Commercial Gas
Water Heaters
CONSERVATIONIST® POWER DIRECT VENT
The BPD-80 tank-type commercial gas water heater is intended for light-duty
applications such as small office buildings and duplex apartment homes. The
BPD-80 features a power direct-vent design, with a factory-installed blower. The
blower permits sealed combustion direct-vent operation, with separate venting and
air intake runs from outside the structure. The BPD-80 offers installation versatility by
allowing venting and intake runs up to 50 equivalent feet, using 3” Schedule 40 PVC
pipe.
The power direct-vent design also eliminates the potential for performance
and safety problems caused by negative air pressure, a problem found in many
commercial applications with inadequate indoor ventilation.
DYNACLEAN™ DIFFUSER DIP TUBE
• Helps reduce lime and sediment buildup and
maximizes hot water output. Made from longlasting PEX cross-linked polymer
BLUE DIAMOND® GLASS COATING
• Provides superior corrosion resistance
compared to the industry-standard glasslining.
HOT SURFACE IGNITION
• Has a solid state ignition surface that does not
flutter or blow out.
• Provides increased reliability and efficiency
over spark ignition systems. Eliminates the
pilot and saves energy.
ENHANCED-FLOW BRASS DRAIN
VALVE
• Have a solid brass, tamper resistant, enhanced
flow, ball type, drain valve.
• Uses a standard female hose fitting that
allows for fast and easy draining during
maintenance.
• Designed for easy operation, this valve
includes an integral screwdriver slot that
features a ¼ turn (open/close) radius, which
not only permits full straight through water
flow but also a quick and positive shut off.
CSA CERTIFIED AND ASME RATED
T&P RELIEF VALVE
MAXIMUM HYDROSTATIC
WORKING PRESSURE 150 PSI
STANDARDS
• Design-certified by CSA International,
according to ANZI Z21.10.3 - CSA 4.3
standards governing storage-type water
heaters.
• Meets the thermal efficiency and standby
loss requirements of the U.S. Department of
Energy and current edition of ASHRAE/IESNA
90.1.
POWERED DIRECT VENTING
• Provides more venting flexibility.
• Roof or sidewall venting with 3” or 4” PVC,
CPVC, ABS or polypropylene.
• Allowable vent lengths of up to 125
equivalent feet make installation easy in any
situation.
QUIET MODULAR BLOWER
• Built-in safety device prevents pilot or main
burner operation if blower is not operating.
• Blower has 100/120V electrical system, with
maximum 2-amp draw.
3-YEAR LIMITED TANK / 1-YEAR
LIMITED PARTS WARRANTY
• For complete warranty information, consult
written warranty or contact A. O. Smith.
BPD-80
SERIES 210/211
©July 2015 A. O. Smith Corporation. All rights reserved.
www.hotwater.com | 800-527-1953 Toll-Free USA | A. O. Smith Corporation | 500 Tennessee Waltz Parkway | Ashland City, TN 37015
Page1 of 2
AOSCG11300

Commercial Gas
Water Heaters
C
A
B
G
D
F
H
E
DIMENSIONS
Model
Number
BPD-80
Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.
Units A B C D E F G H
Inches 70-5/8 61-1/2 26 33-7/8 11 13-1/4 53 15-1/4
cm 179 156 66 86 28 36 135 39 126 kg
Water
Connections
3/4” NPT 1/2” NPT
Connection
Gas
Approx.
Shipping
Weight
277 lbs
RECOVERY CAPACITIES
U.S. GALLONS/HRS. AND LITRES/HR. AT TEMPERATURE RISE INDICATED
Model
Number
BPD-80
Available in LP (Propane) gas
Can be installed up to 10,100 feet without alteration.
Input
Btuh kW
76,000 75 GPH 246 185 148 123 106 92 82 74 67 62 57 53
22.3 280 LPH 932 699 559 466 400 350 311 280 254 233 215 200
SAMPLE SPECIFICATION
Water Heater(s) shall be model BPD-80 AS MANUFACTURED BY A. O. Smith shall be of glasslined design, and gas-fired, equipped to burn _________ gas and
design certified by Underwriters Laboratories under Volume III tests for commercial heaters for delivery of 180°F water, and meets the thermal efficiency and
standby loss requirements of the U. S. Department of Energy and current edition of ASHRAE/IESNA 90.1. Heaters shall have an input rating of _________ and a
recovery rating of _________ GPH at a temperature rise of 100°F with a storage capacity of 75 gallons.
Unit(s) shall be direct-vent design, with an automatic blower-powered, two-pipe air intake and exhaust system communicating directly with the outside of
the building. The blower shall have a safety device that will not allow the operation of the main burners unless the blower is in operation. Unit(s) shall have a
combustion air passage that is internal to the outer jacket of the water heater other than the intake and exhaust connections at the top of the water heater.
Heater tank shall have a 3-year limited warranty against corrosion or sediment buildup as outlined in the written warranty. Fully illustrated instruction manual to
be included.
Approx.
Capacity
U.S.
Litres °C 17°C 22°C 28°C 33°C 39°C 44°C 50°C 56°C 61°C 67°C 72°C 78°C
Gals.
°F 30°F 40°F 50°F 60°F 70°F 80°F 90°F 100°F 110°F 120°F 130°F 140°F
For technical information, call 800-527-1953. A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
www.hotwater.com | 800-527-1953 Toll-Free USA ©July 2015 A. O. Smith Corporation. All rights reserved.
Page 2 of 2
AOSCG11300