The information set forth in this document and all rights in and to inventions
disclosed herein, and patents which might be granted t her eon disclosing,
employing or covering the materials, methods, techniques or apparatus
described herein are the exclusive property of Andrew Corporation.
This document is an operation and maintenance manual. No disclosur e or
reproduction of the infor mation or drawings shall be made of any other
purpose without the prior written consent of Andrew. Use of the information
contained herein to fabricate or assem b le any item in whole or in part is
expressly prohibited
High voltage is used in the operation of
this equipment. Death on contact may
result, if personnel fail to observe t he
following safety precautions:
• Do not be misled by the term “Low Voltage.” Potent ials as low as 50 Volts may cause
death under adverse conditions.
• Do not crush, puncture, disassemble or other wise mutilate batteries. Leaking batteries
can cause serious damage to equipment and injur y to per sonnel.
• Do not remove covers or access plates on the equipment, unless you are author ized to do so.
• Do not work on electronic equipment unless ther e is anot her person nearby who is familiar
with the operation of the equipment and is t r ained in administering first aid.
• Whenever possible, disconnect t he equipment from the power source bef or e beginning
maintenance.
• To prevent electrical shock or damag e to the equipment, do not operate it until you
thoroughly understand the operation and f unction of all controls, indicators, and
connectors.
• Turn off all power to the equipment before replacing any f uses.
FIRST AID
In case of electrical shock:
• Do not try to pull or grab the individual.
• If possible, turn of f the electrical power.
• If you cannot turn off the electrical power, pull, push, or lift the person to safety using a dry
wooden pole, a dry rope, or some other insulating mater ial.
• Send for help as soon as possible.
• After the injured person is no longer in contact with the source of electrical shock , m ove
the person a short distance away and immediately administer firs t aid and ar tificial
resuscitation as required.
Document use is restricted to that described on coverA
Page 3
385700-4006-006LIST OF ABBREVIATIONS AND ACRONYMS
WARNING
The Distribution Line Amplifier is an unlicensed device oper ating
under the conditions of FCC part 15 regulati ons. This equipment
is intended to be installed and operated by professional parties.
It is the responsibility of those parties to insure that the
equipment is operated in compliance with the applicable FCC
part 15 specifications.
LIST OF ABBREVIATIONS AND ACRONYMS
NOTE
All abbreviations/acronyms used in this
manual, other than those listed on this
page, are used per MIL-STD-12D.
BDRBase Data Radio
USERCommunications-Based Train Control
DLADistribution Line Amplifier
ESDSElect r ostatic Discharge Sensitive
FWDForward
LRULine Replaceable Unit
MDRMobile Data Radio
PCPersonal Computer
RCSRadio Communication Subsystem
RFRadio Fr equency
RVSReverse
SSRSpr ead Spect r um Radio
Document use is restricted to that described on coverB
Page 4
385700-4006-006LIST OF REFERENCE DOCUMENTS
LIST OF REFERENCE DOCUMENTS
Andrew Catalog 37 (or latest version)
Drawings:
Assembly, Line Amplifier385700-4000
Document use is restricted to that described on coverC
Table 5-2 Parts List..............................................................................................................5-2
Document use is restricted to that described on coveriii
Page 8
385700-4006-006INTRODUCTION
CHAPTER 1
INTRODUCTION
1.1 GENERAL MANUAL INFORMATION
This manual contains instructions for the operation, maintenance, and support of the
Distribution Line Amplifier (DLA) assembly. T his manual describes the amplifier assembly in
detail. It provides the necessary inform ation for q ualified technical per sonnel to inst all, repair,
and maintain the Distribution Line Amplifier to the line replaceable unit (LRU).
This manual is divided into seven chapters, which consist of sections to describe the
information or procedures in detail. The five chapters are as follows:
• Chapter 1 outlines the contents of this manual and provides a basic equipment
description of the Distribution Line Am plifier.
• Chapter 2 provides preparation for use and installation information.
• Chapter 3 provides operating procedures f or t he equipment.
• Chapter 4 provides preventive and corrective maintenance of the Dist ribution Line
Amplifier assembly.
• Chapter 5 contains a vendor list and parts list for procurement of replacement
parts.
• Chapter 6 provides mechanical outline informat ion
• Chapter 7 contains a schematic of a test fixture for the Alarm/Cont r ol int erface.
1.2 PREPARATION FOR STORAGE OR SHIPMENT
The following paragraphs describe guidelines for long term stor age and the shipment of the
equipment.
1.2.1 Storage
Before storage, wrap the equipment in static shielding bubble wrap. Bubble wrap protects
internal electrostatic discharge sensit ive (ESDS) assemblies, external panels, and connect ors.
Place wrapped equipment in the original shipping containers and seal. Store in a cool dry
place, away from the elements.
1.2.2 Shipment
Ship equipment in the original shipping containers or in a container that provides sufficient
protection for ESDS equipment. Pack the equipm ent in a manner that provides protection for
all external switches and mountings, because these items are most vulnerable to damage
during shipment.
Document use is restricted to that described on cover1-4
Page 9
385700-4006-006INTRODUCTION
1.3 DESCRIPTION OF EQUIPMENT
The Radio Communications Network consists of Base and Mobile Radio Communication
Systems (RCS) and a Wayside Antenna System. The Distribution Line Amplif ier (DLA) is par t
of the distributed Wayside Antenna System based on leaky-feeder cable RADI AX
®
. DLA’s are
used to compensate for attenuation losses in the cable by providing bi-dir ectional amplification
of signals. The DLA also includes a direction control signal and status signals to monitor
amplifier operation.
1.3.1 Type of Equipment
The DLA is a FCC approved bi-directional amplifier that is used with spread spectrum
transceivers that operate in the ISM 2400-2483.5 MHz frequency band. The 4 versions of the
DLA are shown in Table 1-1. The models differ in the number of RF ports and the type of
control interface.
Part NumberDescription
385700-4000-0014 port amplifier with LONWorks™ Interface
385700-4000-0024 port amplifier with dry contact Inter face
385700-4000-0032 port amplifier with LONWorks™ Interface
385700-4000-0042 port amplifier with dry contact Inter face
Table 1-1 – DLA Part Numbers
1.3.2 Purpose of the Equipment
The Distribution Line Amplifier provides selective frequency range amplification of both a
forward (downlink) and reverse (uplink) direction signals in RADIAX
defined as the direction of RF energy from the BDR at the wayside to the MDR. Reverse
direction is defined as the direction of RF energy fr om the MDR to the BDR. T he signals that
appear on the line amplifier RF ports are determined by the USER controlled direction signal.
®
cable. Forward is
Document use is restricted to that described on cover1-5
Page 10
385700-4006-006INTRODUCTION
1.4 LOCATIONS AND DESCRIPTIONS OF MAJOR COMPONENTS
Refer to Figure 1-1 Dist ribution Line Amplifier (4 port) for a view of t he external connections
of the 4 port DLA. The 2 por t DLA does not include J5 or J6. The mechanical outline of t he
DLA is given in CHAPTER 6. The following paragraphs contain the description of the
Distribution Line Amplifier.
Figure 1-1 Distribution Line Amplifier (4 port)
1.4.1 Distribution Line Amplifier Principles of Operation
The bi-directional Distribution Line Amplifier operates within two sub-regions of the 2400 –
2483.5 MHz ISM band. It filters and amplifies at the BDR center f requency of 2416.64 MHz.
in one direction (FW D) and at the MDR center f requency of 2467.86 MHz in another direction
(RVS).
The RF signal at each amplifier is routed thr ough a diplexer (f ilter) to divide the signal int o two
paths: forward and reverse. The DLA has a direct ion control switch which changes the signal
path to the opposite direction upon the command from the user control equipment network
data interface via the alarm and control interface board. The internal status of the DLA is
monitored by the Amplifier Alarm Detectors. The status signals ar e sent to the USER control
equipment network data interface via the alarm and control interface.
The BDR path, also referr ed to as the PA channel or channel 1, contains a power amplifier.
The maximum PA output of the 4 port DLA is < +27 dBm per output port. T he PA output port
of the 2 port DLA is < +30 dBm. The PA channel maintains a constant output power over a
user adjustable range. See Table 1-2 Distribution Line Amplif ier Specifications for the input
range over which the output power is adjustable. The PA channel also contains an input
Document use is restricted to that described on cover1-6
Page 11
385700-4006-006INTRODUCTION
power level alarm as well as an output power alarm. The alarm levels are user adjustable.
The MDR path is also referred to as the LNA channel or channel 2. The LNA channel is
referenced to a pilot tone within the Distribution Line Amplifier. The pilot tone is used (1) to
set the gain of the LNA channel and (2) to provide a method of detecting a f ault y LNA module.
The LNA channel gain is user adjustable. The maximum LNA g ain is +27 dB for the 4 port
DLA per output port and +30 dB for the 2 port DLA. See Table 1-2 Distribution Line Amplifier
Specifications for the range over which the gain is adjustable. Under normal operation, the
input signal is expected to be lower (nominally 10 dB) than the pilot tone.
The PA channel input alarm is used to detect a loss of input signal due t o cable breakage, et c.
The PA channel output alarm and the LNA channel output alarm are combined to indicate an
amplifier failur e.
Refer to Figure 1-2 DLA Block Diagram, for bi-directional amplifier major component
identification.
Document use is restricted to that described on cover1-7
Page 12
385700-4006-006INTRODUCTION
A
Transfer
Relay
Radiax
RF Lightning
Protection
Direction Control
Direction Status
+12 VDC
RF Lightning
Protection
Radiax
Diplexer
Alarm & Control
Interface Board
Radiax Alarm
Detector
LNA Alarm
Detector
USER Control Equipment
PA
LNA
24V Lightning
Protectors
larm & Control
Connections
-10 dBm
PA Alarm
Detector
+12 VDC
Pilot Tone
Generator
Diplexer
+12 VDC
AC-DC
Power Supply
AC
Lightning
Protection
87-265 VAC
Document use is restricted to that described on cover1-8
Figure 1-2 DLA Block Diagr am
Page 13
385700-4006-006INTRODUCTION
1.4.2 Distribution Line Amplifier Major Components
Refer to Figure 1-3 DLA I nternal View for locations of major DLA components. The t est point
locations, Pilot Tone Output J3 on the Pilot Tone Board and Alarm and Control Interface
Board Test Points J4, shown in
Figure 1-3 are used for init ial DLA adjustments and ref erenced later in this manual in section
2.5.
J2
J1
J9J7J6J3J4
J2
J1
J8
J5
Lightning Protection Module
Figure 1-3 DLA Internal View
Refer to section 2.5.1, Distribution Line Amplifier Setup, for PA and LNA outline views and
controls.
Document use is restricted to that described on cover1-9
Page 14
385700-4006-006INTRODUCTION
1.5 EQUIPMENT CHARACTERISTICS
Refer to Table 1-2 Distribution Line Amplifier Specifications. The table contains the
specifications for the DLA. The table includes characteristics and specifications in three
categories: technical, environmental, and physical.
1.5.1 Power and Utility Requirements
The DLA operates across an AC input range of 87 to 265 VAC. No user adjustment is
required.
1.5.2 Environmental Information
The DLA assembly is designed for above and below ground environments. Refer to Table 1-2
Distribution Line Amplifier Specifications, for more det ailed information.
The DLA is housed in a NEMA4X enclosure. It is intended for indoor or outdoor use to
provide a degree of protection against corrosion, windblown dust and rain, splashing water,
and hose-direct water; undamaged by the format ion of ice on the enclosure. The NEMA4X
enclosure is manufactured fr om 16 gauge Type 304 stainless steel.
Document use is restricted to that described on cover1-10
Table 1-2 Distribution Line Amplif ier Specifications
Document use is restricted to that described on cover1-11
Page 16
385700-4006-006INSTALLATION
CHAPTER 2
INSTALLATION
2.1 INSTALLING THE DISTRIBUTION LINE AMPLIFIER EQUIPMENT
This chapter provides informat ion t o inst all the Distribution Line Amplifier (DLA) and to prepare
the equipment for use.
2.1.1 Unpacking and Inspection
Unpacking the Distribution Line Amplifier does not require special procedures. Use normal
shop procedures to unpack the equipment.
Carefully inspect the shipping containers and equipment. If the containers show damage,
inspect the equipment in those containers with extra care. Do not open containers with
extreme damage.
Check equipment for bent frames, protrusions, and dents. Pay close attention to external
brackets, controls and connectors, because they are especially susceptible to damage during
shipment.
If you find damage to t he equipment, notify Andrew Corporation’s Customer Ser vice Center at :
• 1-800-255-1479 (Inside the USA)
• 708-873-2307 (Outside the USA)
2.1.2 Proper Installation of Units
The amplifier has a weatherproof NEMA4X enclosure. The layout is optimized for vertical
mounting of the amplifier with the cables connected at the bottom of the amplifier. The
enclosure is accompanied with hanger brackets that are used to mount the amplifier. The
type of fasteners will depend on the construction of the mounting surface. Typical
construction in a concrete tunnel would be to use concrete anchors embedded in concrete.
Once DLA is mounted, the power connections and RF connections can be made next.
2.2 INTERCONNECTIONS
Refer to Figure 2-1 DLA Forward Direction Interconnect Diagram, for a block diagram of
wiring runs and connector designations. The following paragraphs describe the
interconnections directly related to the Distribution Line Amplifier.
WARNING
Before applying power, verify that the
input/output cables are securely
connected to the DLA Input/Output J3 and
J4 ports. Failure to observe these
warnings will damage the equipment.
2.2.1 Forward Direction Configuration Interconnection
Document use is restricted to that described on cover2-1
Page 17
385700-4006-006INSTALLATION
In normal usage, the RF connections to the Distribution Line Amplifier are made with nonradiating coaxial cable that is attached to t he m ain radiating coaxial cable RADIAX
radiating RF cable is type HELIAX
In the forward configurat ion, connect the HELIAX
®
LDF4-50A (or equivalent) with N male type connectors.
®
coaxial cable coming from the direction of
®
. The non-
BDR or the preceding DLA in a cascaded configuration to the Distribution Line Amplifier at
NORM PA IN/LNA OUT (J4) port on the connector panel of the unit. Connect the HELIAX
coaxial cable coming from the direction of the succeeding DLA in a cascaded conf iguration at
the DLA NORM PA OUT1/LNA IN (J3) port. See Figure 2-1 DLA Forward Direction
Interconnect Diagram for a typical 4 port conf iguration. For 2 port configur ations, J5 and J6
are not connected. Refer to Andrew Catalog, -- HELIAX® Coaxial Cable – for cable and
connector information.
Connect a nominal 120 VAC power source to the DLA connector panel POWER I N (J1) port.
Refer to Figure 2-3 DLA Input VAC Pin-outs.
The ALARM/CONTROL (J2) connector is connected via cable to the USER control equipm ent
network data interface. T he data interface may be represented by eit her LONW ORKS
®
type
connection or by twisted pair cable connection. For the dry contacts ref er to Figur e 2-4 DLA
ALARM/CONTROL Port Pin-outs. The ALARM/CONTROL interface includes a signal that
controls the direction of the line amplifier. In normal usage the direction control is set to
FORWARD.
2.2.2 Reverse Direction Configuration Interconnection
In normal usage, the direction of t he amplifier is reversed by controlling the amplifier from the
ALA RM/CONTROL interface. The signals are connected to t he line amplifier as described in
the previous section. Selecting the reverse direction reverses the direction of the signals
within the line amplifier as well as the signals that appear on J3 and J4 of the line amplifier.
2.3 CABLE AND GROUND REQUIREMENTS
The following paragraphs contain the r equirements for constructing the interconnect cabling
between the DLA vendor supplied equipment.
The chassis of the DLA must be bonded to earth with 6-guage solid conductor. See Figure
1-1. Connection to the DLA is made at ground lug provided at the connector panel of the
DLA.
The RF coaxial cables that are connected to the main radiat ing cable under normal conditions
must support potential bends in the path from the main radiating cable to the DLA plat e. Loss
through this cable must be less than 2 dB.
For the ALARM/CONTROL interface (direction and am plifier status signals), construct signal
cabling using 16 gauge shielded cabling.
All signal cables shall be shielded for EMI reduction.
Document use is restricted to that described on cover2-2
Page 18
BDR 1
®
®
®
A
®
®
®
®
®
®
385700-4006-006INSTALLATION
FORWARD CONFIGURATION : DIRECTION CONTROL = NORMAL
USER Control
Equipment
HELIAX
RADIAX
DLA
ALARM/CONTROL
J2
NORM PA IN
LNA OUT
J4
NORM PA
OUT2
J5
NORM PA OUT1
LNA IN
J3
RADIAX
HELIAX
RADIAX
DL
ALARM/CONTROL
J2
NORM PA IN
LNA OUT
J4
NORM PA
NORM PA OUT1
LNA IN
J3
OUT2
J5
RADIAX
HELIAX
BDR 2
VAC Power
J3 – LNA In2467.84 MHz ± 13.5 MHzIY
J3 – Norm PA Out12416.64 MHz ± 13.5 MHzOY
J4 – Norm PA In2416.64 MHz ± 13.5 MHzIY
J4 – LNA Out2467.84 MHz ± 13.5 MHzOY
J5 – Norm PA Out22416.64 MHz ± 13.5 MHz04 Port only
J6 – Norm Det In2416.64 MHz ± 13.5 MHzI4 Port only
POWER IN
J1
NORM DET IN
J6
RADIAX
POWER IN
J1
NORM DET IN
J6
BDR 1
ZONE
Figure 2-1 DLA Forward Direction Interc onnect Diagram
RF PortFrequencyInput/Output4 Port/2 Port
RADIAX
BDR 2
ZONE
Table 2-1 – Forward Direction RF Port Functions
Document use is restricted to that described on cover2-3
Page 19
BDR 1
®
®
®
A
®
®
®
®
®
®
385700-4006-006INSTALLATION
USER Control
Equipment
HELIAX
RADIAX
DLA
ALARM/CONTROL
J2
NORM PA IN
LNA OUT
J4
NORM PA
OUT2
J5
NORM PA OUT1
LNA IN
J3
RADIAX
HELIAX
RADIAX
DL
ALARM/CONTROL
J2
NORM PA IN
LNA OUT
J4
NORM PA
OUT2
J5
NORM PA OUT1
LNA IN
J3
RADIAX
HELIAX
BDR 2
POWER IN
J1
NORM DET IN
J6
RADIAX
POWER IN
J1
VAC Power
BDR 2
BDR 1
ZONE
ZONE
Figure 2-2 DLA Forward Direction Interc onnect Diagram
RF PortFrequencyInput/Output4 Port/2 Port
J3 – LNA In2467.84 MHz ± 13.5 MHzOY
J3 – Norm PA Out12416.64 MHz ± 13.5 MHzIY
J4 – Norm PA In2416.64 MHz ± 13.5 MHzOY
J4 – LNA Out2467.84 MHz ± 13.5 MHzIY
J5 – Norm PA Out22416.64 MHz ± 13.5 MHzI4 Port only
J6 – Norm Det In2416.64 MHz ± 13.5 MHzO4 Port only
NORM DET IN
J6
RADIAX
Table 2-2 Reverse Direction RF Port Functions
Document use is restricted to that described on cover2-4
Page 20
385700-4006-006INSTALLATION
2.3.1 Connector Pin-outs
Refer to Figures Figure 2-3 and Figure 2-4 for the connector pin-out information for the
Distribution Line Amplifier por t s .
Figure 2-3 DLA Input VAC Pin-outs shows the pin assignments for the Distribution Line
Amplifier POWE R IN connector.
The DLA Power Connector is a MIL-C-26482, Series 2 connector. The connector is
MS3474W14-4P or equivalent. Mating connectors are MS3475W 14-4S, PV75W14-4S,
or equivalent.
Figure 2-3 DLA Input VAC Pin-outs
Document use is restricted to that described on cover2-5
Page 21
385700-4006-006INSTALLATION
Figure 2-4 DLA ALARM/CONTROL Port Pin-outs, shows the pin assignments for the
Distribution Line Amplifier ALARM/CONTROL connector.
Figure 2-4 DLA ALARM/CONTROL Port Pin-outs
The Alarm/Control connector is a MIL-C-26482, Series 1 connector. T he part is MS3124E2016P, KPSE07E20-16P, or equivalent. The mating connectors are MS3126F20-16S,
KPSE06F20-16S, or equivalent. These are crimp connecto rs with a grommet seal and strain
relief. Other options are available including a right angle plug assembly(KPSE08F20-16S)
and solder connections.
Document use is restricted to that described on cover2-6
Page 22
385700-4006-006INSTALLATION
2.4 DISTRIBUTION LINE AMPLIFIER COMPONENT JACK LOCATIONS
The following paragraphs describe the pur pose and location of the jacks for the Distribution
Line Amplifier. Refer to Figure 2-5 DLA Assembly Jack Locations. The amplifier connector
panel contains one data jack, ALARM/CONTROL (J2). The DLA exchanges status and
control signals with USER control equipment over ALARM/CONTROL (J2) port.
The NORM PA OUT1/LNA IN (J3) port and NORM PA IN/LNA OUT (J4) are connected to
RADIAX
®
cable via HELIAX® coaxial cable. The signal (downlink) coming from the BDR is
routed through the section of RADIAX cable to the NORM PA IN/LNA OUT (J4) port of the
DLA. The signal (uplink) com ing from the succeeding DLA NORM PA OUT1/LNA IN RF FWDOUT/RVS IN (J3) port is routed through the section of RADIAX cable to the next DLA in
cascade.
Port POWER IN (J1) connects the DLA to the AC power source.
In the normal direction, NORM PA OUT2 ((J5), if installed, is used with a non cascaded
section of RADIAX
In the normal direction, NORM DET IN (J6), if installed, is used to terminate a section of
RADIAX
®
cable.
®
cable.
Document use is restricted to that described on cover2-7
Figure 2-5 DLA Assembly Jack Locations
Page 23
385700-4006-006INSTALLATION
2.5 PREPARATION FOR USE
CAUTION
Before applying power to the Distribution
Line Amplifier, securely connect the RF
ports to 50-ohm terminations. Failure to
observe these cautions can damage the
equipment.
2.5.1 Distribution Line Amplifier Setup
A Distribution Line Amplifier is part of a wayside antenna system; a RADIAX based signal
distribution system. The amplif ier provides signal gain to of fset the signal loss of the system.
The signal loss is based on the length and type of cable used. The Dist ribution Line Amplif ier
includes gain adjustments for both channels as well as adjustable thresholds for the status
signals.
Channel 1, whose center frequency is 2416.64 MHz, is referred t o as the Power Amplifier ( PA)
or downlink channel. Refer Figure 1-3 DLA Internal View for the location of the PA module
(part number 385700-2012). The output of this channel is a nominal +30 dBm f or a two port
DLA. The output of a 4 port DLA is a nominal +27 dBm per PA output port. For the downlink
channel, the signal input level as well as the output level are monitored. R
, R2, and R3 are
1
adjustment points on the PA module. See Figure 2-7 PA Module Outline for more details.
Channel 2, whose center frequency is 2467.84 MHz, is referred t o as the Low Noise Amplifier
(LNA) or uplink channel. Refer to Figure 1-3 DLA Internal View, f or f or t he location of t he LNA
module (part number 385700-2011). A pilot tone module within the Distribut ion Line Amplif ier
serves as a constant input signal for the LNA channel. The output level of the pilot tone is
monitored within the LNA module. No user adjustment of this sig nal is required. Because of
the diplexers within the DLA the pilot tone may not be observable at the exter nal DLA coaxial
connectors. The input signal range of the LNA channel is approximately -30 dBm to < -100
dBm. R
and R2 are adjustment points on the LNA module. See Figure 2-8 LNA Module
1
Outline for more det ails.
A configuration sheet is included with the DLA that specifies the adjustable settings at the time
of shipping the equipment.
The direction of the DLA must be set by the user for proper operation. The am plifier direction
status is indeterminate after powering up the unit . T his manual assum es t hat either the user’s
system control interface is available or a test box similar t o an example given at the end of this
manual is used.
Document use is restricted to that described on cover2-8
Page 24
385700-4006-006INSTALLATION
2.5.2 Distribution Line Amplifier Initial Operational Adjustments
2.5.2.1 Input AC Power
The Distribution Line Amplifier AC power supply automatically senses the input AC voltag e.
The DLA input voltage range is 87-265 VAC. Refer to Table 1-2 Distribution Line Amplifier
Specifications.
2.5.2.2 Power Amplifier (PA) Channel (Channel 1)
The nominal output level of the PA channel, as set at the time of manufacturing, is set to +27
dBm (4 port) or +30 dBm (2 port). T he output alarm level is set f or a thr eshold of 10 dB below
the expected output level. The expected input is 0 dBm. The input signal level threshold is
set for 10 dB below the input level. If other levels are desired, the cust omer should contact
Andrew with additional information when ordering the equipment. Refer to Figure 2-7 PA
Module Outline, for PA adjustment point s locations.
2.5.2.2.1 PA Equipment Setup
The equipment requir ed t o adjust the PA output level is:
• Signal Generator
• Power Meter or Spectrum Analyzer
• Digital Volt Meter
• small Blade Screwdriver
• ≥ 10 dB power attenuator
• direction control signal
Refer to Table 4-2 Test Equipment for a listing of sug gested equipment . Refer to Fig ure 2-6
PA Output Level Test Setup, f or t est equipment setup.
Direction Control = Forward
Signal
Generator
J4
J2
Distribution Line
Amplifier Assembly
J3
≥10 dB
power
attenuator
Power Meter
or
Spectrum
Analyzer
Figure 2-6 PA Output Level Test Set up
The signal generator should be set for an output frequency of 2416.64 MHz with an output
level of 0 dBm.
The power meter, if used, should be conf igured to measure signals f rom 0 dBm t o +40 dBm.
This can be done by either using the appropriate power sensor head(s) or by using power
attenuators.
Document use is restricted to that described on cover2-9
Page 25
385700-4006-006INSTALLATION
The spectrum analyzer, if used, should be configured as follows:
Center Frequency2416.64 MHz
Span2 MHz
RBW30 KHz
VBW3 Hz
Ref. Levelas required
Attach a ≥ 10 dB, 2 watt or greater, power attenuator to t he spectrum analyzer RF input.
The direction control signal characteristics required will depend on the interface option
installed. The direction must be set t o t he NORMAL state.
R1 = Input Threshold Set
R2 = Output Level Set
R3 = Output Threshold Set
Figure 2-7 PA Module Outline
2.5.2.2.2 PA Input Alarm Adjustment
Set the signal generator out put to RF ON. Adjust the output level of the generator to 10 dB
less than the expected input level. If this level exceeds the range of the input detector, the
detector should be set to its minimum det ectable level.
Document use is restricted to that described on cover2-10
Page 26
385700-4006-006INSTALLATION
Attach a voltmeter to J4-3 on the Alarm I/O board. (PA input alarm test point). TP1 or TP2
can be used as the ground connection. Refer t o Figure 1- 3 DLA Internal View for the locat ion
of the Alarm and Control Int erface Board test points. Standard 0.080 test probes should be
used for test points.
Adjust R1 (Input Alarm Set) on the PA module for TP3 to go to the high condition (≥ 3 VDC),
low (≤1 VDC), and then high again. Reduce the signal generator level by 2 dB and verify that
the alarm is asserted. Increase the signal gener ator level by 4 dB and verify that the alarm is
negated. If needed, readjust R1 and repeat this process as necessary.
2.5.2.2.3 PA Output Adjustment
Set the signal generator output to RF ON at the nominal input level (i.e. 0 dBm). The
maximum input level is +5 dBm. Adjust R2 (Out put Power Set) on the PA module to obtain
the desired amplifier output level. Note that the actual level measured will depend on the
attenuation used on the spectrum analyzer or power meter.
2.5.2.2.4 PA Output Alarm Adjustment
Attach a voltmeter to J4-1 on the Alarm I/O relay board. (P.A. output Alarm test point). TP1 or
TP2 can be used as the ground connection.
Adjust the signal generator level as necessary to obtain 10 dB below the desired output power
as observed at J3 (FWD OUT/RVS IN) port. If this level exceeds the range of the output
detector, the detector should be set t o it s minimum detectable level.
Adjust R3 (output Alarm Set) on PA for high condition (> 3 VDC), low (< 1.0 VDC), and t hen
high again. Reduce the signal gener ator level until the alar m is assert ed. Ver if y that the out put
level is ± 2 dB of the desired level. If needed, readjust R3 and repeat this process as
necessary.
Document use is restricted to that described on cover2-11
The nominal gain of the LNA channel, as set at the time of manuf acturing, is set to 30 dB.
The output alarm level is set for a threshold nominally 10 dB below the expected output pilot
level. The expected signal input range is -40 to -90 dBm. If other settings are desired, the
customer should contact Andrew with additional information when ordering the equipment.
Refer to Figure 2-8 LNA Module Outline, for LNA adjustment points locations.
Figure 2-8 LNA Module Outline
2.5.2.3.1 LNA Adjustment Equipment Setup
The equipment requir ed t o adjust the LNA output level is:
• signal generator
• power meter or spectrum analyzer
• digital volt meter
• small Blade screwdriver
• ≥ 10 dB power attenuator
• 50 ohm SMA termination
• direction control interface
See Table 4-2 Test Equipment, for a listing of suggested equipment. Refer to Figure 2-9
Output Level Test Set Up, f or t est equipment setup.
LNA
The signal generator should be set for an output frequency of 2467.86 MHz with an output
level of -40 dBm.
The power meter, if used, should be configured to measure sig nals from -70 dBm to 0 dBm.
This can be done by either using the appropriate power sensor head(s) or by using
attenuators.
The spectrum analyzer, if used, should be configured as follows:
Document use is restricted to that described on cover2-12
Page 28
385700-4006-006INSTALLATION
Center Frequency2467 MHz
Span2 MHz
RBW30 KHz
VBW3 Hz
Ref. Levelas required
Attach a 10 dB, 2 watt or greater, power att enuator to the spectrum analyzer RF input.
The direction control signal characteristics required will depend on the interface option
installed. The direction must be set t o t he NORMAL state.
Direction Control = Forward
Power Meter
Signal
Generator
J3
Distribution Line
Amplifier Assembly
J4
or
Spectrum
Analyzer
≥10 dB
power
attenuator
Figure 2-9 LNA
Output Level Test Set Up
2.5.2.3.2 LNA Output Adjustment
Disconnect the pilot tone signal fr om the LNA module J5 Aux RF IN port. Terminate the pilot
tone input port with a 50 ohm termination.
Connect the signal generator t o J3 of the DLA as shown in Fig ure 2-9 LNA
Set Up.
Adjust R1 so that the signal at J3 at 2467 MHz is the desired level ±0. 5 dB. The maximum
output value for the LNA channel is +5 dBm.
With the LNA out put set, go to the next step to set the LNA output alarm adjustment.
Output Level Test
Document use is restricted to that described on cover2-13
Page 29
385700-4006-006INSTALLATION
2.5.2.3.3 LNA Output Alarm Adjustment
NOTE
The previous step must be completed
before adjusting the output alarm.
Attach a voltmeter to J4-2 (LNA output Alarm test point) on the Alarm I/O board. TP1 or TP2
can be used as the ground connection.
Adjust R2 on the LNA until the voltage on J4-2 goes high (≥ 3 VDC), low (≤ 1.0 VDC), and
then high again.
Decrease the signal generator output as required to obtain a 10 dB drop in out put level, from
the level set in the previous section, of the LNA channel.
Adjust R2 on the LNA until the voltage on TP2 g oes low (≤ 1.0 VDC), high (≥ 3 VDC), and
then low (≤ 1.0 VDC) again. Increase the sig nal generator input by 10 dB and verify that the
output alarm signal at TP2 is high (≥ 3 VDC) . Decrease the signal generator level by 10 dB
and verify that the output alarm sig nal at TP2 is low (≤ 1.0 VDC). Readjust R2 and repeat as
necessary.
Remove the SMA termination from the LNA m odule J5 Aux RF IN port and reattach the pilot
tone signal cable to the LNA module J5 Aux RF IN port.
2.5.3 Operational Check-Out
Attach a 2 watt or greater 10 dB power attenuat or t o the J3 and J4 ports of the DLA. From the
configuration documentation sent with the amplifier or using on site documentation that
reflects any changes from the factory setting s, determine the output level settings of the PA
and LNA channels, the PA input alarm level, and the PA and LNA output alar m levels.
2.5.3.1 Forward PA Channel Verification
Set the DLA direction to the forward direct ion.
2.5.3.1.1 PA Output Level Verification
Attach either a signal generator (freq uency = 2417 MHz) or a BDR to J4 (FWD IN/RVS O UT)
port of the Distribution Line Amplifier Assembly. Adjust the signal generator or BDR signal
level at J4 to 0 dBm ± 0.1 dB. Using a power meter verif y that the sig nal level at the J3 ( FWD
OUT/RVS IN) port of the Distribut ion Line Amplifier Assem bly equals G
is equal to the expected gain of t he PA channel. If the g ain is not equal to Gpa dBm ± 1
G
pa
dB, perform the steps out lined in section 2.5 f or the PA output adjustment . If af ter complet ing
the amplifier setup procedure t he output level of the PA channel is not G
dBm ± 1 dB where
pa
dBm ± 1 dB and all
pa
Document use is restricted to that described on cover2-14
Page 30
385700-4006-006INSTALLATION
external test measurement cable losses are accounted for, the am plifier should be replaced.
Contact Andrew for additional infor m at ion.
2.5.3.1.2 PA Input Signal Alarm
Attach a voltmeter to J4-3 on the Alarm I/O relay board (PA output alarm test point). TP1 or
TP2 can be used as the ground connection. After removing the signal from the J4 (FWD
IN/RVS OUT) port of the Distribut ion Line Amplif ier Assembly verify t hat J4- 3 is < 0.7 VDC. If
J4-3 is > 1.0 VDC, perform the steps outlined in section 2.5 for the PA input alarm adjust ment .
If after completing the amplif ier setup procedure the input alar m is not < 0. 7 VDC with no input
to J4, the amplifier should be replaced. Contact Andrew for additional inform at ion.
2.5.3.1.3 PA Output Signal Alarm
Attach a voltmeter to J4-1 on the Alarm I/O relay board (PA output alarm test point). TP1 or
TP2 can be used as the ground connection. After removing the signal from the J4 (FWD
IN/RVS OUT) port of the Distribut ion Line Amplif ier Assembly verify t hat J4- 1 is < 0.7 VDC. If
J4-1 is > 1.0 VDC perform the steps outlined in section 2.5 for the PA output alarm
adjustment. If after completing the amplif ier set up procedur e the input alar m is not < 0. 7 VDC
with the expected input to J4, the amplifier should be replaced. Contact Andrew for addit ional
information.
Document use is restricted to that described on cover2-15
Page 31
385700-4006-006INSTALLATION
2.5.3.2 Forward LNA Channel Verification
Set the DLA direction to the forward direct ion.
2.5.3.2.1 LNA Output Level Verification
Attach either a signal generator (f requency = 2467 MHz) or a MDR to J3 (FW D OUT/RVS IN)
port of the Distribution Line Amplifier Assembly. Adjust the signal generator or BDR signal
level at J3 to -50 dBm ± 1 dB. Using a power meter verif y that the sig nal level at the J4 (FWD
IN/RVS OUT) port of the Distribution Line Amplif ier Assembly equals G
is equal to the expected gain of t he LNA channel. If the gain is not equal t o G
G
lna
dBm ± 1 dB where
lna
dBm ± 1
lna
dB perform the steps outlined in sect ion 2. 5 for the LNA output adjustment. If after completing
the amplifier setup procedure the out put level of the LNA channel is not G
dBm ± 1 dB and
lna
all external test measurement cable losses are accounted for, the amplifier should be
replaced. Contact Andrew for additional information.
2.5.3.2.2 LNA Output Signal Alarm
This step assumes that the LNA output level has been set as explained in section 2.5.3.2.1
Attach a voltmeter to J4-2 on the Alarm I/O relay board (LNA output alarm test point). TP1 or
TP2 can be used as the ground connection. Remove the pilot tone cable from the LNA
module J5 Aux RF IN port port. Verify that J4-2 on the Alarm I/O relay board is < 0.7 VDC. If
J4-2 is > 0.7 VDC, perform the steps outlined in section 2.5 for the LNA output alarm
adjustment. If after completing the amplifier setup procedure the output alarm is not < 0.7
VDC with the previously set input level to J3, the amplifier should be replaced. Contact
Andrew for additional informat ion.
2.5.3.3 Reverse PA Channel Verification
Set the DLA direction to the reverse direction.
2.5.3.3.1 PA Output Level Verification
Attach either a signal generator (freq uency = 2417 MHz) or a BDR to J3 (FWD OUT /RVS IN)
port of the Distribution Line Amplifier Assembly. Adjust the signal generator or BDR signal
level at J3 to 0 dBm ± 1 dB. Using a power meter verify that the signal level at the J4 (FW D
IN/RVS OUT) port of the Distribution Line Am plifier Assembly eq uals G
is equal to the expected gain of t he PA channel. If the g ain is not equal to Gpa dBm ± 1
G
pa
dB and the Distribution Line Amplifier has not been tested for the forward direction, perf orm
the steps outlined in section 2.5 for the PA output adjustment. If after completing the
amplifier setup procedure the out put level of the PA channel is not G
external test measurement cable losses are accounted for, the am plifier should be replaced.
Contact Andrew for additional infor m at ion.
dBm ± 1 dB where
pa
dBm ± 1 dB and all
pa
Document use is restricted to that described on cover2-16
Page 32
385700-4006-006INSTALLATION
2.5.3.3.2 PA Input Signal Alarm
Attach a voltmeter to J4-3 on the Alarm I/O relay board (PA output alarm test point). TP1 or
TP2 can be used as the ground connection. After removing the signal from the J3 (FWD
OUT/RVS IN) port of the Distr ibution Line Amplif ier Assembly verify that J4-3 is < 0.7 VDC. If
J4-3 is > 0.7 VDC and the Distribution Line Amplifier has not been tested for the forward
direction, perform t he steps outlined in section 2.5 for the PA input alarm adjustment. If af ter
completing the amplifier setup procedure t he input alarm is not < 0.7 VDC with no input t o J4,
the amplifier should be replaced. Contact Andrew for additional information.
2.5.3.3.3 PA Output Signal Alarm
Attach a voltmeter to TP1 on the Alarm I/O relay board (PA output alarm test point). TP1 or
TP2 can be used as the ground connection. After removing the signal from J3 (FWD
OUT/RVS IN) port of t he Distr ibution Line Amplifier Assembly, verify that J4-1 is < 0.7 VDC. If
J4-1 is > 0.7 VDC and the Distribution Line Amplifier has not been tested for the forward
direction, perform the steps outlined in section 2.5 f or t he PA output alar m adj ustment . I f af te r
completing the amplifier setup procedure the input alar m is not < 0.7 VDC with the expected
input to J4, the amplifier should be replaced. Contact Andrew for additional infor m ation.
2.5.3.4 Reverse LNA Channel Verification
Set the DLA direction to the reverse direction.
2.5.3.4.1 LNA Output Level Verification
Attach either a signal generator (f requency = 2467 MHz) or a MDR to J4 (FW D IN/RVS OUT)
port of the Distribution Line Amplifier Assembly. Adjust the signal generator or BDR signal
level at J4 to -50 dBm ± 1 dB. Using a power meter verif y that the sig nal level at the J3 (FWD
OUT/RVS IN) port of the Distr ibution Line Amplif ier Assembly eq uals G
is equal to the expected gain of t he LNA channel. If the gain is not equal t o G
G
lna
dBm ± 1 dB where
lna
dBm ± 1
lna
dB and the Distribution Line Amplifier has not been tested for the forward direction, perf orm
the steps outlined in section 2.5 for the LNA output adjustment. If after completing the
amplifier setup procedure the output level of t he LNA channel is not G
dBm ± 1 dB and all
lna
external test measurement cable losses are accounted for, the am plifier should be replaced.
Contact Andrew for additional infor m at ion.
2.5.3.4.2 LNA Output Signal Alarm
This step assumes that the LNA output level has been set as explained in section 2.5.3.2.1
Attach a voltmeter to J4-2 on the Alarm I/O relay board (PA output alarm test point). TP1 or
TP2 can be used as the ground connection. Remove the pilot tone cable from the LNA
module J5 Aux RF IN port. Verify that J4- on the Alarm I/O relay board is < 0.7 VDC. If J4-2
is > 0.7 VDC, perform the st eps outlined in section 2.5 for the LNA output alarm adj ustment.
If after com pleting the amplifier setup procedure the output alar m is not < 0.7 VDC with the
previously set input level to J3, the amplifier should be replaced. Cont act Andrew for additional
information.
Document use is restricted to that described on cover2-17
Page 33
385700-4006-006OPERATIONS
CHAPTER 3
OPERATIONS
3.1 WIRING PROTECTION AND GROUNDING
The Distribution Line Amplifier does not have controls and indicators accessible from the
outside of the unit. The DLA has two 10 Ampere fuses F1 and F2 for wiring protection on the
connector panel. Refer to Fig ure 3-1 DLA Connector Panel Layout.
There is a ground stud on the DLA connector panel f or a ground wire connection. Refer to
Figure 3-1 DLA Connector Panel Layout.
Document use is restricted to that described on cover3-1
Figure 3-1 DLA Connector Panel Layout
Page 34
385700-4006-006OPERATIONS
3.2 STARTUP AND SHUTDOWN PRODECURES
The following procedures ensure that installation does not damage the equipment.
3.2.1 DLA Startup
Refer to section 4.2.1, for procedures to properly install the DLA. Mount the DLA in the
equipment room or in the tunnel with no connections made. To start the DLA perform t he
following:
®
1. Securely connect HELIAX
cables to DLA J3 and J4 ports.
2. Connect the USER control equipment to the DLA connector panel J2 port.
3. Connect the VAC power supply to the DLA J1 port.
3.2.2 Normal Operation
Refer to section 1.4.1, Dist ribution Line Amplifier Principles of O peration.
3.2.3 Shutdown
Disconnect the DLA from the VAC power source.
WARNING
IN CASE OF EMERGENCY; Immediately
turn off power to the unit.
Document use is restricted to that described on cover3-2
Page 35
385700-4006-006MAINTENANCE AND TROUBLESHOOTING
CHAPTER 4
MAINTENANCE AND TROUBLESHOOTING
4.1 TROUBLESHOOTING
Before beginning any in-depth tr oubleshooting, ensure that power is available to the unit. Ensure
that all cable connections are secure.
Table 4-1 DLA Fault Isolation, describes the troubleshooting procedures for t he DLA. Locate
the unit’s symptom in the Fault Indication column. The Fault Description column lists
components or functions that can cause faults. The last column, Corrective Action, specifies the
action necessary to correct the fault. After taking corrective action, per form the appropriate
diagnostic procedure to verify that the correct ion was successful.
For malfunctions that the fault isolation table does not list, contact Andr ew’s technical support
personnel.
NOTE
The following table onl y isolates f aul ts to
the LRU level. The test procedures in
Section III of this chapter provide
assistance for further fault isolati on. I f an
LRU fails, return it to the equipment
manufacturer for maintenance or repair.
1No output signalNo input powerVerify power input cable
2No output signalNo power in amplifierReplace fuses
3No output signalsPoor connectionsVerify connections
4
RADIAX
Alarm
No BDR input signalVerify cables connections to J4 (forward
direction) or J3 (reverse direction)
5
RADIAX
Alarm
No BDR input signalVerify preceding cascaded amplifier is
operational
6
RADIAX
7Amplifier AlarmNo BDR and/or MDR
Alarm
No BDR input signalIf valid inputs, replace amplifier
If valid inputs, replace amplif ier
output RF signals
8Direction Control
invalid status
Direction control status
is opposite of direction
If valid inputs, replace amplif ier
control input control
Document use is restricted to that described on cover4-1
Table 4-1 DLA Fault Isolation
Page 36
385700-4006-006MAINTENANCE AND TROUBLESHOOTING
4.2 CORRECTIVE MAINTENANCE
This section describes the removal and replacement of the DLA. See Table 4-1 DLA Fault
Isolation, to determine when to remove and replace a line r eplaceable unit ( LRU).
4.2.1 Remove and Replace DLA
Referring to Figure 4-1 Remove and Replace DLA, perf orm the following actions to r emove the
DLA (shown as Item 2)
1. Disconnect VAC power cable from DLA (2) POWER IN (3) port.
2. Disconnect the USER control equipment data cable that attaches to the DLA’s
ALARM/CONTROL port (6).
®
3. Disconnect the HELIAX
4. Disconnect grounding wire from the grounding stud (7) on the connector panel of
the DLA.
5. Remove four bolts (1) f r om the DLA (2) mounting brackets.
6. Remove DLA (2).
Referring to Figur e 4-1 Remove and Replace DLA, perform t he following actions to replace t he
DLA:
1. Place DLA (2) in position.
2. Secure DLA (2) with four bolts (1) .
3. Reconnect the HELIAX cables to RADIAX input / output ports (4) and (5).
4. Reconnect the USER control equipment data cable that attaches to the DLA’s
ALARM/CONTROL port (6).
5. Reconnect the grounding wire to grounding stud (7).
6. Reconnect the VAC power cable to the POWER IN (3) port.
7. Configure Channel 1 and Channel 2 output level and status alarm
adjustments per section 2.5.2 if not already performed.
cables from the RADIAX® input/out ports (4) and (5).
Document use is restricted to that described on cover4-2
Page 37
385700-4006-006MAINTENANCE AND TROUBLESHOOTING
1
2
7
3
6
4
5
Figure 4-1 Remove and Replace DLA
Document use is restricted to that described on cover4-3
Page 38
385700-4006-006MAINTENANCE AND TROUBLESHOOTING
4.3 TEST PROCEDURES
Refer to Table 4-2 Test Equipment, for a list of test equipment to perform the following test
procedures. If necessary, substitut e an equivalent to the equipment listed.
The following test procedures help the user verif y that a DLA is f ault y. Ret urn f aulty am plif iers t o
Andrew Corporation for maintenance and repair . Refer to paragr aph 2.1.1 for equipment return
information.
Equipment
Qty
Spectrum Analyzer1HP8561B
Power Meter1HP437B
Power Sensor1HP8481A
Power Sensor1HP8481D
Digital Volt Meter1Fluke Model 77
RF Signal Generator1HP 8664A
10 dB Power AttenuatorAs requiredInmet 6N10W-10
Variable AttenuatorAs requiredHP 8495B
Coaxial CablesAs required
Table 4-2 Test Equipment
4.3.1 Inoperative Distribution Line Amplifier
WARNING
Part Number
4.3.1.1 Input Power Verification
Disconnect the power connector to the DLA. Using a DVM verify the levels of the AC input
voltage. See Figure 2-3 DLA Input VAC Pin-outs for additional infor mation. If the input power
level is present, reconnect the power connector to the DLA.
If the input power is available to the DLA, open the amplifier and verify that the LED on the power
supply is illuminated. See Figure 1-3 DLA Internal View. If the LED is illuminated, then verify the
coaxial and Alarm/control signal connections.
If the power supply LED is not illuminated, unscrew the two fuses at t he DLA connector plate.
Document use is restricted to that described on cover4-4
DANGER! High voltage shock hazard.
Page 39
385700-4006-006MAINTENANCE AND TROUBLESHOOTING
Remove the fuses from the holder. Measure the resistance across the fuses. If the r esistance is
> 1.0 ohms, replace the fuse. Reinst all the fuses in the DLA. If the fuses are oper ational and
the power supply remains off, replace t he Dist ribution Line Amplifier.
4.3.1.2 RADIAX
Alarm Asserted
Assertion of the RADIAX input alarm indicates a loss of signal (Signal Center Frequency is
2416.64 MHz) from the preceding Distribution Line Amplifier and or base station radio. The
following trouble shooting procedure assumes that the amplifiers are cascaded in the forward
configuration normal direction mode and that the amplifier has been correctly configured as
indicated in 2.5.
Visually inspect the cable assemblies from the preceding amplifier or radio f or loose connections
and or cable breakage. Tighten all cable connections. Replace br oken or damaged cables as
necessary.
If all cable assemblies are secure and intact, disconnect the cable at J4 of the DLA. Using a
power meter or spectrum analyzer attached to the cable, verif y the presence and expected level
of the RF signal (F
= 2416.64 MHz, 0 dBm nominal). If the signal is present and the alarm is
c
configured correctly (ref er t o section 2.5.2. 2.2) the am plifier should be replaced. If the RF signal
is not present continue to determine the or igin of the signal loss.
4.3.1.3 Amplifier Alarm Asserted
Assertion of the Amplif ier Alar m can be caused by:
• Loss of an input signal on the PA Channel (RADIAX Alar m Asser ted)
• Failure of the PA module
• Loss of the Pilot Tone Signal t o the LNA module
• Failure of the LNA module.
4.3.1.3.1 Loss of PA Input Signal
When the RADIAX Alarm is asserted, t he loss of input signal can also cause the PA module to
also assert its output alarm. With a loss of input signal, the PA module gain is insufficient to
generate a signal level above the level represented by the output thr eshold detector in the PA
module. If both the RADIAX alarm signal and t he Amplifier Alarm sig nals are asser ted, the user
should determine the cause for the loss of input signal.
4.3.1.3.2 PA Module Failure
If the input signal to t he PA channel is at the expected level and the PA channel out put alarm is
asserted, either the PA module has failed or it is incorrectly configured. T he PA module output
alarm can be monitored with a DVM at J4-1 of the Relay/IO board. A voltage level < 1 VDC
indicates a fault condition for the PA channel.
The output signal can be measured with a power meter or spectrum analyzer. If no signal is
detected at the Distribution Line Amplifier output port (J3 f or the forward direction) the unit should
be returned to Andrew Corporation. If a signal is present, the user should confirm that the
amplifier output is below the levels indicated on the configuration sheet attached to the
Distribution Line Amplifier. I f t he input and output signal levels are at t he levels specif ied on the
Document use is restricted to that described on cover4-5
Page 40
385700-4006-006MAINTENANCE AND TROUBLESHOOTING
configuration sheet, t he PA module alarm may be indicating a faulty setting on the output level
monitor. Refer to sect ion 2.5.2.2.4 for details on setting the output alarm. If the output level
monitor is correctly configured, the Distribution Line Amplifier should be returned to Andrew
Corporation.
4.3.1.3.3 Loss of Pilot Tone Signal
In a correctly configured DLA, the pilot tone is monitored by the LNA output detector circuit.
Without the pilot tone there may not be sufficient signal at the LNA module output. As a result,
the LNA module will signal an amplifier failure. T he pilot t one sig nal can be monit ored with either
a power meter or a spectrum analyzer.
Figure 1-3 DLA Internal View shows the location of the pilot tone module and its output port J3.
The expected output at the pilot tone module J3 port is a nominal - 10 dBm signal at 2401 ± 2
MHz. If this signal is not present, the Distribution Line Am plifier should be returned to Andrew
Corporation. If the signal is present, reattach the cable fr om J3 of the pilot tone module to the
LNA module AUX RF input port. Tigh t en t he connections as necessary.
4.3.1.3.4 LNA Module Failure
If the pilot tone signal t o the LNA channel is at the expected level and the LNA channel output
alarm is asserted, either the LNA module has failed or it is incorrectly configured. The LNA
module output alarm can be monitored with a DVM at J4-2 on the Relay/IO board. A voltage
level < 1 VDC indicates a fault condition for the LNA channel.
In order to measure the output of the LNA channel, it is necessary to inject an external signal into
the LNA channel. The external signal can be either a CW signal at a frequency in the passband
of the LNA channel (see Table 1-2 Distribution Line Amplifier Specifications in section 1.5. 2) or it
can be the output signal of an MDR. In either case, the signal input level to J3 of the DLA
(normal forward config uration) should be -50 dBm.
Based on the gain setting specified on t he configuration sheet attached to t he DLA, the external
signal can be verified with a power meter or spectrum analyzer. If no signal is detected at the
Distribution Line Amplifier output port (J4 for t he f orward direct ion) t he DLA should be ret urned t o
Andrew Corporation. If a signal is pr esent, the user should confirm that the amplif ier output is
below the levels indicated on the configuration sheet att ached to the Distribution Line Amplifier .
If the measured level is below the expected value the Distribution Line Amplifier should be
returned to Andrew Corporation. If the input and output signal levels are at the levels specif ied
on the configuration sheet, the PA module alarm may be indicat ing a f aulty sett ing on t he output
level monitor. Refer to section 2.5 for details on sett ing the output alarm. If the output level
monitor is correctly configured, the Distribution Line Amplifier should be returned to Andrew
Corporation
Document use is restricted to that described on cover4-6
Page 41
385700-4006-006ORDERING INFORMATION
CHAPTER 5
ORDERING INFORMATION
5.1 PARTS LIST
This chapter provides a list of replacement parts and mating connectors for the Distribution
Line Amplifier assembly. It also provides vendor names and addresses. Table 1-1 – DLA
Part Numbers lists the various versions of the DLA and t heir respective part num bers. Figure
1-1 Distribution Line Amplifier ( 4 por t) shows all of the items on the list . To procure any of the
parts, contact Andrew Corporation or the appr opr iate vendor for the part.
The parts list includes three columns: Description, Part Number, and Quantity (Qty). The
Description column identifies the specif ic part , beg inning with the assembly or line-r eplaceable
unit (LRU) that contains it. The information in the Description column includes an (AP) symbol
to denote attaching hardware for the LRUs. The Part Number column provides the vendor’s
number for that drawing or par t. T he Quantity column def ines how many of the part icular part
the next higher assembly (NHA) contains.
Table 5-1 provides a list of applicable vendors and their addresses.
Vendor
Andrew Corporation2601 Telecom Parkway
ITT Corporation
ITT Canon Division
BussmanP.O. Box 14460
Table 5-1 Vendors
Address (Phone Number)
Richardson, Texas 75082-3521
(972) 235-7300
666 East Dyer Road
Santa Ana, CA 92702
St Louis, MO 63178
314-394-2877
Document use is restricted to that described on cover5-1
Page 42
385700-4006-006ORDERING INFORMATION
Table 5-2 provides a list of replaceable parts and mating connectors for the am plifier
assemblies.
DescriptionPart NumberQty
Distribution Line Amplifier385700-40001
Mating Power Connector Assembly (J1)MS3475W14-4S1
Mating Alarm/Control Connector (J2)MS3126F20-16S or
1
KPSE08F20-16S
AC Fuses (F1, F2)Bussman MDA-102
Table 5-2 Parts List
Document use is restricted to that described on cover5-2
Page 43
385700-4006-006 MECHANICAL INFORMATION
CHAPTER 6
MECHANICAL INFORMATION
Document use is restricted to that described on cover6-1
Figure 6-1 DLA Mechanical Outline
Page 44
385700-4006-006 ALARM/CONTROL TEST
CIRCUIT
Document use is restricted to that described on cover7-1
CHAPTER 7
ALARM/CONTROL TEST CIRCUIT
The following schematic can be used to construct a test fixture to control the direction of the DLA and to monit or t he status of the various
Figure 7-1
Page 45
385700-4006-006 ALARM/CONTROL TEST
CIRCUIT
Document use is restricted to that described on cover7-2
Page 46
385700-4006-006 ALARM/CONTROL TEST
CIRCUIT
Document use is restricted to that described on cover7-3
Page 47
385700-4006-006 ALARM/CONTROL TEST
CIRCUIT
Document use is restricted to that described on cover7-4
Page 48
385700-4006-006 ALARM/CONTROL TEST
CIRCUIT
Document use is restricted to that described on cover7-5
alarms. The test fixture connects to J2 Alarm/Control of the DLA. This t est f ixture r equ ires an external 24 VDC supply. T he circuit should be
mounted within a metal enclosure so that the required cable shielding integrity is maintained.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.