Amana WS924D1STC, WS936D1, WS900GS, WS900DINTERNAL Installation Manual

PTAC
W
ALL
S
LEEVE
INSTALLATION INSTRUCTIONS
The wall sleeve must be installed before the air conditioner or heat pump chassis can be set in place.
Read the instructions thoroughly before proceeding.
AT TENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to know the product better than the customer. This includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all safety warnings. Often during installation or repair it is pos­sible to place yourself in a position which is more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific good safety practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if there is a direct conflict between existing practices and the content of this manual, the precautions listed here take precedence.
RECOGNIZE THIS SYMBOL AS A SAFETY
PRECAUTIONDESCRIPTON
When 230/208 volt units are to be installed, the power supply may be either cord connected or permanent wiring. Perma­nent wiring may be done through the hard wire junction box, or the accessory subbase.
When 265 volt units are to be installed, the power supply must be permanent wiring. Permanent wiring may be done through the accessory hard wire junction box, or the acces­sory subbase. An exposed cord connection on 265 volt units
is not permitted.
The subbase accessory includes leveling legs. If added wall sleeve support is required and the subbase is not to be used an accessory leveling leg kit may be installed.
INDEX
A TTENTION INST ALLING PERSONNEL................................... 1
KIT ACCESSORIES................................................................. 1
DRAIN KIT ..................................................................... 1
PRE-INST ALLA TION CONSIDERA TIONS.................................. 3
OUTDOOR ENCLOSURE PANEL REMOVAL ................................... 3
WALL SLEEVE INST ALLA TION............................................... 4
KIT ACCESSORIES DRAIN KIT
An indoor/outdoor drain kit is available as an accessory item. When a drain kit is to be installed, do so before installing the wall sleeve in the wall. See the drain kit for actual installation instructions.
SUBBASE, LEVELING LEGS, MAIN DUCT, AND HYDRONIC HEAT KITS
Installation of these kits requires drilling of mounting holes on both sides of the wall sleeve. The minimum required clearance distance between the wall sleeve and wall is shown in Table 1. If the distance between wall sleeve and wall will be at or near the minimum clearance distance, mount these kits on the sleeve before installing the sleeve in the wall. The kit installa­tion instructions are included with the accessory kits.
A3495105r4 01 / 2017
is a registered trademark of Maytag Corporation or its related companies and is used under license to
Goodman Company, L.P., Houston, TX, USA. All rights reserved.
5151 San Felipe, Suite 500Houston, TX 77056 • www.amana-ptac.com
© 1996, 2000, 2004-2005, 2017 Goodman Company, L.P.
Outside
Wall
6
1
1
/
1
6
"
4
1
0
m
m
Internal
Adjacent
Wall
"A"
Minimum
Top of Wall Sleeve
"A"
Minimum
Internal
Adjacent
Wall
4
2
"
1
0
6
5
m
m
Wall Receptacle Within 58" From Bottom Right Side Corner on 208/230 VAC Units Only
Figure 1 - Wall Sleeve Dimensions
4
2
1
1
0
/
4
7
"
M
5
i
m
n
m
i
m
u
m
Finished Floor
4
1
1
/
8
"
3
5
9
m
m
m
"
m
4
u
/
m
1
m
i
5
6
n
1
i
1
4
M
Dimension "B" in Table 1
Allow Front Clearance (See Table 1)
Figure 3 - Minimum Unit Clearances
* To ensure proper airflow and filter removal, it is recommended
the wall sleeve be installed a mini mum of 36” from the ceiling.
Figure 4 - Minimum Interior and Exterior
NOTE: To ensure proper airflow and filter removal, it is recom­mended installation of the wall sleeve be a minimum of 36” from the ceiling.
Figure 2 - Minimum Wall Opening Dimensions
MINIMUM CLEARANC ES AND PROJEC TIONS
MINIMUM CLEARANCES MINIMUM PROJECTION
OPTION
C (Figure 4)B (Figure 3)A (Figure 2)
Inches mm Inches mm Inches mm
Wal l Sl eeve Onl y 3 75 0 0 0 0 Subbase Kit 3 75 3 1 /4 85 2 3/4 70 Leveling Legs Kit 3 75 3 75 2 50 Duct Kit 3 75 0 0 2 3/8 35
Hydronic Heat Kit "A Series" 9 230 0 to 3 1/4
3
0 to 85
3
2
3
75
2
Hydronic Heat Kit "J Series" 6 150 0 0 2 1/2 65 Drain Kit 3 75 '0
1
'0
1
00
Hardwire Kit 3 75 1 1/4 30 0 0
1
If inside mounted then B = 1 1/2 inches (40 mm)
2
To achieve a flush fit between the hydronic front and the finished wall, Dimension “C” must be between 3” and 3 1/8”. If this dimension is more than 3 1/8” there will be a gap between the front and the wall. This gap could permit occupant access to hydronic lines or other dangerous parts. For flush mounts, internal drain kits or flashing are required to prevent leaking from external drains into space. See drain kit installation for details on sleeve positioning for internal drain kits.
3
This dimension can be from 0” to 3-1/4”, but cannot exceed 3-1/4”. If this dimension exceeds 3-1/4”, the skirt around the front will not reach the floor.
Table 1
2