X.Heating Sequence of Operations............... 18
XI.Cooling Sequence of Operations .............. 18
XIl. Startup and Adjustment .............................. 18
XIII. Maintenance................................................. 24
XIV. Accessories and Functional Parts ............ 26
XV. Typical Cooling Performance Data ............ 27
XVI. Wiring Diagram ............................................ 29
Gas-Electric Package
Unit
Cooling and Heating
Installation Instructions
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to
know the product better than the customer. This includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all safety warnings. Often during installation or
repair it is possible to place yourself in a position which
is more hazardous than when the unit is in operation.
Affix These Installation Instructions Adjacent To The Appliance.
Remember, it is your responsibility to install the
product safely and to know it well enough to be able
to instruct a customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific
good safety practices...follow them.
The precautions listed in this Installation Manual
should not supersede existing practices but should
be considered as supplemental information.
Amana
May 1998 (2)11073904
Fayetteville, TN 37334
I. Unit Specifications
MODELPGC24B0452APGC24B0702APGC30B0702APGC36B0702APGC36B09 02A
Cooling Cap acity Btuh24,00024,00030,00036,00036,000
SEER12.5012.5012.3012.0012.00
Heating
2) Specification subject to change without notice. See sales specification sheets for certain BTUH capacities.
3) This PGC series complies with requirements embodied in the American National Standard ANSI-Z21.47 Central Furnaces.
4) Filters are not supplied with units, but filters must be installed in the unit filter rack or in the return air system.
** While the above data is presented as a guide, it is important to electrically connect the unit and properly size overcurrent protection and wires in accordance with the
National Electrical Code and all existing local codes.
Operating tolerance: Minus 5% on 208 VAC, Plus 10% on 208 VAC and 230 VAC, Minus 10% on 230 VAC
Table 1A
Gas Pack Specifications
2
MODELPGC42B0902APGC42B1152APGC48B0902APGC48B1152APGC60B0902APGC60B1352A
Cooling Capacity Btuh42,00042,00048,00048,00060,00060,000
SEE R12.2012.2012.0012.0012.0012.00
Heating
Compressor
Condenser Coil
Condenser Fan
Condenser Fan Motor
Blow er Mot or
Blower Wheel Dia. x W idth (in.)10x1010x1010x1010x1011x811x8
Combustion Blower
Condenser Blower Motor
P ress. S wi t ch Setting (" W.C.)-0.65-0 .65-0.65-0.65-0 .65-0.65
Ignition - Lockout Timing (sec.)444444
Flame Sense Current ( microamps)
Evaporator Coil
Electrical Entrance Size
Approx. Shipping Weight (lbs)521527526526531531
Input B tuh90, 000115,00090,000115,00090,000135,000
2) Specification subject to change without notice. See sales specification sheets for certain BTUH capacities.
3) This PGC series complies with requirements embodied in the American National Standard ANSI-Z21.47 Central Furnaces.
4) Filters are not supplied with units, but filters must be installed in the unit filter rack or in the return air system.
** While the above data is presented as a guide, it is important to electrically connect the unit and properly size overcurrent protection and wires in accordance with the
National Electrical Code and all existing local codes.
Operating tolerance: Minus 5% on 208 VAC, Plus 10% on 208 VAC and 230 VAC, Minus 10% on 230 VAC
1. Installation is to be adjusted to obtain temperature rise within the range specified on the rating plate.
2. The temperature rise is for units installed at 0-2000 feet. At higher altitudes, a properly derated unit will have
approximately the same temperature rise and CFM.
3. The chart is applicable for both vertical and horizontal airflow.
4. All speed tap settings are factory selected according to unit size.
5. Data shown without filters. Consult filter manufacturer for pressure drop to be added.
6. Motor is constant CFM for external static pressures 0.1" to 0.8" W.C.
2. Installation is to be adjusted to obtain temperatures rise within the range specified on the rating plate.
3. The above chart is for information only. For satisfactory operation, external static pressure should not exceed value shown on the rating
plate. The shaded area () indicates in excess of maximum external static pressure allowable when heating.
4. This chart is for units installed at 0-2000 feet. At higher altitudes, a properly derated unit will have approximately the same temperature
rise at a particular CFM, while ESP at that CFM will be lower.
5. Cooling operation may require a different fan speed than heating operation. For details, see Wiring Diagrams.
6. Above chart is applicable for both vertical and horizontal airflow.
External Static Pressure, Inches Water Column
Table 2B
PGB CFM& Temperature Rise vs. External Static Pressure Table
5
II. Safety Information
WARNING
Important
To The Installer
Before installing this unit please read this manual to familiarize yourself with the specific items which must be
adhered to such as maximum external static pressure
to unit, air temperature rise, minimum or maximum CFM
and motor speed connections. Affix these Installation
Instructions adjacent to the appliance.
To The Owner
It is important that you complete the owner registration
card and mail it today. This will assist Amana in contacting you if any service or warranty information should
change in the future. When completing the registration
card, be sure to include the Model, Manufacturing and
Serial Numbers, plus the installation date.
Your warranty certificate is also supplied with the unit.
Read the warranty carefully and note what is covered.
Keep the warranty certificate in a safe place so you can
find it if necessary.
If additional operating Instructions are required, call the
dealer where the purchase was made. Keep this literature in a safe place for future reference.
Do not store gasoline or other flammable
vapors and liquids in the vicinity of this
or any other appliance.
If you smell gas:
• Extinguish any open flame.
• Do not try to light appliance.
• Do not touch any electrical switch: do not use any
phone in building.
• Immediately call gas supplier from a neighbor’s
phone. Follow gas supplier’s instructions.
• If gas supplier cannot be reached, call fire depart-
ment.
WARNING
Improper installation, adjustment, alterations, service or maintenance can cause
property damage, personal injury, or
death. Follow all procedures in this
manual. For assistance or additional information, contact a qualified installer,
service agency, or gas supplier.
WARNING
Should overheating occur or the gas supply fail to shut off, turn off the manual
gas control valve to the furnace before
shutting off the electrical supply.
CAUTION
On PGC48 - 60 and PGB58 Only: To avoid
damage to the compressor, engage the
electrical disconnect switch to the compressor unit four hours prior to operating air conditioner after the electrical disconnect is off for a prolonged period of
time (during vacation, etc.). This time
lapse allows the compressor crankcase
to attain a proper operating temperature.
WARNING
If the information in this manual is not
followed exactly, a fire or explosion may
result causing property damage, personal injury, or death.
WARNING
This product contains or produces a
chemical(s) which may cause death or
serious illness and which are known by
the State of California to cause cancer,
birth defects or other reproductive harm.
CAUTION
This unit should not be used as a “construction heater” during the finishing
phases of construction on a new structure. This type of use may result in premature failure of the unit due to extremely
low return air temperatures and exposure
to very dirty atmospheres.
6
Locating The Unit
WARNING
To avoid possible equipment damage,
fire, personal injury, or death, the following points must be observed when installing the unit.
All Installations:
• For proper flame pattern within the heat exchanger
and proper condensate drainage, the unit must be
mounted level.
• The unit should be as centralized as is practical with
respect to the air distribution system. This unit is for
outdoor installation ONLY!
• The flue outlet hood must be at least 12 inches from
any opening through which flue gases could enter a
building, and at least three feet above any forced air
inlet located within ten feet. The economizer/manual
outdoor air intake/motorized outdoor air intake and
combustion air inlet mounted on the unit are not affected by this restriction.
• To avoid possible corrosion of the heat exchanger,
do not locate the unit in an area where the outdoor
air (i.e., combustion air for the unit) will be frequently
contaminated by compounds containing chlorine or
fluorine. Common sources of such compounds include swimming pools and chlorine bleaches, paint
stripper, adhesives, paints, varnishes, sealers,
waxes (which are not yet dried) and solvents used
during construction and remodeling. Various commercial and industrial processes may also be
sources of chlorine/fluorine compounds.
• To avoid possible illness or death of the building oc-
cupants, do NOT locate outside air intake device
(economizer, manual outdoor air intake, motorized
outdoor air intake) too close to an exhaust outlet,
gas vent termination, or plumbing vent outlet. For
specific distances required, consult local codes.
• Allow clearances from the enclosure as shown in
Figure 1 for fire protection, proper operation, and
service access. These clearances must be permanently maintained.
• The combustion air inlet and flue outlet hoods on
the front of the unit must never be obstructed. If used,
do not allow the economizer/manual outdoor air
damper/ motorized outdoor air damper to become
blocked by snow or debris. In some climates or locations, it may be necessary to elevate the unit to
avoid these problems.
• When the unit is heating, the temperature of the re-
turn air entering the unit must be between 50° F and
100° F.
Ground Level Installations Only:
• When the unit is installed on the ground adjacent to
the building, a level concrete (or equal) base is recommended. Prepare a base the same physical size
as the unit or slightly larger and 3 inches thick.
• The base should also be located where no run-off
of water from higher ground can collect in the unit.
• The feet on the unit may not be removed.
Rooftop Installations Only:
• To avoid possible property damage or personal injury, the roof must have sufficient structural strength
to carry the weight of the unit(s) and snow or water
loads as required by local codes.
• If horizontal air delivery is used, the unit may be installed directly on wood floors or on Class A, Class
B, or Class C roof covering material, provided that
the feet on the unit are not removed.
• To avoid possible personal injury, a safe, flat surface for service personnel should be provided.
• If vertical air discharge is used and the unit is installed on combustible flooring or class A, B, or C
roofing material, then the Amana roof curb (PRC3A
or PRC5A) listed on the unit nameplate is required.
III. General Information
WARNING
Improper installation, repair, operation or
maintenance of this product may result
in property damage, personal injury, or
death from hazards such as fire, explosions, smoke, soot, condensation, electric shock or carbon monoxide.
This unit is approved only for an outdoor installation. To
assure that your unit operates safely and efficiently, it
must be installed, operated, and maintained in accordance with these installation and operating instructions,
all local building codes and ordinances, or in their absence, with the latest edition of the National Fuel Gas
Code. (ANSI Z223.1).
The heating and cooling capacities of the unit should be
greater than or equal to the design heating and cooling
loads of the area to be conditioned. The loads should
be calculated by an approved method or in accordance
with ASHRAE Guide or Manual J - Load Calculations
published by the Air Conditioning Contractors of America.
Obtain from:
American National Standards Institute
1430 Broadway
New York, NY 10018
7
Figure 1
Required Clearances For All Installations
8
Transportation Damage
All units are securely packed in shipping cartons approved by the International Safe Transit Association. The
carton should be checked upon arrival for external damage. If damage is found, a request for inspection by carrier agent should be made in writing immediately.
The unit should be carefully inspected upon arrival for
damage and bolts or screws which may have loosened
in transit. In the event of damage, the consignee should:
1. Make notation on delivery receipt of any visible damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, carrier should be notified as soon as possible-preferably within 5 days.
4. File the claim with the following supporting documents within the 9-month statute of limitations.
a. Original Bill of Lading, certified copy, or indemnity
bond.
b. Original paid freight bill or indemnity in lieu thereof.
c. Original invoice or certified copy thereof, showing
trade and other discounts or reductions.
d. Copy of the inspection report issued by carrier
representative at the time damage is reported to
the carrier. The carrier is responsible for making
prompt inspection of damage and for a thorough
investigation of each claim. The distributor or
manufacturer will not accept claims from dealers
for transportation damage.
NOTE: When inspecting the unit for transportation damage, remove all packaging materials. Follow local codes
when disposing or recycling the packaging material.
IV. Rigging and Handling
CAUTION
To prevent possible property damage, the
unit should remain in an upright position
during all rigging and moving operations.
To facilitate lifting and moving when a
crane is used, place the unit in an adequate cable slide.
Important: If using bottom discharge with roof curb,
ductwork should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in Amana
Roof Curb Installation Instructions.
Refer to the Amana Roof Curb Installation Instructions
for proper curb installation. Curbing must be installed in
compliance with the National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to
be lower than supply air end.
If using a fork lift, see Figure 2 for location of fork prongs.
Make certain prongs support unit weight.
Locating The Thermostat
The thermostat should be mounted 5 feet above the floor,
on a vibration free inside wall in a room or a hallway that
has good air circulation.
Movement of air should not be obstructed by furniture,
door, draperies, etc. The thermostat should not be
mounted where it will be affected by drafts, hot or cold
water pipes or air ducts in walls, radiant heat from fireplace, lamps, the sun, television, etc. Consult the Instruction Sheet packaged with the thermostat for mounting instructions.
All units have one stage of heating and one stage of
mechanical cooling. Units which will have economizers
may use thermostats with one or two stages of cooling.
Figure 2
Rigging
9
V. Gas Piping
IMPORTANT NOTE: This furnace is factory set to oper-
ate on natural gas at the altitudes shown on the rating
plate. If operation at higher altitudes and/or propane gas
operation is required, obtain and install the proper conversion kit(s) before operating this furnace. Failure to
do so may result in unsatisfactory operation and/or equipment damage. (High altitude kits are for U.S. installations only.)
The rating plate is stamped with the model number, type
of gas and gas input rating. Make sure the furnace is
equipped to operate on the type of gas available.
INL ET GA S PRESSURE
NaturalMin. 5.0" W.C., Max. 10.0" W.C.
PropaneMin. 11.0" W. C. , M ax . 14. 0" W. C.
Inlet Gas Pressure Must Not Exceed the Maximum Value Shown
in Table 3.
Table 3
The minimum supply pressure should not vary from that
shown in the table above because this could prevent
the furnace from having dependable ignition. In addition, gas input to the burners must not exceed the rated
input shown on the rating plate. Overfiring of the furnace could result in premature heat exchanger failure.
High Altitude Derate (US. Installations Only Canadian Installations to 4500 Feet Only)
When this furnace is installed at altitudes above 2000
feet, the furnace input must be derated 4% for each 1000
feet above sea level because the density of the air is
reduced.
In some areas the gas supplier will derate the heating
value of the gas at a rate of 4% for each 1000 feet above
sea level. If this is not done, smaller orifices will be required at altitudes above 3500 feet (non-derated natural gas) or 4500 feet (non-derated propane gas).
A different pressure switch will be required at altitudes
more than 4000 feet above sea level. This is required
regardless of the heat content of the fuel used.
High altitude kits can be purchased depending on the
altitude and usage of propane or natural gas. Refer to
the high altitude instruction manual included with this
furnace to determine which high altitude components to
use.
Adjustment of the manifold pressure to a lower pressure reading than what is specified on the furnace nameplate is not a proper derate procedure. With a lower density of air and a lower manifold pressure at the burner
orifice, the orifice will not aspirate the proper amount of
air into the burner. This can cause incomplete combustion of the gas, flashback, and possible yellow tipping.
Gas Piping
IMPORTANT NOTE: To avoid possible unsatisfactory
operation or equipment damage due to under firing of
equipment, do not undersize the natural gas/propane
piping from the meter/tank to the furnace. When sizing
a trunk line as shown in Table 4, include all appliances
on that line that could be operated simultaneously.
The rating plate is stamped with the model number, type
of gas and gas input rating. Make sure the furnace is
equipped to operate on the type of gas available.
The gas line installation must comply with local codes,
or in the absence of local codes, with the latest edition
of the National Fuel Gas Code (ANSI Z223.1).