A.O. Smith BFM 50, BFM 30, BFM 80 User Manual

Page 1
MODELS
BFM 30 BFM 50 BFM 80
INSTALLATION INSTRUCTIONS AND
USERS MANUAL
UNITED KINGDOM
CLOSED COMBUSTION WA TER HEA TER
Page 2
INTRODUCTION
A. O. SMITH DOES NOT ACCEPT ANY RESPONSIBILITY FOR GUARANTEE, SERVICE PROVISION AND/OR PRODUCT LIABILITY IN CASE OF UNAUTHORISED PRODUCT MODIFICATION OR REPAIRS.
2
Page 3
CONTENTS PAGE
1. GENERAL
1.1 Water heater description ..................................................................................................................... 5
1.2 Technical safety equipment ................................................................................................................ 6
1.2.1 Gas control .......................................................................................................................................... 6
1.2.2 Control box...........................................................................................................................................6
1.2.3 Burner automat ................................................................................................................................... .6
1.2.4 Air proving switch................................................................................................................................. 6
1.2.5 Gas control valve ................................................................................................................................. 6
1.3 Technical description ..........................................................................................................................8
1.3.1 Measurements ....................................................................................................................................8
1.3.2 Technical data ................................................................................................................................... 10
2. FOR THE INSTALLER
2.1 Installation instructions ..................................................................................................................... 11
2.1.1 Installation .........................................................................................................................................11
2.1.2 Water connection ............................................................................................................................... 1 1
2.1.3 Condensation drain...........................................................................................................................14
2.1.4 Gas connection ................................................................................................................................. 14
2.1.5 Flue connection (concentric) ............................................................................................................. 1 4
2.1.6 Electrical connection ......................................................................................................................... 16
2.2 Turning the water heater on ..............................................................................................................1 9
2.2.1 Filling the water heater ......................................................................................................................1 9
2.2.2 Turning the water heater on .............................................................................................................. 19
2.2.3 Setting up the pilot flame...................................................................................................................1 9
2.3 Turning the water heater off............................................................................................................... 19
2.4 Usage/temperature control ...............................................................................................................19
2.5 Checking the gas pressures ............................................................................................................ 20
2.6 Conversion to another gas ................................................................................................................2 1
2.7 Maintenance ...................................................................................................................................... 2 2
2.8 Anode ................................................................................................................................................. 22
2.9 Descale procedure............................................................................................................................22
2.10 Condensation....................................................................................................................................23
2.11 Spare parts ........................................................................................................................................ 23
3. FOR THE USER
3.1 Instructions for use ............................................................................................................................ 2 4
3.1.1 Warning ............................................................................................................................................. 24
3.1.2 Filling the water heater ......................................................................................................................24
3.1.3 Turning the water heater on .............................................................................................................. 24
3.2 Usage ................................................................................................................................................2 4
3.3 Turning the water heater off...............................................................................................................2 4
3.4 Maintenance ......................................................................................................................................2 4
4. FAULT FINDING AND CORRECTION
4.1 Fault finding userl .............................................................................................................................. 2 5
4.2 Fault finding installer ......................................................................................................................... 26
4.3 Detailed fault finding installer ............................................................................................................ 27
5. WARRANTY
5.1 Guarantee in general ........................................................................................................................ 3 1
5.2 Guarantee of the tank ........................................................................................................................31
5.3 Conditions for installation and use ................................................................................................... 31
5.4 Exclusions ......................................................................................................................................... 31
5.5 Range of the guarantee .....................................................................................................................3 1
5.6 Claims ............................................................................................................................................... 3 1
5.7 No other guarantee or warranty either expressed or implied is
made on behalf of A.O. Smith Water Products Company.................................................................3 1
3
Page 4
Figure 1
1) TOP-BOX 9) VENTILATION FAN
2) AIR PROVING SWITCH 10) ANODE
3) TEMPERATURE REGULATOR 11) FLUE TUBES ON/OFF SWITCH 12) FLUE BAFFLE RESET-KNOB 13) DIAPHRAGM
4) BURNER CONTROLLER 14) INSULATION
5) GAS VALVE 15) BURNER
6) MANIFOLD / INJECTORS 16) AIR DIFFUSION PLATE
7) PILOT BURNER 17) CONDENSATE DRAIN
8) HORIZONTAL AIR INLET
4
Page 5
1. GENERAL
1.1 Description of the appliance
Construction and fitting out of the storage appliance comply with the European Standard for gas fired hot water storage appliances for sanitary use (EN89). The appliance thereby satisfies the requirements of the European Directive for Gas Appliances, and is therefore entitled to bear the CE mark.
The BFM appliance is an enclosed appliance with a fan in the air inlet ( appliance category C13 or C33 ). The appliance is designed for a concentric flue configuration. A diaphragm, across which the pressure difference can be measured, is fitted in the air inlet system. When the control thermostat calls for heat, the burner control unit carries out a zero position check. The fan is subsequently switched on and, at a signal from the pressure difference switch, the pre-ventilation period (minimally 30 seconds) commences. Following the pre-ventilation period the burner control unit switches on the ignition transformer whereby the first gas valve (the pilot) opens. On receiving an ionisation signal from the ignition burner, the second (main burner) gas valve opens. The appliance is now in operation.
Technically this appliance falls into gas category II
; the appliance is therefore suitable for natural
2L3P
gas as well as propane and butane gases. The storage appliance is suitable for working pressures to 8 bar. A connection is provided for the optional fitting of an extra safety feature, the temperature and pressure valve. The interior of the tank is enamelled for corrosion protection, and a number of magnesium anodes are fitted to the tank for the same purpose.
A thick polyurethane insulating layer between the tank and its steel casing prevents unnecessary heat loss. If the storage appliance is completely filled with water it is under continual mains pressure. When hot water is tapped off the appliance, cold water is immediately introduced. Turbulence strips are placed in the fire tu­bes for the efficient transfer of heat. The flue gases pass their heat to the water by conduction and radiation. The flue gases are led to the flue via the top box. The burner bed consists of a number of bar burners. An injector is screwed into the manifold ahead of each burner, which ensures correct mixing of gas and primary air through injection into the burner inlet venturi. Secondary air is drawn between the bar burners. An air distribution plate, which also functions as a radiant heat shield, is fitted below the burners. Any condensation water produced is captured beneath the combustion chamber and led away via a siphon (see illustration 1).
5
Page 6
1.2 Technical safety equipment
1.2.1 Gas control
The water heaters are equipped with a gas control
valve which regulates the flow of gas to the burner. The combination gas control is equipped with a safety valve, gas control valve, pilot safety valve and burner control (on a standard natural gas setting)
1.2.2 Control box
For safety purposes, water heaters are always fitted
with three thermostats: a control thermostat, a high-limit thermostat and an overheat thermostat.
The desired water temperature is set with the control
thermostat. To protect against freezing, the control thermostat is also fitted with frost protection which ignites the burner when the water temperature drops to
o
C, irrespective of the thermostat’s temperature
20 setting. The overheat thermostat prevents the water reaching too high a temperature.
Should both control and high-limit thermostats
malfunction, the overheat thermostat will automatically shut down the water heater.
The control thermostat can be set at settings 1-4
(approx. 40°C to 73°C). The frost protection ignites the burner if the water temperature drops below 20°C. The switch temperature of the high-limit thermostat is 84°C; the overheat thermostat cuts in at 93°C. The sensor for the control/frost thermostat is located at the level of the control switch; the sensors for the high-limit and overheat thermostats are located near the top of the water heater.
The control box is fitted with an ON/OFF switch (I/0).
At setting I, the gas control operates on the basis of heat demand from the control thermostat. At setting 0 the water heater is switched off. The burner will only ignite on the basis of heat demand from the frost protection.
When the control thermostat calls for heat, the water
heater checks all controls are in the off position. Power is then switched to the ventilation fan. Immediately the air pressure switch opens. The purge cycle starts. This runs for between 30 and 60 seconds after which the safety valve opens and the spark generator is operated.
Gas flows to the pilot burner where it is ignited by the
spark generator. The ionization probe now detects the flame, switches off power to the spark generator and opens the main gas valve.A softlite staged ignition control prevents explosive ignition by allowing a small percentage of total gas rate into the combustion chamber initially followed by the full rate when combustion is established. When the water temperature reaches the set point the water heater is turned off.
If the flame extinguishes whilst in operation both the
safety (pilot) valve and the gas valve will close immediately. If the control thermostat is still calling for heat the burner automation will repeat the ignition procedure.
continues to work.
- An interlocking of the burner automation can be cancelled out by pressing the reset knob. If the procedure does not succeed immediately, wait at least 15 seconds before pressing the interlocking knob again.
If the flame detection falls out during normal operation, the burner automation will automatically repeat its ignition procedure. As long as a flame is detected within the safety period of 50 seconds, the automation will continue to repeat the ignition proce­dure.
As soon as the water temperature has reached the set value, the burner automation will close the gas valves.
The control column has a potential-free contact for external error message.
1.2.3. Ventilation fan
The ventilation fan is installed in the top-box. When heat is required the ventilation fan is switched on by the burner automation. The fan switches off when the main burner has extinguished. The fan can be removed from the top box via the access panel.
1.2.4 Air proving switch
The air proving switch ensures that there is sufficient air flow for the safe operation of the water heater. If the airflow falls below the preset value this will be detected by the air proving switch and the gas supply to both the ignition and main burners will be closed. The air proving switch is preset and cannot be adjusted.
Air proving switches BFM-units
Unit Pstart Poff
(Pa) (Pa)
BFM 30 250 220
BFM 50 250 220
BFM 80 230 205
The air proving switch must always be fitted with the connection points downwards! The air pressure differential switch must always be fitted with the connection points at the bottom, while the pipe with the letter H must be connected to the point P1. Pipe L goes to connection P2.
1.2.5 Gas control
The water heaters are provided with a gas valve that regulates the gas supply to the burners.
The gas control has a safety valve and a gas valve and hence has a B/D-configuration. The position of both valves can be regulated by the burner automation. To ensure improved ignition the gas control valve opening mechanism is fitted with a delay (softlite).
- If no flame is detected within the safety time of 50 seconds, the burner automation will interlock and the reset knob will light up.
- As long as the air proving switch does not operate (remains closed), the burner automation will remain in the waiting position, while the ventilation fan
6
Page 7
Figure 2 - Positioning ventilation
Figure 3 - Differential pressure switch
7
Page 8
1.3 Technical description
1.3.1 Measurements
See figure 4
Size BFM 30 BFM 50 BFM 80
A 1995 1995 2020
B 1795 1795 1820 C 600 600 600 D 520 520 525 E 600 600 590
F 1640 1640 1655 G 1360 1360 1360 H 630 630 625 K 710 710 710
L 1000 1000 1000 M 755 755 755 N 80/125 100/150 130/200
1 Cold water inletRP1½
2 Hot water outletRP 1½
3 Gas valve RP ¾
4 Drain valve ¾"-14 NPT
5 T&P-connection (temperature- and pressure valve) 1"-14 NPT
All dimensions in mm, rounded up to the nearest 5 mm.
8
Page 9
Figure 4
IMD-0057-R0
9
Page 10
1.3.2 Technical data
Heater category:II
2H3+
Description Unit BFM 30 BFM 50 BFM 80
DATA NATURAL GAS G 20
Nominal gas inlet pressure mbar 20 20 20 Burner pressure mbar 12.5 12.5 12.5 Input kW 29 47 75 Output to water kW 27 42 68 Gas consumption* m3/h 3.0 4.7 7.9 Diameter main injector m m 2.60 2.50 2.70 Diameter injector ignition burner mm 0.56 / 0.41 0.56 / 0.41 0.56 / 0.41 Heating time T=45°C mi n 35 25 12
DATA PROPANE/BUTANE G 30 - G 31 G30 G31 G30 G31 G30 G31
Nominal gas inlet pressure mbar 30 37 30 37 30 37 Input kW 29 28 46 44 75 71 Gas consumption kg/h 2.3 2.1 3.6 3.3 5.8 5.3 Diameter main injector m m 1.45 1.40 1.50 Diameter injector ignition burner m m 0.25 0.25 0.25
GENERAL
Storage capacity litre 309 298 2 53 Number of bar burners - 3 5 7 Number of anodes - 2 2 4 Number of flue tubes - 5 7 16 Water connections - Rp11/2 Rp11/2 Rp11/2 Gas connection - Rp3/4 Rp3/4 Rp3/4 Drain connection - 3/4" - 14 NPT 3/4" - 14 NPT 3/4" - 14 NPT Anode - 3/4" - 14 NPT 3/4" - 14 NPT 3/4" - 14 NPT Connection T&P-plug** - 1” - 14 NPT 1” - 14 NPT 1” - 14 NPT Maximum working heat bar 8 8 8 Empty weight kg 27 0 290 3 50
* Gas usage at 1013,25 mbar and 15 °C. ** For a leak-tight connection European coupling pieces with pipe screw-thread according to ISO 228/1 or ISO 7/1 can be
used on the NPT-connection nipples.
10
Page 11
2. FOR THE INSTALLER
If possible, use a trolley or fork-lift truck to move the water heater. Always move the water heater in an upright position.
2.1 Installation instructions
The following distances should be observed:
- Sides of the water heater: 100 cm
(free space for the accessibility of the hand holes)
- Rear of the water heater: 15 cm
- Around top-box and concentric pipe: 15 cm
- Front of the water heater: 100 cm
(free space to take out bar burners)
2.1.2 Water connections
A.O. Smith water heaters are suitable for connection to vented, unvented and pumped pressurised systems. In each case appropriate valves and fittings should be used to ensure the system complies with the requirements of the water by laws, and appropriate building regulations.
When fitting it is essential the rules of 'good practice' are applied at all stages of installation.
Vented systems
If the water heater is to be connected to a cold feed tank or cistern the hot water supply pipe must include an open vent which discharges over the cold feed cistern. The cold feed cistern must have an actual capacity of greater volume than the hourly recovery rate of the water heater(s) which it supplies.The minimum actual capacity is 50 gallons or 227 litres. See diagram 5.
2.1.1 Installation
Installation should be carried out in accordance with all local authority and building regulations, local water authority and fire regulations and the following British standards: British Gas Publication UP1 and UP2. BS 5482 part 1 1979
part 2 1979
part 3 1979 BS 6644 BS 6700 BS 6798
A.O. Smith water heaters are tested to a maximum pressure of 12 bar and a maximum working pressure of 8 bar.
Dead legs on a hot water installation are undesireable. Where possible they should be avoided. Where the inclusion on the system of a dead leg is unavoidable the following restrictions should be applied:
- for pipes not exceeding 19 mm. inside diameter;
maximum lengh of dead leg permitted 12.0 metres;
- for pipes exceeding 19 mm. but not exceeding 25
mm. inside diameter; maximum length of dead leg
7.5 metres;
- for pipes with an inside diameter exceeding 25 mm.
maximum dead leg 3.0 metres.
Diagram 5 - Typical UK vented system
IMD-0065
1) Gas cock
2) Stop valve
3) Three way vent valve
4) T&P valve
5) Non-return valve
6) Circulation pump
7) Drain valve
A) Gas supply B) Hot Water C) Cold Water D) Overflow
E) Return circulation
11
Page 12
Depending on the length and insulation of the water piping and the water demand frequency, it may be necessary to install a circulation system on the drain cock. The return pipe of the circulation piping can be fitted on the top of the drain cock after the sealing plug has been removed (see figure 6).
Unvented
To install an A.O. Smith water heater on an unvented cold water supply system a kit of valves and fittings listed by the water research centre and complying with part G3 of the current building regulations and BS 7206 should be used. Installation should be carried out generally as shown on diagram 7. Kits are available from A.O. Smith or our distributors.
1) Gas cock
2) Stop valve
3) Expansion vessel
4) T&P valve
5) Non-return valve
6) Circulation pump
7) Drain valve
8) Pressure limiting valve
9) Expansion valve
Figure 6
A) Gas supply B) Hot water C) Cold water D) Hot water supply E) Return circulation
Diagram 7 - Connection diagram (unvented system)
12
IMD-0066-R0
Page 13
Depending on the water demand pattern (e.g., small amounts frequently), it may be necessary to circulate the water in the water heater to prevent temperature stratification. Therefore, we recommend that a circulation system is installed in the event of such demand patterns (see figure 8). Kits are available from A.O. Smith or our distributors.
1) Pump (type: Grundfos
UP 20-15 N150, or similar)
2) Non-return valve
3) Gate valve
4) Drain valve
5) Gas valve
A) Cold Water B) Hot Water C) Return circulation pipe D) Gas supply
Figure 8 - Connection diagram including destratification circulation system
IMD-0059
13
Page 14
2.1.3 Condensation drain
In order to guarantee the correct operation of the
water heater, the condensate drain of the water heater must open into the sewer interrupted, provided with an extra stench trap or siphon. A condensation drain section fixed to the water heater should be fitted under the slope. The condensate drain of the water heater must never be sealed.
2.1.4 Gas connection
The gas installation may only be carried out by a
registered installer and in accordance with the relevant local authority and building regulations and followint British standards.
2.1.5 Flue connections (concentric)
The combined flue discharge and air intake tubes
(concentric) should always be assembled with a rising slope towards the flue terminal, and in accordance with the table below.
IMD-0060
figure 9
- Wall configuration (see figure 9)
Type: M2000 MDV SE Manufacturer: Meulink & Grol Pipe material flue tube: Thick-walled aluminium with lip ring seal. Pipe material air supply: Thin-walled galvanised steel plate. Pipe diameter BFM 30: Ø 80 / 125 mm
BFM 50: Ø 100 / 150 mm BFM 80: Ø 130 / 200 mm
Angle: 90° (2 max.)
Flue configuration / horizonal discharge BFM-unit
Measurement BFM 30 BFM 50 BFM 80
min. max. min. max. min. max.
A 0 7000 0 7000 0 7000
B 0 7000 0 7000 0 7000
A+B < 7000 < 7000 < 7000
All measurements are in mm. The following applies for the horizontal pipe: slope of at least 5 mm per metre of pipe to the water heater. NB. Measurements A + B are the total permissible dimensions of the flue, i.e. when A = 1 metre, B = 6 metres (total 7 metres) or A = 4 metres, B = 3 metres (total 7 metres).
14
Page 15
- Roof discharge (see figures 10 and 11).
Type: M2000 DDV SE HR/VR Manufacturer: Meulink & Grol Pipe material flue tube: Thick-walled aluminium with lip ring seal. Pipe material air supply: Thin-walled galvanised steel plate. Pipe diameter BFM 30: Ø 80 / 125 mm
BFM 50: Ø 100 / 150 mm BFM 80: Ø 130 / 200 mm
Angle: 45°/90° (max 2)
Flue configurations roof discharge BFM-unit
Measurement BFM 30 BFM 50 BFM 80
min. max. min. max. min. max.
A 0 7000 0 7000 0 7000
B 0 7000 0 7000 0 7000
A+B < 7000 < 7000 < 7000
All measurements are in mm.
The following applies for the horizontal pipe: slope of at least 5 mm per metre of pipe to the water heater. A maximum of 2 bends (45° or 90°) may be used with
these flue configurations. These will each equate to 1 metre of flue length.
The maximum flue configuration is therefore 7000 mm pipe, 2 bends (45°/90°) and a lead-through set.
IMD-0061
Figure 10 and 11 - Roof discharge.
IMD-0062
15
Page 16
2.1.6 Electrical connection
All electrical connections must be carried out by a
registered electrical contractor to the relevant regulations.
The BFM must be connected to a supply voltage by
means of a permanent electric connection and have a feeder cable not less than 3 x 1,0 mm².
Supply voltage Supply network Mínimum fuse
frequency required
220/240 VAC 50 Hz 1 A
The electrical diagram of the BFM-heater and the connections in the control-column are shown in figures 12 and 13.
Electrical connection diagram BFM
(see figure 12) A) Jacket B) Transformer 230V/238V/2VA C) Air proving switch D) EMC single phase filter E) RESET knob F) Thermostat frost G) Thermostat regulation H) Switch ON/OFF K) Thermostat overheat 93°C L) Thermostat high limit 84°C M) Automatic burner controller N) Plastic connector strip P) Earth terminal block S) Relais
Colour-code cables:
1 Blue 2 Brown 3 Yellow/green 4 Red 5 White 6 White/orange 7 White/violet 8 Black
9 Black/green 10 Black/red 11 Black/white
16
Page 17
IMD 0055 R1
Figure 12 - Electrical connection diagram BFM
17
Page 18
Figure 13 - Connection diagram control-column.
IMD-0063
D) Transformer 230 E) Air proving switch F) EMC single phase filter G) RESET knob H) Thermostat frost K) Thermostat regulation L) Switch ON/OFF
18
M) Thermostat overheat N) Thermostat high limit P) Automatic burner controller R) Relay X) Plastic connector strip Y) Earth terminal block
Page 19
2.2 Turning the water heater on
2.2.1 Filling the water heater
1. Assemble the drain-off tap and check that it is closed.
2. Open the cold water tap to the water heater and open al l taps on hot water outlet points to vent them. The heater is filled as soon as cold water pours out of all outlet points.
3. Close all taps at hot water draining points. The heater is now under water supply pressure. At this pressure, the relief valve if fitted may not release water.
2.2.2 Turning the water heater on
1. Check whether the water heater is filled with water an dwhether the gas pipe to the water heater is open.
2. Vent the gas pipe by opening the pressure gauge nipple at the inlet side of the gas valve. Close the pressure gauge nipple as soon as the gas pipe has been vented.
3. Turn the temperature control knob fully to the left.
4. Turn on- the supply voltage by turning the main switch. NOTE: if the frost-thermostat is calling for heat the burner automation will immediately start its ignition procedure.
5. Turn the ‘I/O’-switch on the column to the ‘T’ position. The control lamp in the switch will light.
6. Turn the temperature control switch to the desired position, preferably position 3 (approximately 60°C). The burner will ignite; the water heater will now work automatically.
7. Check the standing pressure with a manometer which can be connected to the pressure gauge nipple. Check that the working pressure is set to the correct level (see table page 10).
The position of the temperature control knob
coincides with the following temperatures:
Position 1 = app. 40°C Position 2 = app. 50°C Position 3 = app. 60°C Position 4 = app. 70°C
At high temperatures, more calcium precipitation is caused in the water heater. Moreover, the standby­losses of the water heater are greater with higher temperatures. It is recommended to set the control­thermostat at approximately 60°C. For reasons of security, the water heater is provided with a high limit and safety thermostats. The high limit thermostat is an extra control set at 80°C and will operate in the event of excess temperature within the water heater.
If the safety thermostat operates, the ‘RESET’ button must be pressed after the water has cooled down. The water heater will operate again in the usual manner.
2.2.3 Setting up the pilot flame
The pilot flame has been adjusted in the factory and
does not have to be checked.
2.3 Turning the water heater off
For short periods:
1. Turn the temperature knob fully to the left and turn the ‘I/O’-switch in the ‘O’-position.
For longer periods:
1. Switch off the supply voltage.
2. Close the gas tap in the supply line.
3. Close the water supply tap.
4. If there is danger of frost, drain the water heater.
2.4 Usage/temperature control
The water temperature is controlled via the temperature regulator. If the temperature in the water heater falls below the set value, the temperature regulator will call for heat. The burner automation will operate firstly the ventilation fan for its purge cycle, then a spark will ignite the pilot burner. The softlite control then ignites the main burner.
19
Page 20
2.5 Checking the gas pressures
The nominal load has been set at the correct value in
the factory. A further check of the pressure should be carried out during the commissioning of the unit.
A dangerous situation can occur if the following
instructions are not followed carefully. Setting the nominal load is possible as there is a burner pressure control. If you wish to adjust the burner pressure the following procedures must be followed:
1. Switch off main power by turning the I/O switch to ‘0’ position.
2. Connect the U-tube manometer to pressure nipple B.
3. Switch on main power and ensure temperature control is calling for heat.
4. Wait until water heater is firing.
5. Check pressure against table on page 10 for relevant gas and adjust at main gas valve.
6. Switch of main power as no. Y.
7. Remove U-tube manometer and close pressure nipple.
8. Switch on main power and test for gas tightness and correct operation, (Figure 14).
Figure 14 - Checking the gas pressures
20
Page 21
2.6 Conversion to another gas
Important: Install a gas valve suitable for the type of gas to be used.
If the water heater has to function on a gas category (LP or natural gas) other than the gas set as standard (ex works), the water heater must be converted to the applicable gas category with the associated conversion kit(s).
Only an accredited installer may convert the heater.
All the injectors of the main burner bars and the injector of the ignition pilot must be replaced. Regurlary natural gas units do have a burner pressure regulator, but LP-gas units do not. The burner pressure regulator on the gas control must be removed when converting the heater for use on LP­gas (if present). The burner pressure regulator must be fitted on the gas control when converting to natural gas (if required) The table with technical data shows which injectors must be fitted for the gas category in question.
Procedure:
1. Shut the water heater down; close the main inlet gas valve and switch of the electricity supply at the main switch;
2. Remove the burner tray including the gas valve: a. remove the screws of the burner tray housing, b. loosen the wiring of ingition and ionisation pen
on the burner controller, c. loosen the gas control cable, d. dismount the gas supply to the gas valve;
3. Remove the burner tray from underneath the heater;
4. Replace the main injectors and the injector of the ignition burner. Use the table with technical data to check that the diameter of the injectors is correct; Converting from natural gas to LP-gas:
5. a. remove the burner pressure regulator on the
gas control,
b. mount the flat covering plate with sealing
provided in the conversion kit, c. see figure 15; Converting from LP-gas to natural gas: a. remove the flat covering plate with sealing on the
gas control, b. mount the burner pressure regulator on the gas
valve, c. See figure 16;
6. Mount the burner tray;
7. Reconnect the wiring and gas supply to the gas valve;
8. Open the main inlet gasvalve;
9. Check the gas inlet pressure;
10. Switch on the electricity supply at the main switch;
11. Commision the water heater;
12. Adjust the burner pressure to the value as indicated in the technical data;
13. Check the soundness;
14. Check the operation of the heater;
15. Fix the conversion sticker from the conversion kit below the rating plate to the heater, so that is clear on which gas category the heater operates.
AOS 0546
Figure 15 - mounting covering plate with sealing on the gas valve
AOS 547
Figure 16 - mounting burner pressure regulator on the gas valve,
21
Page 22
2.7 Maintenance
The water heater must be checked and cleaned regularly (at least once a year) by an accredited installer, so that proper operation is guaranteed. The bar burners, control and safety valves must also be checked. (see figure 17).
2.8 Anode
The life of the anode is determined by the quality and the quantity of water flowing through the water heater. Therefore, we recommend that the anode is checked regularly - preferably simultaneously with an internal inspection of the enamelled tank. In order to determine the frequency with which the anodes must be replaced, the water side of the boiler must be checked three months after installation. The anodes must be replaced if more than 50% has dissolved at any point on their length.
Procedure:
1. Shut off the cold water supply tap.
2. Completely empty the water heater by means of the
draw-off tap. Remember to ventilate the water heater.
3. Remove the sealing plates at the hand holes on the
outer cover of the water heater.
4. Open the hand holes and inspect the anodes. In
order to guarantee a water-tight seal at the hand holes, the rubber O-rings must be replaced (see figure 18).
If the anodes need replacing:
1. Disassemble the concentric flue tube.
2. Disassemble the electrical connection of the
ventilation fan on the top-box.
3. Loosen the fastening bolts of the top-box.
4. Remove the top-box, the positioning of the anodes
will now become visible (see figure 18).
5. Loosen the anodes with suitable tools and replace
with new ones. NOTE: the anodes must be in contact with the tank (metal on metal). For if the anodes and tank are electrically separated (as a result of the sealant used), the anode cannot perform its function. This can shorten the life-span of the tank.
6. Assemble everything in reverse order.
7. Fill the water heater.
2.9 Descale procedure
Calcium deposition depends on the type of water and the demand. In addition, calcium deposition increases at high water temperatures. A temperature setting of 60°C is recommended, which will keep calcium deposition to a minimum.
Inspection hatches are located on the right and left sides for inspecting and deliming the tank. The hand holes can be reached via the covering plates on the outer jacket.
Figure 17
Empty the water heater before opening the inspection hatches. Deliming must be executed with the correct tools. Consult the supplier of the water heater or the installer on this matter. In order to guarantee a water-tight seal of the hand holes, the rubber O-rings in the hand holes must be replaced (see figure 17).
22
Figure 18 - Maintenance anodes
Page 23
2.10 Condensation
If the water heater has been filled with cold water or if the hot water usage has been very high, normally condensation of the flue gasses will occur on the cold sides of the combustion chamber and the flue tubes. The water drops will fall on to the burner bed which can cause a hissing sound. This is normal and will disappear as soon as the water heater has reached its operating temperature again.
2.11 Spare parts
To order spare parts, it is important to state the water heater type, model and the complete serial number.
Figure 19 - Maintenance anodes
23
Page 24
3. FOR THE USER
3.3 Turning the water heater off
3.1. Instructions for use
Installation and commissioning of the water heater should only be undertaken by a registered installer.
3.1.2 Filling the water heater
1. Assemble the drain-off tap and ensure it is closed;
2. Open the cold water tap to the water heater and open al l taps on hot water drain-off points to vent them. Theheater is filled as soon as cold water pours out of all drain-off points;
3. Close all taps at hot water drain-off points. The heater is now under water supply pressure. At this pressure, the relief valve if fitted may not release water.
3.1.3 Turning the water heater on
1. Check that the water heater is filled with water and that the gas pipe to the water heater is open;
2. Turn the temperature control knob fully to the leftl;
3. Turn on( the supply voltage by turning the main switch. NOTE: if the frost-thermostat has been turned on, the burner automation will immediately start its ignition procedure);
4. Turn the ‘I/O’-switch on the column in the ‘T’ position. The control lamp in the switch will now light;
5. Turn the temperature control switch in the desired position, preferably position 3 (approximately 60°C). The ventilation fan will start. the water heater will ignite and work automatically.
For short periods:
1. Turn the temperature knob fully to the left and turn the ‘I/O’-switch in the ‘O’-position.
For longer periods:
1. Switch off the supply voltage;
2. Close the gas tap in the supply line;
3. Close the water supply tap;
4. If there is danger of frost, drain the water heater.
3.4. Maintenance
The water heater must be checked and cleaned regularly (at least once a year) by an accredited installer, so that proper operation is guaranteed. The bar burners, the pilot burner and the control and safety valves must also be checked.
3.2 Usage
The water temperature is controlled via the temperature regulator. If the temperature in the water heater falls below the set value, the temperature regulator call for heat. The burner automation will operate firstly the ventilation fan for its purge cycle, then a spark will ignite the pilot burner. The softlite control then ignites the main burner.
The temperature is indicated by the position of the temperature dial:
Position 1 = app. 40°C Position 2 = app. 50°C Position 3 = app. 60°C Position 4 = app. 70°C
At high temperatures, more calcium precipitation is caused in the water heater. Moreover, the standby­losses of the water heater are greater at higher temperatures. It is recommended that the control­thermostat be set at approximately 60°C. For reasons of security, the water heater is provided with a high limit and safety thermostats. If the high limit thermostat operates, the burner will not fire until the water has cooled sufficiently to allow the thermostat to automatically reset. The water heater will then return to the control of the temperature regulator.
If the safety thermostat operates due to high temperature the ignition sequence must be repeated after resetting the control.
24
Page 25
4. FAULT FINDING
4.1 Fault finding USER
No or insufficient
hot water.
Check whether the
electricity
is turned on.
Check whether the
gas supply is turned
on.
Does the
ON/OFF switch light
up?
no
Check if
ON/OFF switch in
position 1?
no
Put
ON/OFF switch in
position 1?
yes
yes
Does the
RESETswitch light
up?
yes
Push RESET switch up
to three times
Is the
water heater in
operation?
yes
yes
Reduce the water use
or increase the
control thermostat.
yes
Is the
water heater in
operation?
no
Problem
solved
Is the
water heater in
operation?
no
yes
Problem
solved
no
Consult your installer.
25
Page 26
4.2 Fault finding INSTALLER
Check gas connection
and the electricity
supply make sure that
they are switched on.
Problem
solved
yes
Does the
ON/OFF switch
light up?
no
Check if
ON/OFF switch is in
position 1?
no
Put
ON/OFF switch in
position 1.
yes
Does the
RESET switch
light up?
yes
Push the
RESET button
up to three times
no
Is the
water heater in
operation?
no
26
no
Is the
water heater in
operation?
no
yes
Is the
water heater in
operation?
Problem
solved
See detailed fault finding
no
yes
Problem
solved
Page 27
4.3 Detailed fault finding INSTALLER
Check voltage present at connection 1.
yes
Check
voltage present
after FILTER
yes
Check
voltage present at
gate 3 ON/OFF
switch
yes
Check
voltage present
at gate 11 and 12
CONTROL
THERMOSTAT.
no
no
no
no
Reinstate voltage supply
Ensure connections correct, if yes replace FILTER
Ensure connections correct, if yes replace ON/OFF switch
1. Check if controle thermostat is closed
2. Ensure connections correct.
3. If yes replace CONTROL THERMOSTAT.
yes
27
Page 28
yes
Check
voltage present at
GATE 12 MAXIMUM
THERMOSTAT?
yes
Check
voltage present at
GATE 1 BURNER
AUTOMATION
S4560D 1150?
yes
Check
voltage present at
GATE 8 BURNER
AUTOMATION
yes
Ensure connections correct,
no
if yes replace
MAXIMUM THERMOSTAT
Ensure connections correct,
no
if yes replace
BURNER AUTOMATION
no
Replace
BURNER AUTOMATION
Is VENTILATING FAN
in operation?
yes
Check
voltage present at
GATE 7, BURNER
AUTOMATION
yes
Check
voltage present at
GATE 7, BURNER
AUTOMATION
yes
Ensure connections correct,
no
if yes replace
VENTILATING FAN
Check
no
voltage present at
GATE 3 AIR PROVING
SWITCH
Ensure connections correct
no
Replace
BURNER AUTOMATION
Check
no
voltage present at
GATE 1 AIR PROVING
SWITCH
DISCONNECT
GAS SUPPLY
Disconnect the pipe air supply by removing the elbow at the rear bottom. Measure pressure at hose H at the column.
yesyes
yes
Ensure connections
no
correct,
if yes replace
BURNER
AUTOMATION
28
Page 29
yes
Check
voltage present at
GATE 12 ECO
yes
Check
voltage present at
GATE 11 BURNER
AUTOMATION
yes
no
no
Ensure connections
correct, if yes replace
ECO
Ensure connections
correct
Pressure
H higher then
300 PA?
yes
Measure pressure at
hose
H at the column
Pressure L less
then 0 PA?
yes
Check exhaust system on blockings if the exhaust system is open, replace AIR
PROVING SWITCH
no
correct, if yes
check hose H for
leakkage or blockings
Ensure connections
Ensure connections
no
correct, if yes
check hose L for
leakkage or blockings
Check
voltage present at
GATE 10 BURNER
AUTOMATION
yes
Problem solved
no
voltage present at
GATE 2 BURNER
AUTOMATION
Does the RESET
switch light up?
RESET the water heater
and wait one cycle,
advanced Fault Finding
Check
yes
yes
no
Replace
BURNER AUTOMATION
no
Ensure connections
correct, if yes replace
RESET switch
29
Page 30
Water heater in
in operation?
no
Gas supply
present?
no
Re-instate gas supply
and reset water heater
yes
Problem
solved
yes
IONISATION PROBLEMS.
Carry out 3 RESET cycles to make sure the pilot is provided with gas. Check gasconnections towards the pilot burner. Carry out one more RESET cycle. If no operation is valid replace the entire PILOT BURNER assy. RESET water heater after replacing the PILOT BURNER
Water heater in operation?
yes
Problem
solved
no no
SECUNDARY CIRCUIT,
Check
voltage on
PRIMARY CIRCUIT,
TRANSFORMER
yes
Check
voltage on
TRANSFORMER
no
Ensure connections
correct
Ensure connections
correct. If yes replace
transformer
30
yes
Problem
solved
Page 31
5. WARRANTY
The following conditions form the guarantee agreement between A.O. Smith Water Products Company (the warrantor) and the owner of the water heater.
5.1 Guarantee in general
If within one year of the original installation date of the water heater any part or component other than the tank shall prove upon examination by the warrantor or authorised agent to be defective in material or work­manship, the warrantor will exchange such part or component.
5.2 Guarantee of the tank
If within 3 years of the original installation date, the tank fails due to rust or corrosion from the water side, the warrantor will supply a complete new water heater of equivalent size and duty (excluding delivery and installation charges). On the replacement water heater a guarantee will be granted sufficient to cover the unexpired portion of the original 3 year guarantee of the originally installed water heater.
and laundries or where some industrial degreasing products are used and stored (for further information and advise please contact the A.O. Smith Technical Department).
5.5 Range of the guarantee
All replacement water heaters supplied under the terms of this warranty will be supplied ex stock on an F.O.B. basis. A.O. Smith accepts no responsability for carriage, labour or other installation costs.
5.6 Claims
Any claim under this warranty should be initiated with the dealer who originally sold the water heater or with any other dealer or stockist of the warrantors products.
5.7 No other guarantee or warranty either expressed or implied is made on behalf of A.O. Smith Water Products Company.
With respect to the water heater in question further A.O. Smith does not guarantee this water heater as suitable for purpose except within the terms of warranty detailed above.
5.3 Conditions for installation and use
The guarantee applies to the water heater only while it remains in its orignial location, and is installed in accordance with local plumbing and building regulations and all relevant Codes of Practice.
The water heater should also have been used only: a) for potable water free to circulate at all times and
with the tank free of damaging scale deposits;
b) at temperatures not exceeding the maximum setting
of its thermostat and ECO (Energy Cut Off device);
c) at water pressures and/or energy inputs which do
not exceed those stated on the rating plate of the
water heater; d) in a non corrosive atmosphere or area; e) with an approved temperature and pressure relief
valve of adequate capacity not exceeding the
working pressure rating shown on the water heater,
and installed in conformity with A.O. Smith Water
Products Companies installation instructions; f) when anode(s) have been inspected and renewed,
if they are worn or erroded by 50% of more at any
point of their length.
5.4 Exclusions
The guarantee will be null and void: a) if the water heater has been damaged by an
external cause; b) in case of misuse, neglect (including frost damage)
or incorrect use of the water heater; c) in case of unauthorised alteration, modification or
repair; d) in case of ingress into the water heater of
chemicals, pollutants or contaminants; e) if the hardness of the incoming water is, or has
been, softened below 106 ppm CaCO f) if the water heater is effected by corrosive vapours
such as those found in hairdressers, dry cleaners
;
3
A.O. Smith Water Products Company will not be liable by virtue of this guarantee or otherwise for damage to any persons or property when arising out of contracts or tort.
The terms of this guarantee do not effect your statutory rights under United Kingdom Consumer Legislation.
This guarantee applies to the following models: BFM 30 BFM 50 BFM 80
31
Page 32
32
0305 664 R0
Loading...