Before applying power to the system, verify that the SF Series supply is configured properly for the user’s
particular application.
WARNING!
HAZARDOUS VOLTAGES IN EXCESS OF 280 VRMS, 600V PEAK MAY BE
PRESENT WHEN COVERS ARE REMOVED. QUALIFIED PERSONNEL MUST
USE EXTREME CAUTION WHEN SERVICING THIS EQUIPMENT. CIRCUIT
BOARDS, TEST POINTS, AND OUTPUT VOLTAGES MAY BE FLOATING
ABOVE (BELOW) CHASSIS GROUND.
Installation and service must be performed by qualified personnel who are aware of dealing with
attendant hazards. This includes such simple tasks as fuse verification.
Ensure that the AC power line ground is connected properly to the SFI Series unit input connector
or chassis. Similarly, other power ground lines including those to application and maintenance
equipment must
Always ensure that facility AC input power is de-energized prior to connecting or disconnecting the
input/output power cables.
inadvertent contact with hazardous voltages is eliminated. To guard against risk of electrical shock during
open cover checks, do not touch
capacitors can retain an electrical charge. Use safety glasses during open cover checks to avoid
personal injury by any sudden failure of a component.
be grounded properly for both personnel and equipment safety.
During normal operation, the operator does not have access to hazardous voltages within
the chassis. However, depending on the user’s application configuration, HIGH VOLTAGES
HAZARDOUS TO HUMAN SAFETY may be generated normally on the output terminals.
Ensure that the output power lines are labeled properly as to the safety hazards and that any
any portion of the electrical circuits. Even when the power is off,
Due to filtering, the unit has high leakage current to the chassis. Therefore, it is essential to operate this
unit with a safety ground.
Some circuits are live even with the front panel switch turned off. Service, fuse verification, and
connection of wiring to the chassis must be accomplished at least five minutes
been removed via external means; all circuits and/or terminals to be touched must be safety
grounded to the chassis.
After the unit has been operating for some time, the metal near the rear of the unit may be hot enough to
cause injury. Let the unit cool before handling.
Qualified service personnel need to be aware that some heat sinks are not at ground, but at high
potential.
These operating instructions form an integral part of the equipment and must be available to the
operating personnel at all times. All the safety instructions and advice notes are to be followed.
Neither Elgar Electronics Corporation, San Diego, California, USA, nor any of the subsidiary sales
organizations can accept any responsibility for personal, material or consequential injury, loss or damage
that results from improper use of the equipment and accessories.
SCPI STATUS IMPLEMENTATION............................ 5-1
ii M550292-03 (Programming)
SECTION 1
FEATURES, FUNCTIONS,
AND SPECIFICATIONS
1.1 Introduction
This manual covers the Digital Interface Adapter (DIA) for SF Series supplies. The DIA interface
card enables the user to operate from a computer via the IEEE-488.2 GPIB or RS-232 interface,
allowing full remote programming control and monitoring of the SF Series supply.
1.2
Features
• 16-bit programming and 16-bit readback of voltage and current
• IEEE-488.2 and SCPI compliant command set
Features and Functions
• Current Ramp functions
• Field-upgradable firmware via RS-232
• Soft calibration
• Rear panel IEEE-488.2 and RS-232 control interface
• Rear panel configuration switch
Programmable Functions
• Output current
• Soft limits for current
• Output enable/disable
• Maskable fault interrupt
• Hold and trigger
• Full calibration
M550292-03 (Programming) 1-1
Features, Functions, and Specifications Sorensen SF Series
Readback Functions
• Actual measured voltage and current
• Current settings
• Soft current limit
• Status and Accumulated Status registers
• Programming error codes
• Fault codes
• Manufacturer, power supply model, and firmware version identification
1.3 Specifications
Programming Resolution
Current: 0.002% of full scale
Programming Accuracy
Current: ± ( 0.4% of maximum output current)*
Readback Resolution
Voltage: ± 0.002% of full scale
Current: ± 0.002% of full scale
Readback Accuracy
Voltage: ± ( 0.15% of full scale output voltage)
Current: ± ( 0.4% of full scale output current)*
* After 30 minutes operation with fixed line, load, and temperature.
Note: Refer to the SFA or SFI power supply Operation manual for effects of line regulation,
load regulation, and temperature on accuracy specifications.
Specifications subject to change without notice.
1-2 M550292-03 (Programming)
SECTION 2
CONFIGURATION
The DIA is installed into the supply at the factory. Use the Setup Procedure described below to
configure the DIA for your system and application.
2.1
This procedure is a quick reference for the configuration requirements. Refer to Section 2.2 for
detailed information on the rear panel switches.
1. Set the rear panel Remote/Local switch to Remote (On or 1).
2. Set the rear panel Power On Service Request switch to No Service Request (Off or 0).
3. SFA - Set the GPIB address switches to the desired address.
Setup Procedure
Note:Valid GPIB addresses are 1-30.
SFI – From the Home menu page 3, press (F1) to enter the Remote menu. Select the
IEEE488 address for GPIB programming or baud rate for RS232.
4. Connect the GPIB or RS232 Interface Cable to the supply.
5. Connect power to the unit and turn on the unit.
6. Configure the controller to match the supply identification and configuration. Use one of the
available programs such as IBCONF from National Instruments for GPIB, or set the RS232
baud rate to 19200 for SFA or selected rate for SFI, 8 data bits, no parity, and 1 stop bit.
7. Test the communication interface by issuing a *IDN? Command. This returns the supply’s
model and firmware versions and does not affect the output of the supply.
M550292-03 (Programming) 2-1
Configuration Sorensen SF Series
2.2 Rear Panel Configuration Switch
The DIP switch is accessible from the rear panel to allow configuration of the supply with the
installed DIA for the user’s particular system and application. The following figures show the
configuration, as set up in Section 2.1, and with GPIB address set to five (5) for the SFA.
Note: Two types of DIP switches are utilized; toggle and rocker. For toggle switches, the
shading indicates the position of the toggle switch. For rocker switches, the shading
indicates the depressed side.
Figure 2–1. SFA Configuration Switch
Figure 2–2. SFI Configuration Switch
2.2.1 Remote/Local Selection
Set the rear panel Remote/Local switch to select remote or local operation.
REMOTE/LOCAL SWITCH
Switch Position Description
ON Remote operation selected. *
Local operation selected.
OFF
Front panel control is enabled. Unit will switch to remote
operation upon the first GPIB or RS-232 command.
* In the ON position, the power hardware and GPIB card initialize to the remote state on
power turn on. In addition, front panel control remains disabled regardless of the state of
the GPIB interface REN line or the GTL command. The special command SYST:LOCAL
<on/off> is permitted as a means to revert to front panel control if desired.
2-2 M550292-03 (Programming)
Sorensen SF Series Configuration
Powering up in remote mode will result in the following operating conditions:
REMOTE MODE POWER-ON CONDITIONS
Condition Default
Current
Soft Current Limit Model maximum current
Delay 0.5 seconds
Foldback Protection OFF
Output ON
Hold OFF
Unmask NONE
Service Request
Capability
Initial power–on current. Default value = OA. See
CAL:INIT:CURR
OFF
2.2.2 Power-On GPIB Service Request (PON SRQ) Selection
Set the rear panel PON SRQ switch to ON to cause a GPIB service request to be sent to the
computer controller when the supply is turned on.
POWER-ON GPIB SERVICE REQUEST (PON SRQ) SWITCH
Switch Position Description
ON Power-On SRQ selected
OFF No Power-On SRQ selected
Refer to your specific GPIB controller card manual for further details on serial polling.
2.2.3
Connects GPIB cable shield to chassis ground.
2.2.4
The SFA address selection is binary with switch A0 as the LSB and A4 as the MSB. The rear
panel switch illustration in Section 2.2 shows the address selection 00101 in binary (5 decimal).
The SFI address is selected and enabled from a list in the Remote menu. See SFI Operation
manual for more details on Remote menu, Navigation and Editing.
Shield Ground
Address Selection
The address selection for a unit is the GPIB address of that device (1-30). SCPI reserves
channel 0 as the global channel to address all channels.
M550292-03 (Programming) 2-3
Configuration Sorensen SF Series
ADDRESS SWITCHES
Switch Position Description
ON 1
OFF 0
2.3 Remote Programming Via RS-232
The DIA’s RS-232 interface operates at fixed 19.2Kbaud for SFA and is selectable from 2400 to
19.2Kbaud for the SFI, with 8 data bits, no parity, and 1 stop bit. All DIA commands are
supported at the RS-232 interface with the exception of the Service Request (SRQ) function
which is a GPIB-specific function requiring the dedicated Service Request line of the IEEE-
488.2 interface. In this case, the SRQ function has no effect. The RS-232 interface is
accessible through the rear panel 6-pin RJ-11 connector. The connector is labeled RS232.
Figure 2–3. SF to PC RS-232 Connection (RJ-11 to DB-9)
2-4 M550292-03 (Programming)
SECTION 3
IEEE 488.2 AND SCPI
COMMAND OPERATION
3.1
The following sections describe the operation of the DIA by remote programming using the DIA
IEEE-488.2 and SCPI command sets. The DIA IEEE488.2 and SCPI command sets provide
programming, query, and status commands that facilitate remote control of the power supply.
3.2
The DIA supports the IEEE-488.2 and SCPI 1995.0 status reporting data structures. These
structures are comprised of status registers and status register enable mask pairs. The
following sections describe these pairs.
Introduction
IEEE-488.2 Register Definitions
3.2.1
The SCPI Status Byte status register can be read by the *STB? command or by issuing a GPIB
serial poll. The Status Byte status register can be cleared by the use of the *CLS command.
The DIA can be configured to request service from the GPIB controller by setting the
appropriate bits in the Service Request Enable Register (SRE). The SRE register has the same
bit pattern as the Status Byte. It is modified using the *SRE <mask> command and read with
the *SRE? command. For example, if the SRE register is set to 0x10 (MAV), when the DIA unit
has a message available, the Status Byte register will contain 0x50 (RQS and MAV) and the
SRQ line of the GPIB will be asserted to indicate a request for service. See table below, and
refer to Section 5 for further information.
SCPI Status Byte
M550292-03 (Programming) 3-1
IEEE 488.2 and SCPI Command Operation Sorensen SF Series
SCPI STATUS BYTE
Bit Hex Value Description
0 0x01
1 0x02
2 0x04
3 0x08
4 0x10
5 0x20
6 0x40
7 0x80
Not used.
Protection Event Status flag. Indicates the selected protection
event occurred.
Error/event queue message available. Set when any error/event is
entered in the System Error Queue. It is read using the
SYSTem:ERRor? query.
Questionable Status flag. Indicates the quality of the current data
being acquired. This bit is not used.
Message available (MAV). Indicates a message is available in the
GPIB output queue. Cleared after the GPIB output buffer is read.
Standard Event Status Register (ESR). Summary bit for the ESR.
Set when any of the ESR bits are set and cleared when the ESR is
read.
Request Service flag (RQS) for serial polling or Master Summary
Status (MSS) in response to *STB? If service requests are enabled
(with the *SRE command), this bit represents the RQS and will be
sent in response to a serial poll, then cleared. If RQS is not
enabled, the bit represents the MSS bit and indicates the device
has at least one reason to request service. Even though the device
sends the MSS bit in response to a status query (*STB?), it is not
sent in response to a serial poll. It is not considered part of the
IEEE-488.1 Status Byte.
Operation Status flag. Indicates the current operational state of the
unit. This bit is not used.
3.2.2 Standard Event Status Register (ESR)
The Standard Event Status Register (ESR) can be read by the *ESR? command. Reading this
register or issuing a *CLS command will clear the ESR. Use the *ESE (Standard Event Status
Enable Register) to enable corresponding ESR bits to be summarized in the summary bit of the
SCPI Status byte. To configure the DIA to generate GPIB service requests based on the ESR,
both the Standard Event Status Enable Register and the Service Request Enable Register must
be programmed. See table below, and refer to Section 5 for further information.
STANDARD EVENT STATUS REGISTER
Bit Hex Value Description
0 0x01 Operation Complete
1 0x02 Request Control - not used
2 0x04 Query Error
3 0x08 Device Dependent Error
4 0x10 Execution Error (e.g., range error)
5 0x20 Command Error (e.g., syntax error)
6 0x40 User Request - not used
7 0x80 Power On
3-2 M550292-03 (Programming)
Sorensen SF Series IEEE 488.2 and SCPI Command Operation
3.2.3 Protection Condition and Protection Event Status Register
These two registers have the same bit meanings, but they differ in regards to how they function.
The Protection Condition Register can be read using the STAT:PROT:COND? command. This
command gives the present status condition of the power hardware, so the data is not latched.
It is meant to be used as a polling register.
The Protection Event Status Register can be read by the STATus:PROTection:EVENt?
command. Reading this register, issuing a *CLS command, or issuing a *RST command will
clear the Protection Event Status Register. Bits in the Protection Event Status Register will be
set only when the corresponding bit in the Protection Event Status Enable Register is set and
the corresponding event occurs. The status is then latched and will remain in that state until it is
read or cleared due to some command action. (Use the STATus:PROTection:ENABle <mask>
command to set the Enable Register and the STATus:PROTection:ENABle? query to read the
Enable Register.) To configure the DIA to generate GPIB service requests based on the
Protection Event Status Register, both the Protection Event Status Enable Register and the
Service Request Enable Register (*SRE) must be programmed. For further information, refer to
the table below, and to Section 5.
PROTECTION CONDITION AND EVENT STATUS REGISTERS
Bit Hex Value Description
0 0x01 Not used
1 0x02 Constant current operation
2 0x04 Not used
3 0x08 Overvoltage protection tripped (not applicable for SFA)
4 0x10 Overtemperature protection tripped
5 0x20 Supply external shutdown active
6 0x40 Foldback mode operation
7 0x80 Remote programming error
3.2.4
The Operation Status and Questionable Status Registers will always return 0 when queried.
The Operation Status Enable and Questionable Status Enable Registers can be programmed
and queried to allow SCPI compatibility but have no effect on the Operation Status and
Questionable Status Registers.
3.2.5
Operation Status and Questionable Status Registers
Error/Event Queue
The DIA maintains an Error/Event Queue as defined by SCPI. The queue holds up to 10 error
events. It is queried using the SYSTem:ERRor? command which reads in a First In/First Out
(FIFO) manner. The read operation removes the entry from the queue. The *CLS command
will clear all entries from the queue.
The following error codes are defined in the SCPI 1995.0 specification and are supported by the
DIA. Error codes are in the range of [-32768, 32767]. SCPI reserves the negative error codes
and 0, while error codes greater than 0 are device specific errors.
M550292-03 (Programming) 3-3
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.