Antunes FGA-H010 Installation Manual

A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
2 11/16" (68 mm)
3"
(76 mm)
1 3/8"
(35 mm)
1 11/16" (43 mm)
13/16"
(21 mm)
1 5/32"
(30 mm)
Reset Buttom (Manual Only)
1/2" Conduit
Knockout
1 11/16" (43 mm)
1 5/32"
(30 mm)
1/2" Conduit
Knockout
Versa Plus Gas Pressure Switches Installation Information
IMPORTANT
Please read these instructions carefully to assure correct installation. This equipment must be installed only by a licensed electrician who is experienced with combustion safeguard control systems and understands the functions of inter­locking switches, such as gas pressure switches. Prior to being put into operation in conjunction with the combustion safeguard systems, all switches should be tested for proper range setting and proper wiring. Check piping connections and switch house for leaks with a soap bubble test. All exhaust fans and blowers should be inspected and checked for proper rotation prior to starting up.
Versa Plus Gas Pressure Switches
Antunes Controls new line of gas pressure switches mon­itors gas pressure and breaks the electrical control circuit when pressure drops below or rises above the desired setpoint. The gas pressure settings are adjustable and available in manual or automatic reset operation.
These switches are sturdy and constructed with a dura­ble plastic electrical enclosure and a die-cast aluminum inlet base.
Specifications
Electrical Ratings: 6A @ 120 VAC, 6A @ 240 VAC, 1/8
HP 120 & 240 VAC
Adjustable Operating Pressure: 1.2 to 275 mbar
0.5” W.C. to 4 PSI (different ranges)
NOTE: To avoid initial line fill pressure spikes, unit should be placed downstream of the regulator.
Max. Surge Pressure: 7 PSI (482 mbar)
Ambient Operating Temperature: 5°F to 180°F
(-15°C to 82°C)
Field wiring to be rated @ 90°C (194°F) for maximum ambient
Shipping Weight: 0.5 lbs. (.227 kg)
Options:
4-Pin DIN Connector Neon Lamp Indicator Side Mounting
Dimensions
Gas (Air) Inlet 1/4" NPT
3"
2 11/16"
(76 mm)
(68 mm)
3"
(76 mm)
1 5/32"
(30 mm)
1/2" Conduit
Knockout
1 11/16" (43 mm)
Note: Dimensions are for reference only.
Ranges Available
Low Ranges
Model Part No. W.C. mbar
Automatic Reset
FGA-L010 8261001010 0.5”–4” 1.2–10
FGA-L050 8261002050 1”–20” 2.5–50
FGA-L110 8261003110 4.8”–44” 12–110
FGA-L275 8261004275 28”–110” 70–275
Manual Reset
FGM-L 010 8271001010 0.5”–4” 1.2–10
FGM-L 050 8271002050 1”–20” 2.5–50
FGM-L 075 8271003075 5.2”–30” 13-75
FGM-L 136 8271004136 6.8”–54.5” 17-136
High Ranges
Model Part No. W.C. mbar
Automatic Reset
FGA-H010 8261005010 0.8”–4” 2–10
FGA-H050 8261006050 2”–20” 5–50
FGA-H087 8261007087 5”–35” 13–87
FGA-H275 8261008275 28”–110” 70–275
Manual Reset
FGM-H 050 8271005050 2”–20” 5–50
FGM-H 087 8271006087 8”–35” 20–87
FGM-H 150 8271007150 10”–60” 25–150
(76 mm)
1 3/8"
(35 mm)
3"
Reset Buttom (Manual Only)
13/16"
(21 mm)
1-630-784-1000 Fax: 630-784-1651 Page 1 of 4 P/N 1011063 Rev. A 06/10 1-800-253-2991
A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
Versa Plus Gas Pressure Switches Installation Information
Mounting
All switches can be mounted in either horizontal or verti­cal position. Switches should be reasonably level but do not require accurate leveling.
Single gas switch models have a 1/4” NPT (female) gas inlet on the standard base.
Piping can either be standard black pipe or aluminum tub­ing.
All switches can be support by the inlet pipe, but optional mounting brackets and bases are available (see Figures 1 through 5).
Switches have been factory calibrated and tested for leaks. However, it is recommended that switch, gas pipe inlets, and connections be soap bubble tested for leaks after installation.
STANDARD SWITCH BASE PANEL MOUNTING SUGGESTIONS
OPTIONAL SWITCH BASE SIDE MOUNTING SUGGESTIONS WITH “O” RING
Figure 1
STANDARD SWITCH BASE REMOTE MOUNTING SUGGESTIONS
OPTIONAL SWITCH BASE BOTTOM MOUNTING SUGGESTIONS WITH “O” RING
Figure 2
Operation
LOW GAS PRESSURE MODELS
Low gas pressure switches break the electrical circuit on pressure drop at the point when gas pressure becomes lower than the indicated set pressure.
In order to reset the switch, the gas pressure in the chamber must be higher than the indicated setting. For manual reset switches, the reset button must also then be pressed.
HIGH GAS PRESSURE MODELS
High gas pressure switches break the electrical circuit when pressure rises above the indicated preset pressure.
In order to reset the switch, the gas pressure in the chamber must be lower than the indicated setting. For manual reset switches, the reset button must also then be pressed.
RANGE ADJUSTMENT (ALL MODELS)
To adjust gas pressure cutoff setting, remove the cover. Turn the range scale adjustable knob (Figure 6) clock­wise to increase pressure setting, counterclockwise to decrease pressure setting. Install cover and tighten the two cover screws to prevent tampering.
RANGE SCALE (ADJUSTABLE KNOB)
RESET BUTTON
OPTIONAL SWITCH BASE SIDE-BY-SIDE MOUNTING SUGGESTIONS HIGH AND LOW GAS PRESSURE
Figure 5
Figure 3
Figure 4
Figure 6
Manual ResetAutomatic Reset
1-630-784-1000 Fax: 630-784-1651 Page 2 of 4 P/N 1011063 Rev. A 06/10 1-800-253-2991