American Standard AUD2B080AFV32A, AUD2D120AFV52A, TUD2B060AFV32A, TUD2B080AFV32A, TUD2C080AFV42A Installer's Manual

...
18- CD24D1- 2
Installer’s Guide
Variable Speed, 2-Stage, 80% Upflow/ Horizontal Gas-Fired Furnaces, “Fan Assisted Combustion System” with Whole House Air Cleaner
*UD2B060AFV32A *UD2B080AFV32A *UD2C080AFV42A *UD2B100AFV32A *UD2D120AFV52A
*__First letter may be “A” or “T”
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
For VENT SIZING INFORMATION see:
National Fuel Gas Code ........ ANSI Z223.1/ NFPA 54 (latest version)
CANADA —
Natural Gas Installation Code ..... CAN/ CGA-B149.1 (latest version)
Propane Installation Code ............ CAN/ CGA-B149.2 (latest version)
USA/ CANADA ALTERNATE —
Category I Venting Guide .......... Pub. No. 18-CH23D1 (latest version)
Available in French Canadian (FC)
Upflow/ Horizontal*
This unit is equipped with an integrated high efficiency Whole House Air Cleaner. Careful consideration must be taken in the installation process to avoid personal in­jury, property damage or equipment damage. These in­structions do not cover all variations in systems or pro­vide for every possible contingency. Should further in­formation be desired or particular problems arise which are not covered sufficiently by this manual, contact your local distributor or the manufacturer as listed on the Furnace nameplate. In addition, these Furnaces are suitable for installation in an attic, garage or crawl space with ducted supply and return air.
*Units are BOTTOM RETURN only
Horizontal Conversion for these furnaces
may be left or right side rotation.
Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The signal words for safety markings are WARNING and CAUTION.
a. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious in-
jury.
b. CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate in-
jury. It is also used to alert against unsafe practices and hazards involving only property damage.
A341789P08
Installer’s Guide
SAFETY SECTION
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1 Natural Gas and Propane Installation Code and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CSA B149.1 Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents where
tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas -fired burning appliance to their previous conditions of use.
!
WARNING
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could re­sult in serious injury, death or property damage. Improper servicing could result in dangerous opera­tion, serious injury, death, or property damage.
!
WARNING
Failure to follow safety warnings exactly, could result in a fire or explosion causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas supplier.
The following safety practices and precautions must be followed during the installation, servicing, and opera­tion of this Furnace.
1. Use only with the type of gas approved for this Fur­nace. Refer to the Furnace rating plate.
2. Install this Furnace only in a location and position as specified in “Location and Clearances” (page 4) of these instructions.
3. Provide adequate combustion and ventilation air to the Furnace space as specified in “Air for Combus­tion and Ventilation” (page 9), of these instructions.
4. Combustion products must be discharged outdoors. Connect this Furnace to an approved vent system only, as specified in the “Venting” section (page 12), of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifi­cally for the detection of leaks to check all connec­tions, as specified in the “Gas Piping” section of these instructions on page 19.
6. Always install the Furnace to operate within the Furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accom­panying this Furnace.
7. When a Furnace is installed so that supply ducts carry air circulated by the Furnace to areas outside the space containing the Furnace, the return air shall also be handled by a duct(s) sealed to the Fur­nace casing and terminating outside the space con­taining the Furnace.
© 2008 Trane All Rights Reserved 18-CD24D1-2
!
CAUTION
To prevent shortening its service life, the Furnace should not be used as a “Construction Heater” during the finishing phases of construction until the require­ments listed in item 9, a-i of the safety section of this publication have been met. Condensate in the pres­ence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition which may cause rapid de­terioration of the heat exchanger.
!
CAUTION
Chemicals used to during construction may cause damage to the COLLECTION CELL.
!
WARNING
DO NOT USE SEMI-RIGID METALLIC GAS CONNEC­TORS (FLEXIBLE GAS LINES) WITHIN THE FURNACE CABINET. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
8. A gas-fired Furnace for installation in a residential garage must be installed as specified in “Location and Clearances” section (page 4) , of these instruc­tions.
9. The Furnace may be used for temporary heating of buildings or structures under construction when the following conditions have been met: a. The Furnace venting system must be complete
and installed per manufacturers instructions.
b. The Furnace is controlled only by a room Com-
fort Control (no field jumpers).
c. The Furnace return air duct must be complete
and sealed to the Furnace.
d. The Furnace input rate and temperature rise
must be verified to be within nameplate mark­ing.
e. 100% of the Furnace combustion air require-
ment must come from outside the structure.
f. The Furnace return air temperature range is
between 55
g. Clean the Furnace, duct work, and components
upon substantial completion of the construction process, and verify Furnace and whole house air cleaner operating conditions including igni­tion, input rate, temperature rise and venting, according to the manufacturer's instructions.
h. Remove the Whole House Air Cleaner and
store in a clean, dry location during the construction process. To be reinstalled when construction is complete. See page 27 for proper air cleaner removal.
i. An external field supplied air filter must be
used during construction.
0
and 800 Fahrenheit.
only
Installer’s Guide
Contents
Safety Section 2
Installation Instructions 4
General 4 Location and Clearances 4
Outline Drawings 6
Upflow Installation 7 Horizontal Installation 7 Air For Combustion and Ventilation 9 Duct Connections 10 General Venting 12 Venting Routed Through a Masonry Chimney 12
Field Wiring Diagrams 14
Electrical Connections 19 Gas Piping 19 Combustion and Input Check 21 High Altitude Derate 22
Start-up and Adjustment 23
Preliminary Inspections 23 Lighting Instructions 23 Sequence of Operation 24 Control and Safety Switch Adjustments 24
Conditions Affecting System Operation 26
Whole House Air Cleaner Maintenance 26
IFC Error Flash Codes 28
Checkout Procedure 30
10. This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts.
18-CD24D1-2 3
Installer’s Guide
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equip­ment installed in violation of any code or regulation. It is recommended that Manual J of the Air Condition­ing Contractors Association (ACCA) or A.R.I. 230 be fol­lowed in estimating heating requirements. When esti­mating heating requirements for installation at Alti­tudes above 2000 ft., remember the gas input must be reduced (See combustion and input check page 21).
Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in ship­ment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the de­livering agency.
Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumbing, and flue connections must be adhered to. In the ab­sence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI Z223.1 • National Installation Code, CAN/CGA B149.1. The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or www.aga.org These furnaces have been classified as Fan Assisted Combustion system CATEGORY I furnaces as required by ANSI Z21.47 “latest edition” and CAN/CGA 2.3. Therefore they do not require any special provisions for venting other than what is indicated in these instruc­tions. (Category I defined on pages 12 and 13).
LOCATION AND CLEARANCES
!
WARNING
Do NOT install the Furnace directly on carpeting, tile or other combustible material other than wood flooring.
!
CAUTION
Do NOT install the Furnace in a corrosive or contami­nated atmosphere. Failure to follow this warning could result in early equipment failure.
The location of the Furnace is normally selected by the architect, the builder, or the installer. However, before the Furnace is moved into place, be sure to consider the following requirements:
1. Is the location selected as near the chimney or vent and as centralized for heat distribution as practical?
2. Do all clearances between the Furnace and enclo­sure equal or exceed the minimums stated in Clear ance Table on the Outline Drawings?
3. Is there sufficient space for servicing the Furnace and other equipment? A minimum of 24 inches front accessibility to the Furnace must be provided. Any access door or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the Furnace combustion air openings in the front panel and any closed panel or door provided?
5. Are the ventilation and combustion air openings large enough and will they remain unobstructed? If outside air is used, are the openings set above the highest snow accumulation level? (See the Air for Combustion and Ventilation section, page 9)
6. A heavy gauge steel plate is attached to the
bottom of the unit for protection during ship­ping and handling prior to the unit installa­tion. Leave this plate in place until the unit is ready to be connected to the ductwork.
7. A Pre-filter is the furnace containing a Whole House Air Cleaner. If the use of a Pre-Filter is desired, it must be installed at least 6" away from the Whole House Air Cleaner. The additional pressure drop of the Pre-Filter must be considered during duct design or evaluation to ensure proper airflow.
8. Allow sufficient height in supply plenum above the Furnace to provide for cooling coil installation, if the cooling coil is not installed at the time of this Furnace installation.
9. A Furnace shall be installed so electrical compo­nents are protected from water.
10. DO NOT use silicon based sealant in the airstream. This causes a coating on the FIELD CHARGER pins that will decrease the efficiency of the air cleaner.
11. Allow a minimum of 24 inches clearance in front of the air cleaner to permit removal of COLLECTION CELL and FIELD CHARGER.
12. DO NOT install furnace where the air cleaner can be exposed to UV light.
not required to be installed with
4 18-CD24D1-2
NOTE: Do NOT install an atomizing style humidifier in the return plenum of this unit.
13. Flow-through Bypass Humidifiers
Excessive bypass air may cause water blow-off, which will adversely affect system operation and air cleaner performance. To verify bypass airflow, fol­low the Bypass Humidifier Pre-Installation Check­out and Set-Up Procedures available through your local distributor. Ask for publication number 18­CH37D1-1.
Steam and Flow-through Fan Power Duct­mounted Humidifiers
Follow the humidifier installation instructions. These should only be installed on the supply air side of the system.
Other Duct Mounted Humidifiers are not rec­ommended for installation with the air cleaner.
14. If the Furnace is installed in a residential garage,
it must be installed so that the burners, and the ig­nition source are located not less than 18 inches above the floor and the Furnace must be located or protected to avoid physical damage from vehicles.
15. The whole house air cleaner is designed to run at a maximum indoor relative humidity of 65%.
Installer’s Guide
Figure 1. COMPONENTS OF THE INTEGRATED WHOLE HOUSE AIR CLEANER
1
Components of the integrated Whole House Air Cleaner:
1) FIELD CHARGER - Charges the contaminants
2) COLLECTION CELL - removes and collects very small
impurities from the air.
3) Power Supply - the solid state power supply converts the 24 Volt AC to the high-voltage, direct current required to power the FIELD CHARGER and COLLEC­TION CELL.
Check carefully for any shipping damage. This must be reported to and claims made against the transportation company immediately. Check to be sure all major components are in the unit. Any missing parts should be reported to your supplier
at once, and replaced with authorized parts only.
2
3
18-CD24D1-2 5
Installer’s Guide
MODEL DIM "A" DIM "B" DIM "C" DIM "D" DIM "E"
*UD2B060AFV32A
*UD2B080AFV32A
*UD2B100AFV32A
17-1/2" 9-5/8" 16-1/4" 16" 16"
*UD2C080AFV42A 21" 13-1/16" 19-3/4" 19-1/2" 19-1/2"
*UD2D120AFV52A 24-1/2" 15-5/16" 23-1/4" 23" 23"
* PREFIX LETTER MAY BE "A" OR "T"
(ALL DIMENSIONS ARE IN INCHES)
*UD2 OUTLINE DRAWING
Bottom Return ONLY
6 18-CD24D1-2
INSTALLATION INSTRUCTIONS
!
CAUTION
Bottom panel for furnace to remain in place until unit reaches final installation location. If bottom panel is re­moved before installation the collection cell and field charger must also be removed to protect installation personnel.
!
CAUTION
Remove the COLLECTION CELL and remove and dis­card the cardboard over the cell.
Installer’s Guide
UPFLOW INSTALLATION
Standoffs and screws (See Figure 2) are included with the cased coils for attachment to the Furnace. There are clearance alignment holes near the bottom of the coil wrapper. Drill screws are used to engage the Fur­nace top flanges. The standoff is inserted into the cabi­net alignment hole. The drill screws are inserted through the standoffs then screwed into the Furnace flange. The coil is always placed downstream of the Fur­nace airflow. The above instructions apply only if the coil is on top of an upflow Furnace.
NOTE: No sheetmetal screws may be used from 0-4" from the bottom of the unit. Screws will interfere with the Air Cleaner. See Figure 4.
REMOVING THE BOTTOM PLATE
a. Once the furnace is in place, remove the two screws
located at the front bottom corners of the Furnace.
b. Lean the furnace back slightly and remove the bot-
tom panel.
c. Replace the two screws removed in step a.
REMOVING THE COLLECTION CELL AND FIELD CHARGER
When COLLECTION CELLS and FIELD CHARGER must be removed, follow the steps below. a. Remove the lower furnace door. b. Remove the four screws holding the inner blower
panel and remove panel. Set aside in a safe place until the unit is set in place and ready to start up.
c. Remove the COLLECTION CELL by sliding for-
ward.
Remove the cardboard from the COLLEC­TION CELL and discard. Set aside in a safe place until the unit is set in place and ready to start up.
d. Disconnect the Green return wire and the Red high
voltage wire. Twist and pull the connector on the Red wire to release.
e. Remove the two hold down screws on the bottom of
the FIELD CHARGER and retain.
f. Remove the Field Charger. Set aside in a safe
place until the unit is set in place and ready to start up.
g. Set furnace in place. Repeat step a-g in reverse or-
der. Do Not put cardboard back in Furnace. Inner blower door MUST be put back into place.
FOR VERTICAL
CASED
COIL
U
P
F
F
L
U
O
R
W
N
A
C
E
STANDOFFS
(BOTH SIDES)
STANDOFFS (4)
SCREWS
(BOTH SIDES)
DRILL SCREWS (4)
Figure 2
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in the horizontal position.
IMPORTANT: The 2/4TXC cased coil must be placed downstream of the furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See the 2/4TXC coil Installer's Guide for more details.
The cased coil is secured to the Furnace and both the Furnace and the cased coil must be properly supported. The brackets mount using the rear screws on the coil case and use the screws provided to secure the bracket to the Furnace. The remaining bracket is placed as close to center as possible (horizontally) between the coil case front and the upflow Furnace, converted to horizontal, aligns and attaches to the TXC coil. How­ever, the coil requires additional support. The horizontal Furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the Furnace (See Figure 3 & Clearance Table
1). Line contact is only permissible between lines formed by intersections of the top and two sides of the furnace casing and building joists, studs, or framing.
18-CD24D1-2 7
Installer’s Guide
Typical Upflow/ Horizontal Attic Installation
1
Figure 3
The Furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection from moisture. The Furnace
must be supported at both ends and the middle when in­stalled horizontally. The Furnace must also be elevated approximately 4-6 inches to allow clearance for the con­densate drain to exit the cabinet in the horizontal posi­tion.
The horizontal Furnace may also be suspended from the joists using all-thread rods with a substantial metal support frame that supports the entire length of the furnace. The rods need to be of sufficient length to allow for proper clearances from combustible materials. The frame needs to be at least 32" in length to allow for access to service panels. If the Furnace is suspended using steel strap, it must be sup­ported at all four corners and in the middle at the front of the Furnace.
Materials
• Duct Flanges Two 23.5" Flanges Two Additional Flanges
15.92" (for 17.5" cabinet)
19.42" (for 21" cabinet)
21.92" (for 24.5" cabinet)
• Screws Eight 5/16" Blunt Tip Screws with 5/16" Hex Head
Steps
1. See Figures 5, 6, and 7 for flange orientation.
2. Attach flanges 1, 2, and 3 (Fig 7) to the unit using
the factory provided screws and the pre-drilled holes in the wrapper. Flanges 1 and 2 are the
23.5" flanges that are generic to all units. Flange 3 will be one of two short flanges and the length of which is dependent on the cabinet size.
3. Attach flange 4 (Fig 7) to the duct work (Flanges
should be inside duct work). Flange 4 is the remaining short flange.
4. Place duct work with single flange over the 3
flanges that are currently attached to the unit
5. Attach duct work to remaining 3 flanges.
6. Attach the front flange from step 3 to the unit by
drilling 1/8" holes into the bottom channel. Use the factory provided 5/16" blunt tip screws to attach.
7. Use field supplied material to make an adequate
seal. DO NOT use silicon based sealant in
the airstream.
NOTE: No sheetmetal screws may be used from 0-4" from the bottom of the unit. Screws will interfere with the air cleaner.
Figure 4
NOTE: Do NOT install screws to the bottom of the unit except with Duct Flanges and Screws provided.
GUIDE FOR THE INSTALLATION OF DUCT FLANGES
Failure to use pre-drilled holes and the factory provided screws can potentially damage air cleaner components.
"
!
CAUTION
Figure 5: Horizontal Left
8 18-CD24D1-2
Installer’s Guide
Use pre-drilled holes
1
4
Figure 6: Bottom View - Pre-drilled holes
1
4
2
Use pre­drilled holes
3
2
Use pre­drilled holes
3
AIR FOR COMBUSTION AND VENTILATION
Adequate flow of combustion and ventilating air must not be obstructed from reaching the Furnace. Air open­ings provided in the Furnace casing must be kept free of obstructions which restrict the flow of air. Airflow re­strictions affect the efficiency and safe operation of the Furnace. Keep this in mind should you choose to re­model or change the area which contains your Furnace. Furnaces must have a free flow of air for proper perfor­mance.
Provisions for combustion and ventilation air shall be made in accordance with “latest edition” of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or Sections 7.2, 7.3 or 7.4 of CSA B149.1 Installation Codes, and applicable provi­sions of the local building codes. Special conditions cre­ated by mechanical exhausting of air and fireplaces must be considered to avoid unsatisfactory Furnace op­eration.
Furnace locations may be in “confined space” or “uncon­fined space”. Unconfined space is defined in Table 2 and Figure 8. These spaces may have adequate air by infil­tration to provide air for combustion, ventilation, and dilution of flue gases. Buildings with tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need additional air provided as described for confined space.
Figure 7: Bottom View ­Flange Attachment
Tab le 1
Minimum Clearance to Combustible Materials
Upflow Closet
Left Side 0 inches Front 3 inches (note 1)
Right Side 0 inches Back 0 inches
Flue 6 inches * Top 1 inch
Horizontal Closet
(see note 2)
Top 2 inches Back 3 inches
Flue 6 inches * Sides 1 inch
Front 18 inches (note 1)
Horizontal Alcove
(see note 2)
Top 1 inch Back 0 inches
Flue 6 inches Sides 0 inches
Front 18 inches
* May be 1" when type B-1 vent is used NOTES:
1) Minumum clearance to front on *UD2D120 is 6 inches
2) May be installed on combustible floor when type B-1 vent is used.
UNCONFINED
50 CU. FT. OR MORE PER 1000 BTU/ HR. INPUT ALL EQUIP. INSTALLED
Figure 8
TABLE 2
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE
MAXIMUM BTUH
INPUT RATING
60,000
80,000 100,000 120,000 140,000
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE
FEET OF UNCONFINED SPACE
375 500 625 750 875
1. All air from inside the building as in Figure 10: The confined space shall be provided with two perma­nent openings communicating directly with an addi­tional room(s) of sufficient volume so that the com­bined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utiliza­tion equipment installed in the combined space shall be considered in making this determination. Refer to Table 3, for minimum open areas required.
18-CD24D1-2 9
Loading...
+ 21 hidden pages