Amana PGB58B, PGC(24-60)B User Manual

®
Heating ¡ Air Conditioning
A higher standard of comfort
MODELS
PGC(24-60)B and
PGB58B
Table of Contents
I. Unit Specifications ........................................ 2
II. Safety Information ......................................... 6
III. General Information ...................................... 7
IV. Rigging and Handling ................................... 9
V. Gas Piping .................................................... 10
Vl. Electrical Wiring .......................................... 12
Vll. Circulating Air and Filters .......................... 13
VIII. Flue Vent ....................................................... 16
IX. Condensate Drain ........................................ 16
X. Heating Sequence of Operations............... 18
XI. Cooling Sequence of Operations .............. 18
XIl. Startup and Adjustment .............................. 18
XIII. Maintenance................................................. 24
XIV. Accessories and Functional Parts ............ 26
XV. Typical Cooling Performance Data ............ 27
XVI. Wiring Diagram ............................................ 29
Gas-Electric Package
Unit
Cooling and Heating
Installation Instructions
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to know the product better than the customer. This in­cludes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize your­self with this Instruction Manual. Pay special atten­tion to all safety warnings. Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation.
Affix These Installation Instructions Adjacent To The Appliance.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use.
Safety is a matter of common sense...a matter of think­ing before acting. Most dealers have a list of specific good safety practices...follow them.
The precautions listed in this Installation Manual should not supersede existing practices but should be considered as supplemental information.
May 1998 (2) 11073904
Fayetteville, TN 37334
I. Unit Specifications
MODEL PGC24B0452A PGC24B0702A PGC30B0702A PGC36B0702A PGC36B09 02A Cooling Cap acity Btuh 24,000 24,000 30,000 36,000 36,000 SEER 12.50 12.50 12.30 12.00 12.00 Heating
Input Btuh 45,000 70,000 70,000 70,000 90,000
Output Btuh 35,000 55,000 55,000 55,000 70,000
AFUE 80.9 80.1 80.1 80.1 80.4
Temperature Rise °F 20-50 30-60 30- 60 30-60 40-70
Number of Burn er s 2 3 3 3 4
Compressor
R.L. Amps 12.9 12.9 15 20 20 L.R. Amps 62.5 62.5 76 90.5 90.5
Condenser Coil
Face Area (sq. ft.) 12.3 12.3 12.3 14 14
Rows Deep 1 1/2 1 1/2 2 2 2
Fins/Inch 13 13 13 13 13
Condenser Fan
Diameter (in.) 20 20 20 20 20
CFM 2670 2670 2700 3060 3060
Condenser Fan Motor
Horsepower 1/8 1/8 1/4 1/4 1/4
R.L. Amps 0.8 0.8 1.2 1.5 1.5 L.R. Amps 1.5 1.5 3 3.4 3.4
Blower M o to r
Horsepower 0.5 0.5 0.5 0.5 0. 5
R.L. Amps 4.3 4.3 4.3 4.3 4.3 L.R. Amps Protected by redundant electronic control circuits
Blower Wh eel Dia. x Width (in .) 10x7 10x7 10x7 10x7 10x7
Rated CFM, Cooling 850 850 1100 1300 1300
Max. External 0.8" wc 0.8" wc 0.8" wc 0.8" wc 0.8" wc
Combustion Blower
Diameter x Wi d th (in.) 4 x 1.25 4 x 1.25 4 x 1.25 4 x 1.25 4 x 1.25
No. 11111
Condenser Blower Motor
H.P. 0.03125 0.03125 0.03125 0.031 25 0.03125
F.L. Amps. 0.5 0.5 0.5 0.5 0.5
Press. Switch S ett in g (" W.C.) -0.65 -0.65 -0.65 -0.65 -0.65
Ignition - Lockout Timing (sec.) 4 4 4 4 4
Flame Sense Current (microamps)
Minimum 11111
Maximum 66666
Evaporator Coil
Face Area (Sq. Ft.) 4 4 4 4 4
Rows Deep 22244
Fins/Inch 16 16 16 12 12
External Filter Size (Sq. Ft.) 3.6 3.6 3.6 3.6 3.6
Drain Line Size (in.) 3/4 3/4 3/4 3/4 3/4
Expansion Device (Cooling) Capillary Capillary Capillary Capillary Capillary
Refrigerant Charge Refer to unit nam e p late for correct charg e
Power Supply** 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1
Min. Circuit Ampacity 21.3 21.3 24.3 30.8 30.8
Max. Overcurre n t Device 30 30 35 45 45
Electrical Entrance Size
Power Supply 1 1/4", 1 1/2", 2" 1 1/4", 1 1/2", 2" 1 1/4", 1 1/2", 2" 1 1/4", 1 1/2", 2" 1 1/4", 1 1/2", 2"
Low Voltage 7/8" 7/8" 7/8" 7/8" 7/8"
Approx. Shipping Weight (lb.) 385 39 4 418 437 443
1) United States Installation
2) Specification subject to change without notice. See sales specification sheets for certain BTUH capacities.
3) This PGC series complies with requirements embodied in the American National Standard ANSI-Z21.47 Central Furnaces.
4) Filters are not supplied with units, but filters must be installed in the unit filter rack or in the return air system. ** While the above data is presented as a guide, it is important to electrically connect the unit and properly size overcurrent protection and wires in accordance with the National Electrical Code and all existing local codes. Operating tolerance: Minus 5% on 208 VAC, Plus 10% on 208 VAC and 230 VAC, Minus 10% on 230 VAC
Table 1A
Gas Pack Specifications
2
MODEL PGC42B0902A PGC42B1152A PGC48B0902A PGC48B1152A PGC60B0902A PGC60B1352A Cooling Capacity Btuh 42,000 42,000 48,000 48,000 60,000 60,000 SEE R 12.20 12.20 12.00 12.00 12.00 12.00 Heating
Compressor
Condenser Coil
Condenser Fan
Condenser Fan Motor
Blow er Mot or
Blower Wheel Dia. x W idth (in.) 10x10 10x10 10x10 10x10 11x8 11x8
Combustion Blower
Condenser Blower Motor
P ress. S wi t ch Setting (" W.C.) -0.65 -0 .65 -0.65 -0.65 -0 .65 -0.65
Ignition - Lockout Timing (sec.) 4 4 4 4 4 4
Flame Sense Current ( microamps)
Evaporator Coil
Electrical Entrance Size
Approx. Shipping Weight (lbs) 521 527 526 526 531 531
Input B tuh 90, 000 115,000 90,000 115,000 90,000 135,000
Output Btuh 72,000 89,000 72,000 89,000 72,000 108,000
AFUE 81.4 79.9 81.4 79.9 81.4 80.5
Temperature Rise °F 25-55 40-70 25-55 40-70 25-55 40-70
Number of Bu rners 4 5 4 5 5 6
R.L. Amps 22 22 21.8 21.8 28.8 28.8 L.R. Amps 107 107 105 105 169 169
Face Area (sq. ft.) 17.2 17.2 17.2 17.2 17.2 17.2
Rows Deep 222222
Fins/Inch 13 13 17 17 17 17
Diameter (in.) 242424242424
CFM 3500 3500 3700 3700 4700 4700
Horsepower 1/4 1/4 1/2 1/2 1/3 1/3
R .L. Amps 1.5 1.5 1.5 1.5 2.5 2.5 L.R. Amps 3.4 3.4 3.6 3.6 6.4 6.4
Horsepower 3/4 3/4 3/4 3/4 1 1
R.L. Amps 555577 L.R. Amps
Rated CFM, Cooling 1450 1450 1700 1700 1750 1750
Max. External 0.8" wc 0.8" wc 0.8" wc 0.8" wc 0.8" wc 0.8" wc
Diameter x Width (in.) 4 x 1.25 4 x 1.25 4 x 1.25 4 x 1.25 4 x 1.25 4 x 1.25
No. 111111
H.P . 0.03125 0.03125 0.03125 0.03125 0.03125 0.03125
F.L. Amps. 0.5 0.5 0.5 0.5 0.5 0.5
Minimum 111111
Maximum 666666
Face Area (Sq. Ft.) 5.7 5.7 5.7 5.7 5.7 5.7
Rows Deep 223333
Fins/Inch 15 15 15 15 15 15
External F ilter Size (Sq. Ft.) 5.3 5.3 5.3 5.3 5.3 5.3
Drain Line Size (in.) 3/4 3/ 4 3/4 3/4 3/4 3/4
Expansion Device (Cooling) Capillary Capillary TEV TEV TEV TEV
Refrigerant Charge Refer to unit name plate for correct charge
Power Supply** 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1
Min. Circuit Ampacity 34 34 39.5 39.5 49.7 49.7
Max. Overcurrent Device 50 50 50 50 70 70
Power Supply 1 1/4", 1 1/2", 2" 1 1/4", 1 1/2", 2" 1 1/4", 1 1/2", 2" 1 1/4", 1 1/2", 2" 1 1/4", 1 1/2", 2" 1 1/4", 1 1/2", 2"
Low Voltage 7/8" 7/8" 7/8" 7/8" 7/8" 7/8"
Protected by redundant electronic control circuts
1) United States Installation
2) Specification subject to change without notice. See sales specification sheets for certain BTUH capacities.
3) This PGC series complies with requirements embodied in the American National Standard ANSI-Z21.47 Central Furnaces.
4) Filters are not supplied with units, but filters must be installed in the unit filter rack or in the return air system. ** While the above data is presented as a guide, it is important to electrically connect the unit and properly size overcurrent protection and wires in accordance with the National Electrical Code and all existing local codes. Operating tolerance: Minus 5% on 208 VAC, Plus 10% on 208 VAC and 230 VAC, Minus 10% on 230 VAC
Table 1B
Gas Pack Specifications
3
MODEL PGB58B0902A PGB58B1152A PGB58B1352A Cooling Capacity Btuh 59,500 59,500 59,500 SEER 11.10 11.10 11.10 Heating
Input Btuh 90,000 115,000 135,000
Output Btuh 72,000 92,000 108,000
AFUE 81.4 79.9 80.5
Temperature Rise °F 25-55 25-55 25-55
Number of Burners 4 4 4
Compressor
R.L. Amps 28.8 28.8 28.8 L.R. Amps 169 169 169
Condenser Coil
Face Area (sq. ft.) 17.2 17.2 17.2
Rows Deep 2 2 2
Fins/Inch 17 17 17
Condenser Fan
Diameter (in.) 24 24 24
CFM 4700 4700 4700
Condenser Fan Motor
Horsepower 1/3 1/3 1/3
R.L. Amps 2.5 2.5 2.5 L.R. Amps 6.4 6.4 6.4
Blower Motor
Horsepower 3/4 3/4 3/4
R.L. Amps 5.6 5.6 5.6 L.R. Amps 12.9 12.9 12.9
Blower Wheel Dia. x Width (in.) 11X8 11X8 11X8
Rated CFM, Cooling 1750 1750 1750
Max. External 0.5" wc 0.5" wc 0.5" wc
Combustion Blower
Diameter x Width (in.) 4 x 1.25 4 x 1.25 4 x 1.25
No. 111
Condenser Blower Motor
H.P. 1/32 1/32 1/32
F.L. Amps. 0.5 0.5 0.5
Press. Switch Setting (" W.C.) -0.65 -0.6 5 -0.65
Ignition - Lockout Timing (sec.) 4 4 4
Flame Sense Current (microamps)
Minimum 111
Maximum 666
Evaporator Coil
Face Area (Sq. Ft.) 5.7 5.7 5.7
Rows Deep 4 4 4
Fins/Inch 15 15 15
External Filter Size (Sq. Ft.)
Drain Line Size (in.) 3/4 3/4 3/4
Expansion D evice (Cooling) TEV TEV TEV
Refrigerant Charge Refer to unit name plate for correct charge
Power Supply** 208/230-60-1 208/230-60-1 208/230-60-1
Min. Circuit Ampacity 33.75 33.75 33.75
Max. Overcurrent Device 50 50 50
Electrical Entrance Size
Power Supply 1 1/4", 1 1/2", 2" 1 1/4", 1 1/2", 2" 1 1/4", 1 1/2", 2"
Low Voltage 7 /8" 7/8" 7/8"
Approx. Shippi ng Weight (lbs) 531 531 531
Table 1C
Gas Pack Specifications
4
Nominal
Model
PGC24B0452A 24000 850 45000 930 570 35 A A PGC24B0702A 24000 850 70000 1140 570 45 A B PGC30B0702A 30000 1100 70000 1140 570 45 B B PGC36BO702A 36000 1300 70000 1140 570 45 C B PGC36B0902A 36000 1300 90000 1350 570 55 C C PGC42B0902A 42000 1450 90000 1650 815 40 A A PGC42B1152A 42000 1450 115000 1530 815 55 A B PGC48B0902A 48000 1700 90000 1650 815 40 B A PGC48B1152A 48000 1700 115000 1530 815 55 B B PGC60B0902A 60000 1750 90000 1650 815 40 A A PGC60B1352A 60000 1750 135000 1900 815 55 A B
1. Installation is to be adjusted to obtain temperature rise within the range specified on the rating plate.
2. The temperature rise is for units installed at 0-2000 feet. At higher altitudes, a properly derated unit will have approximately the same temperature rise and CFM.
3. The chart is applicable for both vertical and horizontal airflow.
4. All speed tap settings are factory selected according to unit size.
5. Data shown without filters. Consult filter manufacturer for pressure drop to be added.
6. Motor is constant CFM for external static pressures 0.1" to 0.8" W.C.
7. Maximum External Pressure Limits
PGC 24-42 0.8" W.C. PGC46 & 60 1.0 W.C.
Cooling Nominal
Capacity
(MBh)
Cooling
CFM
(Y+G) (W1) (G) Cool Heat
Nominal
Heating Nominal Nominal Temp. Speed
Capacity
(Input)
Heating
CFM
Fan Only Rise (°F) Taps
Table 2A
PGC Temperature Rise Table
Model Speed CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
Motor 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Hi 2160 31 2120 31 2080 32 2030 33 1990 34 1945 34 1900 35 1835 36
PGB58B0902C Med 1750 38 1750 39 1700 39 1680 40 1680 40 1615 41 1575 42 1490 45
Lo 1490 45 1480 45 1470 45 1450 46 1440 46 1415 47 1360 49 1280 52 Hi 2160 --- 2120 --- 2080 41 2030 42 1990 43 1945 44 1900 45 1835 46
PGB58B1152C Med 1750 49 1750 49 1700 50 1680 51 1650 52 1615 53 1575 54 1470 57
Lo 1490 57 1480 58 1470 58 1460 58 1440 59 1415 60 1360 63 1280 67 Hi 2160 46 2120 47 2080 48 2030 49 1990 50 1945 51 1900 53 1835 54
PGB58B1352C Med 1750 57 1750 58 1700 59 1680 60 1650 61 1615 62 1575 63 1490 67
Lo 1490 67 1480 68 1470 68 1460 68 1440 69 1415 --- 1360 --- 1280 ---
NOTE:
1. All airflow is dry coil.
2. Installation is to be adjusted to obtain temperatures rise within the range specified on the rating plate.
3. The above chart is for information only. For satisfactory operation, external static pressure should not exceed value shown on the rating plate. The shaded area ( ) indicates in excess of maximum external static pressure allowable when heating.
4. This chart is for units installed at 0-2000 feet. At higher altitudes, a properly derated unit will have approximately the same temperature rise at a particular CFM, while ESP at that CFM will be lower.
5. Cooling operation may require a different fan speed than heating operation. For details, see Wiring Diagrams.
6. Above chart is applicable for both vertical and horizontal airflow.
External Static Pressure, Inches Water Column
Table 2B
PGB CFM& Temperature Rise vs. External Static Pressure Table
5
II. Safety Information
WARNING
Important To The Installer
Before installing this unit please read this manual to fa­miliarize yourself with the specific items which must be adhered to such as maximum external static pressure to unit, air temperature rise, minimum or maximum CFM and motor speed connections. Affix these Installation Instructions adjacent to the appliance.
To The Owner
It is important that you complete the owner registration card and mail it today. This will assist Amana in contact­ing you if any service or warranty information should change in the future. When completing the registration card, be sure to include the Model, Manufacturing and Serial Numbers, plus the installation date.
Your warranty certificate is also supplied with the unit. Read the warranty carefully and note what is covered. Keep the warranty certificate in a safe place so you can find it if necessary.
If additional operating Instructions are required, call the dealer where the purchase was made. Keep this litera­ture in a safe place for future reference.
Do not store gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
If you smell gas:
Extinguish any open flame.
Do not try to light appliance.
Do not touch any electrical switch: do not use any
phone in building.
Immediately call gas supplier from a neighbor’s
phone. Follow gas supplier’s instructions.
If gas supplier cannot be reached, call fire depart-
ment.
WARNING
Improper installation, adjustment, alter­ations, service or maintenance can cause property damage, personal injury, or death. Follow all procedures in this manual. For assistance or additional in­formation, contact a qualified installer, service agency, or gas supplier.
WARNING
Should overheating occur or the gas sup­ply fail to shut off, turn off the manual gas control valve to the furnace before shutting off the electrical supply.
CAUTION
On PGC48 - 60 and PGB58 Only: To avoid damage to the compressor, engage the electrical disconnect switch to the com­pressor unit four hours prior to operat­ing air conditioner after the electrical dis­connect is off for a prolonged period of time (during vacation, etc.). This time lapse allows the compressor crankcase to attain a proper operating temperature.
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, per­sonal injury, or death.
WARNING
This product contains or produces a chemical(s) which may cause death or serious illness and which are known by the State of California to cause cancer, birth defects or other reproductive harm.
CAUTION
This unit should not be used as a “con­struction heater” during the finishing phases of construction on a new struc­ture. This type of use may result in pre­mature failure of the unit due to extremely low return air temperatures and exposure to very dirty atmospheres.
6
Locating The Unit
WARNING
To avoid possible equipment damage, fire, personal injury, or death, the follow­ing points must be observed when install­ing the unit.
All Installations:
For proper flame pattern within the heat exchanger
and proper condensate drainage, the unit must be mounted level.
The unit should be as centralized as is practical with
respect to the air distribution system. This unit is for outdoor installation ONLY!
The flue outlet hood must be at least 12 inches from
any opening through which flue gases could enter a building, and at least three feet above any forced air inlet located within ten feet. The economizer/manual outdoor air intake/motorized outdoor air intake and combustion air inlet mounted on the unit are not af­fected by this restriction.
To avoid possible corrosion of the heat exchanger,
do not locate the unit in an area where the outdoor air (i.e., combustion air for the unit) will be frequently contaminated by compounds containing chlorine or fluorine. Common sources of such compounds in­clude swimming pools and chlorine bleaches, paint stripper, adhesives, paints, varnishes, sealers, waxes (which are not yet dried) and solvents used during construction and remodeling. Various com­mercial and industrial processes may also be sources of chlorine/fluorine compounds.
To avoid possible illness or death of the building oc-
cupants, do NOT locate outside air intake device (economizer, manual outdoor air intake, motorized outdoor air intake) too close to an exhaust outlet, gas vent termination, or plumbing vent outlet. For specific distances required, consult local codes.
Allow clearances from the enclosure as shown in
Figure 1 for fire protection, proper operation, and service access. These clearances must be perma­nently maintained.
The combustion air inlet and flue outlet hoods on
the front of the unit must never be obstructed. If used, do not allow the economizer/manual outdoor air damper/ motorized outdoor air damper to become blocked by snow or debris. In some climates or lo­cations, it may be necessary to elevate the unit to avoid these problems.
When the unit is heating, the temperature of the re-
turn air entering the unit must be between 50° F and 100° F.
Ground Level Installations Only:
When the unit is installed on the ground adjacent to
the building, a level concrete (or equal) base is rec­ommended. Prepare a base the same physical size as the unit or slightly larger and 3 inches thick.
The base should also be located where no run-off
of water from higher ground can collect in the unit.
The feet on the unit may not be removed.
Rooftop Installations Only:
• To avoid possible property damage or personal in­jury, the roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes.
• If horizontal air delivery is used, the unit may be in­stalled directly on wood floors or on Class A, Class B, or Class C roof covering material, provided that the feet on the unit are not removed.
• To avoid possible personal injury, a safe, flat sur­face for service personnel should be provided.
• If vertical air discharge is used and the unit is in­stalled on combustible flooring or class A, B, or C roofing material, then the Amana roof curb (PRC3A or PRC5A) listed on the unit nameplate is required.
III. General Information
WARNING
Improper installation, repair, operation or maintenance of this product may result in property damage, personal injury, or death from hazards such as fire, explo­sions, smoke, soot, condensation, elec­tric shock or carbon monoxide.
This unit is approved only for an outdoor installation. To assure that your unit operates safely and efficiently, it must be installed, operated, and maintained in accor­dance with these installation and operating instructions, all local building codes and ordinances, or in their ab­sence, with the latest edition of the National Fuel Gas Code. (ANSI Z223.1).
The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be calculated by an approved method or in accordance with ASHRAE Guide or Manual J - Load Calculations published by the Air Conditioning Contractors of America.
Obtain from:
American National Standards Institute 1430 Broadway New York, NY 10018
7
Figure 1
Required Clearances For All Installations
8
Transportation Damage
All units are securely packed in shipping cartons ap­proved by the International Safe Transit Association. The carton should be checked upon arrival for external dam­age. If damage is found, a request for inspection by car­rier agent should be made in writing immediately.
The unit should be carefully inspected upon arrival for damage and bolts or screws which may have loosened in transit. In the event of damage, the consignee should:
1. Make notation on delivery receipt of any visible dam­age to shipment or container.
2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, carrier should be no­tified as soon as possible-preferably within 5 days.
4. File the claim with the following supporting docu­ments within the 9-month statute of limitations.
a. Original Bill of Lading, certified copy, or indemnity
bond. b. Original paid freight bill or indemnity in lieu thereof. c. Original invoice or certified copy thereof, showing
trade and other discounts or reductions. d. Copy of the inspection report issued by carrier
representative at the time damage is reported to
the carrier. The carrier is responsible for making
prompt inspection of damage and for a thorough
investigation of each claim. The distributor or
manufacturer will not accept claims from dealers
for transportation damage.
NOTE: When inspecting the unit for transportation dam­age, remove all packaging materials. Follow local codes when disposing or recycling the packaging material.
IV. Rigging and Handling
CAUTION
To prevent possible property damage, the unit should remain in an upright position during all rigging and moving operations. To facilitate lifting and moving when a crane is used, place the unit in an ad­equate cable slide.
Important: If using bottom discharge with roof curb,
ductwork should be attached to the curb prior to install­ing the unit. Ductwork dimensions are shown in Amana Roof Curb Installation Instructions.
Refer to the Amana Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors As­sociation Manual.
Lower unit carefully onto roof mounting curb. While rig­ging unit, center of gravity will cause condenser end to be lower than supply air end.
If using a fork lift, see Figure 2 for location of fork prongs. Make certain prongs support unit weight.
Locating The Thermostat
The thermostat should be mounted 5 feet above the floor, on a vibration free inside wall in a room or a hallway that has good air circulation.
Movement of air should not be obstructed by furniture, door, draperies, etc. The thermostat should not be mounted where it will be affected by drafts, hot or cold water pipes or air ducts in walls, radiant heat from fire­place, lamps, the sun, television, etc. Consult the In­struction Sheet packaged with the thermostat for mount­ing instructions.
All units have one stage of heating and one stage of mechanical cooling. Units which will have economizers may use thermostats with one or two stages of cooling.
Figure 2 Rigging
9
V. Gas Piping
IMPORTANT NOTE: This furnace is factory set to oper-
ate on natural gas at the altitudes shown on the rating plate. If operation at higher altitudes and/or propane gas operation is required, obtain and install the proper con­version kit(s) before operating this furnace. Failure to do so may result in unsatisfactory operation and/or equip­ment damage. (High altitude kits are for U.S. installa­tions only.)
The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the furnace is equipped to operate on the type of gas available.
INL ET GA S PRESSURE
Natural Min. 5.0" W.C., Max. 10.0" W.C.
Propane Min. 11.0" W. C. , M ax . 14. 0" W. C.
Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in Table 3.
Table 3
The minimum supply pressure should not vary from that shown in the table above because this could prevent the furnace from having dependable ignition. In addi­tion, gas input to the burners must not exceed the rated input shown on the rating plate. Overfiring of the fur­nace could result in premature heat exchanger failure.
High Altitude Derate (US. Installations Only ­Canadian Installations to 4500 Feet Only)
When this furnace is installed at altitudes above 2000 feet, the furnace input must be derated 4% for each 1000 feet above sea level because the density of the air is reduced.
In some areas the gas supplier will derate the heating value of the gas at a rate of 4% for each 1000 feet above sea level. If this is not done, smaller orifices will be re­quired at altitudes above 3500 feet (non-derated natu­ral gas) or 4500 feet (non-derated propane gas).
A different pressure switch will be required at altitudes more than 4000 feet above sea level. This is required regardless of the heat content of the fuel used.
High altitude kits can be purchased depending on the altitude and usage of propane or natural gas. Refer to the high altitude instruction manual included with this furnace to determine which high altitude components to use.
Adjustment of the manifold pressure to a lower pres­sure reading than what is specified on the furnace name­plate is not a proper derate procedure. With a lower den­sity of air and a lower manifold pressure at the burner orifice, the orifice will not aspirate the proper amount of air into the burner. This can cause incomplete combus­tion of the gas, flashback, and possible yellow tipping.
Gas Piping
IMPORTANT NOTE: To avoid possible unsatisfactory
operation or equipment damage due to under firing of equipment, do not undersize the natural gas/propane piping from the meter/tank to the furnace. When sizing a trunk line as shown in Table 4, include all appliances on that line that could be operated simultaneously.
The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the furnace is equipped to operate on the type of gas available.
The gas line installation must comply with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code (ANSI Z223.1).
Connecting The Gas Piping - Natural Gas
Natural Gas Capacity of Pipe
in Cubic Feet of Gas Per Hour (CFH)
Length of
Pipe in Feet 1/2 3/4 1 1 1/4 1 1/2
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
Press u re = .5 0 PSIG or l e ss and Pres sure Drop of 0.3" W .C. (Bas e d
Btuh Furnace Input
CFH=
Calorific Value of Gas
Nominal Black Pipe Si ze (inches)
on 0. 60 Spec ific G ravity Ga s)
Table 4
Refer to Figure 3 for the general layout at the furnace. The following rules apply:
1. Use black iron or steel pipe and fittings for the build­ing piping.
2. Use pipe joint compound on male threads only. Pipe joint compound must be resistant to the action of the fuel used.
3. Use ground joint unions.
4. Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a mini­mum of three inches long.
5. Use two pipe wrenches when making connection to the gas valve to keep it from turning.
6. Install a manual shut-off valve in a convenient loca­tion (within six feet of unit) between the meter and the unit.
7. Tighten all joints securely.
10
Figure 3
Proper Piping Practice
WARNING
To avoid personal injury or property dam­age, be sure there is no open flame in the vicinity during air bleeding procedure.
There will be air in the gas supply line after testing for leaks on a new installation. Therefore, the air must be bled from the line by cracking open the ground joint union until pure gas is expelled. Tighten union and wait for five minutes until all gas has been dissipated in the air. Be certain there is no open flame in the vicinity during air bleeding procedure. The unit is placed in operation by closing the main electrical disconnect switch for the furnace.
Tanks And Piping for Propane Gas Units
Checking The Gas Piping
CAUTION
To avoid the possibility of personal in­jury, property damage or fire, the follow­ing instructions must be performed re­garding gas connections and pressure testing:
• This unit and its gas connections must be leak tested before placing in opera­tion. Because of the danger of explosion or fire, never use a match or open flame to test for leaks. Never exceed speci­fied pressures for testing. Higher pres­sure may damage gas valve and cause overfiring which may result in heat fail­ure.
• This unit and shut-off valve must be dis­connected from the gas supply during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.48 kPa).
• This unit must be isolated from the gas supply system by closing the manual shut-off valve during any pressure test­ing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.48 kPa).
WARNING
Personal Injury Hazard Failure to detect a propane gas leak could
result in an explosion or fire which could cause death, serious personal injury, or property damage.
Iron oxide (rust) can reduce the level of odorant in propane gas. A gas detecting device is the only reliable method to de­tect a propane gas leak. Contact the lo­cal propane supplier about installing a warning device to sound an alert if a gas leak should develop.
All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters (See NBFU Manual 58).
For satisfactory operation, propane gas pressure must be 10 inch W.C. at the furnace manifold with all gas ap­pliances in operation. Maintaining proper gas pressure depends on three main factors:
1. Vaporization rate, which depends on (a) tempera­ture of the liquid, and (b) wetted surface area of the container or containers.
2. Proper pressure regulation. (Two-stage regulation is recommended from the standpoint of both cost and efficiency.)
3. Pressure drop in lines between regulators, and be­tween second stage regulator and the appliance. Pipe size required will depend on length of pipe run and total load of all appliances.
Complete information regarding tank sizing for vapor­ization, recommended regulator settings and pipe siz­ing is available from most regulator manufacturers and propane gas suppliers.
11
Special pipe dope must be used when assembling pip­ing for this gas as it will quickly dissolve white lead or most standard commercial compounds. Shellac base compounds resistant to the actions of liquefied petro­leum gases such as Gasolac, Static, Clyde or John Crane are satisfactory.
Please refer to Figure 4 for typical propane gas instal­lations.
Figure 4
Typical Propane Gas Piping
WARNING
Failure to follow the instructions on Page 6 of this manual when the presence of gas is suspected could result in death or serious personal injury. An undetected gas leak would create a danger of explo­sion or fire.
If the propane gas furnace is installed in an excavated area or a confined space, it is strongly recommended contacting a propane gas supplier about installing a warning device to warn of a gas leak.
Propane gas is heavier than air and any leaking gas can settle in low areas or confined areas.
Propane gas odorant may fade, making the gas undetectable except with a warning device.
Vl. Electrical Wiring
WARNING
To avoid personal injury or death due to electrical shock, disconnect the electri­cal power before electrically connecting the unit.
The units are designed for operation on 60 hertz current and at voltages as shown on the rating plate. All internal wiring in the unit is complete. It is necessary to bring in the power supply to the contactor as shown on the unit wiring diagram which is supplied with each unit. The 24V wiring must be connected between the unit control panel and the room thermostat. Refer to Figure 5 for location of low voltage terminal board and Figure 6 for proper thermostat wiring.
Table 5
Propane Pipe Sizing
Low Voltage Board
Figure 5
Low Voltage Control Box
12
Please refer to the unit wiring diagram for electrical con­nections. When installed, the unit must be electrically grounded in accordance with local codes or in the ab­sence of local codes with the latest edition of National Electrical Code, ANSI/NFPA No. 70.
WARNING
To avoid death or personal injury due to electrical shock, wiring to the unit must be properly grounded.
CAUTION
To avoid personal injury or property dam­age due to fire, use only copper conduc­tors.
The best protection for the wiring is the smallest fuse or breaker which will hold the equipment on the line during normal operation without nuisance trips. Such a device will provide maximum circuit protection. DO NOT EX­CEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.
Be sure line voltage connections are made through weatherproof fittings. All exterior power supply and ground wiring must be in approved weatherproof con­duit. Low voltage wiring from the unit control panel to the thermostat requires coded cable. For ground level and rooftop wiring refer to Figure 8.
CAUTION
To prevent improper and dangerous op­eration due to wiring errors, label all wires prior to disconnection when servicing controls. Verify proper operation after servicing.
Vll. Circulating Air and Filters
Airflow Conversion
Units can easily be converted from horizontal to vertical airflow delivery.
Units will ship from the factory ready for horizontal air­flow. If conversion to vertical airflow is necessary, pro­ceed as follows:
IMPORTANT: Be sure to save the flue hood assembly (cardboard box) which is shipped in the return air com­partment of the unit.
Remove panels from the bottom of the unit, saving
the mounting screws.
Remove insulation from outside of supply duct cover.
No insulation should face outside.
Relocate the panels on to the side of the unit, se-
curing with the screws removed earlier.
The unit will deliver the same amount of air whether
the airflow is vertical or horizontal. For details, see the fan tables on Pages 2 - 5.
Unit Voltage
The unit transformer is factory connected for 230V op­eration. If the unit is to operate on 208V, reconnect the transformer primary lead and induced draft blower mo­tor leads as shown on the unit wiring diagram.
Heat Anticipator Setting
The heat anticipator in the room thermostat must be correctly adjusted to obtain the proper number of heat­ing cycles per hour and to prevent the room tempera­ture from overshooting the room thermostat setting. Heat anticipator must be set at 0.8 amps.
Figure 6
Typical Thermostat and Unit 24 V Wiring
Hookup
Figure 7
Airflow Conversion
Ductwork
CAUTION
To avoid possible fire, the cardboard shipping support (located behind the supply panel) must be removed before operation.
IMPORTANT: Be sure to save the flue hood assembly which is shipped in a cardboard box in the return air compartment of the unit.
13
Typical Wiring
(Ground Level)
Disconnect Switch
High Voltage Source
High Voltage Entrance
Low Voltage Entrance
Rooftop
Curb
Junction
Box
Low Voltage
Entrance
Typical Wiring
(Rooftop)
Disconnect Switch
High Voltage Source High Voltage
Entrance
Figure 8
Typical Electrical Wiring
14
Duct systems and register sizes must be properly de­signed for the C.F.M. and external static pressure rating of the unit. Ductwork should be designed in accordance with the recommended methods of Air Conditioning Con­tractors of America Manual D (Residential) or Manual Q (Commercial). All ductwork exposed to the outdoors must include a weatherproof barrier and adequate insulation.
A duct system should be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems, pamphlets No. 90A and 90B.
The warm air supply duct from the unit through a wall fabricated of combustible material may be installed with­out clearance. However, minimum clearances for the unit must be observed as shown in Section III.
It is recommended that the outlet duct be provided with an access panel. This access should be large enough to inspect the air chamber downstream from the heat exchanger for any smoke or combustion gas leaks. A cover should be tightly attached to prevent air leaks.
For horizontal airflow, duct flange dimensions on the unit are shown in Section III.
For vertical airflow, the ductwork should be attached to the roof curb prior to installing the unit. Ductwork dimen­sions are shown in the Amana PRC roof curb installa­tion manual.
If desired, supply and return duct connections to the unit may be made with flexible connections to reduce pos­sible noise transmission.
Filters
Important: If you will be using the Over/Under Transition Kit, (PDTROU3A or PDTROU5A) you cannot use the unit filter rack.
If you are using the Over/Under transition kit or are sim­ply choosing not to use this filter rack, the filter(s) may be located in the return air duct(s) or return air filter grille(s). Filters installed external to the unit should be sized in accordance with their manufacturer recommen­dations. If you choose to use a throwaway filter it should be sized for a maximum face velocity of 300 feet per minute.
Important: The PGC 42 and 48 package units contain an evaporator drip pan installed on the return air side of the indoor coil.
If an economizer is to be installed on these units, the drip pan must be removed. The pan can be removed by cutting it away. It will not be needed when an econo­mizer is installed.
If filters are to be installed on these units, they must be from filter kit PFK5B1 or PFK5B6. The filters in these kits are sized to fit with the drip pan in place.
Filter Installation
Important: When installing a filter, always make certain
the air flow arrows on the filter point toward the indoor blower.
To install a filter in the filter rack, proceed as follows:
1. Disconnect power to the unit.
2. Locate the filter access door above the return air opening. See Figure 9.
Filter Access Door
WARNING
Never operate furnace without a filter in­stalled as dust and lint will build up on internal parts resulting in loss of effi­ciency, equipment damage, and possible fire.
A return air filter is not supplied with this unit; however, there must be a means of filtering all of the return air. For your convenience, this unit contains a factory in­stalled filter rack. If you choose to install the return air filter in the unit filter rack, use the appropriate Amana filter kit or a permanent filter that is properly sized as follows:
Model Amana Kit #
PGC24, 30, or 36
PGC42, 48, 60
or PGB58
The Amana filter kit includes a permanent filter, door label, and installation instructions. PFK3A1 and PFK5B1 contain filter, label, and instructions for one unit. PFK3A6 and PFK5B6 contain filters, labels, and instructions for six units.
PFK3A1 or
PFK3A6
PFK5B1 or
PFK5B6
Required Perm anent
Filter Size
26" x 20" x 1"
32-5/8" x 22-3/8" x 1"
Figure 9
Filter Access Door
3. Remove the four 5/16" sheet metal screws and set the filter access door aside.
4. Insert the filter into the filter rack channels and lower into place. Make sure the filter slides completely to the bottom so no part of the filter remains outside the back panel.
5. Return the filter access door to its original position and secure it with the four sheet metal screws.
6. a. If you are using an Amana filter kit, affix the FIL­TER ACCESS label to the filter access door.
b. If you are NOT using an Amana filter kit, clearly mark the filter access door “FILTER ACCESS”.
7. Reconnect the power.
NOTE: A clean permanent filter installed as described above will have a negligible effect on air flow.
15
VIII. Flue Vent
Flue Hood And Air Inlet Hood Installation
The flue hood and air inlet hood are packaged in a box which is located inside the return air compartment. They must be installed prior to operation of the unit. See Fig­ure 10.
To install the flue hood cover:
1. Remove the flue hood from inside the box.
2. Slide the upper lip of the hood cover under the top edge of the unit.
3. Attach the flue hood with two sheet metal screws.
To install the air inlet hood:
1. Remove hood from inside box.
2. Attach hood by using three sheet metal screws.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as the range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust the thermostat so appliance will operate continuously.
5. Test for spillage at the draft hood relief opening af­ter five minutes of main burner operation. Use the flame of a match or candle.
6. After it has been determined that each appliance remaining connected to the common venting sys­tem properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace damp­ers, and any other gas-burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the common venting system must be corrected in accordance with the latest edition of the National Fuel Gas Code, (ANSI Z223.1).
If resizing any portion of the common venting system, use the appropriate table in Appendix G, in the latest edition of the National Fuel Gas Code, (ANSI Z223.1).
Figure 10
Air Inlet Hood and Flue Hood
Replacing a Indoor Furnace
WARNING
To prevent property damage, personal injury or death, do not vent this unit with any other appliance.
When an existing indoor furnace is removed from a venting system servicing other appliances, the venting system may be too large to properly vent the remaining attached appliances (water heater, etc.).
The following steps must be followed with each appli­ance remaining connected to the common venting sys­tem placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no block­age or restriction, leakage, corrosion and other de­ficiencies which could cause an unsafe condition.
IX. Condensate Drain
Condensate Drain Connection
The evaporator condensate drain connection is 3/4" FPT. Clean out the inside of the drain connection to assure good condensate water runoff before connecting drain line. The drain line should have a trap on it to prevent debris, insects and dirt from being drawn into the return air system. Refer to Figure 11 for location. A 1" mini­mum head is recommended to allow draining against the negative pressure inside the unit.
1" Minimum
Pitch Toward Drain
Trap
The Drain Connection Must Be The Same Size as On Unit or Larger
Figure 11
Typical Condensate Drain
NOTE: To avoid double trapping and an overflowing
drain pan, soft plastic drain lines are not recommended.
Condensate Drain Connection
16
Air Circulation Blower
ON
OFF
Gas Valve
Ignitor
Pressure Switch (N.O. Contacts)
Combustion Blower
Thermostat
Timing Chart for Normal Robertshaw Operation (PGB & PGC)
OPEN
CLOSED
ON
OFF
CLOSED
OPEN
ON
OFF
ON
OFF
Se conds 0 34 38 110 0 90
Ignitor OFF
Thermostat ON
Air Blower ON
Gas Valve Opens
Purge Ends.
Thermostat OFF
Combustion Product
Figure 12
Air Blower OFF
Combustion
Blower OF F
Indoor F an
Outdoor Fan and Compressor
Thermostat
On Off
On Off
On Off
Seconds 0 15 0 45 (approx.) (approx.)
Figure 13A
PGB Timing Chart for Normal Cooling Operation
Indoor Fan
Outdoor Fan and Compressor
Thermostat
On Off
On Off
On Off
Seconds 0 30 0 30 (approx.) (approx.)
Figure 13B
PGC Timing Chart for Normal Cooling Operation
17
X. Heating Sequence of Operations PGB & PGC)
Normal Sequence of Operation - Heating
See Figure 12
1. Thermostat calls for heat. The combustion blower is immediately energized.
2. The pressure switch contacts transfer.
3. The ignitor is energized and allowed to preheat for 38 seconds.
4. The gas valve is energized delivering gas to the burners and starting combustion.
5. The control checks the signal from the flame sen­sor. Gas flow will continue only if a proper signal is present within seven seconds after the gas valve opens. As soon as flame is proven, the ignitor is de­energized.
6. The unit will continue to fire while the helical fan control heats up. The fan control will start the main circulating air blower approximately 75 seconds af­ter the gas valve opens (this time may vary depend­ing on the control setting).
7. The furnace will deliver heat to the conditioned space until the thermostat is satisfied.
8. The gas valve and combustion blower will be de­energized when the thermostat opens.
9. There is a 90 second delay (approximate) before the main air blower stops. This allows any additional heat in the heat exchanger to be transferred to the conditioned space.
PGC Normal Sequence of Operations - Cooling
See Figure 13B
1. Thermostat calls for cooling. The compressor, in­door fan, and outdoor fan are energized.
2. Approximately 30 seconds later, the indoor fan ramps up to full speed.
3. The unit will deliver cooling to the conditioned space until the thermostat is satisfied.
4. The compressor and outdoor fan will be de-ener­gized when the thermostat opens. It is normal for the scroll compressor to produce a short burping sound at this time as its internal pressures are equal­ized. (The PGC48 has a piston compressor. All other PGC and PGB have scroll compressors.)
5. Refrigerant will continue to flow through the capil­lary tube (sizes 24 to 42) until the high and low side pressures are approximately equal. For the PGC48, 60 and PGB58 refrigerant will continue to flow through the thermal expansion valve until the high and low side pressures are approximately 50 PSI apart.
6. The indoor fan continues to run for approximately 30 seconds after the thermostat is satisfied. This allows additional cooling from the indoor coil to be transferred to the conditioned space. Then, the in­door fan ramps down in 30 seconds to the OFF con­dition.
XIl. Startup and Adjustment
Heating Startup
XI. Cooling Sequence of Operations
PGB Normal Sequence of Operations - Cooling
See Figure 13A
1. Thermostat calls for cooling. The compressor and outdoor fan are energized.
2. Approximately 15 seconds later, the fan time delay relay closes. The indoor fan now begins operation.
3. The unit will deliver cooling to the conditioned space until the thermostat is satisfied.
4. The compressor and outdoor fan will be de-ener­gized when the thermostat opens. It is normal for the scroll compressor to produce a short burping sound at this time as its internal pressures are equal­ized.
5. Refrigerant will continue to flow through the capil­lary tube (sizes 24 to 42) until the high and low side pressures are approximately equal. Refrigerant will continue to flow through the thermal expansion valve until the high and low side pressures are approxi­mately 50 PSI apart.
6. The indoor fan continues to run for approximately 45 seconds after the thermostat is satisfied. This allows additional cooling from the indoor coil to be transferred to the conditioned space.
General Information
This furnace is equipped with an electronic ignition de­vice which lights the burners. It also has a power vent blower to exhaust combustion products.
On new installations, or if a major part such as the gas valve, pressure switch or fan/limit control has been re­placed, the operation of the furnace must be checked.
Check furnace operation as outlined in the following in­structions. If any sparking, odors, or unusual noises are encountered, shut off electrical power and recheck for wiring errors, or obstructions in or near the blower mo­tors. Various shipping materials must be removed be­fore the indoor and outdoor fans can be operated.
Heat Anticipator Setting
The heat anticipator in the room thermostat must be correctly adjusted to obtain the proper number of heat­ing cycles per hour and to prevent the room tempera­ture from over-shooting the room thermostat setting. Heat anticipator must be set at 0.8 amps.
Roll-out Protection Control
If the flames from the burners are not properly drawn into the heat exchanger, a protection device will open, causing the gas valve to close. The protection device is located on the manifold assembly (Figure 14).
18
WARNING
To avoid the risk of fire or explosion, a qualified servicer must investigate the problem which caused the roll-out pro­tection device to open before manually resetting the device.
Flame Roll-Out
Protector
(Manual Re s et)
Figure 14
Rollout Protection
(Shown Without Heat Shield)
Reset After Lock-out
Should ignition not be achieved after three tries for any reason, it will be necessary to reset the electronic igni­tion module. To reset, it is only necessary to turn the thermostat below room temperature for thirty seconds, and then reset it to the desired temperature. The fur­nace may also be reset after lockout by disengaging the electric disconnect switch to the furnace for thirty sec­onds.
Operating Instructions (Heating)
NOTE: Figure 16 illustrates the proper gas valve mount-
ing location.
Flame Roll-Out
Protector
(Manual Reset)
Secondary Limit Control
On the PGC and PGB series, a second limit control is placed on the blower scroll that will open if the blower should fail, causing elevated temperatures at the con­trol. The reason for elevated temperatures at the control should be ascertained and repaired prior to resetting this manual reset control. The secondary limit control is lo­cated behind the front center panel on the blower scroll. (Figure 15).
Secondary Limit
NOTE: Position of Limit Control
Differs From Model to Model.
Control
Figure 15
Position of Limit Control
Figure 16
Gas Valve
1. Close the manual gas valve external to the furnace.
2. Turn off the electrical power supply to the furnace.
3. Set the room thermostat to its lowest possible set­ting.
4. Remove the right hand door on the front of the fur­nace by removing screws.
5. This furnace is equipped with an ignition device which automatically lights the burner. Do NOT try to light burner by any other method.
6. Turn the gas control valve knob to the OFF position. Do not force. (Figure 16).
7. Wait five minutes to clear out any gas.
8. Smell for gas, including near the ground. This is im­portant because some types of gas are heavier than air. If you have waited five minutes and you do smell gas, immediately follow the instructions on Page 6 of this manual. If you have waited five minutes and you do NOT smell gas, turn the gas control valve knob to the ON position. (Figure 16).
9. Replace the door on the front of the furnace.
10.Open the manual gas valve external to the furnace.
11.Turn on the electrical power supply to the furnace.
12.Set the thermostat to desired setting.
NOTE: There is a one minute delay between thermo­stat energizing and burner firing.
19
Gas Input And Pressures
Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate.
Checking Gas Pressure
Gas inlet pressure should be checked and adjusted in accordance to the type of fuel being consumed.
To adjust the pressure regulator, remove the adjustment screw or cover on the gas valve. Turn out (counterclock­wise) to decrease pressure, turn in (clockwise) to in­crease pressure. Only small variations in gas flow should be made by means of the pressure regulator adjustment. In no case should the final manifold pressure vary more than plus or minus 0.3 inches water column from the specified pressure. Any major changes in flow should be made by changing the size of the burner orifices.
With Power And Gas Off:
1. Connect a water manometer or adequate gauge to the manifold gas pressure tap of the gas valve.
As an alternative method, inlet gas pressure can also be measured by removing the cap from the dripleg and installing a predrilled cap with a hose fitting. (See Figure
17).
With Power And Gas On:
2. Put furnace into heating cycle and turn on all other gas consuming appliances.
INLET GAS PRESSURE
Natural Min. 5.0" W.C., Max. 10.0" W.C.
Propane Min. 11.0" W.C., Max. 14.0" W.C.
Inlet Gas Pressure Must Not Exceed the Maximum Val­ues shown in Table Above.
If operating pressures differ from above, make neces­sary pressure regulator adjustments, check piping size, etc., and/or consult with local utility.
Check The Gas Input (Natural Gas Only)
NOTE: On outdoor equipment, the gas input will vary
with the temperature of the gas. Rated input will be ob­tained at approximately 10° F. With warmer ambient and gas temperatures, the input will decrease. Example: At 70° F the input will decrease 12%.
To measure the gas input using the gas meter proceed as follows:
1. Turn off gas supply to all other appliances except the furnace.
2. With the furnace operating, time the smallest dial on the meter for one complete revolution. If this is a 2 cubic foot dial, divide the seconds by 2; if it is a 1 cubic foot dial, use the seconds as is. This gives the seconds per cubic foot of gas being delivered to the furnace.
3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CU­BIC FOOT
Example: Natural gas with a heating value of 1000 BTU per cubic foot and 34 seconds per cubic foot as deter­mined by Step 2, then:
Input = 1000 x 3600 / 0.34 = 106,000 BTU per Hour. NOTE: BTU content of the gas should be obtained from the gas supplier. This measured input must not be greater than shown on the unit rating plate.
4. Relight all other appliances turned off in Step 1 above. Be sure all pilot burners are operating.
Figure 17
Measuring Inlet Gas Pressure
Alternate Method
Check The Manifold Pressure
A tapped opening is provided in the gas valve to facili­tate measurement of the manifold pressure. A U Tube manometer having a scale range from 0 to 12 inches of water should be used for this measurement. The mani­fold pressure must be measured with the burners oper­ating.
Check Main Burner Flame
Flames should be stable, soft and blue, (dust may cause orange tips but they must not be yellow). They should extend directly outward from the burner without curling, floating or lifting off.
Check Temperature Rise
Check the temperature rise through the unit by placing thermometers in supply and return air registers as close to the furnace as possible. Thermometers must not be able to see the furnace heat exchangers, or false read­ings could be obtained.
1. All registers must be open; all duct dampers must be in their final (fully or partially open) position and the unit operated for 15 minutes before taking read­ings.
2. The temperature rise must be within the range speci­fied on the rating plate.
NOTE: Air temperature rise is the temperature differ­ence between supply and return air.
20
With a properly designed system, the proper amount of temperature rise will normally be obtained when the unit is operated at rated input with the recommended blower speed.
If the correct amount of temperature rise is not obtained, it may be necessary to change the blower speed. A higher blower speed will lower the temperature rise. A slower blower speed will increase the temperature rise.
NOTE: Blower speed MUST be set to give the correct air temperature rise through the furnace as marked on the rating plate.
Important Note: If an installation uses a different blower speed for cooling than is used for heating, do not set the thermostat fan switch to ON (constant fan operation) during the heating season without first confirming the cooling fan speed will give a temperature rise within the limits listed on the unit nameplate. Temperature rises outside the limits listed could result in premature heat exchanger failure.
Changing Blower Speeds (PGB Units)
WARNING
To avoid personal injury or death due to electric shock, remove electrical power from the unit before changing speed taps on the blower motor.
A multi-speed motor is used in the furnace blower. It provides easy speed selection for both heating and cool­ing air flow. Section II shows the CFM and E.S.P. rela­tionship for proper selection of heating and cooling speeds. Cooling speed should be set for about 400 CFM per ton cooling capacity.
Refer to the Wiring Diagram on the furnace to connect the proper wires to the correct motor leads. All unused motor leads must be taped or securely covered with wire nuts.
Checking External Static Pressure
The total external static pressure must be checked on this unit to determine if the airflow is correct.
Changing Blower Speeds (PGC Units)
WARNING
To avoid personal injury or death due to electric shock, remove electrical power from the unit before changing speed taps on the blower motor.
PGC-B models include a BPM (brushless permanent magnet) motor. Under identical conditions, it operates at a lower power consumption than most PSC motors. Within the allowable range of external static pressures, the BPM motor will automatically adjust its RPM to de­liver the CFM listed in the blower performance table. As static pressure increases, the RPM, current draw, and operating sound level of the motor will also increase. External static pressures in excess of those listed on the nameplate may result in unsatisfactory operation, equipment damage, and/or loss of warranty coverage.
The PGC-B models also include a speed tap board lo­cated on the blower housing. The speed tap settings have been factory selected according to unit size and performance. Field select taps are provided on the speed tap board to assist the final installer. The ADJ. tap is factory set for normal (NORM) operation. Three LED’s are provided on the speed tap board. These lights indi­cate to the servicer which mode of operation the motor is experiencing, that is Heating (W1), Fan Only (G) or Cooling (Y and G).
Refer to the wiring diagram on the unit to verify speed tap settings.
Check Limit And Fan Control
1. Check limit control (Figure 18) operation after 15 minutes of operation by blocking the return air grille(s).
a. After several minutes the main burners must go
OFF. Blower will continue to run.
b. Remove air restrictions and main burners will re-
light after a cool down period of a few minutes.
2. Adjust the thermostat setting below room tempera­ture.
a. Main burners must go off. b. Circulating Air Blower should continue to run briefly
until supply air temperature drops to approximately 90-100° F.
Fan and limit controls are preset at the factory. The con­trol is set for the fan to go off at 90-100° F:
NOTE: If necessary, adjust fan ON/OFF settings to ob­tain satisfactory comfort level. The fan comes on at ap­proximately 125° F.
WARNING
To avoid personal injury, property dam­age, fire, or premature failure of the heat exchanger, do not adjust the limit con­trol, which is set at the factory.
21
Figure 18
Fan and Limit Control
CAUTION
This unit should not be used as a “con­struction heater” during the finishing phases of construction on a new struc­ture. This type of use may result in pre­mature failure of the unit due to extremely low return air temperatures and exposure to very dirty atmospheres.
WARNING
To avoid personal injury or death, always disconnect electrical power before in­specting or servicing the unit. All com­pressor protection devices reset auto­matically, energizing the contactor and outdoor fan.
Short Cycle Protector (Figure 19)
The short cycle protector is located in the blower com­partment. Each time the compressor shuts off for any reason, the short cycle protector will open. It will take about 3 to 4 minutes before the short cycle protector will reset and allow compressor startup to occur.
All wiring connected to the short cycle protector is 24V. If the compressor cycles on the short cycle protector without cycling on any of the other compressor protec­tion devices and before the call for cooling ends, com­mon causes include:
Interruption of the line voltage power.
Improper thermostat installation, defective thermo-
stat wiring, or defective thermostat.
Rapid adjustments of the room thermostat.
To Turn Off Unit
1. Set the thermostat to lowest setting.
2. Turn off the electrical power supply to the furnace.
3. Remove the right hand door on the front of the fur­nace by removing screws.
4. Turn the gas control valve knob to the OFF position. Do not force. See Figure 16.
5. Close manual gas shutoff valve external to the fur­nace.
6. Replace the door on the unit.
7. If cooling and/or air circulation will be desired, turn ON the electrical power.
Cooling Startup Compressor Protection Devices
The PGC and PGB includes components which are de­signed to protect the compressor against abnormal op­erating conditions. These include the short cycle pro­tector, external compressor protector (PGC24-42, 60 and PGB58 only), and high pressure cutout.
These controls reset automatically. Excessive cycling of the controls should be investigated before continuing operation.
(NOTE: The operation of the indoor blower will not be affected by any of the above compressor protection de­vices.)
Short Cycle
Protecto r
Figure 19
Short Cycle Protector Location
High Pressure Cutout (Figure 20)
An automatic reset high pressure control is located in the compressor discharge line. (See Figure 20) This control protects the unit from excessively high refriger­ant pressure.
High pressures can result from:
Inoperative outdoor fan motor.
Outdoor coil restricted with debris.
Recirculation of hot condenser air.
Overcharge of refrigerant.
22
Important Note: Never close the compressor suction line to test its pumping efficiency. This will seriously dam­age the compressor and void its warranty.
The compressor may run backwards (noisy opera-
tion) for 1 or 2 seconds at shutdown. This does not harm the compressor.
These scroll compressors have copper plated steel
suction tubes. If removal and reconnection becomes necessary, use silfos with minimum 5% silver or sil­ver braze material with flux.
Operating pressures and current draws may differ
from standard reciprocating compressors. See Sec­tion XV for typical cooling performance data.
Reciprocating Compressor
The PGC48 includes a reciprocating compressor with a crankcase heater. See the caution for the PGC48 be­fore starting cooling operation.
CAUTION
To avoid severe personal injury or fire, refrigerant must be removed from both the low and the high pressure sides of the system before heat is applied.
Figure 20
High Pressure Protection Devices
Scroll Compressors
PGC 24, 30, 36, 42, 60, and PGB58 units include scroll compressors. The installer and servicer should be aware of the following differences between scroll compressors and reciprocating compressors:
These scroll compressors include a thermostat (ex-
ternal compressor protector) mounted to the top of the compressor. THIS PROTECTIVE DEVICE SHOULD NEVER BE BYPASSED FOR ANY PUR­POSE.
On a scroll compressor, due to its inherent ability to
handle liquid refrigerant, a crankcase heater is not required.
CAUTION
To avoid severe personal injury or fire, refrigerant must be removed from both the low and the high pressure sides of the system before heat is applied.
The scroll compressors use white oil which is com-
patible with 3GS. If the addition of oil in the field is required, 3GS may be used .
Operating Instructions (cooling)
CAUTION
On PGC48 Only: To avoid damage to the compressor, engage the electrical dis­connect switch to the compressor unit four hours prior to operating air condi­tioner after the electrical disconnect is off for a prolonged period of time (during vacation, etc.). This time lapse allows the compressor crankcase to attain a proper operating temperature.
(NOTE: Mechanical cooling cannot be reliably provided at ambient temperatures below 50° F. If low ambient cooling will be required a downflow economizer is avail­able. See Section XIV.)
1. Turn on the electrical power supply to the unit.
2. Place the room thermostat selector switch in the COOL position (or AUTO if available, and if auto­matic changeover from cooling to heating is desired).
3. Set the room thermostat to the desired temperature.
23
XIII. Maintenance
WARNING
To avoid personal injury or death due to electrical shock, disconnect electrical power before performing any mainte­nance.
Important Note: Touching the ignitor body with bare fin­gers, rough handling, or vibration could result in early ignitor failure. Only a qualified servicer should ever handle the ignitor.
Have the furnace checked at least once a year before the heating season begins, to be sure that the combus­tion air inlet and flue outlet hoods are not blocked by debris, which would prevent adequate combustion air and a properly operating vent system.
Replacing Or Cleaning Filter
A return air filter is not supplied with this unit; however, there must be a means of filtering all of the return air. The filter(s) may be located in the return air duct(s), re­turn air filter grille(s) or in the filter rack in the unit. Con­sult with your installing dealer for the actual location of the return air filter(s) for your unit.
Dirty filters are the most common cause of inadequate heating or cooling performance. Filter inspection should be made at least every two months; more often if nec­essary because of local conditions and usage.
Dirty throwaway filters should be discarded and replaced with a new, clean filter. Dirty permanent filters should be washed with water, thoroughly dried and sprayed with a filter adhesive before being reinstalled. (Filter adhesives may be found at many hardware stores.) Permanent fil­ters should last several years. However, should one become torn or uncleanable, it should be replaced.
If the installation has the return air filter located in the unit filter rack and it must be replaced, use the appropri­ate Amana filter or a permanent filter that is properly sized as follows:
When installing a new filter or reinstalling an old one, always make certain the air flow arrows on the filter point in the proper direction. If using the unit filter rack, the airflow arrows must point toward the indoor blower.
To inspect the filter in the filter rack, proceed as follows:
1. Disconnect power to the unit.
2. Locate the filter access door (Figure 9) and remove the four sheet metal screws.
3. Pull out the filter and inspect. Clean or change as necessary.
4. Insert the filter into the filter rack channels and lower into place. Make sure the filter slides completely to the bottom so no part of the filter is left outside the back panel.
5. Return the filter access door to its original position and secure it with the four sheet metal screws.
6. Reconnect the power.
Maintaining Cabinet Finish
Use a fine grade automotive wax on the cabinet finish to maintain the original high luster. This is especially im­portant in areas with high ultraviolet radiation.
Clean Outside Coil (Qualified Servicer Only)
The coil with the outside air flowing over it should be inspected annually and cleaned as frequently as neces­sary to keep the finned areas free of lint, hair and de­bris.
Blower Motor
The air circulating blower motor bearings are perma­nently lubricated.
Model Amana Part #
PGC24, 30, or 36 C4855623 26" X 20" X 1"
PGC42, 48, 60
or PGB58
C4855627 32-5/8" X 22-3/8" X 1"
Required Permanent
Filter Size
Figure 21
Blower Motor and Housing
(NOTE: Brushless Permanent Magnet (BPM) blower mo­tors are permanently lubricated and do not have oil ports. Oil cannot be added to these motors.
Induced Draft Motor Lubrication
The induced draft motor is permanently sealed and does not require additional oiling.
24
Flame Sensor (Qualified Servicer Only)
Under some conditions, the fuel or combustion air sup­ply can create a nearly invisible coating on the flame sensor. This coating acts as an insulator causing a drop in the flame sensing signal. If this occurs, a qualified servicer should carefully clean the flame sensor with emery cloth or steel wool. After cleaning, the microamp signal should be in the range listed in Table 1A.
Figure 22
Induced Draft Motor
Condenser Fan Motor Lubrication
The condenser fan motor bearings are permanently lu­bricated and do not require additional lubrication.
Ignitor (Qualified Servicer Only)
If the ignitor and the surrounding air are at about 70° F and the ignitor wires are not connected to any other elec­trical components, the resistance of the ignitor should not exceed 200 ohms. If it does, the ignitor should be replaced.
Compressor
The compressor motor is permanently lubricated and hermetically sealed. It does NOT require oiling.
Flue Passages
At the start of each heating season, inspect, and if nec­essary clean the furnace flue passages.
Cleaning Flue Passages (Qualified Servicer Only)
1. Shut off electric power and gas supply to the fur­nace.
2. Remove burner assembly and disconnect the gas line and remove the manifold brackets from the par­tition panel.
3. Remove the induced draft blower and the collector box from the partition panel.
4. Remove tube inserts and turbulators from heat ex changer.
5. The primary heat exchanger tubes can be cleaned using a round wire brush attached to a length of high grade stainless steel cable, such as drain cleanout cable. Attach a variable speed reversible drill to the other end of the spring cable. Slowly rotate the cable with the drill and insert it into one of the primary heat exchanger tubes. While reversing the drill, work the cable in and out several times to obtain sufficient cleaning. Repeat for each tube.
6. When all heat exchanger tubes have been cleaned, replace the parts in the reverse order in which they were removed.
7. To reduce the chances of repeated fouling of the heat exchanger, perform the steps listed in Startup and Adjustment, Section XII.
Figure 23
Removal of Fan Motor
25
Burners
WARNING
To avoid personal injury or death due to electrical shock, do not remove any internal compartment covers or attempt any adjustment. Contact a qualified ser­vicer at once if an abnormal flame ap­pearance should develop.
At least once a year, prior to or during the heating sea­son, make a visual check of the burner flames.
NOTE: This will involve removing and reinstalling the right front door on the unit, which is held by several screws. If you are uncertain about your ability to do this, contact a qualified servicer.
If a strong wind is blowing, it may alter the airflow pat­tern within the furnace enough that an inspection of the burner flames is not possible.
The inspection of the burner flames must be performed with the heat shield in place. Only a qualified servicer should ever remove the heat shield from the manifold assembly.
For further information on the yearly inspection, con­sult the User Manual. It is recommended that a quali­fied servicer inspect and service the unit at least once each year.
Turn the furnace on at the thermostat. Wait a few min­utes, since any dislodged dust will alter the normal flame appearance. Flames should be predominantly blue and directed into the tubes. They should not be yellow. They should extend directly outward from the burner ports without curling downward, floating or lifting off the ports.
XIV. Accessories and Functional Parts
Accessories
Additional Amana accessories can be purchased to fit specific application needs. Accessories can be ordered by description in Table 5. Each accessory includes its own separate instructions.
Pre ssure Drop of Tra nsition Kit
Model
PDTROU3A PDTROU5A
700 900 1200 1400 1600 1800
0.07 0.11 0.19
--- --- --- 0.06 0.08 0. 10
CFM
--- --- ---
Table 6
Transition Kit Pressure Drop
Replacement Parts
1. Refer to the description in Table 7 when ordering any of the listed functional parts. Be sure to provide the fur­nace model, manufacturing, and serial numbers with the order.
Gas Valve BPM Blower Motor (PGC)
Heat Exchanger Blower Motor (PGB)
Gas Orifice, Natural Pressure Switch Hose
Evaporator Coil Induced Draft Blower
Gas Orifice, Propane Time Delay Relay
Transformer Blower Relay (PGB)
Burner Compressor
Ignitor Pressure Switch
Combustion Relay Contactor
Flame Sensor Flame Roll-Out Switch Blower Wheel Condenser Fan Blade
Ignition Control High Pressure Cutout
Blower Housing Condenser Fan Motor
Fan /Limit Switch Compressor Time Delay
Speed Tap Board (PGC) Condenser Coil
Table 7
Functional Parts List
2. Although only functional parts are shown in Table 7, all sheet metal parts, doors, etc. may be ordered by de­scription or by referring to the Parts Manual.
3. Parts are available from your Amana distributor.
Transition Kit
Accessory
Duct Transit i on Round
Duct Transit i on Over/Under
Rooftop Curb
Downflow Economi z er
Fresh Air Intake
Baromet ri c Rel ief Hood
50° F Compressor Loc k out
Am b i ent Thermostat Kit
Em ergenc y Heat Relay
Circ u i t Breaker Kit
Elect ric Heat K i t
Table 5
Accessory List
26
XV. Typical Cooling Performance Data
Outdoor Indoor PGC24 PGC30 PGC36
Air Temp.
at
Condenser
Inlet
(Dry Bulb)
° F. ° F. ° F. PSIG PSIG Amps ° F. PSIG PSIG Amps ° F. PSIG PSIG Am ps
115 72 12 91 324 12. 7 12 89 322 15. 9 12 87 352 19. 4
110 72 12 90 304 12. 1 12 88 303 15. 1 12 87 332 18. 5
105 72 12 90 286 11. 6 12 88 285 14. 5 12 86 310 17. 6
100 72 12 89 269 11. 1 12 87 267 13. 9 12 85 293 16. 9
95 72 13 88 251 10.6 13 86 249 13.3 13 85 274 16.1
90 72 13 88 236 10.2 13 86 232 12.8 13 84 255 15.4
85 72 13 87 221 9.8 13 85 217 12.4 13 83 238 14.8
80 72 13 86 203 9.3 13 84 203 12.0 13 83 223 14.2
75 72 13 86 189 9.0 13 84 189 11.6 13 82 207 13.7
Air
Temp.
at Evap.
Inlet
(Wet Bulb)
A B CDE B CDE B CDE
77 7 92 325 12. 8 7 89 320 15.8 7 88 351 19.3
67 17 91 324 12.7 17 88 322 15.8 17 87 352 19.3 62 23 90 326 12.8 23 87 322 15.8 23 86 352 19.3 77 7 91 308 12. 2 7 89 304 15.2 7 87 332 18.5
67 17 80 304 12.1 17 88 303 15.1 17 86 331 18.4 62 23 89 304 12.1 23 87 302 15.1 23 85 329 18.4 77 7 90 288 11. 7 7 88 285 14.5 7 86 311 17.6
67 18 89 286 11.6 18 87 283 14.5 18 85 312 17.6 62 23 88 286 11.6 23 86 282 14.4 23 84 311 17.6 77 8 89 269 11. 1 8 87 267 13.9 8 86 293 16.9
67 18 89 271 11.2 18 86 267 13.9 18 85 292 16.8 62 23 88 271 11.2 23 85 267 13.9 23 84 290 16.7 77 8 89 255 10. 7 8 87 251 13.4 8 85 275 16.2
67 18 88 252 10.7 18 86 249 13.3 18 84 274 16.1 62 23 87 254 10.7 23 85 249 13.3 23 83 274 16.1 77 8 88 237 10. 2 8 86 234 12.9 8 84 255 15.4
67 18 87 234 10.2 18 86 231 12.8 18 83 256 15.4 62 24 86 235 10.2 24 84 231 12.8 24 83 254 15.4 77 8 87 222 9.8 8 86 217 12. 3 8 84 240 14.8
67 18 86 221 9. 8 18 84 216 12.3 18 83 238 14.7 62 24 86 220 9. 8 24 83 216 12.3 24 82 239 14.8 77 8 87 203 9.3 8 85 202 11. 9 8 83 224 14.3
67 18 86 205 9. 4 18 84 202 11.9 18 82 221 14.2 62 24 85 206 9. 4 24 83 202 11.9 24 81 221 14.2 77 8 86 189 9.0 8 84 189 11. 6 8 83 208 13.7
67 19 85 191 9. 0 19 83 189 11.6 19 82 207 13.7 62 24 85 190 9. 0 24 82 187 11.6 24 81 206 13.6
Indoor
Air Temp.
Difference
Betw e en Coil Inlet
and Outlet
Pressure @ Unit
Gauge Fitti ng s
Low Side
High Side
Amps
Total to
Unit
Indoor
Air Temp.
Difference
Betw e en Coil Inlet
and Outlet
Pressure @ Unit
Gauge Fitti ng s
Low Side
High Side
Amps
Total to
Unit
Indoor
Air Temp.
Difference
Betw e en Coil Inlet
and Outlet
Pressure @ Unit
Gauge Fitti ng s
Low Side
High Side
Amps
Total to
Unit
A Columns - All data based on indoor dry bulb of 80° F and rated air flow. As indoor dry bulb temperature increases, a slight increase wil B Columns - A properly operating unit should be within ±3° F of the typical (dry bulb) value shown.
C Columns - A properly operating unit should be within ±3 PSIG of the typical value shown. D Columns - A properly operating unit should be within ±7 PSIG of the typical value shown. E Columns - A properly operating unit should be within ±2 amps of the typical value shown.
between inlet and outlet. Low and high side pressures and power will not change.
Table 8A
27
l occur in indoor air temperature differential
Outdoor Indoor PGC42 PGC48 PGC60 and PGB58
Air Temp.
at
Condenser
Inlet
(Dry Bulb)
° F. ° F. ° F. PSIG PSIG Amps ° F. PSIG PSIG Amps ° F. PSIG PSIG Amps
115 72 12 85 331 23.1 13 88 327 23.8 15 83 342 34.8
110 72 13 85 313 22.2 13 87 308 23.2 15 82 322 33.2
105 72 13 84 293 21.2 13 86 290 22.5 15 81 303 31.8
100 72 13 83 276 20.4 13 86 273 21.9 15 80 285 30.4
95 72 13 82 258 19.6 13 85 257 21.2 16 80 267 29.2
90 72 13 82 241 18.8 14 84 240 20.6 16 79 250 28.0
85 72 13 81 224 18.1 14 83 225 20.0 16 78 234 26.9
80 72 13 81 210 17.5 14 82 210 19.4 16 78 218 25.9
75 72 14 80 196 16.9 14 82 196 18.8 16 77 203 24.9
A Columns - All data based on indoor dry bulb of 80° F and rated air flow. As indoor dry bulb temperature increases, a slight increase wil B Columns - A properly operating unit should be within ±3° F of the typical (dry bulb) value shown.
C Columns - A properly operating unit should be within ±3 PSIG of the typical value shown. D Columns - A properly operating unit should be within ±7 PSIG of the typical value shown. E Columns - A properly operating unit should be within ±2 amps of the typical value shown.
Air
Temp.
at Evap.
Inlet
(Wet Bulb)
A BCDEBCDEBCDE
77 7 86 332 23.1 8 88 327 23.8 9 83 343 34.9
67 18 85 332 23.1 18 88 327 23.8 21 82 342 34.7 62 23 84 332 23.2 24 87 326 23.7 26 81 341 34.6 77 8 85 313 22.2 8 88 308 23.2 10 82 323 33.3
67 18 84 312 22.1 18 87 308 23.1 21 81 322 33.2 62 23 83 311 22.1 24 86 307 23.1 27 80 321 33.1 77 8 84 294 21.3 8 87 291 22.5 10 82 303 31.8
67 18 83 294 21.3 18 86 290 22.5 21 80 303 31.8 62 23 82 293 21.2 24 85 290 22.4 27 80 302 31.7 77 8 84 277 20.4 8 86 274 21.9 10 81 285 30.5
67 18 83 275 20.4 19 85 273 21.8 21 80 285 30.5 62 24 82 274 20.3 24 84 272 21.8 27 79 284 30.4 77 8 83 259 19.6 8 85 256 21.3 10 80 268 29.2
67 18 82 257 19.5 19 84 256 21.2 22 79 267 29.2 62 24 81 256 19.5 25 84 255 21.1 28 78 266 29.1 77 8 82 241 18.8 8 84 240 20.6 10 79 251 28.1
67 19 81 240 18.8 19 83 240 20.6 22 78 250 28.0 62 24 80 240 18.8 25 83 239 20.5 28 77 249 27.9 77 8 82 226 18.1 9 84 225 20.0 11 79 234 27.0
67 19 81 225 18.1 19 83 224 20.0 22 78 233 26.9 62 24 80 223 18.0 25 82 224 19.9 28 77 232 26.8 77 8 81 211 17.5 9 83 200 19.4 11 78 218 25.9
67 19 80 211 17.5 20 82 209 19.4 22 77 218 25.9 62 24 79 208 17.4 25 81 209 19.3 28 76 217 25.8 77 9 80 196 16.9 9 82 196 18.8 11 78 204 25.0
67 19 79 194 16.8 20 81 195 18.8 22 76 203 24.9 62 25 79 194 16.8 25 80 195 18.8 28 76 202 24.8
between inlet and outlet. Low and high side pressures and power will not change.
Indoor
Air Temp.
Difference
Between
Coil Inlet
and Outlet
Pressure @ Un it
Gauge Fi t tings
Low Side
High Side
Amps
Total to
Unit
Indoor
Air Temp. Difference
Between
Coil Inlet
and Outlet
Pressure @ Un it
Gauge Fi t tings
Low Side
High Side
Amps
Total to
Unit
Indoor
Air Temp.
Difference
Between
Coil Inlet
and Outlet
l occur in indoor air temperature differential
Pressure @ Un it
Gauge Fi t tings
Low Side
High Side
Amps
Total to
Unit
Table 8B
28
XVI. Wiring Diagram
PGC24 - 36
29
PGC 4231PGC 48
30
PGC 60
CONT
ACTOR (CC
GAS
CMP
YL-11
GY-25
208 VOLT INSTALLATION
VALVE
IGNITION CONTROL
(TERMINAL ORDER REARRANGED)
VALVE
21 3
PRESSURE
SWITCH (PS)
NC NO
TRANSFORMER
COM
MOVE BK23 AND BK33 WIRES FROM TRANSFOR MER
FOR PROPER OPERATION ON 208 VOLT THE
FOLLOWING CHA NGES MUST BE MADE:
L
GND
T
R
T
R
IGN IGN
L
R2
BK
ROLLOUT
LIMIT (RL)
TERMINAL
BOARD
BR-22
GY-20
BU-10
RD-1
BR-21
CWGRY
R1
SHORT CYCLE
Y1
PROTECTOR (SCP)
OR
-8 BU
COMB
BLOWER
BK
RD
(208V)
GY-80
-1
BK
-14
Y2
YL
-3
RD
-18 RD
-19 VT-37
)
L1
BK-13
T1
GY-70
BK
-1
RD
-1
L2
T2
VT(COM)
(230V)
Ø
L2 L1
FIELD CONNECTION
208/240 VAC 1
GND
WARNING:C 1%
!
GND
DISCONNECT POWER
BR BROWN
WH WHITE
BU BLUE
GY GRAY
RD RED
COLOR CODE
YL YELLOW
OR ORANGE
11160801 REV. 0
BEFORE SERVICING
LOW VOLTAGE
LOW VOLTAGE FIELD
HI VOLTAGE
HI VOLTAGE FIELD
VT VIOLET
GN GREEN
BK BLACK
BK-14
YL-4
BU-29
OR
COM
OR-16
GY-35
RD-1
VT
-47VT-47
208
LINE
240
LOAD
BR-21
GY-30
OR-49
SECO N D ARY LIMIT
TH
GND
VALVE
OR-19
240 TERMINAL TO 208 TERMINAL.
UNPLUG RED COMBUSTI O N BL OWER LEAD FROM
COMBUSTION RELAY NUMBER 6 TERMINAL.
ATTACH BLACK BLOWER LEAD TO TERMINAL.
TAPE UNUSED RED LEAD.
2
RL
GAS
VALVE
SEC
H
S
IGNITOR
1
LIMIT
NO
FL
PS
NC
FLAME
SENSOR
7
8
FLAME
SENSOR
RS
C
-15
COMBUSTION
RELAY (CR)
65
IGNITOR
RD-23
RD-22
BK-33
L2
L1
IGN
IGN
IGNITION
CONTROL
C
Y
8
CR 7
TAP BO A R D
RGW
CR
35
G
W
3
4
BK-23
RD-18
(FC)
SCP
Y2 R2
1
2
RD-10
COM
BK-27
RD-19
APA
C
RD-10
R
CS
YL
-12
HERM
I
T
C
GY-40
VT-20VT-20
VT-20
BU
WIRING
Ø
1
COMPRESSOR
WARNING: DISCONNECT POWER BEFORE SERVICING.
READ BEFORE OPERATING OR SERVICING THIS UNIT.
HIGH PRESS
BU
FAN
O
R
(1)
TAP
BOARD
IMPORTANT:
(2)
(3)
(4)
!
2. AMANA APPROV ED R EPLACEMENT PARTS MUST BE
1. SET HEAT ANTICIPATOR ON ROOM THERMOSTAT
AT 0.8 AMPS.
(5)
(6)
(7)
(8)
(9)
(10)
4. EQUIPPED FOR 230 VOLT, FOR 208 VOLT SEE
INSTRUCTIONS AT TOP OF THIS DIAGRAM.
MUST BE USED.USE COPPER CONDUCTORS ONLY.
USED WHEN SERVICING.
(11)
(12)
(13)
(14)
(15)
(16)
OR-8
YL
GY-40
BU-2
VT-37
CONTROL
FAN LIMIT
(FL)
YL-11
CC
R1 Y1
HIGH
PRESS
FC
Y
-4
** *
TAP BOARD
CYGWR
SEE
DETAIL
HARNESS
AIR
CIRCULATION
BK-1
BR-11
BK-27
FAN
O.D.
MOTOR
(ACB)
BLOWER
RD-1
GN-1
COMB
BLOWER
COM
24 V
208
(230 V)
(208 V)
230
X'FMR
RC
CR
46
GY-1
BU-2
GY-3
YL-5
YL-6
YL-7
YL-8
BU-9
YL-11
RD-12
OR-15
HARNESS
DETAIL
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
** COOL
(11)
TAP
(ACB)
AA
* HEAT
TAP
MODEL NO.
FACTORY WIRED
MOTOR CONNECTI ONS
PGC60B0902A
C
COMP
S
R
OD
ICM
FAN
CAP
FAN
COM
HERM
CC
T1 T2
YL-16
(12)
(13)
(14)
(15)
(16)
BA
PGC60B1352A
GND
WARNING:
DISC ONNECT POWER B EFORE SERVI CING.
!
L1 L2
32
PGB 58
CMP
YL-11
GY-25
GAS
VALVE
21 3
BU-10
PRESSURE
SWITCH
NC
NO
TRA NSFOR MER
L1
ROLLOUT
LIMIT
(RL)
TERMINAL
BOARD
RD-1
BR-22
RD
OR
BR-21
GY-20
CWGRY
(PS)
OR-16
COM
GY-35
BU-51O
RD-1
VT
-47
208240
LINE
COM
LOAD
FAN
TIME
(FD)
DELAY
H
H
1
-41
-8 BU
COMB
BLOWER
GY-80
RD
BK
(230V)
(208V)
OR
-15
7
COMBUS TI ON
RELAY (CR)
8
6
GY
1
(FR)
FAN RELAY
3
BK
GY
-45
3
VT-37
BU
-51
GY-70
BU-29
1
5
3
4
2
-45
5
24
L2
L1
T1
CONTACTOR
YL-3
(CC)
T2
VT-20
-10
RD
S
R
C
RD-10
YL
-12
BK-23O BK-13O
-23
VT-37
COM
BK-27
CAPACITOR
FAN
HERM
L2
BR BROWN
WH WHITE
BU BLUE
GY GRAY
GND
WARNING:
FIELD CONNECTION
208/240 VAC 1ø
!
DISCONNECT
POWER
BEFORE
SERVICING
COLOR CODE
VT-27
GND
CYCLE
SHORT
PROTECTOR
Y1Y2R1
(SCP)
11161001 REV. 0
R2
BK
-1
RD RED
LOW VOLTAGE
LOW VOLTAGE FIEL D
HI VOLTAGE
HI VOLTAGE FIELD
YL YELLOW
OR ORANGE
VT VIOLET
GN GREEN
BK BLACK
VT (COM)
BK-14
BU
VT-20
HIGH PRESS
BU
1ø WIRING
COMPRESSOR
IMPORTANT:
READ BEFORE OPERATING OR SERVICING THIS UNIT.
WARNING: DISCONNECT POWER BEFORE SERVICING.
!
5. EQUIPPED FOR 230 VOLT, FOR 208 VOLT SEE
INSTRUCTIONS AT TOP OF THIS DIAGRAM.
3. IF ANY ORIGINAL WIRE IS REPLACED, 105° C WIRE
MUST BE USED.USE COPPER CONDUCTORS ON LY.
2. AMANA APPR OVED REPLACEMENT PARTS MUST BE
USED WHEN SERVICING.
1. SET HEAT ANTICIPATOR ON ROOM THERMOSTAT
AT 0.8 AMPS.
4. WIRE NUT AND TAPE UNUSED MOTOR LEADS.
FOR PROPER O PERAT ION ON 208 VOLT THE
FOLLOWING CHANGES MUST BE MADE:
208 VOLT INSTALLATION
GND
T
VALVE
IGN IGN
IGNITION CONT ROL
(TERMINAL ORDER REARRANGED)
IGNITOR
BU
-2
GY-40
FLAME
SENSOR
*
GY-30
BR-21
OR-49
SECONDARY LIMIT
TH
VALVE
RD-23
RD-22
BK-33
L2
RS
L1
IGN
GND
IGN
VT-14
RD-18
FAN LIMIT
RD-2 4 L O
CONTROL
**
BK-27
VT-20
BR-11
BK-26 HI
BU-23 MED
AIR
BLOWER
CIRCULA TI ON
FAN
O.D.
MOTOR
(ACB)
VT-27O
IGNITION
CONTROL
OR-19
MOVE BK23 AN D BK3 3 WIRES FROM TRANSFORMER
240 TERMINAL TO 208 TERMINAL.
UNPLUG RED COMBUSTION BLOWER LEAD FROM
COMBUSTION RELAY NUMBER 6 TERMINAL.
ATTACH BLACK BLOWER LEAD TO TERMINAL.
TAPE UNUSE D RED LEAD.
L
2
R
RL
T
H
R
S
L
1
GAS
VALVE
SEC
LIMIT
FL
FLAME
SENSOR
IGNITOR
8
FRHH
CR7
NO
C
PS
NC
CR
35
G
W
(FC)
(FL)TUTN
BR-25
VT-14
YL-11
FACTORY WIRED MOTOR CONNECTIONS
CAPACITOR
CAP
CC
FR31
SCP
Y2 R2
R1 Y1
YDNSO
HIGH
PRESS
24 V
FD
13
RC
COMB
BLOWER
COM
208
(230 V)
(208 V)
230
X'FMR
CR
46
ACB
HI
LO
MED
*
FC
* *
2
5
FR
4
COMP
R
OD
FAN
CAP
FAN
COM
HERM
HI BLACK 26BLUE 23
** COOLING BLOWER SPEED
RED 24 HI BLACK 26
RD-18 TO MOTOR WIRE SPEED BL-2 TO MOTOR WI RE
LOW
MED
SPEED
* HEAT ING BLOWER S P EED
3
3
MOTOR
SPEEDS
MODEL NO.
PGB58B135 HI HI BLACK 26BLACK 263
PGB58B090
PGB58B115
C
S
GND
WARNING:
DISCONNECT POWER BEFORE SERVICING.
CC
T1 T2
!
L1 L2
33
Loading...