Installer's
DMPR-IN-38A
18-HE60D104-1
Guide
Customer Property: Contains
wiring and service information. Please retain.
Models : Used With:
BAYDMPR051A T*C036-060A*R
Y*C036-060A*R
WSC036-060A*R
BAYDMPR052A T*C036-060A*E
Y*C036-060A*E
BAYDMPR054A T*C072-120A*R
Y*C072-120A*R
WSC072-120A*R
Library Service Literature
Product Section Unitary
Product Unitary Accessories
Model Econ., Dmprs. Motors, etc.
Literature Type Installer's Guide
Sequence 38A
Date October 2001
File No. SV-UN-ACC-DMPR-IN-38A 10/01
Supersedes -DMPR-IN-38
0-50% Motorized
Outside Air Damper
BAYDMPR055A T*C072-120A*E
Y*C072-120A*E
Installation - Field Installed
Note: This instruction covers installation of
BAYDMPR051A, BAYDMPR052A
(T/W/Y036-060 units) and
BAYDMPR054A,BAYDMPR055A
(T/W/Y072-120 units)
Parts List
1 - Motorized OA Damper Assembly
10 - Screws (T/W/Y036-060 units)
12 - Screws (T/W/Y072-120 units)
1 - Sealant; Silicone Rubber
1 - Blockoff; Bottom
Uncrate the damper and locate all parts shown in
Figure 1.
3. Once the damper is in place, lift the damper and panel
assembly to align the upper two screw holes. Secure the
top by inserting 2 screws, top left 1 then top right 2. Refer to Figure 3.
4. Pull out on the bottom of the damper and secure bottom
left 3. Refer to Figure 3.
Figure 2
Downflow Installation
DISCONNECT TO PREVENT INJURY OR DEATH
OPEN AND LOCK UNIT
FROM ELECTRICAL SHOCK OR CONTACT WITH
MOVING PARTS.
Each damper ships with items 1, 2 and 3 attached. Remove
screws completely from items 1 and 2. Remove item 3 by
loosening the 3 screws but do not remove them. Refer to
Figure 1.
Figure 1
5. Remove the filter access panel. Position the adapter
backing plate inside the filter section. The adapter backing plate will slip over the 3 screws that were loosened in
Figure 1. Align the screw engagement hole in the
adapter backing plate, with the screw clearance hole in
panel and secure lower right side of damper with screw
4. Refer to Figure 3.
6. Install the bottom blockoff and secure with 3 screws. Refer to Figure 3.
7. Refer to Figure 6 for sealing instructions.
Wiring Connections
Reliatel Units
Locate unit wiring harness plug P7 and plug into J7 on the
acturator motor.
1. Remove unit end panel, retain the screws removed from
the top of panel and the screws removed from bottom of
panel for use later.
2. To install the damper, lift into position by fitting the upper
left hand corner around the channel in the cabinet post.
Then pivot the economizer into the opening in the cabinet. Refer to Figure 3.
Electromechanical Units
Locate unit wiring harness plug PPM2A and plug into the
acturator motor wiring harness.
2