8 CHANNEL BI-DIRECTIONAL
CONTACT CLOSURE SYSTEM
Features:
8 Channels Bi-Directional, Form-C
(Normally Open or Normally Closed) Dry
Contact Closure
Latching Relays reduce power
requirement
Maintains Contact Status through
Power-Cycle and Loss-of-Optical-Power.
User Control to Reset all Contact Status
Diagnostics: Power, Optical Presence
and Channel Indicators
High Density DB26 Data Connector with
Adaptor to screw terminal
Specifications:
Data:
Contact Closure Rating...............0.5A Max.
40 Volt DC or Peak AC Per Channel
Response Time...................................5 ms
Connector .....................DB26 with Adaptor
to Screw Terminal
Optical:
Wavelength..........................1310/1550 nm
Loss Budget (62.5/125µ)....................12 dB
Connector .............................................. ST
Temperature (Operating)
-40°C to +75°C, non-condensing
Power Supply:
Module – 12 VDC (AFI Part # PS-12+)
Rack Card – AFI SR 20/2
Size:
Module ...........................81/8” x 41/8” x 1.5”
Rack Card 6½” x 5” x2”
Product Ordering Information:
MTX = Module Transmitter–Signal Source
MRX = Module Receiver–Signal Receive
RTX = Rack Card Transmitter-Signal Source
RRX = Rack Card Receiver–Signal Receive
Example: MTX-82B to RRX-82B
9/24/2012 JPM
82B
SERIES
MULTIMODE
Photo of another product which has
the same packaging.
The American Fibertek 82B Series multiplexes 16 total channels (8 in each
direction) of dry latching contact closure on one multimode fiber. Individual
channel LEDs on the transmitter and the receiver units indicate the channel
status.
The contact output relays are latching which maintain their states when either
optical power is removed (fiber disconnected) or the fiber modules lose DC
power. A reset button is available to clear all contact status to the default
state.
These systems require no field adjustments at installation or additional
maintenance thereafter. Diagnostic indicators provide a qu ick visual i ndication
of system status.
Equipment may be ordered as stand alone modules or rack cards that are
mounted in the SR-20/2 or SR20H/2(redundant power supply) AFI Card
Cage.
CONTACT
INPUTS
Channels 1 to 8
CONTACT
OUTPUTS
Channels 9 to 16
MTX-82B
or
RTX-82B
ONE
MULTIMODE
FIBER
MRX-82B
or
RRX-82B
CONTACT
OUTPUTS
Channels 1 to 8
CONTACT
INPUTS
Channels 9 to 16