A. O. Smith BLN-80 User Manual

Commercial Gas Water Heaters
CONSERVATIONIST® ULTRA-LOW NOX
CONSERVATIONIST® ULTRA-LOW NOX
The BLN-80 commercial gas water heater meets California Air Quality Management District Requirements for NOx emissions of 14 ng/j or 20 ppm. This model is equipped with a pre-wired, factory-mounted blower. This blower provides more efficient control of heat and helps ensure an adequate supply of make-up air. Prior to ignition, the control proves a working draft.
FACTORY-INSTALLED BLOWER
QControl proves draft prior to ignition QNo draft hood or barometric damper required QBlower is factory-mounted with a 6-foot power cord: requires 120V, 3 amp or less
electrical system connection
INTELLI-VENT™ GAS CONTROL
QEquipped with nearly indestructible silicon nitride hot surface ignitor QAdvanced electronics for precise control of water temperature QEasy-to-understand system diagnostics
RATED AS CATEGORY I APPLIANCE
QCategory I appliance: uses standard metal, single-wall or “B” type vent QMay be common vented with other Category I appliances
QVent connects directly to blower outlet
FULLY AUTOMATIC CONTROL SYSTEM
QAuto-reset gas shutoff device prevents excessive water temperature QAdjustable thermostat with 120°F - 180°F range
QGas pressure regulator
GLASSLINED TANK
Q Exclusive CoreGard™ anode rods with stainless steel core provides additional
corrosion protection
HANDHOLE CLEANOUT
QAllows easy access to tank interior for cleaning
CSA CERTIFIED AND ASME RATED T&P RELIEF VALVE
BLN-80
MAXIMUM HYDROSTATIC WORKING PRESSURE: 150 PSI
80% THERMAL EFFICIENCY
CODES AND STANDARDS
Q Design-certified according to ANSI Z21.10.3-CSA 4.3 standards governing storage-type
water heaters
QCalifornia Energy Commission QMeets the thermal efficiency and standby loss requirements of the U.S. Department of
Energy and current edition of ASHRAE/IESNA 90.1
QDesign-certified by Underwriters Laboratories QCertified for use on combustible flooring QComplies with SCAQMD Rule 1146.2 and other Air Quality Management Districts with
similar requirements of 14 ng/j or 20 ppm
THREE YEAR LIMITED TANK AND ONE YEAR LIMITED PARTS WARRANTY
QFor complete warranty information, consult written warranty or contact A. O. Smith.
OPTIONS
OPTIONAL LEG KIT TO MEET NSF STANDARD 5
QbPart #9006645005)
Intelli -Vent™ is a registered tradem ark of Emerson Electric Company
March 2013R
Page 1 of 2
AOSCG10801
Commercial Gas Water Heaters
TOP VIEW
*INSTALL IN ACCORDANCE WITH LOCAL CODES
Dimensions in Inches/centimeters
Model Units A B C D E F G H J K L M
BLN-80
INCHES
65-7/8 57-7/8 30-15/16 25-1/4 15-1/2 4 15-3/8 16 2-1/4 1 1/2 12-1/4
CM
167.22 145.23 78.58 64.14 38.6 10.2 40.0 40.6 5.71 NPT NPT 31.1
Recovery Capacities (based on 80% thermal efficiency)
Approximate
Model
Capacity
Gallons Litres Btu/Hr. kW/Hr.
BLN-80 74 280 75,100 22
Input Rating
Type
of
Gas
GPH
LPH
30°F/ 17°C
243 920
40°F/
23°C
182 688
50°F/ 28°C
145 549
60°F/ 33°C
122 460
Temperature Rise
70°F/
80°F/
39°C
44°C
104
91
392
344
90°F/ 50°C
81
306
100°F/
56°C
73
277
110°F/
61°C
66
251
120°F/
67°C
60
228
130°F/
72°C
56
213
Gas and Electrical Characteristics
Model
Type of Gas Inches W.C. kPa Volts/Hz Amperes
BLN-80 Natural 4.0 1.12 120/60 <5
Natural gas water heater(s) shall be A. O. Smith BLN ________________ or equal, with a storage capacity of __________ gallons, an input rating of ________BTUs per hour, a recovery rating of ______GPH at 100°F rise and a maximum hydrostatic working pressure of ________ psi. Water heaters(s) shall be supplied with a factory-installed blower and 6-foot power cord; control will prove draft prior to ignition. Glasslined water heater(s) shall also be protected against electrolytic corrosion by a factory-installed A. O. Smith CoreGard™ anode rod. In addition, water heater(s) shall be equipped with: 1) An Intelli-Vent™ gas control system with silicon nitride hot surface ignitor, advanced electronics for precise control of water temperature, and easy-to-understand system diagnostics. 2) An auto-reset gas shutoff device, a gas pressure regulator, CSA Certified and ASME rated T&P relief valve. 3) Certification by Underwriters Laboratories under Volume III tests for commercial water heaters for delivery of 180°F water. 4) Design certification according to ANSI Z21.10.3 - CSA 4.3 standards governing storage-type water heaters. 5) Meets the thermal efficiency and standby loss requirements of the U.S. Department of Energy and current edition of ASHRAE/IESNA 90.1 and meets Ultra-low NOx emissions of 14 ng/j or 20 ppm. 6) Have a 3-year limited tank and 1-year limited parts warranty against corrosion as outlined in the written warranty.
Manifold Pressure Electrical Characteristics
SUGGESTED SPECIFICATION
140°F/
78°C
52
199
For Technical Information and Automated Fax Service, call 800-527-1953. A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
www.hotwater.com
Page 2 of 2
AOSCG10801
Loading...