AMETEK SFA Series User Manual

SFA Series DC
Power Supplies
Operation Manual
M550292-01 Rev G www.programmablepower.com
About AMETEK
AMETEK, Inc. is a leading global manufacturer of electronic instruments and electromec hanical devices with annualized sales of $2.5 billion. The Company has over 11,000 colleagues working at more than 80 manufacturing facilities and more than 80 sales and service centers in the United States and around the world.
Trademarks
AMETEK is a registered trademark of AMETEK, Inc. Other trademarks, registered trademarks, and product names are the property of their respective owners and are used herein for identification purposes only.
Notice of Copyright
SFA Series DC Power Supplies Operation Manual
Inc. All rights reserved.
© 2004-2008 AMETEK Programmable Power,
Exclusion for Documentation
UNLESS SPECIFICALLY AGREED TO IN WRITING, AMETEK PROGRAMMABLE POWER, INC. (“AMETEK”):
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY
TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR
EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK, AND
(c) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH,
ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURA CY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED AMETEK CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION, WHICH IS POSTED AT WWW.PROGRAMMABLEPOWER.COM.
Date and Revision
June 2009 Revision G
Part Number
M550292-01
Contact Information
Telephone: 800 733 5427 (toll free in North America) 858 450 0085 (direct) Fax: 858 458 0267 Email: sales@programmablepower.com service@programmablepower.com Web: www.programmablepower.com
i
This page intentionally left blank.
ii
G
G
Important Safety Instructions
Before applying power to the system, verify that your product is configured properly for your particular application.
WARNIN
WARNIN
Only qualified personnel who deal with attendant hazards in power supplies, are allowed to perform installation and servicing.
Ensure that the AC power line ground is connected properly to the Power Rack input connector or chassis. Similarly, other power ground lines including those to application and maintenance equipment must be grounded properly for both personnel and equipment safety.
Always ensure that facility AC input power is de-energized prior to connecting or disconnecting any cable.
In normal operation, the operator does not have access to hazardous voltages within the chassis. However, depending on the user’s application configuration, HIGH VOLTAGES HAZARDOUS TO HUMAN SAFETY may be normally generated on the output terminals. The customer/use r must ensure that the output power lines are labeled properly as to the safety hazards and that any inadvertent contact with hazardous voltages is eliminated.
Guard against risks of electrical shock during open cover checks by not touching any portion of the electrical circuits. Even when power is off, capacitors may retain an electrical charge. Use safety glasses during open cover checks to avoid personal injury by any sudden component failure.
Neither AMETEK Programmable Power Inc., San Diego, California, USA, nor any of the subsidiary sales organizations can accept any responsibility for personnel, material or inconsequential injury, loss or damage that results from improper use of the equipment and accessories.
Hazardous voltages may be present when covers are removed. Qualified personnel must use extreme caution when servicing this equipment. Circuit boards, test points, and output voltages also may be floating above (below) chassis ground.
The equipment used contains ESD sensitive ports. When installing equipment, follow ESD Safety Procedures. Electrostatic discharges might cause damage to the equipment.
SAFETY SYMBOLS
iii
This page intentionally left blank.
iv
Product Family: SFA Series DC Power Supplies
Warranty Period: Five Years
WARRANTY TERMS
AMETEK Programmable Power, Inc. (“AMETEK”), provides this written warranty covering the Product stated above, and if the Buyer discovers and notifies AMETEK in writing of any defect in material or workmanship within the applicable warranty period stated above, then AMETEK may, at its option: repair or replace the Product; or issue a credit note for the defective Product; or provide the Buyer with replacement parts for the Product.
The Buyer will, at its expense, return the defective Product or parts thereof to AMETEK in accordance with the return procedure specified below. AMETEK will, at its expense, deliver the repaired or replaced Product or parts to the Buyer. Any warranty of AMETEK will not apply if the Buyer is in default under the Purchase Order Agreement or where the Product or any part thereof:
is damaged by misuse, accident, negligence or failure to maintain the same as
specified or required by AMETEK;
is damaged by modifications, alterations or attachments thereto which are not
authorized by AMETEK;
is installed or operated contrary to the instructions of AMETEK;
is opened, modified or disassembled in any way without AMETEK’s consent; or
is used in combination with items, articles or materials not authorized by AMETEK.
The Buyer may not assert any claim that the Products are not in conformity with any warranty until the Buyer has made all payments to AMETEK provided for in the Purchase Order Agreement.
PRODUCT RETURN PROCEDURE
1. Request a Return Material Authorization (RMA) number from the repair facility (must be done in the country in which it was purchased):
In the USA, contact the AMETEK Repair Department prior to the return of the
product to AMETEK for repair: Telephone: 800-733-5427, ext. 2295 or ext. 2463 (toll free North America)
858-450-0085, ext. 2295 or ext. 2463 (direct)
Outside the United States, contact the nearest Authorized Service Center
(ASC). A full listing can be found either through your local distributor or our website, www.programmablepower.com, by clicking Support and going to the Service Centers tab.
2. When requesting an RMA, have the following information ready:
Model number
Serial number
Description of the problem
NOTE: Unauthorized returns will not be accepted and will be returned at the shipper’s expense. NOTE: A returned product found upon inspection by AMETEK, to be in specification is subject to
an evaluation fee and applicable freight charges.
v
This page intentionally left blank.
vi
FCC NOTICE
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
M550292-01 Rev G
vii
This page intentionally left blank.
viii
M550292-01 Rev G
ABOUT THIS MANUAL
This manual has been written expressly for the Sorensen SFA Series of power supplies that have been designed and certified to meet the Low Voltage and Electromagnetic Compatibility Directive Requirements of the European Community.
Since the Low Voltage Directive is to ensure the safety of the equipment operator, universal graphic symbols have been used both on the unit itself and in this manual to warn the operator of potentially hazardous situations (see Safety page).
M550292-01 Rev G
ix
This page intentionally left blank.
x
M550292-01 Rev G
CONTENTS
SECTION 1 OVERVIEW.....................................................................1-1
1.1 GENERAL DESCRIPTION...............................................................1-1
1.2 TECHNICAL SPECIFICATIONS ........................................................1-2
1.2.1 Environmental Characteristics................................................................1-2
1.2.2 Electrical Characteristics........................................................................1-3
1.2.3 SFA Series Voltage and Current Specifications.....................................1-4
1.2.4 Physical Characteristics .........................................................................1-5
SECTION 2 INSTALLATION...............................................................2-1
2.1 INSPECTION................................................................................2-1
2.2 CONTENTS OF SHIPMENT.............................................................2-1
2.3 INPUT/OUTPUT CONNECTIONS .....................................................2-2
2.4 LOCATION AND MOUNTING ...........................................................2-3
2.4.1 6U Chassis Removal from Rack.............................................................2-3
2.5 WIRE SELECTION........................................................................2-6
2.5.1 Wire Size................................................................................................2-6
2.6 LOAD CONSIDERATIONS...............................................................2-8
2.6.1 Inductive Loads ......................................................................................2-8
2.7 OUTLINE DRAWINGS....................................................................2-8
SECTION 3 OPERATION ...................................................................3-1
3.1 CONTROLS AND INDICATORS........................................................3-1
M550292-01 Rev G ix
Contents Sorensen SFA Series
3.1.1 Shaft Lock (Option) ................................................................................3-4
3.2 LOCAL OPERATION ..................................................................... 3-4
3.2.1 Floating and Polarized Output................................................................3-5
3.2.2 Initial Setup.............................................................................................3-5
3.2.3 Current Mode Operation.........................................................................3-6
3.2.4 Overcurrent Protection...........................................................................3-6
3.2.5 Analog Control Connector (J1)...............................................................3-7
3.3 REMOTE CURRENT PROGRAMMING............................................3-11
3.4 REMOTE SENSING ....................................................................3-12
3.5 REMOTE OUTPUT ON/OFF CONTROL .........................................3-14
3.6 REMOTE OVERCURRENT SETPOINT............................................3-15
3.7 REMOTE SHUTDOWN (S/D) .......................................................3-16
3.8 MASTER/SLAVE OPERATION......................................................3-16
3.8.1 Parallel Operation.................................................................................3-16
SECTION 4 VERIFICATION AND CALIBRATION..............................4-1
4.1 INTRODUCTION ...........................................................................4-1
4.1.1 Verification and Calibration Cycle ..........................................................4-1
4.1.2 Preparation.............................................................................................4-1
4.2 STANDARD VERIFICATION AND CALIBRATION PROCEDURE.............. 4-2
4.2.1 Current Mode .........................................................................................4-2
4.2.2 Resistor Programming Current Sources ................................................4-3
4.3 ISOLATED ANALOG (OPTION) VERIFICATION AND CALIBRATION
PROCEDURE...............................................................................4-3
4.3.1 Current Mode .........................................................................................4-4
SECTION 5 MAINTENANCE..............................................................5-1
5.1 INTRODUCTION ...........................................................................5-1
5.2 PREVENTIVE MAINTENANCE.........................................................5-1
5.3 FUSES .......................................................................................5-3
M550292-01 Rev G
x
Sorensen SFA Series Contents
LIST OF TABLES
Table 2–1. 5kW to 15kW and 20kW to 30kW Series Input/Output Connectors..................2-4
Table 2–2. Input Connections.............................................................................................2-4
Table 2–3. Output Connections ..........................................................................................2-4
Table 2–4. Minimum Wire Size ...........................................................................................2-6
Table 2–5 Wire Resistance and Voltage Drop....................................................................2-7
Table 2–6 Maximum AC Current Ratings ...........................................................................2-8
Table 2–7 Recommended Lugs..........................................................................................2-8
Table 2–8. Recommended Sense Connector Tools ...........................................................2-8
Table 3–1. ANALOG CONTROL Connector (J1), Designations and Functions................3-10
Table 5–1. Recommended Annual Inspection....................................................................5-2
Table 5–2. Fuse Values......................................................................................................5-3
LIST OF FIGURES
Figure 1-1. Model Number Decoding..................................................................................1-1
Figure 2-1. SFA Series Outline Drawing, 3U Models, 5kW to 15kW...................................2-9
Figure 2–2. SFA Series Outline Drawing, 6U Models, 20kW to 30kW ..............................2-10
Figure 3-1. Front Panel Controls and Indicators (3U model shown)...................................3-1
Figure 3-2. Rear Panel Connectors (3U model shown) ......................................................3-3
Figure 3-3. Shaft Lock.........................................................................................................3-4
Figure 3-4. ANALOG CONTROL Connector (J1) Pin-out...................................................3-8
Figure 3–5. Remote Current Programming Using Resistance..........................................3-11
Figure 3–6. Remote Current Programming Using 0-5 VDC or 0-10 VDC Voltage Source3-12
Figure 3–7. Remote Sensing Operation at the Load * ......................................................3-13
Figure 3–8. Remote On/Off Control by Contact Closure ...................................................3-14
Figure 3–9. Remote On/Off Using Isolated AC or DC Voltage Source.............................3-14
Figure 3–10. Remote On/Off Using Isolated TTL/CMOS Voltage Supply.........................3-15
Figure 3–11. Remote Overcurrent Set Using DC Voltage Source....................................3-15
Figure 3–12. Remote Shutdown Using DC Voltage Source..............................................3-16
Figure 3–13. Master/Slave Connection.............................................................................3-17
Figure 4-1. Precision Current Shunt....................................................................................4-2
Figure 4-2. Potentiometer Locations...................................................................................4-5
M550292-01 Rev G
xi
M550292-01 Rev G xii
1.1 GENERAL DESCRIPTION
The Sorensen SFA Series power supplies are designed specifically for high power laser driver applications requiring variable DC current sources with fast output response times.
SECTION 1
OVERVIEW
A variety of user interfac es are available, ranging from man ual front–panel co ntrol and standard non–isolated remote analog control, to optional GPIB or isolated remote analog control.
NOTE: The SFA Series power su pplies a re not designed for series operation and therefore must not be used as such.
Figure 1-1 decodes the SFA Series model number.
Figure 1-1. Model Number Decoding
M550292-01 Rev G 1-1
Sorensen SFA Series Overview
1.2 TECHNICAL SPECIFICATIONS
The following sections provide environmental, electrical, and physical characteristics for the SFA Series power supplies.
Note: Specifications are subject to change without notice. Note: The SFA Series power supplies are intended for indoor use only. Please
refer to Section 2.4 for use/location requirements.
1.2.1 ENVIRONMENTAL CHARACTERISTICS
Parameter Specification
Temperature Coefficient Ambient Temperature
Operating Storage
Cooling
Humidity
Altitude
0.03%/°C of maximum output current rating for current set point.
0 to 50°C
-25° to 65°C Internal fans; vents on sides and rear. (Units may be stacked without
clearance above or below). 95% maximum, non-condensing, 0 to 50°C; 45°C maximum wet-bulb
temperature Operating full power available up to 5,000 feet (1,524m),
derate 10% of full power for every 1,000 feet higher non-operating to 40,000 feet (12,192m)
1-2 M550292-01 Rev G
Sorensen SFA Series Overview
1.2.2 ELECTRICAL CHARACTERISTICS
Parameter Specification
Input Power
Voltage (Standard) 208/220 VAC±10% (tested to 187-242 VAC)
Voltage (Options)
Frequency 47 to 63 Hz
Phases
380/400 VAC±10% (tested to 342-440 VAC) 440/480 VAC±10% (tested to 396-528 VAC)
3–phase, 3–wire plus ground. Not phase rotation sensitive. Neutral not used.
Front Panel Meter Accuracy
Voltage ±0.5% of full-scale + 1 digit Current ±0.5% of full-scale + 1 digit Load Regulation (Specified at no load to full load, nominal AC input) Current 0.1% of maximum output current Line Regulation (Specified ±10% of nominal AC input, constant load)
Current 0.05% of maximum output current
Current Ripple 1% p-p of full-scale current
The output current will recover to within 1% of the set current
Transient Response
value within 1ms for a 10 to 100% or 100% to 10% step load change
(10-90% current, full resistive load, nominal AC input):
250A/ms (400A/ms typical) rise, 200A/ms typical fall;
Output Slew Rate
Current Overshoot
Stability
Remote Control/Monitor
Power Factor
M550292-01 Rev G
160V models, 87A/ms/5kW (145A/ms/5kW typical), rise, 60A/ms, typical, fall
100V models, 190A/ms/5kW (238A/ms/5kW typical), rise, 104A/ms, typical, fall
Maximum 8% of full-scale for 0 to 100% change into a resistive load
±0.05% of set point after 8–hr. warm-up at fixed line, load, and temperature.
On/Off control via contact closure, 6-120 VDC or 12-240 VAC, and TTL or CMOS switch, current monitor, OCP limit set, summary fault status
>0.9 typical for 208/220VAC input >0.78 typical for 380/400VAC input >0.7 typical for 440/480VAC input
1-3
Sorensen SFA Series Overview
Parameter Specification
Efficiency 87% typical at full load, nominal line
REMOTE PROGRAMMING
Accuracy
CONSTANT CURRENT ±0.8% of full-scale output Overcurrent Protection ±1% of full-scale output
Resistive Control Input
CONSTANT CURRENT (0-100%)
Voltage Control Input
Constant Current (0-100%) 0–5 VDC or 0–10 VDC Overcurrent Protection (OCP)
(0-110%)
Remote Sensing
Overvoltage Protection
ISOLATED ANALOG CONTROL (OPTION)
Input to Output Isolation
0–5 k
0–5.5 VDC
Terminals are provided to sense output voltage at point of load for accurate voltage measurement.
Fixed at approximately 110% of the rating compliance voltage. Reset requires cycling the front panel standby power switch off/on
600 V Compliant with maximum terminal float voltage. Recommended operation under SELV normal conditions. (Standard Non-isolated Analog programming 300V maximum. Recommended operation under SELV normal conditions).
1.2.3
SFA SERIES VOLTAGE AND CURRENT SPECIFICATIONS
Ratings
Voltage 5 kW 10 kW 15 kW 20 kW 25 kW 30 kW
0-60V 0-83A 0-167A 0-250A 0-333A 0-417A 0-500A 0-100V 0-50A 0-100A 0-150A 0-200A 0-250A 0-300A 0-160V 0-31A 0-63A 0-94A 0-125A 0-156A 0-188A
NOTE: Contact factory for availability on specific models
1-4 M550292-01 Rev G
Sorensen SFA Series Overview
1.2.4 PHYSICAL CHARACTERISTICS
Dimension 3U Models 6U Models
Width 19.00 in (48.3 cm) 19.00 in (48.3 cm) Depth 25.12 in (63.8 cm) 25.12 in (63.8 cm) Height 5.25 in (13.3 cm) 10.5 in (26.7 cm) Weight 80 lbs (36 kg) maximum 160 lbs (73 kg) maximum
M550292-01 Rev G
1-5
Sorensen SFA Series Overview
This page intentionally left blank.
1-6 M550292-01 Rev G
2.1 INSPECTION
Inspect the shipping carton for possible damage before unpacking the unit. Carefully unpack the equipment. Save all packing materials until inspection is complete. Verify that all items listed on the packing slips have been received. Visually inspect all exterior surfaces for broken knobs, connectors, or meters. Inspect for dented or damaged exterior surfaces. External damage may be an indication of internal damage. If any damage is evident, immediately contact the carrier that delivered the unit and submit a damage report. Failure to do so could invalidate future claims. Direct repair issues to Customer Service at 1­800-733-5427.
SECTION 2
INSTALLATION
2.2 CONTENTS OF SHIPMENT
Depending on the model, configuration, and options available for your SFA Series power supply, the ship kit may include additional parts and accessories. At a minimum, the ship kit that accompanies your SFA Series power supply includes the following items:
AMETEK manuals CD-ROM, Part No. M550008-01 containing the SFA Series DC Power Supplies Operation Manual Part No. M550292-01 (this manual)
Sense mating connector (Molex P/N 39-01-4031) with loose contacts (Molex P/N 39-00-0182)
J1 mating connector (Cinch P/N DB25P or equivalent) normally shipped attached to rear panel J1
Back shell for J1 (DB25) mating connector (Cinch P/N DCH-B-001 or equivalent)
M550292-01 Rev G 2-1
Installation Sorensen SFA Series
Screw, lock washer, and nut for AC input and DC output connections: 5–15 kW: ¼-20UNC-2B x ½", 4 ea AC input only 20–30 kW: 3/8-16UNC-2B x 7/8", 6 ea
Black screw, 10-32UNC-2B x ½", front panel rack fastener: 5–15 kW: 4 ea 20–30 kW: 8 ea
If any of these parts are missing, please contact Customer Service at 1-800-733-5427.
2.3 INPUT/OUTPUT CONNECTIONS
WARNING!
High voltage present! Risk of electrical shock. Do not remove cover. Refer to qualified service personnel.
Table 2–1 lists all external connections for the SFA Series models. Table 2–2 and Table 2–3 provide input and output connection descriptions by power supply type.
For permanently connected equipment, a readily accessible disconnect device shall be incorporated in the fixed wiring. For pluggable equipment, the socket outlet shall be installed near the equipment and shall be easily accessible.
Take precautions to ensure that the concentration of ozone is limited to a safe value. The recommended long-term exposure limit for ozone is 0.1 PPM (0.2 mg/m
3
).
CAUTION!
Do not use the SFA power supplies in series operation.
CAUTION!
For proper connection to the mains, a 100–amp circuit breaker or fuse for 3U units and a 200–amp circuit breaker or fuse for 6U units is required.
WARNING!
Under no condition should the negative output terminal exceed 300V to earth ground for non-isolated Analog programming. (600V for supplies with the Isolated Analog option installed.)
2-2 M550292-01 Rev G
Sorensen SFA Series Installation
CAUTION!
Floating the negative output terminal floats the power supply’s internal control circuitry common level to the same potential as the negative output terminal. On a standard non-isolated supply the common of the analog control connector (J1) floats at the same potential as the negative output terminal. Damage may occur if the non-isolated analog control connector of a supply is connected to an external ground referenced input/output device. Such a connection creates ground loop currents. To correct ground loop problems the Isolated Analog option is advised in order to isolate the external ground reference signals from the internal control circuitry of the supply.
2.4 LOCATION AND MOUNTING
WARNING!
To reduce the risk of fire or electrical shock, install the SFA Series unit in a temperature and humidity controlled indoor area, free of conductive contaminants.
CAUTION!
The unit should be provided with proper ventilation. The rear and both sides of the unit should be free of obstructions. To ensure proper airflow, a minimum 4" clearance from the rear air outlet is required. The unit should not be installed in a raised ambient temperature greater than 50°C.
2.4.1
CAUTION!
This unit is intended for installation in a protected environment. No user serviceable parts inside. Service to be performed by qualified personnel only.
The SFA Series models are designed for mounting in a standard 19-inch equipment rack. If additional instrumentation is mounted in the rack, no additional clearance is required between the SFA series and other power supplies or instruments.
1. Support the unit using rack mount slides or appropriate L brackets
(suggested parts are listed below). Rack Mount Slide Kit:
5–15kW units: P/N K550212-01
20–30kW units: P/N K550213-01
2. Secure the unit in place using the screws provided.
6U CHASSIS REMOVAL FROM RACK
The slides have a Front Disconnect Feature and lock at full extension. To return the chassis back into the rack from full extension, depress the flat
steel spring inward (located on the slides) and push the chassis back. To disconnect and remove the chassis from the rack, depress the flat steel
spring inward (located on the slides) and pull the chassis forward.
M550292-01 Rev G
2-3
Installation Sorensen SFA Series
WARNING!
The 6U SFA Series unit weighs up to 160 lbs (73kg) depending on the model. A minimum three-person lift is required!
When the chassis is at full extension, the flat springs are located approximately one (1) inch behind the front EIA RETMA rails. Access the springs with a flat blade screwdriver or similar device to release from lockout or to remove the chassis from the rack.
The slides can be mounted to the chassis with this spring oriented on the top or the bottom of the slide.
Table 2–1 provides details of the SFA Series input and output connectors and their functions.
Connector Function Connects To
Pos. Threaded Stud Neg. Threaded Stud Pos. Bus Bar Neg. Bus Bar
ANALOG CONTROL Connector (J1)
Sense Connector Used for remote sense Refer to Section 3.4
Output Power: 3U models (see
6U models (see
Control Interface
Table 2–3) Table 2–3)
User load(s)
See Table 3–1 for description
Parallel In-Out Used for parallel operation Refer to Section 3.8
Table 2–1. 5kW to 15kW and 20kW to 30kW Series Input/Output Connectors
Power Supply Type Connection Description
5 kW to 15 kW Bus Bar with holes for 1/4"–20 bolts 20 kW to 30 kW Bus Bar with holes for 3/8"–16 bolts
Table 2–2. Input Connections
Power Supply Type Connection Description
5 kW to 15 kW ≥60V 20 kW to 30 kW 60V
3/8" Threaded Studs Bus Bar with holes for 3/8" bolts
Table 2–3. Output Connections
2-4 M550292-01 Rev G
Sorensen SFA Series Installation
CAUTION! Prevent damage to the unit: follow torque specifications, use correct size wire ferrule (if used), and proper size ferrule crimping tool.
TORQUE SPECIFICATIONS
The unit’s Phoenix Connectors require 18 in-lb to 20 in-lb (2 Nm to
2.3 Nm) torque.
Wire ferrules are recommended; their size must match the wire
gauge.
Crimp tool size must be appropriate to the ferrule size.
Wire insulation should be stripped back no more than 5/8 inch for
the ferrule.
For more information on this AC input connector, please look up Phoenix Contact part number HDFKV 16 at www.phoenixcontact.com.
M550292-01 Rev G
2-5
Installation Sorensen SFA Series
2.5 WIRE SELECTION
Care must be taken to properly size all conductors for the input and output of the power supply. This section provides guidance in the selection of wire size. Note that cables with Class B or C stranding should be used. Fine stranded cables should not be used unless crimp-on lugs or ferrules are used that are approved for fine stranded cables.
2.5.1 WIRE SIZE
The tables below will assist in determining the appropriate wire size for both the input and output connections Table 2–4 below gives minimum recommended wire size. This table is derived from the National Electrical Code; it is for reference only. Local laws and conditions may have different requirements. Note that these recommendations are for copper wire only. For higher ratings, wires can be paralleled; refer to the National Electrical Code.
Size Temperature Rating of Copper Conductor
60°C 75°C 85°C 90°C
AWG MCM
Types: RUW,
T, TW, UF
Types: FEPW,
RHW, RH, RUH,
THW, THWN,
XHHW, USE, ZW
Types: V, MI Types: TA, TBS,
SA, AVB, SIS, FEP, FEPB, RHH, THHN,
XHHW
Current Rating
14 20 20 25 25 12 25 25 30 30 10 30 35 40 40
8 40 50 55 55 6 55 65 70 75 4 70 85 95 95 3 85 100 110 110 2 95 115 125 130 1 110 130 145 150 0 125 150 165 170
00 145 175 190 195
000 165 200 215 225
0000 195 230 250 260
Table 2–4. Minimum Wire Size
When determining the optimum cable specification for your power applications, the same engineering rules apply whether going into or out of an electrical
2-6 M550292-01 Rev G
Sorensen SFA Series Installation
device. Thus, this guide applies equally to the input cable and output cable for this Sorensen instrument and application loads.
Power cables must be able to safely carry maximum load current without overheating or causing insulation destruction. It is important to everyday performance to minimize IR (voltage drop) loss within the cable. These losses have a direct effect on the quality of power delivered to and from instruments and corresponding loads.
When specifying wire gauge, consider the operating temperature. Wire gauge current capability and insulation performance drops with the increased temperature developed within a cable bundle and with increased environmental temperature. Thus, short cables with generously derated gauge and insulation properties are recommended for power source applications.
Be careful when using published commercial utility wiring codes. These codes are designed for the internal wiring of homes and buildings and accommodate the safety factors of wiring loss, heat, breakdown insulation, aging, etc. However, these codes consider that up to 5% voltage drop is acceptable.
Such a loss directly detracts from the quality performance specifications of this Sorensen instrument. Also, consider how the wiring codes apply to bundles of wire within a cable arrangement.
In high performance applications requiring high inrush/ transient currents, additional consideration is required. The cable wire gauge must consider peak currents, which may be up to ten times the average values. An underrated wire gauge adds losses, which alter the inrush characteristics of the application and thus the expected performance.
Table 2–5 presents wire resistance and resulting cable voltage drop at maximum rated current.
Column 1 Column 2 Column 3 Column 4
Size
(AWG)
14 20 0.257 5.14 12 25 0.162 4.05 10 30 0.102 3.06
8 40 0.064 2.56 6 55 0.043 2.36 4 70 0.025 1.75
2 95 0.015 1.42 1/0 125 0.010 1.25 3/0 165 0.006 1.04
Amperes
(Maximum)
Ohms/100 Feet
(One Way)
Voltage Drop/100 Feet
(Column 2 x Column 3)
Table 2–5 Wire Resistance and Voltage Drop
M550292-01 Rev G
2-7
Installation Sorensen SFA Series
Refer to Table 2–6 for AC input current requirements and Section 1.2.3 for output current requirements.
Input V
5 kW 10 kW 15 kW 20 kW 25 kW 30kW
200-240VAC 21 41 62 83 103 124 340-440VAC
480VAC 13 26 39 52 65 78
Refer to Table 2–7 for input/output lug recommendations.
Lug Manufacturer 3U Models Input/Output 6U Models Input/Output
Panduit “PN” Series or equivalent “LCA” Series or equivalent
The recommended tools for installation and extraction of the sense connector are listed next, in Table 2–8.
Tool
14
Table 2–6 Maximum AC Current Ratings
27 40 54 67 80
Table 2–7 Recommended Lugs
Manufacturer
Input Line Current
Manufacturer P/N
Unit of
Measure
Amps AC
per phase
Crimping Device Molex 11-01-0197 Extracting Device Molex 11-03-0044
Table 2–8. Recommended Sense Connector Tools
2.6 LOAD CONSIDERATIONS
2.6.1 INDUCTIVE LOADS
To prevent damage to the power supply from inductive loads, the SFA has incorporated a overvoltage shutdown circuit on the output. The overvoltage is preset for approximately 110% of the total rated output voltage. If the output voltage exceeds this amount for more than a few milliseconds, the output will shutdown. In order to reset the unit, the input standby switch, will need to be cycled on and off.
2.7 OUTLINE DRAWINGS
Figure 2-1 and Figure 2–2, next, show the outlines and overall dimensions of the 3U and 6U models of the SFA Series product line.
2-8 M550292-01 Rev G
Sorensen SFA Series Installation
Slide Mounting
8-32UNC-2B 4PL Nearside 3PL Far side
Figure 2-1. SFA Series Outline Drawing, 3U Models, 5kW to 15kW
M550292-01 Rev G
2-9
Installation Sorensen SFA Series
Slide Mounting
8-32UNC-2B 6PL Nearside 7PL Far side
Figure 2–2. SFA Series Outline Drawing, 6U Models, 20kW to 30kW
2-10 M550292-01 Rev G
3.1 CONTROLS AND INDICATORS
Refer to Figure 3-1 and the corresponding descriptions below for an explanation of front panel controls and indicators on the SFA Series power supply.
SECTION 3
OPERATION
Figure 3-1. Front Panel Controls and Indicators (3U model shown)
Voltage Display: 3½ digit green LED display indicates the DC output voltage of the supply.
1
Current Display: 3½ digit green LED display indicates the DC output current of the supply.
2
Display indicates the OCP setting when the SET/RESET OVERCURRENT PROTECTION button is pushed.
ADJUST Overcurrent Potentiometer: Adjusts the overcurrent trip level.
3
M550292-01 Rev G 3-1
Operation Sorensen SFA Series
CURRENT MODE Indicator: Green LED lights when in the constant–current mode of operation.
4
When in the constant–current mode, the output current will regulate to the set value and the output voltage will vary with the load. This is the normal operating mode for the SFA.
OVERCURRENT FAULT Indicator: Red LED indicates output current has exceeded preset level,
5
and power supply output is turned off. MODULE FAULT Indicator: Yellow LED indicates an internal fault such as bias supply, thermal, or
6
converter failure.
SET/RESET OVERCURRENT PROTECTION Pushbutton: Depress button to view OCP
7
level. Push and hold for 4 seconds to reset OCP condition. CURRENT knob: 10–turn adjustment sets the output current. (Optional shaft locks not
8
shown. Please see Section 3.1.1). ON/OFF Switch: Two–position switch enables or disables the power supply.
9
WARNING!
The OFF position of the power switch does not remove voltage from the input terminal blocks. Remove all external power before servicing the unit.
3-2 M550292-01 Rev G
Sorensen SFA Series Operation
Refer to Figure 3-2 and the corresponding descriptions below for an explanation of rear panel connectors.
10
11 12
151413
17 16
Figure 3-2. Rear Panel Connectors (3U model shown)
DC OUTPUT: Positive (+) and negative (–) outputs. Threaded studs for 5-15kW models; bus bars
10
for 20-30kW models.
ANALOG CONTROL Connector (J1): I/O connector for input programming and analog
11
output monitoring signals as well as status indication and remote shutdown signals. See Table 3–1 for individual pin descriptions.
18
SENSE Connector (J3): Input connector for load voltage sensing to provide a more
12
accurate voltage measurement for remote voltage readback and front panel voltage meter display (see Section 3.4).
PARALLEL IN Connector: Allows master/slave configuration of up to five units when
13
connected to another unit’s PARALLEL OUT connector (see Section 3.8).
PARALLEL OUT Connector: Allows master/slave configuration of up to five units when connected
14
to another unit's PARALLEL IN connector (see Section 3.8).
RS232 Connector: Optional RJ-11 connector for remote control.
15
Dipswitch: Eight–position dipswitch to configure an SFA Series unit with an IEEE option.
16
GPIB Connector: Optional connector for remote control.
17
AC Input Bus Bars: Connection for 3-phase AC and Ground.
18
M550292-01 Rev G
3-3
Operation Sorensen SFA Series
3.1.1 SHAFT LOCK (OPTION)
This option replaces the standard control knob with a two-piece shaft lock. This is installed over the current adjustment potentiometer shaft to prevent rotating under conditions of shock, vibration, or accidental contact. For adjustment, the following steps apply:
1. Loosen the shaft by rotating the outer locking nut counter-clockwise with a 7/16-inch wrench.
2. Adjust the shaft with a flat screwdriver to the desired output level.
3. Tighten the outer locking nut, rotating clockwise, to approximately 5 LB­in (0.56 N-m).
NOTE: Take care not to over-torque the outer nut. Should the cone nut become loose or jammed with the outer locking nut, re-torque the cone nut with a 1/2-inch wrench to approximately 15 LB-in (1.69 N-m).
Figure 3-3. Shaft Lock
CAUTION! Never completely loosen the cone nut, or remove the shaft lock from the chassis.
3.2 LOCAL OPERATION
The SFA Series power supply is shipped from the factory configured for local current control and local voltage sensing. The ANALOG CONTROL connector is supplied with a mating connector with remote ON/OFF jumpered for ON (terminal 5 shorted to terminal 6).
Prior to turning the unit on, rotate the current potentiometer fully counterclockwise (minimum output). Then, turn the power ON and adjust the current to the desired output.
3-4 M550292-01 Rev G
Sorensen SFA Series Operation
This section provides an overview of front panel operation and initial functional tests of the power supply.
3.2.1 FLOATING AND POLARIZED OUTPUT
The SFA Series supply can be set up for a Positive or Negative supply, as well as standard operation as a floating output supply.
FLOATING OUTPUT
The output terminals are normally floating from chassis ground. No extra steps or connections are required for a floating output.
POSITIVE SUPPLY SETUP
Attach the negative output terminal to the supply chassis. The output reference is now chassis ground. When the output voltage is set or programmed, the supply will output a positive potential from chassis ground.
NEGATIVE SUPPLY SETUP
Attach the Positive output terminal to the supply chassis. The output reference is now chassis ground. When the output voltage is set or programmed, the supply will output a negative potential from chassis ground.
CAUTION!
Floating the negative output terminal floats the power supply’s internal control circuitry common level to the same potential as the negative output terminal. On a standard non-isolated supply the common of the analog control connector (J1) floats at the same potential as the negative output terminal. Damage may occur if the non-isolated analog control connector of a supply is connected to an external ground referenced input/output device. Such a connection creates ground loop currents. To correct ground loop problems the Isolated Analog option is advised in order to isolate the external ground reference signals from the internal control circuitry of the supply.
3.2.2 INITIAL SETUP
Before connecting the unit to an AC outlet, ensure that the front panel ON/OFF power switch is in the off position and that the current control knob is fully counterclockwise. Check the ANALOG CONTROL (J1) mating connector on the rear panel to verify that pins 5 and 6 (Remote Output On/Off) are shorted together to enable the output of the supply (see Section 3.5). This is the default configuration installed from the factory. Apply power to the AC mains input.
M550292-01 Rev G
3-5
Operation Sorensen SFA Series
3.2.3 CURRENT MODE OPERATION
When the supply is in the Current Mode (the default mode for the SFA Series), the output current of the supply is controlled by the Current knob on the front panel or by the remote current input (see Section 3.3). To verify operation in current mode, follow the steps below:
1. Connect a high current DC ammeter across the rear panel positive and negative output terminals, observing the correct polarity. Select wire leads of sufficient current carrying capacity and an ammeter range compatible with the units maximum rated output current. NOTE: If a high current ammeter is not available, you may simply short the output terminals together. This will not harm the supply.
2. Turn on the power supply.
3. Slowly rotate the Current knob clockwise and observe both the front panel current display and the output of the ammeter. The minimum range should be from 0A to the maximum rated current output of the supply. The front panel display and ammeter readings should track within the accuracies of the meter and the front panel display.
4. Note the reading on the voltage display. This is the compliance voltage of the load at the present output current. Note the maximum compliance voltage is set by the specific model of the supply.
5. Check that the green Current Mode indicator is on.
6. Turn the Current knob fully counterclockwise.
7. Turn the power supply off.
8. Disconnect the ammeter or short from the output terminals.
If Current mode operation did not function as indicated above, recheck your setup and perform the check again. If the function continues to fail, contact the factory for assistance.
3.2.4 OVERCURRENT PROTECTION
The Overcurrent Protection (OCP) function allows the supply to shutdown the output when it exceeds a preset current. This may be used to protect sensitive circuits or loads from damage caused by an excessive current on the output of the supply. To verify OCP operation, follow the steps below:
1. Connect a short or an appropriate load across the output terminals.
2. Rotate the Current control knob fully counterclockwise (this sets the current control at 0 Amps)
3. Turn on the power supply.
4. Press and hold the Set/Reset Overcurrent Protection pushbutton on the front panel and observe the reading on the current display. This is the
3-6 M550292-01 Rev G
Sorensen SFA Series Operation
present setting of the OCP limit. The factory default setting is approximately 110% of the maximum rated output of the supply.
5. While holding down the Set/Reset button, use a small adjustment
screwdriver to adjust the OCP setting by turning the 4-turn recessed adjust potentiometer counterclockwise. As you adjust the potentiometer the reading on the current display should decrease (increase as you adjust in a clockwise direction).
6. Set the OCP to about 80-90% of the maximum rated output current and
note the OCP current value. Release the Set/Reset pushbutton.
7. Rotate the Current knob clockwise until the current display indicates
you are about 2-3% below the OCP voltage value noted above.
8. Slowly continue to increase the output of the supply until you exceed
the value of the OCP setting. At this point the OCP light should turn on and the output of the supply will turn off causing the output to go to 0 volts (as indicated on the voltage display).
9. Turn the Current knob fully counterclockwise, then press and hold the
Set/Reset pushbutton until the OCP light turns off.
10. Reset the OCP setting as appropriate for your application per steps 4
and 5 above. If you do not chose to use OCP, then the OCP adjust may be set fully clockwise to approximately 110% of the rated output current of the supply.
If OCP mode did not function as indicated above, recheck your setup and perform the check again. If the function continues to fail, contact the factory for assistance.
3.2.5 ANALOG CONTROL CONNECTOR (J1)
The ANALOG CONTROL connector on the rear panel allows the unit to be configured for different operating configurations: local and remote current programming, current and voltage output monitoring, output enable/disable, etc. The setup and operating requirements of each configuration are provided in Sections 3.3 through 3.7.
ISOLATED ANALOG CONTROL (OPTION)
The Isolated Analog Control uses the same Analog Control connector (J1). This option fully isolates remote control signals and allows control of units not connected to a common ground. Control ground is isolated from power ground, which protects against potential damage from systems with high electrical noise or large ground loop currents.
NOTE: Some standard analog programming signals may not be available with this option. See Table 1.2.2 for details.
M550292-01 Rev G
3-7
Operation Sorensen SFA Series
CAUTION!
This option is not intended to allow operation of the power supply at excessive voltages. Refer to Section 2 INSTALLATION for maximum terminal voltages.
Following are Figure 3-4 with the connector's pin-out diagram, and Table 3–1 with ANALOG CONTROL connector designations and functions:
Figure 3-4. ANALOG CONTROL Connector (J1) Pin-out
Schematic
Symbol
Electrical
Chars.
Designator
1
ISO
ON/OFF
Zin ~ 6 k
2 ISO RTN
3
REM OC
SET
Zin ~
20 k
4 Not Used
Functional Description
Isolated remote on/off. Externally supplied AC/DC voltage source for on/off control. A positive (+) 12 to 240 VAC or 6 to 120 VDC voltage will turn on the supply. This input control is optically isolated from the power supply circuit up to 500 VDC. See Section 3.5.
Isolated circuit return used with isolated on/off control J1-1 and J1-14.
Remote overcurrent set. A remote signal sets the overcurrent trip level. 0-5.5 VDC = 0-110%. Apply a 10.5 VDC to 13.3 VDC signal for 4 seconds to reset an OCP condition. See Section 3.6.
Must sink
5 ON/OFF
~1mA to
enable
6
7 I MON
3-8 M550292-01 Rev G
COM
-
Zout ~
100
Remote on/off. Switch/relay contacts or a direct short between this terminal and circuit common turns on the unit.
Circuit Common. Same potential as the negative output terminal.
Output current monitor. 0-10 VDC equals 0-100% rated current. Minimum load resistance 10kΩ.
Sorensen SFA Series Operation
Schematic
Symbol
Electrical
Chars.
Designator
8 Not Used 9 Not Used
10 IP 5V
11
ISET
Zin ~ 10k
*
12 SENSE
13 SENSE +
Zout ~
100
~ 1000Ω to
neg (–)
output
terminal
~ 1000Ω to
pos (+)
output
terminal
Remote current programming using a 0-5 VDC source. Do not exceed 13.3 VDC.
0-5 VDC (0-100%) front panel current control monitor output. Minimum load resistance 10kΩ.
Remote Sense (–) on 60 volts output units. (For new installations, use J3, recommended only for backward compatibility in existing systems.)
Remote Sense (+) on <60 volts output units. (For new installations, use J3, recommended only for backward compatibility in existing systems.)
Functional Description
Isolated TTL/CMOS on/off control. A high state TTL/CMOS voltage turns on the power supply, and a low state or open connection turns the supply off.
14
ISO
TTL/CMOS
Zin ~ 2.2k
15 Not Used
16 IP 10V
Zin ~ 20k
17 FAULT
Zout ~
100
Remote current programming using a 0-10 VDC source. Do not exceed 25 VDC.
Fault state output. A high state (approximately +10 VDC) indicates a converter, temperature or bias supply fault, and the LED on the front panel will illuminate.
Shutdown fault. This terminal goes to high state in the event of converter, temperature, overvoltage or bias supply fault. A
18 S/D FAULT
Zout ~
100
7 VDC to 13.3 VDC signal can be applied to this pin to shutdown the output of the unit. An 8 VDC minimum output signal is provided into a 10 kminimum load, in the event of an internally generated shutdown.
19 V MON
Zout ~
100
Output voltage monitor. 0-10 VDC equals to 0-100% rated voltage. Minimum load resistance 10kΩ.
M550292-01 Rev G
3-9
Operation Sorensen SFA Series
Schematic
Symbol
Designator
20 Not Used 21 Not Used
22
23 IP RTN
24
25 IP RTN
IP RES
COM
Electrical
Chars.
*
~ 10.8V
compliance
Zin ~ 10k
Zin ~ 10k
-
Functional Description
1 milliamp current source for remote current programming using resistance. 0-5k ohm resistor referenced to common will program the output from 0-100%.
Current programming return. Used with J1-10, J1-16 or J1-22 and must be referenced to or within ±3V of the circuit common.
Circuit common. Same potential as the negative output terminal.
Current programming return. Used with J1-10, J1-16 or J1-22 for remote current programming and must be referenced to or within ±3V of the circuit common.
Table 3–1. ANALOG CONTROL Connector (J1), Designations and Functions
Control ground is isolated from power ground with the isolated analog control (option).
See Section 3.2.5.1
*
Signals not available with isolated analog control (option).
CAUTION!
If standard analog programming is used, note the programming return (J1-6 & J1-24) is at the same potential as the negative output terminal of the power supply. Observance of return connections should be made with respect to input programming signal equipment. Improper connection may result in ground loops and as a result internal power supply damage may occur. (Output current then flows to chassis by means of external connection to the J1 common (J1-6 & J1-24)).
3-10 M550292-01 Rev G
Sorensen SFA Series Operation
3.3 REMOTE CURRENT PROGRAMMING
Remote current programming is used for applications that require the output current be programmed (controlled) from a remote source. An external resistance or external voltage source may be used as a programming device. When using remote current programming, a shielded, twisted-pair, hookup wire is recommended to prevent noise interference with programming signals.
1. Remote Current Programming Using Resistance:
The resistance coefficient for remote current programming is 5k ohms/100% rated output with respect to terminal J1-23 (IP RTN). The programming current from terminal J1-22 (IP RES) is factory set for 1 milliampere. This yields a coefficient of 1.0% of rated output current for each 50 ohms. If multiple switches or relays are used to program different levels, make-before-break contacts are recommended. Note that if an external resistance is used for remote programming, the current programming return (IP RTN), terminal J1-23, must be connected directly to or within ±3 volts (see note) of the power supply common terminal, J1-24. See Figure 3–5 for connection requirements.
Figure 3–5. Remote Current Programming Using Resistance
2. Remote Current Programming Using a 0-5 VDC or 0-10 VDC Voltage
Source: A DC voltage source for remote current programming is connected between J1-10 (IP 5V) or J1-16 (IP 10V) and the return terminal J1-23 (IP RTN). Note that the return terminal J1-23 (IP RTN) must be referenced directly to or within ±3V (see note) of the power supply common, J1-24. The voltage coefficient for 5V remote current programming is 50 millivolts = 1% of rated output, i.e., for a 300 amp model, each 50 millivolts of programming voltage equals 3 amps of output current. The voltage coefficient for 10V remote current programming is 100 millivolts = 1% of rated output, i.e., for a 300 amp
M550292-01 Rev G
3-11
Operation Sorensen SFA Series
model, each 100 millivolts of programming voltage equals 3 amps of output current. See Figure 3–6 for connection requirements.
1
16 IP 10V
COM 6
IP 5V 10
0-5 VDC VOLTAGE SOURCE
+
13
-
23 IP RTN
+
0-10 VDC VOLTAGE
-
SOURCE
Figure 3–6. Remote Current Programming Using 0-5 VDC or 0-10 VDC Voltage Source
3.4 REMOTE SENSING
Remote voltage sensing is recommended for accurate voltage measurement, whether you connect sensing leads to the load or directly to the output terminals. This will provide the most accurate voltage readback and front panel voltage meter display.
CAUTION!
If the power supply is operated with load power lines disconnected and sensing line connected, internal power supply damage may occur. (Output current then flows through sensing terminals.)
To use remote voltage sensing, connect the power supply as described below. See Figure 3–7 for connection requirements.
Connect sensing leads from the load positive to J3-1 and the load negative to J3-2. A shielded, twisted-pair, hookup wire is recommended to avoid potential noise interference.
3-12 M550292-01 Rev G
Sorensen SFA Series Operation
Figure 3–7. Remote Sensing Operation at the Load *
* For accurate measurements through remote voltage readback and front panel voltage meter display.
M550292-01 Rev G
3-13
Operation Sorensen SFA Series
3.5 REMOTE OUTPUT ON/OFF CONTROL
Remote on/off control may be accomplished by contact closure or by an isolated external AC/DC or TTL/CMOS voltage source.
1. Remote on/off by contact closure. Output is on when contacts (J1-5 and J1-6) are closed. See Figure 3–8 for connection requirements.
1
ON/OFF 5
6
14
25
Figure 3–8. Remote On/Off Control by Contact Closure
2. Remote on/off control may be accomplished by an external 12 to 240 VAC or 6 to 120 VDC or TTL/CMOS source. Application of AC/DC or high state TTL/CMOS voltage will turn on the power supply. See Figure 3–9 and Figure 3–10 for connection requirements.
ISO ON/OFF 1
+
ISO RTN 2
14
-
AC OR DC
SOURCE
25
Figure 3–9. Remote On/Off Using Isolated AC or DC Voltage Source
3-14 M550292-01 Rev G
Sorensen SFA Series Operation
1
ISO RTN 2
14 ISO TTL/CMOS
25
Figure 3–10. Remote On/Off Using Isolated TTL/CMOS Voltage Supply
3.6 REMOTE OVERCURRENT SETPOINT
CAUTION!
Do not program the remote overcurrent set point greater than 10% (5.5V) above the power supply rated current (except as noted) as internal power supply damage may occur.
A remote DC voltage source can be connected externally between terminals J1­6 (COM) and J1-3 (REM OC SET) to set the output overcurrent trip level. A 0-
5.5 VDC signal equals 0-110% of rated output voltage. See Figure 3–11 for
connection requirements.
1
REM OV SET 3
0-5.5 VDC VOLTAGE SOURCE
+
COM 6
-
13
Figure 3–11. Remote Overcurrent Set Using DC Voltage Source
NOTE: The Remote OCP trip level will ALWAYS take precedence over the
local trip level, even if the local OCP trip level is set to a lower value. To reset an OCP externally, apply a 10.5–13.3 VDC signal to J1-3 for a minimum of four (4) seconds.
M550292-01 Rev G
3-15
Operation Sorensen SFA Series
3.7 REMOTE SHUTDOWN (S/D)
A remote +12 VDC voltage can be connected externally between terminals J1­18 (S/D Fault) and J1-24 (COM) to disable, i.e., shut down the output of the power supply. Disabling or opening the +12 VDC signal will allow the unit to revert to normal operation.
Figure 3–12. Remote Shutdown Using DC Voltage Source
3.8 MASTER/SLAVE OPERATION
The following modes of operation are used for applications requiring more current or voltage than is available from a single power supply. To meet the requirements for greater output voltage or current, up to five supplies may be connected in parallel.
3.8.1 PARALLEL OPERATION
In the parallel mode of operation, a master/slave configuration is established. Up to five power supplies may be paralleled using this configuration. To set up the parallel mode of operation, connect the interface cable (P/N 890-453-03) from the master unit to the slave unit(s), as shown below in Figure 3–13. Next connect the positive outputs of supplies together and the negative outputs of the supplies together. It is recommended that the outputs are connected together as close to the load as practical.
3-16 M550292-01 Rev G
Sorensen SFA Series Operation
Figure 3–13. Master/Slave Connection
NOTE: The OCP circuit remains active for all units in parallel operation. If the units are set to different OCP levels, the paralleled system will trip according to the lowest setting. For ease of use, adjust the OCP levels for the slaves to maximum and adjust the master OCP level to the desired setting.
M550292-01 Rev G
3-17
Operation Sorensen SFA Series
This page intentionally left blank.
3-18 M550292-01 Rev G
VERIFICATION AND CALIBRATION
4.1 INTRODUCTION
This section provides verification and calibration procedures for the standard SFA Series power supplies and isolated analog control (option).
SECTION 4
4.1.1 VERIFICATION AND CALIBRATION CYCLE
It is recommended that the power supply be calibrated and/or verified once each year of operation.
4.1.2 PREPARATION
WARNING!
Hazardous voltages exist on the rear of the supply. Great care must be taken to avoid both the input terminals, and while the supply is enabled, the output terminals. Only authorized personnel should perform this procedure.
Due to the importance of accurate readings to performance, only technically trained personnel should perform calibration procedures.
The calibration and adjustment procedures require two digital multimeters. To set up for the calibration procedures, first perform the following:
1. Remove prime AC power.
2. Connect the power supply to a precision current shunt (as shown in
Figure 4-1 below) capable of a minimum of 10% above full rated output. A fan may be required to cool the shunt.
M550292-01 Rev G 4-1
Verification and Calibration Sorensen SFA Series
SHUNT
Figure 4-1. Precision Current Shunt
4.2 STANDARD VERIFICATION AND CALIBRATION
PROCEDURE
All calibration potentiometers can be adjusted through access holes in the top cover of the SFA Series unit. It is not necessary to remove the top cover to perform the calibration procedures.
4.2.1 CURRENT MODE
1. Set the SFA Series unit to operate in remote current programming mode using an external 0-5 Vdc voltage source as shown in Figure 3–6 in Section 3.3 Remote Current Programming.
2. Attach a precision meter across the shunt Kelvin terminals.
3. Attach a precision meter in parallel with the voltage programming source.
4. Set the voltage source to 0.0V ± 1mV.
5. Apply AC power and verify the current mode indicator is illuminated.
6. Verify the unit is set to 0A ± 0.8% of full-scale output. If necessary, adjust R55 for zero current through the shunt. (See Figure 4-2.)
7. Set the programming voltage to 5.0V ± 1mV.
8. Verify the unit is set to 100% ± 0.8% of full-scale output current. If necessary, adjust R69 for 100% of full-scale current on the shunt.
9. Set the programming source for 0.5V ± 1mV.
4-2 M550292-01 Rev G
Sorensen SFA Series Verification and Calibration
10. Verify the unit is set to 10% ± 0.8% of full-scale output current. If
necessary, adjust R55 for 10% of full-scale current on the shunt.
11. Repeat the steps above as required to obtain the required accuracy.
12. Set the programming source to obtain 100% output current on the
shunt. Verify that the front panel meter displays 100% ± 1% of full-scale output current. If necessary adjust R85 such that the current display reads 100% current.
CAUTION!
Hazardous voltages may be present on the output after the output is disabled due to stored capacitive charge. Allow 5 minutes to drain the output capacitive charge to safe levels before connecting or removing output wiring.
4.2.2
RESISTOR PROGRAMMING CURRENT SOURCES
1. Disable AC power to the unit. Turn the front panel Current knob fully
counterclockwise.
2. Connect the power supply to a precision current shunt (see Figure 4-1,
Section 4.1.2 Preparation).
3. Set the SFA Series unit to operate in remote current programming
mode using resistance by connecting a 5K ohm (1% or better tolerance) resistor as shown in Figure 3–5 in Section 3.3 Remote Current Programming.
4. Attach a precision meter across the shunt Kelvin terminals.
5. Apply AC power and enable the unit via the front panel On/Off switch.
6. Verify there is 5V ±1% across the resistor. If necessary, adjust R45 to
measure 5.00V read back on the voltmeter.
7. Disable AC power to the unit.
8. Remove all connections to the remote analog control connector (J1),
except the jumper between pins 5 and 6.
4.3 ISOLATED ANALOG (OPTION) VERIFICATION AND
CALIBRATION PROCEDURE
All calibration potentiometers can be adjusted through access holes in the top cover of the SFA Series unit. It is not necessary to remove the top cover to perform the calibration procedures.
M550292-01 Rev G
4-3
Verification and Calibration Sorensen SFA Series
4.3.1 CURRENT MODE
1. Set the SFA Series unit to operate in remote current programming mode using an external 0-5 Vdc voltage source as shown in Figure 3–6 in Section 3.3 Remote Current Programming.
2. Attach a precision meter across the shunt Kelvin terminals.
3. Attach a precision meter in parallel with the voltage programming source.
4. Set the voltage source to 0.0V
± 1mV.
5. Apply AC power and verify the current mode indicator is illuminated.
6. Verify that the unit is set to 0A
± 0.8% of full-scale output. If necessary,
adjust R47 for zero current through the shunt (see Figure 4-1 in Section
4.1.2 Preparation).
7. Set the programming voltage to 5.0V
8. Verify that the unit is set to 100%
± 1mV.
± 0.8% of full scale output current. If
necessary, adjust R33 for 100% of full scale current on the shunt.
9. Set the programming source for 0.5V
10. Verify that the unit is set to 10%
± 1mV.
± 0.8% of full scale output current. If
necessary, adjust R47 for 10% of full scale current on the shunt.
11. Repeat the steps above as required to obtain the required accuracy.
12. Set the programming source to obtain 100% output current on the shunt. Verify that the front panel meter displays 100%
± 1% of full-
scale output current. If necessary adjust R85 such that the current display reads 100% current.
CAUTION!
Hazardous voltages may be present on the output after the output is disabled. Allow 5 minutes to drain any charge to safe levels before connecting or removing output wiring.
4-4 M550292-01 Rev G
Sorensen SFA Series Verification and Calibration
STANDARD CALIBRATION ADJUSTMENT
R71 = IPRES (1mA) Adjust R87 = Voltage Meter Adjust R86 = Current Meter Adjust R69 = 100% Current Adjust R55 = Zero Current Adjust
ISOLATED ANALOG (OPTION) CALIBRATION ADJUSTMENT
R86 = Voltage Meter Adjust R87 = Current Meter Adjust R33 = 100% Current Adjust R47 = Zero Current Adjust
FACTORY USE ONLY
R35 R73 R37 R74 R39 R82 R45 R85 R46 R90
Figure 4-2. Potentiometer Locations
M550292-01 Rev G
4-5
Verification and Calibration Sorensen SFA Series
This page intentionally left blank.
4-6 M550292-01 Rev G
5.1 INTRODUCTION
This chapter contains preventive maintenance information for the SFA Series power supplies.
SECTION 5
MAINTENANCE
WARNING!
All maintenance that requires removal of the cover of the unit should only be done by properly trained and qualified personnel. Hazardous voltages exist inside the unit. Disconnect the supply from the input power before performing any maintenance. Service, fuse verification, and connection of wiring to the chassis must be accomplished at least five minutes after power has been removed via external means; all circuits and/or terminals to be touched must be safety grounded to the chassis.
5.2 PREVENTIVE MAINTENANCE
No routine maintenance on the SFA Series is required, aside from periodic cleaning of the unit when needed:
Once a unit is removed from service, vacuum all air vents, including the front
panel grill. Clean the exterior with a mild solution of detergent and water. Apply the solution onto a soft cloth, not directly to the surface of the unit. To prevent damage to materials, do not use aromatic hydrocarbons or chlorinated solvents for cleaning.
Low–pressure compressed air may be used to remove dust from in and
around components on the printed circuit boards.
WARNING!
The OFF position of the power switch does not remove voltage from the input terminal blocks. Remove all external power before performing any service.
M550292-01 Rev G 5-1
Maintenance Sorensen SFA Series
An annual inspection of the SFA Series unit is recommended. Table 5–1 lists the visual inspection checks to be performed, and the corrective action to be taken.
Table 5–1. Recommended Annual Inspection
Item Inspect For Corrective Action
External connector plugs and jacks
Chassis, fan, and extruded heatsinks
External electrical wiring
External solder connections
Dirt and moisture buildup
Front panel controls and meters
Looseness, bent or corroded contacts, damage or improper seating in mating connector
Clean contacts with solvent moistened cloth, soft bristle brush, small vacuum, or low compressed air.
Replace connectors damaged, deeply corroded, or improperly seated in mating connector.
Dirt and corrosion Clean with cloth moistened with
soapy water.
Broken, burned or pinched
Repair or replace defective wires.
wire; frayed, worn or missing insulation
Corrosion, loose, cracked, or
Clean and resolder connections.
dirty connections Short circuits, arcing,
Clean as required.
corrosion, overheating Dirt and corrosion
Clean with cloth moistened with soapy water.
Use a Kimwipe tissue and GTC glass–cleaning compound to clean the meter faces.
CAUTION!
For safe and continued operation of the SFA Series, always operate the unit in a temperature and humidity controlled, indoor area, free of conductive contaminants. Remember to keep the rear and sides of the unit free of obstructions to ensure proper ventilation.
5-2 M550292-01 Rev G
Sorensen SFA Series Maintenance
5.3 FUSES
There are no user replaceable components in the power supply.
WARNING!
Only properly trained and qualified personnel should remove the cover from the power supply. Service, fuse verification, and connection of wiring to the chassis must be accomplished at least five minutes after power has been removed via external means; all circuits and/or terminals to be touched must be safety grounded to the chassis.
CAUTION!
To reduce the risk of fire or electrical shock, replace fuses only with the same type and rating.
Internal fuses are listed in Table 5–2. Note, however, that failure of one of these fuses indicates a more serious problem has occurred. Please contact the factory for further assistance.
PCB Part No. Reference Value Manufacturer Part No.
Bias Supply F1, F2, F3 600 Volt, 5 Amp Littelfuse KLK-5
Module Controller F1 600 Volt, 30 Amp Littelfuse KLKD30
Table 5–2. Fuse Values
M550292-01 Rev G
5-3
Maintenance Sorensen SFA Series
This page intentionally left blank.
5-4 M550292-01 Rev G
C
Circuit Breaker Requirements, 2-2, 2-5 Controls and Indicators, 3-1
Analog Control (J1), 3-7
Current Mode
Operation, 3-6 Verification and Calibration, 4-2
F
Fuses, 5-3
I
Inductive Loads, 2-8 Input/Output Connections, 2-2
Connector Functions, 2-4
Isolated Analog Control, 3-7
J
INDEX
Mounting Hardware, 2-3
O
Operation
Current Mode, 3-6 Local, 3-4 Master/Slave, 3-16 Parallel, 3-16 Remote Current Programming, 3-11 Remote Output On/Off Control, 3-14 Remote Overvoltage Setpoint, 3-15 Remote Sensing, 3-12
Remote Shutdown, 3-16 Overvoltage Protection, 3-6 Ozone Precaution, 2-2
P
Parallel Operation, 3-16 Potentiometer Locations, 4-5
J1 Connector, 3-7
L
Loads
Inductive, 2-8
Location and Mounting, 2-3
M
Maintenance
Annual Inspection, 5-2 Fuses, 5-3 Preventive, 5-1
Master/Slave Operation, 3-16
M550292-01 Rev G Index 1
Rack slides, 2-3 Remote Current Programming, 3-11 Remote Output On/Off Control, 3-14 Remote Overvoltage Setpoint, 3-15 Remote Sensing, 3-12 Remote Shutdown, 3-16
R
Index Sorensen SFA Series
S Setup, 3-5 Shaft Lock, 3-4 Specifications, 1-2
Current, 1-4 Electrical Characteristics, 1-3 Environmental Characteristics, 1-2 Noise, 1-4 Physical Characteristics, 1-5 Ripple, 1-4 Voltage, 1-4
V
Ventilation, 2-3 Verification and Calibration, 4-2
Current Mode, 4-2
W
Wire Size, 2-6
Index 2 M550292-01 Rev G
Loading...