A.O. Smith BFC - 30, BFC - 60 User Manual

28
28
30
30
50
50
60
60
Installation
Installation
Installation
User and
User and
User and
WATER PRODUCTS
WATER PRODUCTS
WATER PRODUCTS
COMPANY
COMPANY
COMPANY
A DIVISION OF A. O. SMITH CORPORATIONA DIVISION OF A. O. SMITH CORPORATION
A DIVISION OF A. O. SMITH CORPORATION
XTRA HIGH EFFICIENCYXTRA HIGH EFFICIENCY
www.aosmithinternational.com
your installer
gis
Read this manual carefully
Trademarks
Liability
Warning
Read this manual carefully before starting up the water heater. Failure to read this manual and to follow the instructions in this manual may lead to accidents, personal injury, and damage to the appliance.
Copyright © 2008 A.O. Smith water Products Company
All rights reserved.
Nothing from this publication may be copied, reproduced and/or published by means of printing, photocopying or by whatsoever means, without the prior written approval of A.O. Smith water Products Company.
A.O. Smith water Products Company reserves the right to modify specifications stated in this manual.
Any brand names mentioned in this manual are registered trademarks of their respective owners.
A.O. Smith water Products Company accepts no liability for claims from third parties arising from improper use other than that stated in this manual and in accordance with the General Conditions registered at the Eindhoven Chamber of Commerce.
Refer further to the General Conditions. These are available on request, free of charge.
Although considerable care has been taken to ensure a correct and suitably comprehensive description of all relevant components, the manual may nonetheless contain errors and inaccuracies.
Should you detect any errors or inaccuracies in the manual, we would be grateful if you would inform us. This helps us to further improve our documentation.
More information
If you have any comments or queries concerning any aspect related to the appliance, then please do not hesitate to contact:
A.O. Smith water Products Company
PO Box 70
5500 AB Veldhoven
Netherlands
Telephone: (free) 0870 - AOSMITH
0870 - 267 64 84
General: +31 40 294 25 00
Fax: +31 40 294 25 39
E-mail : info@aosmith.nl
Website: www.aosmithinternational.com
In the event of problems with connecting to the gas, electricity or water supply, please contact your installation's supplier/installation engineer .
Instruction manual BFC 3
gis
4 Instruction manual BFC
gis
Table of contents
1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - 9
1.1 About the appliance - - - - - - - - - - - - - - - - - - - - - - - - - - - - 9
1.2 What to do if you smell gas- - - - - - - - - - - - - - - - - - - - - - - - - 9
1.3 Regulations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 9
1.4 Target groups - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 10
1.5 Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 10
1.6 Forms of notation - - - - - - - - - - - - - - - - - - - - - - - - - - - - 11
1.7 Overview of this document - - - - - - - - - - - - - - - - - - - - - - - - 12
2 Working principle of the appliance- - - - - - - - - - - - - - - 13
2.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 13
2.2 General working principle of the appliance - - - - - - - - - - - - - - - - 13
2.3 The appliance's heating cycle - - - - - - - - - - - - - - - - - - - - - - 14
2.4 Protection for the appliance - - - - - - - - - - - - - - - - - - - - - - - 14
2.5 Safety of the installation - - - - - - - - - - - - - - - - - - - - - - - - - 16
3 Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - 17
3.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 17
3.2 Packaging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 17
3.3 Environmental conditions- - - - - - - - - - - - - - - - - - - - - - - - - 17
3.4 Technical specifications - - - - - - - - - - - - - - - - - - - - - - - - - 20
3.5 Installation diagram - - - - - - - - - - - - - - - - - - - - - - - - - - - 23
3.6 Water connections, Unvented - - - - - - - - - - - - - - - - - - - - - - 24
3.7 Water connections, Vented- - - - - - - - - - - - - - - - - - - - - - - - 25
3.8 Gas connection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 26
3.9 Air supply and flue - - - - - - - - - - - - - - - - - - - - - - - - - - - - 26
3.10 Electrical connection - - - - - - - - - - - - - - - - - - - - - - - - - - - 32
3.11 Checking the supply pressure and burner pressure - - - - - - - - - - - - 36
4 Conversion to a different gas category - - - - - - - - - - - - 39
5 Filling - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 43
5.1 Filling the appliance - - - - - - - - - - - - - - - - - - - - - - - - - - - 44
6 Draining - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
6.1 Draining unvented installations - - - - - - - - - - - - - - - - - - - - - - 46
6.2 Draining vented installations - - - - - - - - - - - - - - - - - - - - - - - 46
7 The control panel- - - - - - - - - - - - - - - - - - - - - - - - 49
7.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 49
7.2 Controls - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 49
7.3 Meaning of icons- - - - - - - - - - - - - - - - - - - - - - - - - - - - - 49
7.4 Electronic controller ON/OFF switch - - - - - - - - - - - - - - - - - - - 49
7.5 Navigation buttons - - - - - - - - - - - - - - - - - - - - - - - - - - - - 49
7.6 PC connection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 50
8 Status of the appliance - - - - - - - - - - - - - - - - - - - - - 51
8.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 51
8.2 Operating modes - - - - - - - - - - - - - - - - - - - - - - - - - - - - 51
8.3 Error conditions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 52
8.4 Service condition- - - - - - - - - - - - - - - - - - - - - - - - - - - - - 53
Instruction manual BFC 5
Table of contents
9 Starting and running - - - - - - - - - - - - - - - - - - - - - - 55
9.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 55
9.2 Starting and running- - - - - - - - - - - - - - - - - - - - - - - - - - - - 55
9.3 The appliance's heating cycle - - - - - - - - - - - - - - - - - - - - - - - 55
10 Shutting down - - - - - - - - - - - - - - - - - - - - - - - - - 57
10.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 57
10.2 Shut the appliance down for a brief period ("OFF mode") - - - - - - - - - - 57
10.3 Electrically isolating the appliance - - - - - - - - - - - - - - - - - - - - - 57
10.4 Shutting the appliance down for a long period - - - - - - - - - - - - - - - 57
11 Main menu - - - - - - - - - - - - - - - - - - - - - - - - - - - 59
11.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 59
11.2 Notational convention for menu-related instructions - - - - - - - - - - - - 59
11.3 Switching on the "ON mode" - - - - - - - - - - - - - - - - - - - - - - - 59
11.4 Setting the water temperature - - - - - - - - - - - - - - - - - - - - - - - 59
11.5 Week program - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 60
11.6 Starting and stopping the week program - - - - - - - - - - - - - - - - - - 60
11.7 Changing the appliance's standard week program - - - - - - - - - - - - - 60
11.8 Adding times to a week program- - - - - - - - - - - - - - - - - - - - - - 62
11.9 Deleting times from a week program- - - - - - - - - - - - - - - - - - - - 63
11.10 Extra period- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 63
11.11 Programming an extra period - - - - - - - - - - - - - - - - - - - - - - - 64
11.12 Settings- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 65
12 Service program - - - - - - - - - - - - - - - - - - - - - - - - 67
12.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 67
12.2 Setting the hysteresis - - - - - - - - - - - - - - - - - - - - - - - - - - - 67
12.3 Displaying the error history - - - - - - - - - - - - - - - - - - - - - - - - 67
12.4 Displaying the appliance history - - - - - - - - - - - - - - - - - - - - - - 68
12.5 Display the selected appliance - - - - - - - - - - - - - - - - - - - - - - 68
12.6 Switching the pump on or off - - - - - - - - - - - - - - - - - - - - - - - 68
12.7 Setting the service interval - - - - - - - - - - - - - - - - - - - - - - - - 68
12.8 Setting the display contrast - - - - - - - - - - - - - - - - - - - - - - - - 68
12.9 Setting the display backlight time - - - - - - - - - - - - - - - - - - - - - 68
12.10 Setting the display scroll speed - - - - - - - - - - - - - - - - - - - - - - 68
13 Troubleshooting - - - - - - - - - - - - - - - - - - - - - - - - 69
13.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 69
13.2 Troubleshooting table for general errors - - - - - - - - - - - - - - - - - - 70
13.3 Troubleshooting table for displayed errors - - - - - - - - - - - - - - - - - 72
14 Maintenance frequency- - - - - - - - - - - - - - - - - - - - - 83
14.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 83
14.2 Determining service interval - - - - - - - - - - - - - - - - - - - - - - - - 83
15 Performing maintenance - - - - - - - - - - - - - - - - - - - - 85
15.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 85
15.2 Preparation for maintenance - - - - - - - - - - - - - - - - - - - - - - - 85
15.3 Water-side maintenance - - - - - - - - - - - - - - - - - - - - - - - - - 87
15.4 Gas-side maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - 88
15.5 Finalizing maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - 88
16 Warranty (certificate) - - - - - - - - - - - - - - - - - - - - - - 89
16.1 General warranty - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 89
6 Instruction manual BFC
16.2 Tank warranty - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 89
16.3 Conditions for Installation and use - - - - - - - - - - - - - - - - - - - - 89
16.4 Exclusions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 90
16.5 Scope of the warranty - - - - - - - - - - - - - - - - - - - - - - - - - - 90
16.6 Claims - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 90
16.7 Obligations of A.O. Smith - - - - - - - - - - - - - - - - - - - - - - - - 90
17 Appendices - - - - - - - - - - - - - - - - - - - - - - - - - - - 91
17.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 91
17.2 Electrical diagram - - - - - - - - - - - - - - - - - - - - - - - - - - - - 92
17.3 Week program card - - - - - - - - - - - - - - - - - - - - - - - - - - - 95
Instruction manual BFC 7
Table of contents
8 Instruction manual BFC
gis
0063

1 Introduction

1.1 About the appliance
1.2 What to do if you smell gas
This manual describes how to install, service and use the BFC appliance. The BFC appliance is a condensing water heater with a fan in the air intake. The BFC can be installed as either an open or room-sealed appliance. A concentric chimney connector is fitted standard to the appliance. Alternatively, the appliance can be connected using a parallel system.
The alternative installation types are B23, C13, C33, C43, C53 and C63.
The information in this manual applies to the: BFC 28, BFC 30, BFC 50 and BFC
60.
The appliance has been manufactured and equipped in accordance with the European standard for gas-fired storage water heaters for the production of domestic hot water (EN 89). The appliances are therefore compliant with the European Directive for Gas Appliances, and and are entitled to bear the CE mark.
Warning
Read this manual carefully before starting up the water heater. Failure to read the manual and to follow the printed instructions may lead to personal injury and damage to the appliance.
Warning
If there is a gas smell:
No naked flames! No smoking!
Avoid causing sparks! Do not use any electrical equipment or switch, i.e. no telephones, plugs or bells!
1.3 Regulations
Open windows and doors!
Shut off the mains gas supply valve!
Warn occupants and leave the building!
After leaving the building, alert the gas distribution company or your installation engineer.
As the (end) user, installation engineer or service and maintenance engineer, you must ensure that the entire installation complies, as a minimum, with the official local:
building regulations;
energy supplier's directives for existing gas installations;
directives and technical guidelines for natural gas installations;
safety requirements for low-voltage installations;
regulations governing the supply of drinking water;
regulations governing ventilation in buildings;
regulations governing the supply of air for combustion;
regulations governing the discharge of products of combustion;
requirements for installations that consume gas;
regulations governing indoor waste water disposal;
Instruction manual BFC 9
1
Introduction
gis
regulations imposed by fire brigade, power companies and municipality.
Furthermore, the installation must comply with the manufacturer's instructions.
Note
Later amendments and/or additions to all regulations, requirements and guidelines published on or prior to the moment of installing, will apply to the installation.
1.4 Target groups
1.5 Maintenance
The three target groups for this manual are:
(end) users;
installation engineers;
service and maintenance engineers.
Symbols on each page indicate the target groups for whom the information is intended. See the table.
Target group symbols
Symbol Target group
(End) user
Installation engineer
Service and maintenance engineer
A service should be carried out at least once a year, both on the water side and on the gas side. Maintenance frequency depends, among other things, on the water quality, the average burning time per day and the set water temperature.
Note
To determine the correct maintenance frequency, it is recommended to arrange for the service and maintenance engineer to check the appliance on both the water and gas side within three months following installation. Based on this check, the best maintenance frequency can be determined.
Note
Regular maintenance extends the service life of the appliance.
Note
Both the end user and the service and maintenance engineer are responsible for regular maintenance. They will need to establish clear agreements on this.
Note
If the appliance is not regularly maintained, the warranty will become void.
10 Instruction manual BFC
gis
1.6 Forms of notation
The following notation is used in this manual:
Note
Important information.
Attention
Ignoring this information can lead to the appliance being damaged.
Warning
Failure to carefully read this information may lead to personal injury and
serious damage to the appliance.
Instruction manual BFC 11
1
Introduction
gis
1.7 Overview of this document
Chapter Target groups Description
Working principle of the appliance
Installation This chapter describes the installation activity to be
Filling This chapter describes how to fill the appliance.
Draining This chapter describes how to drain the appliance.
The control panel This chapter describes the general control of the
Status of the appliance This chapter describes the status (mode or condition) that
Starting and running This chapter describes how to start the appliance running.
Shutting down This chapter describes how to shut the appliance down for
The table provides an overview of the contents of this document.
Contents of this document
This chapter describes how the appliance functions.
completed before you actually start up the appliance.
appliance using the display.
the appliance may have, and possible actions to take.
The general heating cycle of the appliance is also described.
a brief or long period of time.
Main menu This chapter describes the main menu of the display. This
is the actual menu for the user, however the installation engineer and service and maintenance engineers will also need to use this menu.
Service program This chapter describes the service menu. It is mainly
intended for the installation engineer and service and maintenance engineers. End users may also refer to this chapter for additional information about the appliance.
Troubleshooting This chapter is mainly intended for the installation
engineer and the service and maintenance engineer. It describes appliance errors. These errors are indicated on the display. A troubleshooting table of possible causes and solutions is provided. End users may also refer to this chapter for additional information about the appliance.
Maintenance frequency This chapter describes how to determine the optimum
frequency at which to carry out maintenance. Both the end user and the service and maintenance engineer are responsible for regular maintenance. They need to reach clear agreement on this.
Note
If the appliance is not regularly maintained, the
warranty will become void.
Performing maintenance This chapter sets out the maintenance tasks to be carried
out during a service.
Warranty (certificate) This chapter states the warranty terms and conditions.
12 Instruction manual BFC
gis
2 Working principle of
the appliance
2.1 Introduction
2.2 General working
principle of the appliance
Legend
Only applicable numbers are mentioned.
1. cover
2. hot water outlet
3. electrical connector block
4. electronic controller
5. pressure switch
6. control panel
7. temperature sensor T
8. combustion chamber
9. anode
10. tank
11. heat exchanger
12. inspection and cleaning opening
13. temperature sensor T
14. cold water inlet
15. drain valve
16. gas control
17. burner
18. fan
19. air supply hose
20. hot surface igniter
21. flame probe
22. chimney pipe
23. siphon
24. insulation layer
1
2
Topics covered in this chapter:
General working principle of the appliance;
The appliance's heating cycle;
Protection for the appliance;
Safety of the installation.
The figure shows a cut-away view of the appliance.
Cut-away view of the appliance
1
2
3
4
5
6
7
8
9
10
11
12
13
16
17
18
19
20
21
22
14
15
IMD-0070 R1
23
24
Instruction manual BFC 13
2
Working principle of the appliance
gis
In this appliance the cold water enters the bottom of the tank via the cold water inlet (14). Once heated by the combustion chamber (8) and heat exchanger (11), the hot tapwater leaves the tank through the hot water outlet (2). Once the appliance is completely filled with water, it remains constantly under water supply pressure. As hot water is drawn from the appliance, it is immediately replenished with cold water.
The air required for combustion is forced into the burner (17) by the fan (18).
The gas is fed to the burner via the gas valve (16). Thanks to the modulated supply of gas and air, the optimum gas/air mixture is always achieved. The special construction of the burner causes the mixture to form a vortex (the cyclone effect), before it becomes ignited. This vorticity improves the ignition on the hot surface igniter (20), as well as ensuring optimum combustion efficiency. Through the special design of the heat exchanger (11), the flue gases are first led downwards via the combustion chamber, then upwards again via the heat exchanger, then once more downwards beside the water in the tank. In this process, the flue gases gradually become cooler. Because the cooled flue gases flow alongside the cold water lower down in the tank, they start to condense. This condensation causes latent heat energy to be released, which is transferred to the cooler water, thereby increasing the energy performance of the unit. The condensate yielded by this process is discharged via the siphon (23).
The insulation layer (24) prevents heat from escaping. The inside of the tank is enamelled to protect against corrosion. The anodes (9) provide extra protection against corrosion.
For use during maintenance, the appliance has an inspection and cleaning opening (12).
2.3 The appliance's heating cycle
2.4 Protection for the appliance
2.4.1 Introduction
The water temperature is measured by temperature sensors T1 (7) in the top of the tank (10) and T2 (13) at the bottom of the tank. These temperatures are sent to the electronic controller. Based on these two observations, the electronic controller calculates a net water temperature: T between the temperatures at the top and bottom of the tank. As soon as falls below the set water temperature (T "heat demand". The gas control (16) is opened, and the gas is mixed with air. This mixture is ignited by the hot surface igniter (20) and the water becomes heated. As soon as electronic controller stops the heating cycle.
The electronic controller assumes a certain margin both when registering and ending heat demand. We refer to this margin as the hysteresis (12.2 "Setting
the hysteresis").
The electronic controller monitors the water temperature and ensures safe combustion. This is achieved by:
the Water temperature protection;
•theGas valve;
the Fan;
the Pressure switch;
the Flame probe.
rises above T
Tnet
), the electronic controller registers a
set
the heat demand ends, and the
set
. The value of T
net
net
lies
Tnet
14 Instruction manual BFC
gis
2.4.2 Water temperature protection
The electronic controller uses temperatures sensors T1 (7) and T2 (13) to monitor three temperatures that are important for safety. The table explains the functioning of the temperature sensors.
Temperature protection
Protection Description
Against frost (T1 < 5°C or T2 < 5°C)
For maximum water temperature (T1 > 85°C or T2 > 85°C)
For extra safety (T1 > 93°C or T2 > 93°C)
2.4.3 Gas valve
The frost protection cuts in. The water is heated to 20°C.
The high-limit safeguard serves to prevent overheating and/or excessive formation of scale in the appliance. If the high-limit safeguard is activated, the heating is stopped. This causes the water in the tank to cool down. Once the water has cooled sufficiently (T1 < 78°C), the electronic controller resets the appliance.
A lockout error of the water heater controller takes place. The controller must be manually reset before the appliance can resume operation (8.3 "Error
conditions"). The reset may only be performed if T
The electronic controller opens the gas valve so that gas can be supplied to the burner. As a safety measure, the gas valve has a double shut-off. The double shut-off guarantees complete isolation of the appliance from the gas supply.
To help ensure smooth ignition, the gas valve opens gradually ('softlite").
<78°C.
1
2.4.4 Fan
The fan (18) provides an optimum air supply when there is a heat demand. As a safety feature, the fan ensures that any gases present in the combustion chamber are removed, both before and after combustion. We refer to this as pre- and post-purge.
The fan speed is continuously monitored by the electronic controller (4). The electronic controller takes control if the speed of rotation varies too much from the set value.
2.4.5 Pressure switch
The pressure switch ensures the discharge of flue gases and the supply of incoming air during the pre-purge and normal running of the appliance. The default state of the pressure switch is open. When sufficient pressure difference is reached, the pressure switch closes. However, in the event of a fault, the pressure switch is tripped open, and the heating cycle is interrupted. The table shows the trip point per appliance.
Note
The trip point of the pressure switch is not adjustable.
Pressure switch trip points
Appliance Closing pressure
differential
BFC 28
BFC 30
BFC 50
BFC 60
635 Pa < 605 Pa
>
> 855 Pa < 825 Pa
>
885 Pa < 855 Pa
>
1085 Pa < 1055 Pa
Opening pressure differential
Instruction manual BFC 15
2
2.4.6 Flame probe
2.5 Safety of the instal­lation
2.5.1 Unvented installation
Working principle of the appliance
gis
To ensure that no gas can flow when there is no combustion, the water heater is fitted with a flame probe (21). The electronic controller uses this probe to detect the presence of a flame, by means of ionisation detection. The electronic controller closes the gas control the instant it detects that there is a gas flow but no flame.
In addition to the appliance's standard built-in safety monitoring, the appliance must also be protected by an expansion vessel, expansion valve, pressure reducing valve, non-return valve and a T&P valve.
The use of an expansion vessel, expansion valve and/or pressure reducing valve depends on the type of installation: unvented or vented.
With an unvented installation, an expansion valve valve and expansion vessel prevent the buildup of excessive pressure in the tank. This prevents damage being caused to the enamelled coating (in the appliance) or to the tank. A non­return valve prevents excessive pressure buildup in the water supply system. This valve also prevents water from flowing backwards from the tank into the cold water supply system. The pressure reducing valve protects the installation against an excessively high water supply pressure (> 8 bar). These components are fitted to the cold water pipe (3.7 "Water connections, Vented").
2.5.2 Vented installation
With a vented installation, excess pressure is taken up by the open cold water head tank. The height of the head tank determines the working pressure in the water heater, which may not exceed 8 bar. The installation must also be fitted with a vent pipe from the hot water pipe, that opens into the cold water tank.
Ideally, the vent pipe should discharge into a separate tundish/drain or otherwise to the open cold water head tank. The water heater should also be fitted on the hot water side with a stop valve (3.6.2 "Hot water side").
2.5.3 T&P valve
A T&P valve is only mandatory in an unvented installation. However, A.O. Smith also recommends the use of a T&P valve in vented installations.
A T&P (Temperature and Pressure Relief) valve monitors the pressure in the tank and the water temperature at the top of the tank. If the pressure in the tank becomes excessive (> 10 bar) or the water temperature is too high (> 97°C), the valve will open. The hot water can now flow out of the tank. Because the appliance is under water supply pressure, cold water will automatically flow into the tank. The valve remains open until the unsafe situation has been rectified. The appliance is fitted standard with a connecting point for a T&P valve (3.6.2 "Hot water side").
16 Instruction manual BFC
is

3 Installation

Warning
Installation work should be carried out by an approved installation engineer in compliance with the general and local regulations imposed by the gas, water and power supply companies and the fire service.
The appliance may only be installed in a room that complies with the requirements stated in national and local ventilation regulations (1.3 "Regulations").
3.1 Introduction
3.2 Packaging
3.3 Environmental conditions
This chapter describes the installation activities to be carried out before you actually start using the appliance (9 "Starting and running"), namely:
Packaging;
Environmental conditions;
Technical specifications;
Water connections, Unvented;
Water connections, Vented;
Gas connection;
Air supply and flue;
Electrical connection;
Checking the supply pressure and burner pressure;
In the event of conversion to a different gas category, see conversion (4 "Conversion to a different gas category").
To avoid damaging the appliance, remove the packaging carefully.
We recommend unpacking the appliance at or near its intended location.
Attention
The appliance may only be manoeuvred in an upright position. Take care
that the appliance is not damaged after unpacking.
The appliance is suitable for either open or room-sealed combustion. If installed as a room-sealed appliance, then the availability of the necessary external air supply will depend on the place of installation. In this event, there are no additional ventilation requirements.
If the appliance is to be installed as an open system, then it will be subject to the guidelines and ventilation regulations that are in force locally.
The alternative installation types are B23, C13, C33, C43, C53 and C63.
Attention
The appliance may not be used in rooms where chemical substances are stored or used, due to the risk of explosion and/or corrosion of the appliance. Some propellants, bleaching agents, degreasing agents etc. disperse vapours which are explosive and/or which cause accelerated corrosion. If the appliance is used in a room in which such substances are present, the warranty will be void.
Instruction manual BFC 17
3
Installation
3.3.1 Air humidity and ambient temperature
The boiler room must be frost-free, or be protected against frost. The table shows the environmental conditions that must be adhered to for correct functioning of the electronics present in the appliance to be guaranteed.
Air humidity and ambient temperature specifications
Air humidity and ambient temperature
Air humidity max. 93% RV at +25°C
Ambient temperature Functional: 0 <
3.3.2 Appliance maximum floor load
In connection with the appliance's weight, take account of the maximum floor loading, refer to the table.
Weight specifications related to maximum floor load
Weight of the appliance filled with water
BFC 28 394 kg
BFC 30, BFC 50, BFC 60 582 kg
is
T < 60°C
3.3.3 Water composition
The appliance is intended for heating drinking water. The drinking water must comply with the regulations governing drinking water for human consumption. The table gives an overview of the specifications.
Water specifications
Water composition
Hardness (alkaline earth ions)
Conductivity > 125 µS/cm
Acidity (pH value) 7.0 < pH value < 9.5
Note
If the water specifications deviate from those stated in the table, then the
tank protection cannot be guaranteed (16 "Warranty (certificate)").
3.3.4 Working clearances
For access to the appliance, it is recommended that the following clearances are observed (see figure):
AA: around the appliance's control column and cleaning openings: 100 cm.
BB: all sides of the appliance: 50 cm.
Above the appliance (room to replace the anodes):
- 100 cm if using fixed anodes, or
- 50 cm if using flexible anodes.
> 1.00 mmol/l:
German hardness> 5.6° dH
French hardness > 10.0° fH
English hardness > 7.0° eH
18 Instruction manual BFC
is
A
If the available clearance is less than 100 cm, flexible magnesium anodes may be ordered.
Note
When installing the appliance, be aware that any leakage from the tank and/or connections can cause damage to the immediate environment or floors below the level of the boiler room. If this is the case, the appliance should be installed above a wastewater drain or in a suitable metal leak tray.
The leak tray must have an appropriate wastewater drain and must be at least 5cm deep with a length and width at least 5cm greater than the diameter of the appliance.
Working clearances
B
B
A
A A
IMD-0228 R1
Instruction manual BFC 19
3
A
5
Installation
is
3.4 Technical specifica­tions
3.4.1 Dimensions of the appliance
Legend
See the table.
The appliance is supplied without accessories. Check the dimensions (3.4.1 "Dimensions of the appliance"), gas data (3.4.3 "Gas data") and other specifications (3.4.2 "General and electrical specifications") of any accessories you plan to use.
Plan and elevation of the appliance
Hx
30º
3
45º
2
18º
D
2
6
3
Hy
Ny
5
4
45º
G
5
N
K
S
6
1
P
M
4
R
7
H
W
IMD-0073 R
20 Instruction manual BFC
is
Dimensions (all sizes in mm, unless otherwise stated)
Dimen sion
Description BFC
28
BFC 30
BFC 50
BFC 60
A Total height 1390 1910 1910 1910
D Diameter of the appliance 705 705 705 705
G Flue gas outlet diameter 80/125 100/150 100/150 100/150
H Height of flue/air supply 1365 1905 1905 1905
Hx x position of flue 265 265 265 265
Hy y-position of flue 375 375 375 375
K Height of gas connection 1270 1800 1800 1800
M Height of cold water supply 170 160 160 160
N Height of hot water outlet 1405 1940 1940 1940
Ny y-position of hot water outlet 205 205 205 205
P Height of cleaning opening 170 175 175 175
R Height of drain valve connection 85 75 75 75
S Height of T&P valve connection 900 1410 1410 1410
W Height of condensation drain 125 145 145 145
1 Cold water supply connection (ext.) R1
2 Hot water outlet (ext.) R11/
3 Gas valve connection (int.) Rp3/
4 Drain valve connection (int.)
3
/4"
/
2
2
4
R11/
R11/
Rp3/
3
/4"
2
2
4
R11/
R11/
Rp3/
3
/4"
2
2
4
R11/
R11/
Rp3/
3
/4"
2
2
4
1
5 T&P valve connection (int.) 1-11.5 NPT 1-11.5 NPT 1-11.5 NPT 1-11.5 NPT
6 Inspection/cleaning opening 95x70 95x70 95x70 95x70
7 Condensation drainage connection (int.) Ø40 Rp1 Rp1 Rp1
3.4.2 General and electrical specifications
General and electrical specifications
DESCRIPTION Unit BFC 28 BFC 30 BFC 50 BFC 60
Volume litres 217 368 368 368
Empty weight kg 177 214 214 214
Maximum operating pressure bar 8 8 8 8
Number of anodes - 4 4 4 4
Fan rotation speed at ignition rpm 4500 4500 4500 4500
Operational speed of fan rpm 5000 5400 6000 6660
Diameter of air restrictor mm 23.0 23.0 28.0 29.0
Heating time T = 45°C minutes 22 35 24 19
Electrical power consumption W 275 275 275 275
Supply voltage (-15% +10% VAC)
Mains frequency Hz (± 1Hz) 50 50 50 50
IP class - 30 30 30 30
volts 230 230 230 230
Instruction manual BFC 21
3
Installation
is
3.4.3 Gas data
Gas data
Description II
Gas category 2H: G20 - 20 mbar
Injector orifice diameter mm 4.90 5.10 7.00 7.10
(1) = Blank plate (2) = Burner pressure regulator
Nominal load (gross calorific value) kW 32.1 34.5 52.6 63.2
Nominal output kW 30.5 32.7 48.8 59.6
Supply pressure mbar 20 20 20 20
Burner pressure mbar 8.5 8.5 8.5 11.5
Gas consumption
General 3+
Injector orifice diameter mm 2.50 2.60 3.40 3.80
(1) = Blank plate (2) = Burner pressure regulator
Gas category: G30-30 mbar (butane)
Nominal load (gross calorific value) kW 30.7 32.8 50.6 59.4
Nominal output kW 29.8 31.8 48.1 57.4
Supply pressure mbar 30 30 30 30
Burner pressure
Gas consumption
Gas category: G31-37 mbar (propane)
Nominal load (gross calorific value) kW 29.0 30.9 50.3 59.1
Nominal output kW 28.1 29.8 47.7 56.9
Supply pressure mbar 37 37 37 37
Burner pressure
Gas consumption
(*) Based on 1013.25 mbar and 15 °C. (†) If using a blank plate instead of a burner pressure regulator, it is assumed that the burner pressure is equal to
the supply pressure. In practice, however, the burner pressure will be lower.
2H3+
(*)
(†)
(*)
(†)
(*)
Unit BFC
28
1 or 2 2 2 2 2
m3/h 3.1 3.3 5.0 6.0
1 or 2 1 1 1 1
mbar----
kg/h 2.2 2.4 3.7 4.3
mbar----
kg/h 2.1 2.2 3.6 4.2
BFC 30
BFC 50
BFC 60
22 Instruction manual BFC
is
3.5 Installation diagram
Legend
Only applicable numbers are mentioned.
1. pressure reducing valve
(mandatory)
3. T&P valve (mandatory)
4. stop valve (recommended in
pipe C and mandatory in pipe A)
5. non-return valve (mandatory)
6. circulation pump (optional)
9. drain valve
10. manual gas valve (mandatory)
11. service stop valve
12. temperature gauge (optional)
13. condensation drainage
14. hot water draw-off points
15. expansion valve (mandatory)
16. expansion vessel (mandatory)
17. 3-way aeration valve
(recommended)
18. water tank
19. float valve A. cold water supply B. hot water supply C. circulation pipe D. gas supply E. overflow pipe H. overflow pipe
Installation diagram
UNVENTED
10
D
VENTED
14 1414
B
11
T
12
3
4
6
5
4
C
16
1
4
5
15
9
13
H
19
17
14
11
B
12
T
E
18
C
A
A
4
D
10
4
3
5
464
C
9
13
IMD-0464 R0
Instruction manual BFC 23
3
Installation
is
3.6 Water connections, Unvented
3.6.1 Cold water side
3.6.2 Hot water side
Warning
The installation should be carried out by an authorised installation engineer,
in compliance with general and local regulations (1.3 "Regulations").
See (A) in the installation diagram (3.5 "Installation diagram").
1. Fit an approved stop valve (4) on the cold water side as required by applicable regulations (1.3 "Regulations").
2. The maximum working pressure of the appliance is 8 bar. Because the pressure in the water pipe at times can exceed 8 bar, you must fit an approved pressure-reducing valve (1).
3. Fit a non-return valve (5) and an expansion vessel (16).
4. Fit an expansion valve (15) and connect the overflow side to an open wastewater pipe.
See (B) in the installation diagram (3.5 "Installation diagram").
Note
Insulating long hot water pipes will prevent unnecessary energy loss.
1. Optional: fit a temperature gauge (12) so you can check the temperature of the tap water.
2. Fit the T&P valve (3).
3. Fit a stop valve (11) in the hot water outlet pipe for servicing.
3.6.3 Circulation pipe
See (C) in the installation diagram (3.5 "Installation diagram").
If an immediate flow of hot water is required at draw-off points, a circulation pump can be installed. This improves comfort and reduces water wastage.
1. Fit a circulation pump (6) of the correct capacity for the length and resistance of the circulation system.
2. Fit a non-return valve (5) behind the circulation pump to guarantee the direction of circulation.
3. Fit two stop valves for service purposes (4).
4. Connect the circulation pipe to the cold water supply pipe.
3.6.4 Condensation drainage
1. Fit a sloping wastewater pipe to the siphon (13) for condensation drainage and connect this to the wastewater discharge in the boiler room.
Attention
All fittings behind the siphon must be condensation-resistant.
24 Instruction manual BFC
is
3.7 Water connections, Vented
3.7.1 Cold water side
3.7.2 Hot water side
3.7.3 Circulation pipe
Warning
The installation should be carried out by an authorised installation engineer,
in compliance with general and local regulations (1.3 "Regulations").
See (A) in the installation diagram (3.5 "Installation diagram").
1. Fit an approved stop valve (4) on the cold water side between the cold water head tank (18) and the appliance, as required by regulations (1.3 "Regulations").
See (B) in the installation diagram (3.5 "Installation diagram").
Note
Insulating long hot water pipes prevents unnecessary energy loss.
1. Fit the T&P valve (3).
2. Optional: fit a temperature gauge (12) so you can check the temperature of the tap water.
3. Fit a stop valve (4) in the hot water outlet pipe, for use when servicing.
4. If a circulation pipe is required, continue further by installing the circulation pipe (3.6.3 "Circulation pipe").
See (C) in the installation diagram (3.5 "Installation diagram").
If an immediate flow of hot water is required at draw-off points, a circulation pump can be installed. This improves comfort and reduces water wastage.
1. Fit a circulation pump (6) of the correct capacity for the length and resistance of the circulation system.
2. Fit a non-return valve (5) behind the circulation pump to guarantee the direction of circulation.
3. Fit two stop valves for service purposes (4).
4. Connect the circulation pipe to the cold water supply pipe.
3.7.4 Condensation drainage
1. Fit a sloping wastewater pipe to the siphon (13) for condensation drainage and connect this to the wastewater discharge in the boiler room.
Attention
All fittings behind the siphon must be condensation-resistant.
Instruction manual BFC 25
3
Installation
is
3.8 Gas connection
3.9 Air supply and flue
3.9.1 Introduction
Warning
The installation should be carried out by an authorised installation engineer,
in compliance with general and local regulations (1.3 "Regulations").
Attention
Make sure that the diameter and length of the gas supply pipe are large
enough to supply sufficient capacity to the appliance.
See (D) in the installation diagram (3.5 "Installation diagram").
1. Fit a manual gas valve (10) in the gas supply pipe.
2. Blow the gas pipe clean before use.
3. Close the manual gas valve.
4. Fit the gas supply pipe to the gas control.
Warning
After fitting, check for leaks.
This section covers the following subjects:
Requirements for flue gas discharge materials
Concentric connections
Parallel connections
3.9.2 Requirements for flue gas discharge materials
Warning
The installation should be carried out by an authorised installation engineer,
in compliance with general and local regulations (1.3 "Regulations").
Depending on the approved installation types, there are several alternatives for connecting the air supply and flue gas discharge.
The appliances are approved for installation types B23, C13, C33, C43, C53 and C63.
The figure and table give information about these appliance types. For an explanation of the possibilities, please contact the manufacturer.
26 Instruction manual BFC
is
Types of appliances
C43
B23 C33
C13 C53
IMD-0468 R0
Instruction manual BFC 27
3
Installation
is
Explanation of type of appliance
Type of appliance Description
B23 Air for combustion is drawn from the boiler room.
C13 Concentric and / or parallel wall flue terminal
C33 Concentric and / or parallel roof flue terminal
C43 Appliances on common air supply and flue gas discharge (concentric and / or
C53 Air supply and flue terminal types mixed.
C63 Appliances supplied without flue components and / or terminal. These
3.9.3 Concentric connections
parallel) in multi-storey building.
appliances must be installed in compliance with local regulations.
Note
Make sure that the chimney discharges into an area where this is permitted
for this category of appliance.
The table shows the requirements for concentric systems.
Warning
Install flue gas discharge pipe runs with a run-off of 5 mm per metre.
Flue gas discharge requirements for concentric systems (C13, C33)
Appliance Diameter Maximum length Maximum
number of 90º bends
BFC 28 80/125 mm 40 m 7
BFC 30 100/150 mm 40 m 7
BFC 50 100/150 mm 40 m 7
BFC 60 100/150 mm 15 m 4
Attention
Both conditions stated in the table must be fulfilled.
Even if there are less bends than the stated maximum, the maximum pipe length may not be exceeded.
Even if the total pipe length is less than the stated maximum, the maximum number of bends may not be exceeded.
The following example illustrates how to use the table.
Practical example of concentric flue gas discharge
Example
The figure shows a BFC 30 installation. The appliance must be fitted with 25 m of concentric pipe (C13/C33) and four 90 degree bends. We need to check whether this configuration complies with the requirements stated in the table.
28 Instruction manual BFC
is
Appliance with concentric flue gas discharge material
IMD-0284 R1
According to the table, the maximum length allowed is 40 metres, and there may be up to seven 90 degree bends. Both requirements are fulfilled.
Specifications
Attention
For type C13 and C33 installations,A.O. Smith prescribes the use of a roof or wall-mounted terminal, exclusively of a type approved for the appliance. Use of an incorrect roof or wall-mounted flue terminal can cause the installation to malfunction.
Instruction manual BFC 29
3
Installation
is
Concentric wall flue terminal specifications C13
Specification Description
Wall flue terminal set:
1X Wall flue terminal (incl. wall flange & clamping ring)
1X Pipe 500mm
1X Bend 90°
Pipe material Construction Concentric
Pipe diameters Flue BFC 28
No other wall flue terminal is permitted. Use this item number to order the wall conduit set from supplier,
(1)
manufacturer or wholesaler.
Concentric roof flue terminal specifications C33
Art. No. BFC 28
BFC 30-50-60
Construction Concentric
Manufacturer Muelink & Grol
Model M2000 MDV SEC
Flue Thick-walled aluminium with lip ring seal
Air supply Thin-walled galvanised sheet steel
BFC 30-50-60
Air supply BFC 28
BFC 30-50-60
0302 515 0302 504
Ø 80 mm Ø 100 mm
Ø 125 mm Ø 150 mm
1
1
Specification Description
Roof flue terminal set:
1X Wall flue terminal (incl. clamping ring)
1X Pipe 1000mm
1 X Mounting flange
Pipe material Construction Concentric
Pipe diameters Flue BFC 28
No other wall flue terminal is permitted. Use this item number to order the wall conduit set from supplier,
(1)
manufacturer or wholesaler.
Art. No. BFC 28
BFC 30-50-60
Construction Concentric
Manufacturer Muelink & Grol
Model M2000 DDV HR-C
Flue Thick-walled aluminium with lip ring seal
Air supply Thin-walled galvanised sheet steel
BFC 30-50-60
Air supply BFC 28
BFC 30-50-60
0305 042 0304 423
Ø 80 mm Ø 100 mm
Ø 125mm Ø 150 mm
1
1
30 Instruction manual BFC