American Time Wireless Controller User Manual

Page 1
Installation and Operation Manual
Wireless Controller
Part # H004417 Rev. 2 December 2013
Page 2
Safety Precautions
Disconnect and lock out electrical power to the unit before removing the wiring compartment cover or front panel.
The SiteSync IQ Wireless Controller operates from 120vac electrical power.
Voltage applied to clock and signal relay contacts must not exceed 120vac.
To protect against shorts between power and signal circuits, all wires connected to the power, clock and signal circuit terminals must be insulated to 300vac.
The only serviceable parts behind the front panel are, tone selection shunt jumpers and surge suppression switches.
The SiteSync IQ System Controller should be installed in a secure location protected from:
• Physical damage
• Water, including condensation
• Direct sunlight
• Operation by untrained personnel
American Time
140 3rd Street South PO Box 707 Dassel, MN 55325-0707
Phone: 800-328-8996 Fax: 800-789-1882
american-time.com
2
© American Time
Page 3
Table of Contents
Introduction ................................................................................................................................................................................. 4
Wireless Controller Installation .................................................................................................................................................. 5
Operation ..................................................................................................................................................................................... 6
Bell ........................................................................................................................................................................... 6
Tone .......................................................................................................................................................................... 7
Clock ......................................................................................................................................................................... 7
Testing Operaton of Wireless Signal Circuits ............................................................................................................... 8
Troubleshooting ........................................................................................................................................................................... 9
Appendix A: Wall Hanging Diagram ............................................................................................................................................. 10
Appendix B: Relay Wiring Diagram .............................................................................................................................................. 11
Appendix C: Clock Relay Wiring Diagram .................................................................................................................................... 12
Appendix D: Replacing Fusess .................................................................................................................................................... 13
© American Time
3
Page 4
Introduction
SiteSync IQ Wireless Controller
Installation Manual
The SiteSync IQ Wireless Controller provides synchronized control of secondary system clocks and electrical circuits such as those for controlling signaling devices and lights. Synchronization and event programming are achieved wirelessly from a SiteSync IQ Wireless System Controller. Manual control of signal circuits is achieved wirelessly via commands from a SiteSync IQ Wireless System Controller (keypad or Remote Connect Web Interface) or via panel switches on the front of the Wireless Controller.
SiteSync IQ Wireless Controller Standard Features
Introduction
• Power switch
• Power On indication LED
• Wall mounting hanger (molded into enclosure)
• Knock out wiring compartment
• Screw terminal main power input and relay contacts
• Relay surge suppression on/off switches
• Removable relay contact fuses
• Removable main power fuse
Installation
• Relay status indicator LEDs
• Manual control of signal circuits
• Flexible control of four signal circuits
SiteSync IQ Wireless Controller Specications
• Dimensions: ......................... 81/2"h x 101/8"w x 5"d
• Weight: ................................4 lbs.
Operation Controller
• Power: ..................................120vac hard-wired
• Operating temperature: ....... 41° to 131° degrees F
• Humidity: ............................. 0% - 95% Non-condensing
• Dry contacts: ....................... 10A 240v (resistive), optional 15A (resistive) 240v (socketed) clock only
• Receiver frequency: ............450-470 MHz (factory set)
• Paging format: ..................... POCSAG, Narrow band
• Data baud rate: ...................512 BPS
• Receiver sensitivity: .............10uV/M
Troubleshooting
• Channel spacing: ................12.5 KHz
Appendix
4
© American Time
Page 5
SiteSync IQ Wireless Controller Installation Manual
Mounting the SiteSync IQ Wireless Controller
The SiteSync IQ Wireless Controller should be:
• Located indoors in a dry location
• Mounted upright on a vertical surface
• Protected from physical damage
• Protected from water, including condensation
• Out of direct sunlight
• Operated by trained personnel
Controller Installation
Introduction
An area at least 24" wide x 24" high should be reserved to allow a clearance of at least 12" below and on the left side of the SiteSync IQ Wireless Controller. Wiring for power, clock and signal circuits must enter through conduit knockouts along the bottom of the enclosure. Connection for the tone output is located on the left side.
The SiteSync IQ Wireless Controller is designed to be wall-mounted by a molded hanger
24"
and screws. Appendix A shows a diagram for locating wall hangers at the appropriate spacings to mate with the unit.
At least 12"
24"
Manual On
System On
At least 12"
Wall
Electrical Connections
WARNING
To prevent electrical shock, do not apply electrical power to the SiteSync IQ Wireless Controller, clock relays or signal relays before completing all wiring connections.
120vac Supply Connections
120vac supply connections are located on the block of three (3) screw terminals located center left inside the wiring compartment. The hot terminal is located at the far left position of this block of three. The neutral terminal is located at the center position of this block of three. The ground terminal is located on the right side of this block of three.
Installation
OperationController
Troubleshooting
Fuse
A 2 amp - 250vac fuse protects the power input circuit. Each clock and signal relay circuit is protected by an 8 amp - 250vac fuse.
WARNING
To protect against shorts between power and signal circuits, all wires connected to the power, clock, and signal circuit terminals must be insulated to 300vac.
Clock Connections
CAUTION
To prevent damage to relays, relay contact voltage must not exceed 240vac.
Appendix B shows wiring connections to the SiteSync IQ Wireless Controller and secondary clocks for all clock types controlled by the SiteSync IQ Wireless Controller.
Signal Circuit Connections
CAUTION
To prevent damage to relays, relay contact voltage must not exceed 240vac.
Terminals for connecting to the normally open and common contacts of the optional signal circuit relays are located in the wiring compartment at the bottom of the enclosure.
© American Time
Appendix
5
Page 6
Operation
Side & Front View
SiteSync IQ Wireless Controller
Installation Manual
Front View - Open
2
Introduction
1
4
Installation
1. Power Switch
2. Power LED
3. 3 Position Relay Switches
4. RCA Jack
5. Tone Card
6. Bell Relay 1 Surge Switch
7. Bell Relay 2 Surge Switch
8. Bell Relay 3 Surge Switch
9. Bell Relay 4 Surge Switch
10. Power Input Fuse
Operation Controller
11. Hot
12. Neutral
13. Ground
14. Relay Connections
15. Relay Output Fuses
3
5
8 7
6
9
16. NC Surge Switch Clock B
17. NO Surge Switch Clock B
18. NC Surge Switch Clock A
19. NO Surge Switch Clock A
10
11
12
17 16
18 19
15
14
13
A power switch (#1) is located on the left side of the SiteSync IQ Wireless Controller. When power is connected and the power switch is in the on position the power LED (#2) located in the top right corner of the front panel will light red.
WARNING
The power switch only removes power to the internal circuitry of the SiteSync IQ Wireless Controller. If performing
Troubleshooting
maintenance within the wiring panel located at the bottom of the SiteSync IQ Wireless Controller, power should be removed prior to service.
Bell Relays
The SiteSync IQ Wireless Controller can be thought of as an extension to the SiteSync IQ System Controller wired relays. When the SiteSync IQ System Controller activates its on-board wired relays, it also sends out a message to activate the SiteSync IQ Wireless Controller relays. Each wired relay on the System Controller corresponds to the same wired relay on the Wireless
Appendix
Controller: i.e. Bell one on the system controller corresponds to bell one on the wireless controller; Bell two corresponds to bell two, and so on.
Each Wireless Controller bell relay comes equipped with a three position switch (#3). These switches allow the user to manually operate each circuit, turn them off or allow automatic control from the SiteSync IQ System Controller via wireless signals.
The bell relays on the SiteSync IQ Wireless Controller can be manually activated by moving the corresponding switch to the top (On or Test) position. A red LED will light indicating that the relay is currently active.
To disable a relay simply place the corresponding switch in the center position. The LEDs above and below the relay switch will turn off when the corresponding switch is in the OFF position.
Automatic bell relay operation is achieved by placing the corresponding switch in the down (Auto) position. In this position the SiteSync IQ System Controller has complete control of the bell relay. A yellow LED will light indicating the relay is ready for a message from the System Controller. A red LED will light indicating the relay is active.
6
© American Time
Page 7
SiteSync IQ Wireless Controller Installation Manual
Operation
Ton e
The audible tone output is located on the left side of the SiteSync IQ Wireless Controller via a RCA style jack (#4). The tone output is a low level non-amplied signal intended for input to an amplied system.
Tone Selection
n
Note: Power should be disconnected and off before making any jumper selections.
Tone Selection
The Tone card (#5) installed on the SiteSync IQ Wireless Controller provides a menu of eight tones of which four can be selected to be triggered from the SiteSync IQ System Controller. Place up to four jumper shunts at the lettered positions (see above) that correspond to the desired tones (use Tone Selection Table above). The tones will be assigned to the trigger terminals in the order they fall into from A to H where the rst tone selected on the way from A to H is assigned to SiteSync IQ System Controller circuit 1, the next tone selected is assigned to circuit 2, and so on. If more than four tones are selected via jumpers, only the rst four (from A to H) are assigned to the SiteSync IQ System Controller circuits 1 through 4. If less than four tones are selected, then only the circuits needed to correspond to the number of tones will be operational.
Tone Selection Table A* 512 Hz Steady B* Slow Whoop C* Siren D* Mechanical Bell E Klaxon F Night Ringer G Double Chime H Doorbell
*Factory Defaults
Introduction
Installation
OperationController
Troubleshooting
Clock
Clock relays are located on the far right side of the block of 14 screw terminals (#14) inside the wiring panel. (See Appendix B for wiring diagram)
© American Time
Appendix
7
Page 8
Operation
nNote: For AUTO operation, reference the SiteSync IQ Operation Manual (Part # H004095)
SiteSync IQ Wireless Controller
Installation Manual
Testing Wireless Operation of Signal Circuits
Signal circuits can be controlled manually with the MAN key on the SiteSync IQ System Controller acting as a momentary push­button switch. To initiate manual wireless control:
Using the SiteSync IQ System Controller
Introduction
uPress MAN, enter User Lock (unless User Lock is disabled) and press OK (unless User Lock is disabled).
nNote: If circuit numbers are not highlighted, press 0 to select wireless circuit activation.
vPress any combination of keys 1-4 to select or deselect the circuits to be turned on with the MAN key. The MAN key can be
pressed as many times as needed. Control of the signal circuits reverts to its previous state (AUTO or OFF) upon exiting this menu.
Installation
nNote: Reference Setting Signal Circuit Schedule and Duration in SiteSync IQ System Controller Operation Manual.
nNote: Upon pressing MAN, a TX will appear in the upper right hand corner to signify that the wireless activation is being
transmitted.
Manual Signal TX Select Circuits: 0=WL 7=All Circuit: 1234567
Operation Controller
nNote: The Remote Connect Web Interface may also be used to manually activate circuits via the Circuit tab..
Man=Signal OK=Exit
Troubleshooting
Appendix
8
© American Time
Page 9
SiteSync IQ Wireless Controller Installation Manual
Troubleshooting
SiteSync IQ Wireless Controller power LED OFF when power is connected
• Verify power switch is in the ON position
• Disconnect power to the SiteSync IQ Wireless Controller and remove the junction box cover. Restore power and carefully check for 120vac between terminals H and N.
• Disconnect power and remove the front panel. Check power input fuse (F2) and replace if necessary.
Secondary Clocks not synchronized with System Controller
• If system controller time was recently changed, allow up to 24 hours for secondary clocks to re-synchronize to the system controller.
• Make sure there is sufcient voltage across each secondary clock.
• If fewer than 25 secondary AllSync clocks are connected to the SiteSync IQ Wireless Controller, the secondary clocks might not recognize the correction from the SiteSync IQ Wireless Controller. Connect all intended clocks and allow time for the normal SiteSync IQ Wireless Controller correction. If secondary clocks still have not corrected, you may need to disable surge suppression circuitry (set surge switches S7 and S8 to the OFF position to disable surge suppression circuitry).
• Check for signal reception at installation location. Contact American Time Technical Support or reference the SiteSync IQ Site Survey instructions.
Signal Circuits Not responding to programmed events
Introduction
Installation
OperationController
• Make certain that SiteSync IQ System Controller circuits are set to AUTO and signal circuits are enabled. Press 8 on the System Controller keypad, enter User Lock, if applicable, then press
 .
• Conrm that signal circuits and events programmed to control them are assigned to the same schedule.
• Check for correct voltage at signal relay contacts.
• Check for signal reception at installation location.
• Check for signal reception at installation location. Contact American Time Technical Support or reference the SiteSync IQ Site Survey instructions.
Power outage during Daylight Saving Time Correction
• If there is a power outage during the correction period for Daylight Saving Time, the secondary clocks might not correct. In this event wait for the next 12 hour correction.
Troubleshooting
Appendix
© American Time
9
Page 10
Appendix A: Wall Mounting Diagram
8
1
/
2
Introduction
4
Installation
3
/
4
SiteSync IQ Wireless Controller
Installation Manual
Operation Controller
Troubleshooting
4
3
/
4
Appendix
10 /
16
1
10
7
5
/
8
Note: This diagram is not to scale.
© American Time
Page 11
SiteSync IQ Wireless Controller Installation Manual
Appendix B: Relay Wiring Diagram
Wired Signal Circuit Installation
To install wired signal circuits (for electrical device control including bells, tone generators, lights, etc.):
1. Disconnect and lock out power to the SiteSync IQ Wireless Controller and any circuit wiring.
2. Remove the cover from the Wireless Controller. a. Remove 2 screws from each side of the wire compartment cover. b. Remove the wire compartment cover
3. Route signal circuit wires into the wiring compartment of the Wireless Controller. a. Remove knockout(s) below wire compartment. b. Use copper conductors only. c. Use strain relief connector ttings in the knockout holes to secure the wires. d. Route the wires into the wiring compartment, leaving enough slack to make all connections to the relay terminals.
4. Connect signal wires to the circuit relay terminals. a. Route the power (feed) line of each circuit to the COM terminal of the desired circuit (1-6) being connected. b. Route the switched (load) line of each circuit to the NO terminal of the desired circuit (1-6) being connected. c. Label the wires for each circuit as desired.
5. Replace the wire compartment cover.
Note: The signal circuits are protected with surge suppression components. In some applications, this protection can cause
n
leakage current to trigger the output device(s) when the circuit is switched OFF. In these cases, the surge protection switches can be moved to the OFF position. Contact American Time Technical Support with any questions at 800-328-8996.
6. Apply power to the Wireless Controller and signal circuit(s).
Introduction
Installation
OperationController
7. Test the signal circuits using the Sitesync IQ System Controller circuit menu or Remote Connect circuit tab.
Example
FUSED POWER SOURCE
BLACK
WHITE
NO
BELL 1
BELL 4BELL 3BELL 2
COMNONO COMCOMNOCOM NO COMCOMNO
BELL 5/CLK A
BELL 6/CLK B
NCNC
Troubleshooting
Appendix
© American Time
See larger clock relay detail on Page 12
11
Page 12
Appendix C: Clock Relay
SiteSync IQ Wireless Controller
Wiring Diagram
Wired Clock Circuit Installation
To install wired clock circuits:
1. Disconnect and lock out power to the SiteSync IQ Wireless Controller and any circuit wiring.
2. Remove the cover from the Wireless Controller.
Introduction
a. Remove 2 screws from each side of the wire compartment cover. b. Remove the wire compartment cover.
3. Route clock circuit wires into the wiring compartment of the Wireless Controller. a. Remove knockout(s) below wire compartment. b. Use copper conductors only. c. Use strain relief connector ttings in the knockout holes to secure the wires. d. Route the wires into the wiring compartment, leaving enough slack to make all connections to the relay terminals.
4. Connect clock wires to the circuit relay terminals.
Installation
5. Replace the wire compartment cover.
6. Apply power to the wireless controller and clock circuit(s).
7. Test the clock circuit. Clock relay B should activate at HH:57:54 for 8 seconds and at 05:57:54 for 14 seconds.
Installation Manual
Operation Controller
120/24 VAC
Troubleshooting
Appendix
AC RTN
BELL 5/CLK A BELL 6/CLK B
NO C NC CNO NC
RUN MOTOR
RETURN
CORRECTION
Clock Code 01 - 3 wire Synchronous
12
© American Time
Page 13
SiteSync IQ Wireless Controller Installation Manual
Appendix D: Replacing Fuses
Introduction
H004408
Installation
H004406
OperationController
Part Number Description Where used
H004406 Fuse 2A 250V 5x20 Fast Glass, SSIQ
WRLS CNTR
H004408 Fuse 8A 250V 5x20 Fast Glass, SSIQ
WRLS CNTR
Power input (F2)
Relay contacts (F3-F8)
Troubleshooting
Appendix
© American Time
13
Loading...