•If devices are to be powered, field installed wiring will
need to be run from thermostat location to unit location
and from door sensor location to PTAC location and from
wired magnet to sensor location.
•If wireless platform DP01G, DP01E or DL01E are being
utilized, then room numbers MUST BE CONFIGURED in
the control board prior to binding wireless devices.
•All units must have DT01G antenna for wireless devices
to communicate properly.
Sequence of installation:
•1) Mount the peripherals
2) Verify operation of the door sensor
3) Program room numbers
4) Bind peripherals
5) Reattach peripherals to their mounted backplates
6) Install optional security screws
•Installation and videos are available on our website at
www.amana-ptac.com.
•Use only one DD01E Passive Infrared Motion Sensor (PIR)
door switch combination device and/or one DS01E to one
DigiSmart™ PTAC unit.
:
Front Mounting Screw
accessed
through louvers.
3. Remove cabinet front from chassis by tilting the bottom of the front forward, lifting slightly up and forward.
4. Mount the antenna as high up on the control panel as
possible and as far to the right as possible in a location
that will not interfere with the reinstallation of the PT AC
polymer room front. Mark holes for screw location. Remove antenna housing and drill two 1/8” holes where
marked. Some units may have the holes already predrilled in the correct location.
Antenna Installation For DT01G Kit
A DT01* antenna must be installed on the digital PTAC to
allow operation of either the DS01* remote RF thermostat
or a DD01* combination PIR motion sensor and door switch.
Preparation
1. Disconnect power to the unit by unplugging the power
cord at the wall outlet or subbase, or disconnect power
at the fuse box or circuit breaker.
2. If the cabinet front is screwed to the chassis, remove
the 1/4” screw (or screws). See following figure.
Wire
DT01* Mounting
5. Remove antenna cable and route cable through opening in bottom of antenna housing.
6. Mount antenna housing with two screws as shown in
figure. (NOTE: The Amana® brand logo should be in
the lower right hand corner).
7. Plug wire harness from antenna into connector on the
control board to the right of the master switch, being
careful not to bend and/or break the wires when you
connect the cable to the PT AC. Gently push the connector into place by pushing on the edge of the connector with your thumb nails. Avoid pushing directly on
the wires.
8. Restore power to the PTAC unit.
9. Reinstall the polymer room cover .
NOTE: The LED must be oriented at the top of the antenna
housing (the Amana® brand logo will be on the lower right)
for proper unit operation.
2
Thermostat Installation for DS01E Kit
NOTE: A DT01* must be installed on the digital PTAC unit
for the DS01* to be operable.
Skip these steps if not installing.
1. Select thermostat mounting location about five feet
above the floor, on an inside wall, out of direct sunlight, away from sources of radiant heat (lamps, fireplaces, heating and air conditioning equipment, etc.),
away from windows or door to the outside, and avoid
areas with poor air circulation. If the PIR in the thermostat is to be used with a DD01* device as a 2nd motion sensor , point the thermostat towards the area where
you are requiring additional motion sensing.
Ensure location is out of the path of foot traffic where
a person might accidentally bump into the thermostats
and damage the device.
2. Remove thermostat from mounting plate by pulling apart
at the bottom of the thermostat about 1”, and slide
thermostat up to release from the top of the mounting
plate.
3. Place thermostat mounting plate against the wall at desired location and mark placement of mounting holes.
Make sure the UP arrow is pointing up on the mounting
plate.
TWO JUMPERS
FACTORY DEFAULT
“BATTERY”
BATTERY CONNECTION
NOTE: For battery connection the 2 jumpers must be posi-
tioned as shown above, with jumpers on the center & left
pins.
TERMINAL BLOCK
4. If mounting in drywall, tap plastic anchors into wall. For
other surfaces, drill a 3/16” hole.
5. Screw mounting plate to the wall.
MOSTAT INTO PLACE UNTIL AFTER BINDING PROCESS.
See Binding Instructions on page 10.
6. Install four (4) AA batteries (included) into the back of
the thermostat. Terminals are marked “+” and “-” for
polarity.
NOTE: Do not install thermostat on wall plate until all configuration settings and binding processes have been completed.
DO NOT SNAP THER-
WIRED POWER OPTION
1. If the option for wired power is used, the two thermostat wires (20 gauge minimum field supplied) can be
connected to the thermostat.
2. Route wires through the opening in the mounting plate.
3. Loosen set screws on wired terminal and insert wires
into the opening. Tighten set screws. (See following
figure for powered connection with 2 jumpers).
TWO JUMPERS MOVE D TO
“EXT POWR”
POWERED CONNECTION
NOTE: For powered connection, the 2 jumpers must be
positioned as shown above, with jumpers on the center &
right pins.
4. Connect wires at PTAC unit to terminal pins C and R.
The wire harness kit PWHK01C is required for this connection.
3
Mounting Sensor/Door Magnet Installation
for DD01E Kit
WIRED MAGNET AND POWERED DOOR
SENSOR OPTION
DD01E must be mounted on the top door frame as close to
the door as possible in the horizontal position.
A DT01E must be installed in the PTAC unit for the DD01E to
be operable.
Skip these steps if not installing.
1. Remove motion sensor from mounting plate by pulling
apart.
2. Mount the back plate on the door trim directly above
the door using the enclosed screws. (Position so the UP
arrow is pointing up.) Mount the DD01E as low as possible on the door frame to be as close to the moving
part of the door as possible without interfering with
the door opening or closing. Choose a location for mounting the back plate that will provide good coverage of
the PIR for motion into the room. Make sure that the
DD01E will not interfere with the normal opening and
closing of the door .
DO NOT SNAP MOTION SENSOR IN PLACE UNTIL AFTER
BINDING PROCESS.
See Binding Instructions, page 10.
DD01*
DOOR TRIM
DOOR
(CENTER MAGNET WITH 01*)DD
In cases where there is no top door frame, the sensor will
need to be mounted on the wall next to the door. In these
cases a wired magnet (a field supplied single pole single
throw wired magnet) can be recessed or surface mounted
and wired to the door sensor. The magnet will be a recessed
style magnet with wired switch. The wires for the sensor
(20 gauge field supplied) in the magnet will need to be run
during construction. Two wires will be run from the door
sensor location to the PTAC unit; the remaining two wires
will be run from the magnet location to the sensor location.
The door sensor has four (4) terminal locations for wired
power and/or wired magnets. The two (2) terminals closest
to the binding button are for wired magnet and the top two
(2) terminals are for wired power.
Run the magnet wires through the opening in the center of
the door sensor wall plate.
CONNECTING MAGNET
Using a pocket size straight blade screw driver push down
on the terminal button to open the socket, insert wire into
socket and release the terminal button. Insert one wire into
each of the two (2) terminals. See image below for wire
locations.
POWER CONNECTION
If using the wired powered option for the door sensor, using
a pocket size straight blade screw driver, push down on the
terminal button to open the socket. Insert wire into socket
and release the terminal button. Insert one wire into each
of the two (2) terminals. See following for wire locations.
Connect the power wires from the door sensor to the PTAC
on terminals C & R. The wire harness kit PWHK01C is
required for this connection.
DD01E Mounting
3. Install two (2) AA batteries (included) into the back of
the thermostat. Terminals are marked “+” and “-” for
polarity. Do NOT put batteries into the device until
AFTER the magnet location is selected to test.
4
Viewed from the back with the power block
T
in upper right corner.
+
-
Battery Holder
Power Connection
Battery
Holder
Note: For battery connection, the jumper must be placed
as shown above
Power Connection
Binding Button
-
+
Binding Button
-
+
Wired
Magnet
Connection
Pins
Wired
Magnet
Connection
Jumper
on Pins
Battery
Connection
Door Magnet Installation
NOTE: Magnet buckets are shipped from the factory with the
magnets in position A. The position may change based on
the door and door frame alignment on page 6.
Mount the door magnet holder on the front of the door
where it will be as close as possible to the bottom of the
motion sensor but no more then 1/8" from the bottom center
of the motion sensor (DD01E) when the door is closed.
Select the correct slot in the magnet holder (there are three
slots) to obtain 15/16" from back of sensor mounting plate
to the center of the magnet. (If you can easily slide a
business card between the magnet and the DD01E sensor,
unit is properly placed vertically.) See image below for
magnet and sensor alignment.
Screw in place with the 2 screws provided. Open and close
the door to make sure that the magnet holder and motion
sensor will not interfere with normal opening and closing
of the door. See images on pages five and six.
ALIGNMEN
GUIDES
ON BOTTOM
OF DD01E
Power Connection
-
+
Battery
Holder
Note: For 24v powered connection, the jumper must be
placed as shown above
Binding Button
Wired
Magnet
Connection
Jumper
on Pins
Powered
Connection
CENTER OF MAGNET
SENSOR
MOUNTING
PLATE
Do NOT install batteries until you are ready to test the
magnet location with DD01E.
MUST BE 15/16” FROM THE
SENSOR MOUNTING PLATE
(IN HOLDER)
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.