROR CODES illustrates possible numeric failures.
FIGURE 18
GAS VALVE LED FLASHING
This condition results from a failure to establish burner ignition after three
successive trials. In such cases:
1. Investigate the possible cause and remedy any observations.
2. Momentarily depress the button on the display panel to reset the lockout
condition.
3. Confirm proper appliance operation.
Possible Cause Remedy
1. Burner ground wire broken1. Check wire and connection
or corrodedat burner
2. Connectors unplugged2. Check connections
3. Igniter broken3. Replace igniter
4. Flame probe faulty4. Replace flame probe
5. Gas shut off5. Turn on gas supply
6. Clogged gas valve6. Replace gas valve
7. Faulty gas valve7. Replace gas valve
8. Defective control8. Replace control
9. Burner improperly adjusted9. Adjust burner
10. Dirty burner10. Clean burner
15
Page 16
ERROR CODES
The following Error Codes are external to the controller.
01 Pressure Switch Fail On, should be Off
11 Pressure Switch Fail Off, should be On
02 Ignition Fail after 3 attempts
04 ECO Open
05 Temperature Probe Open
15 Temperature Out of Bounds < 30 degrees
25 Temperature Out of Bounds > 220 degrees
The following Error Codes are internal to the controller.
113 Flame On Should be Off Fail
22 Ignition Relay Fail is On, should be Off
112 Ignition Relay Fail is Off, should be On
101 K2 Fail in K1
102 Main Loop Fail in K2
103 K1 Fail in Main Loop
Gas Valve Power Supply. (*WDPS Watch Dog Power Supply).
106 WDPS Fail to be Off
107 WDPS Fail to be Off
108 WDPS Fail to be On
116 Gas Valve Relay Fail is off, should be On
117 Gas Valve Relay Fail is On, should be Off
Checks The ROM (Read Only Memory).
200 CRC Check Sum Error
Checks The CPU (Central Processing Unit).
201 CPU Instruction Test Error
202 CPU Instruction Test Error
203 CPU Instruction Test Error
Possible CauseRemedy
1. No Input Power1. Apply Power
2. Wiring Disconnected2. Check all wiring
3. One or more wiring receptacles 3. Reconnect plugs on control,
disconnected from controlconfirm all are fully seated
4. LED burned out4. Ignore or replace control
NO LOW VOLTAGE (Figure 20)
24V AC LED Off
Checks the RAM (Random Acess Memory).
205 RAM Test Fail
SW Check to see what the Last State it was in.
ie., Fails if it can from the wrong place
125 State Error
126 State Error
128 State Error
127 State Error
129 State Error
131 State Error
132 State Error
These State Numbers are not used.
230 Executed State 3 (Not Implimented) h.s.
240 Executed State 4 (Not Implimented) h.s
210 Executed State 10 (Not Implimented) h.s.
213 Executed State 13 (Not Implimented) h.s.
214 Executed State 14 (Not Implimented) h.s.
216 Executed State 16 (Not Implimented) h.s.
FAULT CONDITIONS
The controller is set up to provide additional status indicators under Fault
Conditons. The following figures are possible Fault Conditions.
NO INCOMING LINE VOLTAGE (Figure 19)
Line LED Off
NO LOW VOLTAGE, 24V AC LED Off
FIGURE 20
NOTE: The transformer is of Class II variety and has an internal non-
replaceable fuse. If blown, a problem may exist with the control which is
affecting the transformer. In such cases, the control should be replaced as
well.
Possible CauseRemedy
1. Transformer wiring problem1. Repair Wiring
2. Defective Transformer2. Replace Transformer
3. LED burned out3. Ignore or replace control
TEMPERATURE PROBE FAULT (Figure 21)
Water Temp LED Flashing
NO INCOMING LINE VOLTAGE, Line LED Off
FIGURE 19
TEMPERATURE PROBE FAULT, Water Temp LED Flashing
FIGURE 21
This condition accommodates multiple failure modes. To more accurately
determine the cause of failure, press the pushbutton on the display board.
16
Page 17
Display Flashes 05 when button is pressed:
Possible CauseRemedy
1. Temperature Probe wiring1. Repair Wiring
open
2. Defective probe2. Replace probe
Display Flashes 15 when button is pressed:
Possible CauseRemedy
1. No water in tank and tank1. The symptom does not
in freezing conditionsreflect a control problem
2. Water in tank above freezing2. Temperature probe out of
tolerance, replace temp.
probe
Display Flashes 25 when button is pressed:
Possible CauseRemedy
1. Water in tank is low, probe1. Fill tank
immersed in steam
2. Probe wiring shorted2. Repair wiring
3. Defective probe3. Replace probe
ECO SWITCH OPEN (Figure 22)
ECO LED Flashing:
CONTROL BAD, All LEDs Flashing
FIGURE 23
Possible CauseRemedy
1. Temp. Probe unplugged1. Check connectors
2. Temp. probe wiring damaged2. Repair wiring
3. Water in tank too hot3. Normal condition when
water temperature
exceeds safety limit.
Allow water to cool or
admit water into tank and
manually reset the control.
Determine cause for
overtemp condition.
COMBUSTION AIR BLOCKAGE (Figure 24)
Pressure Switch LED Flashing:
ECO SWITCH OPEN, ECO LED Flashing
FIGURE 22
Possible CauseRemedy
1. This indicates the control has1. Press button on the
failed on of its internaldisplay board to reset
diagnostic self-tests.control. If this error
occurs repeatedly,
replace control.
CONTROL BAD (Figure 23)
All LEDs Flashing:
COMBUSTION AIR BLOCKAGE, Pressure Switch LED Flashing
FIGURE 24
Possible CauseRemedy
1. Combustion air blocked1. Check exhaust piping and
flue for obstructions
2. Blower not operating:2. a. Repair wiring
a. Check blower wiringb. Replace blower motor
b. Check blower motor
3. Defective air switch3. Replace air switch
4. Pressure switch jumped out4. This controller must sense
an open contact on the
blower proving airflow
switch before the blower
comes on. Check to see if
blower proving airflow
switch is still connected to
the unit.
17
Page 18
PRIOR TO START UP
REQUIRED ABILITY
ADJUSTMENT PROCEDURE
INITIAL START-UP
INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY
EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD
INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS SUPPLY AND
ELECTRICAL WORK ARE REQUIRED.
Before attempting start-up, thoroughly study and familiarize yourself with
the exact sequence of operation and all other details on the specific heater
being used.
The power burner is equipped with an ignition system which automatically
sequences prepurge and ignition, senses and ignites main burner flame
and sequences burner operation. Heater is equipped with an ignition control
which locks out after three unsuccessful ignition attempts. Familiarize
yourself with the sequence of operation of this unit prior to start-up.
Be certain that the water heater is full of water, that air is purged from all
lines, there are no leaks (gas and water), and all inlet water lines are open.
The following test equipment should be on hand (all test equipment must be
acclimated to ambient temperature before calibration and use.)
Two U-tube manometers or calibration 0-10" and 0-35" W.C. pressure
gauges.
Attach a gas pressure gauge or manometer to the upstream side of
main gas cock and a gas pressure gauge or manometer to the manifold
pressure tap (see Figure 15).
You are now ready to begin the burner start-up procedure.
OPERATING INSTRUCTIONS
IMPORTANT
IT IS RECOMMENDED THAT A QUALIFIED SERVICE TECHNICIAN PERFORM
THE INITIAL FIRING OF THE HEATER. AT THIS TIME THE USER SHOULD ASK
THE TECHNICIAN ANY QUESTIONS IN REGARD TO THE OPERATION AND
MAINTENANCE OF THE UNIT.
CAUTION
BEFORE PROCEEDING WITH THE OPERATION OF THE UNIT, MAKE SURE
HEATER AND SYSTEM ARE FILLED WITH WATER AND ALL AIR IS EXPELLED
FROM HEATER AND PIPING.
NEVER OPERATE THE HEATER WITHOUT FIRST BEING CER TAIN IT IS FILLED
WITH WATER AND A TEMPERATURE AND A PRESSURE RELIEF VALVE IS
INSTALLED IN THE RELIEF VALVEOPENING OF THE HEATER. DO NOT
ATTEMPT TO OPERATE HEATER WITH COLD WATER INLET VALVE CLOSED.
FILLING:
1. Close the heater drain valve.
2. Open a nearby hot water faucet to permit the air in the system to
escape.
3. Fully open the cold water inlet pipe valve allowing the heater and
piping to be filled.
4. Close the hot water faucet as water starts to flow.
5. The heater is ready to be operated.
THE MAIN MANUAL GAS SHUTOFF VALVE MUST HAVE BEEN CLOSED
FOR AT LEAST FIVE (5) MINUTES. THIS WAITING PERIOD IS AN IMPORTANT
SAFETY STEP. ITS PURPOSE IS TO PERMIT GAS THAT MIGHT HAVE
ACCUMULATED IN THE COMBUSTION CHAMBER TO CLEAR. IF YOU DETECT
GAS AT THE END OF THIS PERIOD, DO NOT PROCEED WITH LIGHTING.
RECOGNIZE THAT GAS ODOR, EVEN IF IT SEEMS WEAK, MAY INDICATE
THE PRESENCE OF ACCUMULATED GAS SOMEPLACE IN THE AREA WITH
A RISK OF FIRE OR EXPLOSION. SEE THE FRONT PAGE FOR STEPS TO BE
TAKEN.
DO NOT USE THIS HEATER IF ANY PART HAS BEEN UNDER WATER.
IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE
HEATER AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND
ANY GAS CONTROL WHICH HAS BEEN UNDER WATER.
LIGHT THE UNIT IN ACCORDANCE WITH THE OPERATING INSTRUCTIONS
LABEL ATTACHED TO THE HEATER.
THESE INSTRUCTIONS ARE REPEATED IN THE LIGHTING AND OPERATING
LABEL ILLUSTRATION ON PAGE 20 IN THIS MANUAL.
A minimum gas supply pressure of 5.0" W.C. (4.5" on BTH 150 and 199) for
natural gas (11.0" W.C. for L.P. Gas) is required before making any
adjustment to the gas control pressure regulator Attempts to adjust the
regulator during periods of low gas supply pressure could result in overfiring
of the heater when the gas supply pressure returns to normal.
1. Check gas line pressure with a manometer.
2. Check manifold pressure (see Table 4, page 20) using a pressure
gauge (manometer) connected to the manifold pressure tap on the
gas control valve, (Figure15).
If full rate adjustment is required, remove cover screw from top of the
gas control valve, (Figure 15).
Using a small screwdriver, turn adjusting screw clockwise to increase
or counterclockwise to decrease gas pressure to obtain 4.0" on
BTH 120 and 250 (3.5" on BTH 150 and 199) for natural gas (10.0" W.C.
for L.P. Gas) Water Column.
3. Cycle the burner on and off several times to check its operation.
4. Check the operation of the limit and operating controls.
5. Check the vent system seams and joints and ensure that there is no
discharge of flue products into the room.
6. Check the input rate:
For appliance installation locations with elevations above 2000 feet, refer
to HIGH ALTITUDE INSTALLATIONS section of this manual.
a. Attach a pressure gauge (manometer) to the manifold pressure tap
(Figure 16) and refer to Table 4, page 20 for correct pressure.
b. Use this formula to clock the meter. Be sure other gas consuming
appliances are not operating during this interval.
3600
X H = Btuh
T
Should it be necessary to adjust the gas pressure to the burner, to obtain
the full input rate, the steps below should be followed:
T = Time in seconds to burn 1 cubic foot of gas. (With a stopwatch read
the gas meter and measure the amount of time required for the
heater to consume 1 cubic foot of gas.)
H = Heating value of gas (in Btus per cubic foot of gas).
Btuh = Actual heater input rate, in Btuh.
EXAMPLE: (Using BTH-199,900 heater)
T = 18.9 seconds
H = 1050 Btu/ft.
BTUH = ?
For high altitude installations, compare result to the derated input
required for the elevation at the installation location.
c. Remove the pressure regulator cover screw (Figure 16) and adjust
the pressure by turning the adjusting screw with a small
screwdriver. Do not exceed 4.0" on BTH 120 and 250 (3.5" on BTH
150 and 199) Water Column.
Clockwise to increase gas pressure and input rate.
Counterclockwise to decrease gas pressure and input rate.
d. Clock the meter as in step (b) above.
e. Repeat steps (c) and (d) until the specified input rate is achieved.
f. Turn the manual gas valve to OFF. Replace the pressure regulator
cover screw. Remove the pressure gauge or manometer from the
manifold pressure tap. Replace the set screw in the manifold pressure
tap. If the gas pressure regulator cannot be adjusted to give the full
input rating with sufficient gas pressure at the valve, check to ensure
the unit is equipped with the correct orifice.
3
3600
X 1050 = 199,900 Btuh
18.9
18
Page 19
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING:
explosion may result causing property damage, personal injury or loss of life.
If you do not follow these instructions exactly, a fire or
19
Page 20
HIGH ALTITUDE INSTALLATIONS
UNDER NO CIRCUMSTANCES SHOULD THE INPUT EXCEED THE RATE
WARNING
SHOWN ON THE HEATER RATING PLATE. OVERFIRING COULD RESULT IN
DAMAGE OR SOOTING OF THE HEATER.
CATHODIC PROTECTION
CAUTION
HYDROGEN GAS CAN BE PRODUCED IN A HOT WATER SYSTEM SERVED
BY THIS HEATER THAT HAS NOT BEEN USED FOR A LONG PERIOD OF
TIME (GENERALLY TWO WEEKS OR MORE). HYDROGEN GAS IS
EXTREMELY FLAMMABLE. To reduce the risk of injury under these
conditions, it is recommended that a hot water faucet be opened for several
minutes before using any electrical appliance connected to the hot water
system. If hydrogen is present, there will probably be an unusual sound
such as air escaping through the pipe as the water begins to flow. There
should be no smoking or open flame near the faucet at the time it is open.
PRECAUTIONS
IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT OPERATE HEATER
UNTIL ALL CORRECTIVE STEPS HAVE BEEN MADE BY A QUALIFIED
SERVICEMAN.
1. FLOODING TO OR ABOVE THE LEVEL OF THE BURNER OR CONTROLS
2. EXTERNAL FIRING
3. DAMAGE
4. FIRING WITHOUT WATER
5. SOOTING
WARNING
BTH HEATERS ARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR
ALTITUDES UP TO 6500 FEET. INSTALLATIONS ABOVE 6500 FEET MAY
REQUIRE REPLACEMENT OF THE BURNER ORIFICE. CALL THE TECHNICAL
CENTER @ (800) 627-1953 FOR REQUIREMENTS.
Some gas utility companies derate their gas for altitude, making it
unneccessary to install high altitude orifices. Call the local gas or utlity
company to verify BTU content.
Due to the input rating reduction at high altitudes, the output rating of the
appliance is also reduced and should be compensated for in the sizing of
the equipment for applications.
MAINTENANCE
GENERAL
KEEP APPLIANCE AREA CLEAR AND FREE FROM COMBUSTIBLE
MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
(SEE WARNING ON PAGE 5, LOCATING THE HEATER).
Water heater maintenance includes periodic tank flushing and cleaning,
and removal of lime scale. The unit should be inspected and adjusted to
maintain proper combustion. Refer to the following table. A periodic
inspection of the venting system should be made. Where used, the water
circulating pump should be oiled.
NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED
WITH WATER AND A TEMPERATURE AND PRESSURE RELIEF VALVE IS
INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER.
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT
OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE APPLIANCE.
GENERAL INFORMATION
POWER BURNER
The initial start-up procedure of the unit is provided on page 18.
The sequence of operation of the unit is provided on page 15.
It is important to note that the controller has a reset button on the control
box, Figure 1. The reset button is a safety device and would not normally
be used.
HIGH LIMIT
The high limit (not adjustable) is factory set to cutout at 202°F. The controller
must be manually reset by depressing the reset button on front of the
control when water temperature drops to below 160°F.
TABLE 4
GAS SUPPLY SPECIFICATIONS
Max. Gas Supply Press. W.C.14.014.014.0
Nominal Gas Supply Press. W.C 7.07.011.0
Minimal Gas Supply Press. W.C.5.04.511.0
Manifold Press. W.C.4.03.510.0
BTH 120BTH 150BTH 120
& 250& 199150 & 199
Natural Gas Natural Gas L.P. Gas
MAINTENANCE SCHEDULE
Following are the instructions for performing some of the recommended
maintenance. Unit inspection and adjustment should be performed by a
competent technician.
COMPONENTOPERATIONINTERVALREQUIRED
TankSedimentMonthlyFlushing
Removal
TankLime ScaleSemiUN-LIME
RemovalAnnuallyDelimer
AnodeInspectSemiReplace as
RodsAnnuallyRequired
Relief ValveInspectSemi
Annually
SAE No. 20
CirculatingOilingFour Months non-detergent
Pump (1)motor oil
Clean Inlet
BlowerScreen andAs RequiredSoft Brush
Blower Wheel
Vent SystemInspectEvery 3Joints should
Monthsbe sealed
(1) If furnished with oiling provision.
®
20
Page 21
FLUSHING
1. Turn off the heater electrical disconnect switch.
2. Open the drain valve and allow water to flow until it runs clean.
3. Close the drain valve when finished flushing.
4. Turn on the heater electrical disconnect switch.
DRAINING
The heater must be drained if it is to be shut down and exposed to
freezing temperatures. Maintenance and service procedures may also
require draining the heater.
1. Turn off the heater electrical disconnect switch.
2. Close the cold water inlet valve to heater.
3. Open a nearby hot water faucet to vent the system.
4. Open the heater drain valve.
FIGURE 25
To dissolve and remove the more stubborn mineral deposits, A.O. Smith
UNLIME® Professional Delimer should be used.
5. If the heater is being drained for an extended shutdown, it is suggested
the drain valve be left open during this period.
Follow FILLING instructions when restoring hot water service.
SEDIMENT REMOVAL
Waterborne impurities consist of the particles of soil and sand which
settle out and form a layer of sediment on the bottom of the tank.
For convenience, sediment removal and lime scale removal should be
performed at the same time.
LIME SCALE REMOVAL
The amount of calcium carbonate (lime) released from water is in direct
proportion to water temperature and usage. The higher the water
temperature or water usage, the more lime deposits are dropped out of
the water. This is the lime scale which forms in pipes, heaters and on
cooking utensils.
Lime accumulation not only reduces the life of the equipment but also
reduces efficiency of the heater and increases fuel consumption.
The usage of water softening equipment greatly reduces the hardness
of the water. However, this equipment does not always remove all of the
hardness (lime). For this reason it is recommended that a regular schedule
for deliming be maintained.
The depth of lime buildup should be measured periodically. Heaters will
have about 3" of lime buildup when the level of lime has reached the
bottom of the cleanout opening or about 1" of lime buildup if it has reached
the drain valve opening. A schedule for deliming should be set up, based
on the amount of time it would take for a 1" buildup of lime.
Example 1:
Initial inspection shows 1/2" of lime accumulation. Therefore, the heater
can be delimed once a year.
Example 2 :
Initial inspection shows 2" of lime accumulation. Therefore, the heater
should be delimed every 3 months.
Sediment and lime scale removal may be accomplished through the
cleanout opening furnished on the heater, see Figure 25. The heater must
be drained, see DRAINING, before removing cleanout cover on tank.
A.O. Smith UNLIME® Professional Delimer is an easy to handle patented
food grade acid formulated specifically for lime scale removal from all
types of water using equipment. Available in 1 gallon (part no. 4763) and
5 gallon (part no. 4813) sizes. Hydrochloric base acids are not
recommended for use on glass-lined tanks.
A.O. Smith Form No. 4800, entitled Why, When and How, describes tank
cleaning methods and materials. UNLIME and the booklet may be obtained
through your A.O. Smith dealer or distributor.
The cleanout opening is shown in Figure 25. To clean heater through
cleanout opening, proceed as follow:
1. Turn off water inlet valve, the heater electrical disconnect switch and
open drain valve.
2. Remove outer cover plate from lower side of heater jacket.
3. Remove cover from cleanout opening.
4. Remove lime, scale or sediment using care not to damage the
glass-lining.
5. Inspect cleanout plate gasket: If new gasket is required, replace with
A. O. Smith part no. 99038.
6. Install cleanout plate. Be sure to draw plate up tight by tightening
screws securely.
7. Close drain valve, open water inlet line and turn on the power burner
electrical disconnect switch.
8. Check for water leakage.
9. Replace outer jacket cover plate.
ANODE INSPECTION AND REPLACEMENT
This water heater is equipped with multiple sacrificial anodes. Anodes
protect the glass-lined tank from corrosion by sacrificing themselves
through electrolysis. When the anode material is consumed, there is no
more protection and corrosion of the tank accelerates
Inspection of the anode every 6 to 12 months allows you to identify a
spent anode and replace it. Replace the anode when its diameter is 3/8"
of an inch, or annually which ever is first. Aggressive, very hot and
softened water causes rapid consumption of the anode requiring frequent
inspections. Anodes are available from your distributor or A.O. Smith.
21
Page 22
To inspect or replace an anode:
The anodes on this heater are easily accessible from the top of the
heater making replacement simple and quick.
1. Turn the heater off per the lighting instructions. Connect a hose to the
drain valve . Locate the hose's discharge in an area where hot water
will not cause any damage or injury.
2. Open the drain valve to flush any sediment out of the bottom of the
heater.
BEFORE MANUALLY OPERATING THE VALVE, MAKE SURE THAT A DRAIN
CAUTION
LINE HAS BEEN ATTACHED TO THE VALVE TO DIRECT THE DISCHARGE
TO AN OPEN DRAIN. FAILURE TO TAKE THIS PRECAUTION COULD MEAN
CONTACT WITH EXTREMELY HOT WATER PASSING OUT THE VALVE
DURING THIS CHECKING OPERATION.
If the temperature and pressure relief valve on the heater discharges
periodically or continuously, it may be due to thermal expansion of water in
a closed water supply system, or, it may be due to a faulty relief valve.
3. Shut off the cold water supply. Make sure all hot water fixtures and
circulating pumps are turned off.
4. Wait for water flow from the hose to stop. Remove the anode using a
socket of the appropriate size Sometimes a pry bar will be required to
loosen the anode plug . Do not use an impact wrench.
5. Inspect and replace the anode as required. Use a pipe tape or sealant
when reinstalling the anode.
6. Close the drain valve . Open a hot water fixture to allow air to escape.
Open the cold water supply to heater and allow the tank to fill. Follow
the lighting instructions.
7. Check your anode and drain valve for leaks.
DRAIN VALVE AND ACCESS PANELS
The heaters are equipped with a 3/4" drain valve.
An access panel covers the cleanout opening in the tank which is sealed
by a gasket and cover, figure 25.
RELIEF VALVE
At least twice a year, the temperature and pressure relief valve should be
checked to ensure that it is in operating condition. To check the relief valve,
lift the lever at the end of the valve several times. The valve should seat
properly and operate freely.
If water does not flow, remove and inspect for obstructions or corrosion.
Replace with a new valve of the recommended size as necessary.
Inspection of the valve should be performed at least every three years. Do
not attempt to repair the valve, as this could result in improper operation
and a tank explosion. In areas with poor water conditions, it may be
necessary to inspect the T&P valve more often than every three years.
Thermal expansion is the normal response of water when it is heated. In
a closed system, thermal expansion will cause the system pressure to
build until the relief valve actuation pressure is equaled. Then, the relief
valve will open, allowing some water to escape, slightly lowering the
pressure.
Contact your water supplier or local plumbing inspector on how to control
this situation.
Two common corrections are listed in the Checklist and Service Information
which appears later in this manual.
ABOVE ALL, DO NOT PLUG THE TEMPERATURE AND PRESSURE RELIEF
VALVE. THIS IS NOT A SOLUTION AND CAN CREATE A HAZARDOUS
SITUATION.
CIRCULATING PUMP
The water heating system may include a circulating pump. Where used, it
should be lubricated as directed by the circulator manufacturer.
VENT SYSTEM
Examine the vent system every 3 months. Points of inspection are as
follows:
1. Check for obstructions and/or deterioration of vent piping and vent
hood. Replace immediately where needed.
2. Vent pipe and vent hood screen should be cleaned of foreign material
and soot. The screen is located inside the vent hood outlet and is
accessible from the outside of the hood. Do not reach inside the vent
hood when the heater is in operation.
3. Check all vent system connections for leakage and reseal as required
using Hi Temp Silicone sealer or equivalent.
22
Page 23
INSTALLATION DIAGRAMS
ONE TEMPERATURE - ONE HEATER VERTICAL STORAGE TANK FORCED CIRCULATION
WITH OR WITHOUT BUILDING RECIRCULATION
CAUTION: IF BUILDING COLD
WATER SUPPLY HAS A BACK-
FLOW PREVENTER, CHECK
VALVE OR WATER METER WITH
CHECK VALVE PROVISIONS
FOR THERMAL EXPANSION OF
WATER IN THE HOT WATER
SYSTEM MUST BE PROVIDED
NOTE: CONNECT RETURN
LINE FROM HOT WATER
CIRCULATING LOOP (IF USED)
TO COLD WATER INLET LINE.
* PIPE TO OPEN DRAIN
INST ALL IN ACCORDANCE WITH
LOCAL CODES
ONE TEMPERA TURE - ONE HEA TER HORIZONTAL STORAGE T ANK
FORCED CIRCULA TION WITH OR WITHOUT BUILDING RECIRCULA TION
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED
SAFE TEMPERATURE AT FIXTURES. SEE WATER
TEMPERATURE CONTROL WARNING ON PAGE 4.
IF HIGHER PREHEAT TEMPERATURES ARE
NECESSARY TO OBTAIN ADEQUATE BOOSTER
OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT
WATER SUPPLIED TO FIXTURES.
*PIPE TO OPEN DRAIN
INST ALL IN ACCORDANCE
WITH LOCAL CODES
23
Page 24
TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE
WITH OR WITHOUT BUILDING RECIRCULATION
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE
DANGER
TEMPERATURE AT FIXTURES. SEE WATER
TEMPERATURE CONTROL WARNING ON PAGE 4. IF
HIGHER PREHEAT TEMPERATURES ARE NECESSARY
TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN
ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO
FIXTURES.
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A
BACK-FLOW PREVENTER, CHECK VALVE OR WATER
METER WITH CHECK VALVE PROVISIONS FOR THERMAL
EXPANSION OF WATER IN THE HOT WATER SYSTEM
MUST BE PROVIDED.
*PIPE RELIEF VALVE TO OPEN DRAIN.
NOTE: IF TEMPERED WATER IS
RECIRCULATED, RETURN LINE SHOULD BE
CONNECTED AT POINT A.
INSTALL IN ACCORDANCE WITH LOCAL
CODES.
24
Page 25
TWO TEMPERATURE - TWO HEATERS HIGH TEMPERATURE
WITH OR WITHOUT BUILDING RECIRCULATION
TWO TEMPERATURE - THREE HEATERS (TWO PRE-HEATERS/ONE BOOSTER HEATER)
WITH OR WITHOUT BUILDING RECIRCULATION
MUST BE IDENTICAL HEATERS
FOR MULTIPLE HEATER INSTALLATION SEE MANIFOLD KIT
SPECIFICATIONS, PAGE 28.
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACK-FLOW
PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE
PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER
SYSTEM MUST BE PROVIDED.
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT
FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 4.
IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN
ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT
WATER SUPPLIED TO FIXTURES.
25
Page 26
TWO TEMPERATURE - TWO HEATERS (ONE PRE-HEATER/ONE BOOSTER HEATER)
WITH OR WITHOUT BUILDING RECIRCULATION
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT
DANGER
FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 4.
IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN
ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT
WATER SUPPLIED TO FIXTURES
* PIPE RELIEF VALVE TO OPEN DRAIN
** 140°F TO 150°F SHOULD BE MAXIMUM WATER TEMPERATURE
MAINTAINED IN THE PRE-HEATERS.
120°F SHOULD BE THE MINIMUM TEMPERATURE OF WATER IN THE
PRE- H EATERS.
CONNECT CIRCULATING LINE FROM FIXTURES, IF USED, TO COLD
WATER SUPPLY LINE OF PRE-HEATER.
CONNECT CIRCULATING LINE OF 180°F OR BOOSTED WATER, IF
USED, TO INLET WATER LINE TO BOOSTER.
INSTALL IN ACCORDANCE WITH LOCAL CODES.
26
Page 27
TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE
WITH RECIRCULATION OF SANITIZING LOOP
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT
FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 5.
IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN
ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT
WATER SUPPLIED TO FIXTURES.
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACK-FLOW
PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE
PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER
SYSTEM MUST BE PROVIDED.
*PIPE RELIEF VALVE TO OPEN DRAIN
INSTALL IN ACCORDANCE WITH LOCAL CODES
NOTE 1: TOGGLE SWITCH CONTROLS 180°F WATER CIRCULATION.
INSTALL ON OR CLOSE TO DISHWASHER. TOGGLE SWITCH MUST BE
CLOSED (ON) DURING THE RINSE OPERATION AND OPEN (OFF) WHEN
DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY.
NOTE 2: INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED
TEE BEYOND THE DISHWASHER TAKEOFF IN THE SANITIZING LOOP.
CONTROL SHOULD BE SET AT 185°F.
NOTE 3: ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE
DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK.
NOTE 4: IF TEMPERED WATER IS RECIRCULATED, RETURN LINE SHOULD
BE CONNECTED AT POINT A.
27
Page 28
MANIFOLD KITS
Precision cut type L all copper A.O. Smith manifold kits assure water flow balance of all units. Without this balance, the full water
heating and storage potential of the system cannot be achieved. Plus, the units with the higher water flow may have a shortened life.
Unions shown in piping diagrams are not included in the manifold kits.
Dimensions shown are for minimum space occupied by the water heaters assemblies.
Space for the venting system and unit servicing must be added.
28
Page 29
CHECKLIST AND SERVICE INFORMATION
IMPORTANT
The installer may be able to observe and correct certain problems which
might arise when the unit is put into operation or when it is re-fired after a
prolonged shutdown. HOWEVER, it is recommended that only qualified
servicemen, using appropriate test equipment, be allowed to service the
heater.
BE SURE TO TURN OFF THE ELECTRICITY WHENEVER POSSIBLE OR
APPROPRIATE WHILE CHECKING EQUIPMENT.
WARNING
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN SERIOUS
PERSONAL INJURY OR DEATH.
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN
SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND
DANGEROUS OPERATION.
VERIFY PROPER OPERATION AFTER SERVICING.
BURNER OPERATIONAL PROBLEMS
1. Refer to TROUBLESHOOTING.
NOT ENOUGH OR NO HOT WATER
1. Be certain the electrical disconnect switch serving the water heater
is in the ON position.
2. Check the fuses.
The electrical disconnect switch usually contains fuses.
3. The capacity of the heater may have been exceeded by a large
demand for hot water.
Large demands require a recovery period to restore water
temperature.
4. Colder incoming water temperature will lengthen the time required to
heat water to the desired temperature.
If the heater was installed when incoming water temperature was
warm, colder water creates the effect of less hot water.
5. Look for hot water wastage and leaking or open hot water faucets.
The sounds are normal, however, the tank bottom should be cleaned.
Refer to MAINTENANCE for details.
2. Some of the electrical components of the water heater make sounds
which are normal.
Contacts click or snap as the heater starts and stops.
Transformers often hum.
WATER LEAKAGE IS SUSPECTED
1. Check to see if the water heater drain valve is tightly closed. Also
check the cleanout opening for leakage.
2. The apparent leakage may be condensation which forms on cool
surfaces of the heater and piping.
3. If the outlet of the relief valve is leaking it may represent:
Excessive water pressure.
Excessive water temperature.
Faulty relief valve.
Excessive water pressure is the most common cause of relief valve
leakage. It is often caused by a closed system. If a check valve is in the
inlet system it will not permit the expanded hot water volume to equalize
pressure with the main. The relief valve must release this water or the
water heater or plumbing system will be damage d. Refer to MAINTENANCE-
RELIEF VALVE section in this manual.
When such a condition is encountered, local codes or inspection agency
should be consulted to determine which system is acceptable in your area.
See CLOSED SYSTEM section in this manual also.
TROUBLE-SHOOTING
WARNING
JUMPING OUT COMPONENTS AND/OR CIRCUITS DURING
TROUBLESHOOTING CAN CAUSE SERIOUS PROBLEMS WITH THE UNITS
OPERATING SEQUENCE AND IGNITION SAFETY. IF YOU DO NOT HAVE
THE PROPER TEST EQUIPMENT, I.E. A VOLT-OHM METER AND A
MICROAMMETER, DO NOT ATTEMPT TO TROUBLESHOOT OR REPAIR A.O.
SMITH EQUIPMENT.
6. Sediment or lime scale may be affecting water heater operation.
Refer to MAINTENANCE for details.
7. The heaters temperature high limit sensor has activated. Press the
reset button on the thermostat.
8. Burner may not be firing at proper rate.
Check gas pressure. Adjust to obtain required manifold pressure.
9. Burner fan wheel may be dirty.
Clean fan wheel with a stiff brush.
10. Condensate hose may be blocked where it connects to the exhaust
elbow.
Verify the condensate drains from the unit without restriction.
WATER IS TOO HOT
1. Refer to WATER TEMPERATURE CONTROL.
WATER HEATER MAKES SOUNDS
1. Sediment or lime scale accumulations cause rumbling and pounding
noises when the heater is operating.
ALTERING THE CONTROLLER AND/OR CONTROLLER WIRING IN ANY WAY
COULD RESULT IN INTERNAL DAMAGE TO THE MODULE CIRCUITS,
POSSIBLY ALTERING THE IGNITION SEQUENCE ALLOWING GAS VALVES
TO OPEN BEFORE THE HOT SURFACE IGNITER IS UP TO IGNITION
TEMPERATURE.
NOTE: ANY BYPASS OR ALTERATION OF THE UNITS SAFETIES WILL
RESULT IN VOIDING THE APPLIANCE WARRANTY.
Before performing any troubleshooting familiarize yourself with the particular
appliance.
Refer to the SEQUENCE OF OPERATION and the connection diagram located
on page 15 before continuing.
Make sure the appliance is connected to a 120V AC power supply, manual
gas valve is in the ON position, and all electrical connections are secure
before continuing to troubleshoot this appliance.
CAUTION
THE WATER HEATER IS POLARITY SENSITIVE. BEFORE APPLYING
ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY HEATED WIRE
TO GROUND CHECK INDICATES ZERO VOLTAGE.
29
Page 30
MOTOR WILL NOT RUN
1. Confirm 120V AC to the controller. Also, to verify correct polarity, check
for 120 V AC between hot supply and ground.
If there is no voltage, check for a loose connection where it connects to
the controller.
2. If there is 120 volts to the controller, check for loose connections or a
locked rotor. If the rotor cannot be freed the motor and blower assembly
must be replaced.
MOTOR RUNS, PREPURGE TIME ELAPSES BUT MAIN
FLAME NOT ESTABLISHED.
1. Check to see if main manual gas valve is open.
2. Check for a loose connection at the transformer, or a defective
transformer.
3. Check for a loose connection at the gas valve.
4. Check for open pressure switches or open reset button. Check for
blockage in the intake and exhaust venting or at the vent hoods. If no
blockage is found, check vinyl tubing for cuts or crimps. If this tubing is
damaged it must be replaced. If these steps do not eliminate the problem,
replace the pressure switches.
5. Check to see if there is resistance across the igniter terminal with an
OHM meter. If there is no continuity, the igniter is broken and should be
replaced.
If the igniter appears to function properly, then verify that the inlet
pressure is 14.0" W.C. maximum. The gas valve supplied on this appliance
is not designed to open against a higher pressure. At this time also
check that the inlet pressure is not lower than the minimal gas supply
pressure, as shown in Table 4: that is, for Natural Gas, 5.0" W.C. for
BTH 120 & 250 or 4.5" W.C. for BTH 150 & 199 or; for L.P. Gas, 11.0"
W.C. if the inlet pressure is not within these limits then adjust the supply
pressure accordingly.
If the inlet pressure falls within the allowable limits, then verify that the
manifold pressure, when the gas is fully open, with the heater running,
is as called out in Table 4: that is, for Natural Gas, 4.0" W.C. for BTH 120
& 250 or 3.5" W.C. for BTH 150 & 199 or; for L.P. Gas, 10.0" W.C. If the
manifold pressure is not correct then adjust accordingly. See
ADJUSTMENT PROCEDURE in OPERATING INSTRUCTIONS selection,
page 18, for the manifold pressure adjustment procedure.
6. If the inlet and manifold pressures are within the limits specified in step
5, then reset the appliance. Verify 24V AC at the gas valve during the
three (3) second ignition trial, after the igniter reaches operating
temperature. If 24V AC at the gas valve is not seen during this period,
the controller must be replaced.
If there is 24V AC at the gas valve during the four second ignition trial
and the manifold pressure does not increase above 0" W.C. then verify
that the manual gas control valve is in the ON position (see page 20).
If the valve is in the ON position and the previous voltage and gas
pressure conditions are met, then the gas valve is defective and must
be replaced.
the inlet pressure is not greater than 14.0" W.C. or lower than the
minimal gas supply pressure, as shown in Table 4: that is, for Natural
Gas, 5.0" W.C. for BTH 120 & 250 or 4.5" W.C. for BTH 150 & 199 or; for
L.P. Gas, 11.0" W.C. pressure. Also, the manifold pressure should rise
during the three (3) second trial for ignition to the manifold pressure
value for the individual unit listed in Table 4: that is, for Natural Gas, 4.0"
W.C. for BTH 120 & 250 or 3.5" W.C. for BTH 150 & 199 or; for L.P. Gas,
10.0" W.C. If the manifold pressure is not correct then adjust accordingly.
See ADJUSTMENT PROCEDURE in OPERATING INSTRUCTIONS section,
page 18, for the manifold pressure adjustment procedure.
3. Check for the reversed polarity in the supply wiring. This controller is
polarity sensitive. If the hot and neutral supply wires are reversed, the
controller will not sense flame. Reverse the supply wires and try to fire
the unit.
NOTE: Always turn off and disconnect main supply wiring before servicing
the unit.
4. Check connecting wire to the flame sensor. Verify that the flame sensor
has not been damaged in any way.
5. Verify that the air supply is adequate. The air inlet screen or blower
wheel may be restricted. Also, check the installation for proper ventilation.
See AIR REQUIREMENTS.
6. Check the venting system for the correct sizing, excess or insufficient.
See VENTING.
7. Check for a maximum inlet pressure of 14.0" W.C. and the manifold
pressure as listed in Table 4: that is, for Natural Gas, 4.0" W.C. for BTH
120 & 250 or 3.5" W.C. for BTH 150 & 199 or; for L.P. Gas, 10.0" W.C.
Please note that the manifold pressure listed is the maximum value for
the manifold pressure. Do not set the manifold pressure higher than the
value shown for your heater in Table 4. Overfiring the heater will result
in rough ignition and/or noisy operation.
8. Confirm that the air inlet screen (see Figures 7 & 8) is free of obstructions.
CAUTION
Do not reach into the burner housing or combustion chamber if the heater
is still hot. Allow the heater to cool and always use gloves as the combustion
chamber and the burner sleeve and housing can become very hot after
operation. Overfiring is a dangerous condition that must be corrected
immediately.
NOISY BURNER OPERATION
The exhaust of this unit produces some noise. This noise may be
objectionable if the exhaust terminal is located too close to the opening of
an occupied space. The noise may also be objectionable if the exhaust is
located in the confined space between two buildings such as an alley or
walkway. Since everyone's perception and tolerance for background noise
varies, there is no standard recommendation. The best option when the
noise is a concern is to locate the exhaust as far away from any occupied
spaces as practical.
If noise becomes more than one can tolerate, a dampening muffler is available
through our Product Service Division. See REPLACEMENT PARTS segment
below.
GAS FAILS TO SHUT OFF
Note that a positive manifold pressure reading of approximately 1.5"
W.C. is normal during the prepurge portion of the ignition cycle due to
the location of the gas orifice.
MOTOR RUNS, BURNER LIGHTS MOMENTARILY,
THEN LOCKS OUT
1. Reset the appliance two more times to ensure that all of the air has been
purged from the gas line.
2. If the burner lights momentarily but does not sustain ignition, verify that
Check for defective gas valve or thermostat. If operation is incorrect,
replace.
REPLACEMENT PARTS
Replacement parts may be ordered through A.O. Smith dealers, authorized
servicers or distributors. Refer to the Yellow Pages for where to call or
contact the A.O. Smith Water Products Company, 5621 W. 115th Street,
Alsip, IL 60482, 1-800-433-2545. When ordering parts be sure to state the
quantity, part number and description of the items including the complete
model and serial number as it appears on the product. Refer to the parts list
for more information.
30
Page 31
Model BTH Limited Warranty
A. O. Smith Corporation, the warrantor, extends the following LIMITED WARRANTY to the owner of this water heater.
1.THE TANK
If the glass-lined tank in this water heater shall prove upon examination by the warrantor to have leaked due to natural corrosion from potable water
therein, during the first THREE years after initial installation, the warrantor will supply a replacement tank less burner and controls or a complete new
A.O. Smith water heater of equivalent size and current model at the warrantor's option. Some government agencies are requiring energy efficient
standards for water heaters. In the event regulations prohibit sale of a model of equivalent size and construction, A.O. Smith will provide a model
which complies with the regulations of your area., in which case the consumer will be charged the difference in price between the like replacement
and the energy efficient model required. The warranty on the replacement water heater will be limited to the unexpired term of the original warranty.
2.ALL OTHER PARTS
If within ONE year after initial installation of this water heater, any part or portion shall prove upon examination by the warrantor to be defective in
material or workmanship, the warrantor will repair or replace such part or portion at its option.
3.CONDITIONS AND EXCEPTIONS
This warranty shall apply only when the water heater is installed in accordance with local plumbing and building codes, ordinances and regulations,
the printed instructions provided with it and good industry practices. In addition, a temperature and pressure relief valve, certified by A.G.A. and
approved by the American Society of Mechanical Engineers, must have been installed.
a. This warranty shall apply only when the heater is used:
(1) at temperatures not exceeding the maximum setting of its thermostat;
(2) at water pressure not exceeding the working pressure shown on the heater;
(3) when operated free of the damaging effects of uncontrolled water hammer;
(4) when filled with potable water, free to circulate at all times;
(5) in a non-corrosive and non-contaminated atmosphere;
(6) with factory approved anode(s) installed;
(7) in the United States, its territories or possessions, and Canada;
b. Any accident to the boiler, any misuse, abuse (including freezing) or alteration of it, any operation of it in a modified form, or any attempt to repair
tank leaks will void this warranty.
c. This warranty is void if a device acting as a backflow prevention device (check valves etc.) is installed in the cold water supply the heater is
connected to, unless an effective method of controlling thermal expansion is also installed at the heater(s) and operational at all times. The relieve
4.SERVICE AND REPAIR EXPENSES
5.LIMITATIONS ON IMPLIED WARRANTIES
6.CLAIM PROCEDURE
7.DISCLAIMERS
valve installed on the heater is not an acceptable method.
Under the limited warranty the warrantor will provide only a replacement water heater or part thereof. The owner is responsible for all other costs.
Such costs may include but are not limited to:
a. Labor charges for service removal, repair or reinstallation of the water heater or any component part;
b. Shipping, delivery, handling, and administrative charges for forwarding the new heater or replacement part from the nearest distributor and
returning the claimed defective heater or part to such distributor.
c. All cost necessary or incidental for any material and/or permits required for installation of the replacement.
Implied warranties, including the warranty of merchantability imposed on the sale of this heater under state law are limited to one (1) year duration
fo rthe heater or any of its parts. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply
to you.
Any claim under the warranty should be initiated with the dealer who sold the boiler, or with any other dealer handling the warrantors products.
Ifthis is not practicable, the owner should contact:
U.S. CustomersCanadian Customers
A. O. Smith CorporationA. O. Smith Enterprises Ltd.
5621 W. 115th StreetP. O. Box, 310 - 768 Erie Street
a. The warrantor will only honor replacement with identical or similar water heater or parts thereof which are manufactured or distributed by the
warrantor.
b. Dealer replacements are made subject to in-warranty validation by warrantor.
NO OTHER EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF OF THE WARRANTOR WITH RESPECT TO THE HEATER OR
THE INSTALLATION, OPERATION, REPAIR OR REPLACEMENT OF THE BOILER. THE WARRANTOR SHALL NOT BE RESPONSIBLE FOR
WATER DAMAGE, LOSS OF USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE TO PERSONAL PROPERTY OR OTHER
CONSEQUENTIAL DAMAGE. THE WARRANTOR SHALL NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR DAMAGE
TO ANY PERSONS OR PROPERTY, WHETHER DIRECT OR INDIRECT, AND WHETHER ARISING IN CONTRACT OR TORT.
a. Some states do not allow the exclusion or limitation of the incidental or consequential damage, so the above limitations or exclusions may not
apply to you.
b. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Fill in the following for your own reference. Keep it. Registration is not a condition of warranty. The model and serial number are found on the heaters
rating plate.
Date Installed________________________Model No. __________ Serial No. ________________________________________________
Dealers Name _____________________________________________________________________Phone No. ________________________________________________
Dealers Address__________________________________________________City and State___________________________________________Zip Code _____________
FILL IN WARRANTY AND KEEP FOR FUTURE REFERENCE.
31
Page 32
A.O. SMITH WATER PRODUCTS CO., INC.
5621 W. 115TH STREET ALSIP, ILLINOIS 60803
PHONE: 1-800-433-2545 FAX: 1-800-433-2515
WWW.HOTWATER.COM E-MAIL: PARTS@HOTWATER.COM
32
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.