Altusen PE6208, PE8108, PE8208, PE3208, PE1108 User Manual

...
eco PDU PE Series
PE1108 / PE1208 / PE3108 / PE3208 / PE6108 / PE6208 /
PE8108 / PE8208
Power Distribution Unit
User Manual
www.aten.com
ii
FCC Information
This is an FCC Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
RoHS
This product is RoHS compliant.
SJ/T 11364-2006
The following contains information that relates to China.
eco PDU PE Series User Manual
iii
User Information
Online Registration
Be sure to register your product at our online support center:
Telephone Support
For telephone support, call this number:
User Notice
All information, documentation, and specifications contained in this manual are subject to change without prior notification by the manufacturer. The manufacturer makes no representations or warranties, either expressed or implied, with respect to the contents hereof and specifically disclaims any warranties as to merchantability or fitness for any particular purpose. Any of the manufacturer's software described in this manual is sold or licensed as is. Should the programs prove defective following their purchase, the buyer (and not the manufacturer, its distributor, or its dealer), assumes the entire cost of all necessary servicing, repair and any incidental or consequential damages resulting from any defect in the software.
The manufacturer of this system is not responsible for any radio and/or TV interference caused by unauthorized modifications to this device. It is the responsibility of the user to correct such interference.
The manufacturer is not responsible for any damage incurred in the operation of this system if the correct operational voltage setting was not selected prior to operation. PLEASE VERIFY THAT THE VOLTAGE SETTING IS CORRECT BEFORE USE.
PE Device Safety Notice
International http://support.aten.com
North America http://www.aten-usa.com/product_registration
International 886-2-8692-6959
China 86-10-5255-0110
Japan 81-3-5615-5811
Korea 82-2-467-6789
North America 1-888-999-ATEN ext 4988
United Kingdom 44-8-4481-58923
Set the maximum permissible breaker protection in the building circuitry to the
current rating specified on the rating plate. Observe all national regulations and safety codes as well as deviations for breakers.
Only connect the PE Device to a grounded power outlet or a grounded system! Make sure that the total current input of the connected systems does not exceed
the current rating specified on the rating plate of the PE Device.
There is a risk of explosion if the battery is replaced with an incorrect type.
Dispose of used batteries according to the relevant instructions.
iv
Package Contents
The eco PDU PE Series package consists of:
1 PE1108 / PE1208 / PE3108 / PE3208 / PE6108 / PE6208 /
PE8108 / PE8208 Power Distribution Unit
1Power Cord
1 Rack Mount Kit
1 Software CD
1 Quick Start Guide
Check to make sure that all of the components are present and in good order. If anything is missing, or was damaged in shipping, contact your dealer.
Read this manual thoroughly and follow the installation and operation procedures carefully to prevent any damage to the switch or to any other devices on the eco PDU installation.
* Features may have been added to the eco PDU since this manual was
published. Please visit our website to download the most up-to-date version.
Copyright © 2011 ATEN® International Co., Ltd.
Manual Part No. PAPE-0345-AX1G
Printing Date: 2011-10-20
Altusen and the Altusen logo are registered trademarks of ATEN International Co., Ltd. All rights reserved. All
other brand names and trademarks are the registered property of their respective owners.
eco PDU PE Series User Manual
v
Contents
FCC Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
SJ/T 11364-2006. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Online Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Telephone Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
User Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
PE Device Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Package Contents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viii
Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viii
Product Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Chapter 1.
Introduction
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
PE Series eco PDU Comparison Chart. . . . . . . . . . . . . . . . . . . . . . . . . 3
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Remote Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Cable Holders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
PE1108A / PE3108A Front View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
PE1208A / PE3208A Front View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
PE1108A / PE1208A / PE3108A / PE3208A Rear View . . . . . . . . . . . . 8
PE1108A / PE1208A / PE3108A / PE3208A Readout Section . . . . . . . 9
PE1108B / PE1108G / PE3108B / PE3108G Front View . . . . . . . . . . 10
PE1208B / PE1208G / PE3208B / PE3208G Front View . . . . . . . . . . 10
PE1108B / PE1108G / PE1208B / PE1208G / PE3108B / PE3108G /
PE3208B / PE3208G Rear View . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
PE1108B / PE1108G / PE1208B / PE1208G / PE3108B / PE3108G /
PE3208B / PE3208G Readout Section . . . . . . . . . . . . . . . . . . . . . . . . 11
PE6108A / PE8108A Front View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
PE6208A / PE8208A Front View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
PE6108A / PE6208A / PE8108A / PE8208A Rear View . . . . . . . . . . . 12
PE6108A / PE6208A / PE8108A / PE8208A Readout Section . . . . . . 13
PE6108B / PE6108G / PE8108B / PE8108G Front View . . . . . . . . . . 14
PE6208B / PE6208G / PE8208B / PE8208G Front View . . . . . . . . . . 14
PE6108B / PE6108G / PE6208B / PE6208G / PE8108B / PE8108G /
vi
PE8208B / PE8208G Rear View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
PE6108B / PE6108G / PE6208B / PE6208G / PE8108B / PE8108G /
PE8208B / PE8208G Readout Section. . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 2.
Hardware Setup
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Securing the Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Securing the Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 3.
Basic Operation and First Time Setup
Operation Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Browser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
eco Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
First Time Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Network Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Changing the Administrator Login. . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Moving On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Chapter 4.
Browser Operation
Logging In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
The eco PDU Main Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Page Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Outlet Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
User Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Administrator Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
The System Log Event List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Device Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Device Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Date/Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Login Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Working Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Account Policy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Login String / IP Filter / Mac Filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Authentication & Authorization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
eco PDU PE Series User Manual
vii
Private Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Firmware File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Backup/Restore. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Appendix
Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
The eco PDU’s Main Power Cord . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Securing the Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
International. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
IP Address Determination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
PE1108A / PE1208A / PE3108A / PE3208A. . . . . . . . . . . . . . . . . . . .61
PE1108B / PE1208B / PE3108B / PE3208B. . . . . . . . . . . . . . . . . . . .62
PE1108G / PE1208G / PE3108G / PE3208G . . . . . . . . . . . . . . . . . . . 63
PE6108A / PE6208A / PE8108A / PE8208A. . . . . . . . . . . . . . . . . . . .64
PE6108B / PE6208B / PE8108B / PE8208B. . . . . . . . . . . . . . . . . . . .65
PE6108G / PE6208G / PE8108G / PE8208G . . . . . . . . . . . . . . . . . . . 66
Administrator Login Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
viii
About This Manual
This User Manual is provided to help you get the most from your eco PDU system. It covers all aspects of installation, configuration and operation. An overview of the information found in the manual is provided below.
Chapter 1, Introduction, introduces you to the eco PDU system. Its purpose, features and benefits are presented, and its front and back panel components are described.
Chapter 2, Hardware Setup, provides step-by-step instructions for setting up your installation.
Chapter 3, Basic Operation and First Time Setup, explains the procedures that the Administrator employs to set up the eco PDU network environment, and change the default username and password.
Chapter 4, Browser Operation, describes how to log in to the eco PDU with an internet browser, and explains the layout and components of the eco PDU’s user interface.
An Appendix, provides specifications and other technical information regarding the eco PDU.
Conventions
This manual uses the following conventions:
Monospaced Indicates text that you should key in.
[ ] Indicates keys you should press. For example, [Enter] means
to press the Enter key. If keys need to be chorded, they appear together in the same bracket with a plus sign between them: [Ctrl+Alt].
1. Numbered lists represent procedures with sequential steps.
Bullet lists provide information, but do not involve sequential
steps.
Indicates selecting the option (on a menu or dialog box, for
example), that comes next. For example, Start
Run
means to open the Start menu, and then select Run.
Indicates critical information.
eco PDU PE Series User Manual
ix
Product Information
For information about all ALTUSEN products and how they can help you connect without limits, visit ALTUSEN on the Web or contact an ALTUSEN Authorized Reseller. Visit ALTUSEN on the Web for a list of locations and telephone numbers
International – http://www.aten.com North America – http://www.aten-usa.com
x
This Page Intentionally Left Blank
1
Chapter 1
Introduction
Overview
ATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency of data center power usage The ALTUSEN PE1108 / PE1208 / PE3108 / PE3208 / PE6108 / PE6208 / PE8108 and PE8208 eco PDUs are intelligent PDUs that contain 8 AC outlets and are available in various IEC or NEMA socket configurations.
They provide secure, centralized, intelligent, power management (power on, off, cycle) of data center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well as the ability to monitor the center's health environment via sensors*. The basic characteristics of each model are shown in the table on page 3.
ALTUSEN eco PDUs offer remote power control combined with real-time power measurement - allowing you to control and monitor the power status of devices attached to the PDUs, either at the PDU device or outlet level, from practically any location via a TCP/IP connection.
The power status of each outlet can be set individually, allowing users to switch each device On/Off. The eco PDU also offers comprehensive power analysis reports which can separate departments and locations, providing precise measurements of current, voltage, power and watt-hour in a real-time display.
Installation and operation is fast and easy: plugging cables into their appropriate ports and user-friendly browser-based configuration and management is all that is entailed. Since the eco PDU firmware is upgradeable over the Net, you can stay current with the latest functionality improvements simply by downloading updates from our website as they become available.
ALTUSEN eco PDU supports any 3rd party v3 SNMP Manager Software and ALTUSEN eco Sensors (eco PDU Manager Software). ALTUSEN eco Sensors provides you with an easy method for managing multiple devices, offering an intuitive and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it.
(Continues on next page.)
2
(Continued from previous page.)
With its advanced security features and ease of operation, the eco PDU is the most convenient, most reliable, and most cost effective way to remotely manage power access for multiple computer installations and allocate power resources in the most efficient way possible.
Note: Sensors are optional accessories. A sensor-enabled installation is
required to generate a more complete energy-efficient data and chart. Higher sensor installation density is helpful to generate more accurate data. See Optional Accessories, page 7, for further information.
Chapter 1. Introduction
3
PE Series eco PDU Comparison Chart
Note: For the complete specifications of individual models, please reference
Specifications, page 61.
Model
Power Cord (IEC C19 to)
Outlets
Monitoring
Level
Amps
Per Port Total
PE1108A NEMA 5-15P NEMA 5-15R PDU 12A 12A
PE1108B NEMA 6-15P IEC C13 PDU 12A 12A
PE1108G IEC C14 IEC C13 PDU 10A 10A
PE1208A NEMA 5-20P NEMA 5-20R PDU 16A 16A
PE1208B NEMA 6-20P IEC C13 / C19 PDU 12A / 16A 16A
PE1208G IEC C20 IEC C13 / C19 PDU 10A / 16A 16A
PE3108A NEMA 5-15P NEMA 5-15R Outlet 12A 12A
PE3108B NEMA 6-15P IEC C13 Outlet 12A 12A
PE3108G IEC C14 IEC C13 Outlet 10A 10A
PE3208A NEMA 5-20P NEMA 5-20R Outlet 16A 16A
PE3208B NEMA 6-20P IEC C13 / C19 Outlet 12A / 16A 16A
PE3208G IEC C20 IEC C13 / C19 Outlet 10A / 16A 16A
PE6108A NEMA 5-15P NEMA 5-15R PDU 12A 12A
PE6108B NEMA 6-15P IEC C13 PDU 12A 12A
PE6108G IEC C14 IEC C13 PDU 10A 10A
PE6208A NEMA 5-20P NEMA 5-20R PDU 16A 16A
PE6208B NEMA 6-20P IEC C13 / C19 PDU 12A / 16A 16A
PE6208G IEC C20 IEC C13 / C19 PDU 10A / 16A 16A
PE8108A NEMA 5-15P NEMA 5-15R Outlet 12A 12A
PE8108B NEMA 6-15P IEC C13 Outlet 12A 12A
PE8108G IEC C14 IEC C13 Outlet 10A 10A
PE8208A NEMA 5-20P NEMA 5-20R Outlet 16A 16A
PE8208B NEMA 6-20P IEC C13 / C19 Outlet 12A / 16A 16A
PE8208G IEC C20 IEC C13 / C19 Outlet 10A / 16A 16A
4
Features
Power Distribution
Space saving 1U rack mount design with rear mounting IEC or NEMA outlet models 3 digit 7-segment front panel LED shows Current / IP Address for PDU /
Outlet
Remote users can monitor outlet status via web pages on their browsers Safe shutdown support Separate power for the unit's own power and its power outlets. The user
interface is still accessible even when an overload condition trips the devices' circuit breaker
Remote Access
Remote power control via TCP/IP and a built in 10/100 Ethernet port Network Interfaces: TCP/IP, UDP, HTTP, HTTPS, SSL, SMTP, DHCP,
NTP, DNS, 10Base-T/100Base-TX, auto sense, Ping
eco PDU Power Management software – eco Sensors Supports SNMP Manager V3
Operation
Local and Remote power outlet control (On, Off, Power Cycle) by
individual outlets
Power-on sequencing – users can set the power on sequence and delay
time for each port to allow equipment to be turned on in the proper order
Easy setup and operation via a browser-based user interface Multibrowser support (IE, Mozilla, Firefox, Chrome, Safari, Opera,
Netscape)
RTC support to keep the timer running during times of no power. Up to 8 user accounts and 1 administrator account.
Chapter 1. Introduction
5
Management
Power status measurement at the PDU/Outlet level LED indicators for current and IP address at the PDU device and/or Outlet
levels.
Real-time current, voltage, and kWH displayed in a browsed-based UI for
monitoring at the PDU level (PE1108 / PE1208 / PE6108 / PE6208) and at the outlet level (PE3108 / PE3208 / PE8108 / PE8208)
Current and voltage threshold setting Naming support for outlets User outlet access assignment on an outlet-by-outlet basis. Event logging and syslog support Upgradeable firmware Multilanguage support: English, Traditional Chinese, Simplified Chinese,
Japanese, German, Italian, Spanish, French.
Security
Two-level password security Strong security features include strong password protection and advanced
encryption technologies – 128 bit SSL
Remote authentication support: RADIUS
6
Requirements
Browsers accessing the eco PDU unit must support SSL 128 bit
encryption.
For cold booting of attached computers, the computer's BIOS must
support Wake on LAN or System after AC Back.
For Safe Shutdown:
The computer must be running Windows (Windows 2000 or higher) or
Linux.
The Safe Shutdown program (available by download from our website
or on the software CD included), must be installed and running on the computer.
Chapter 1. Introduction
7
Optional Accessories
Sensors
Sensors are optional accessories. You can use the eco PDU unit without sensors. However, if you want to have complete energy management of an instrumented data center with the use of the eco PDU, you would need to use eco Sensors software and install 4 sensors for each of the racks to generate a complete energy-efficient data and chart. Higher sensor installation density is helpful to generate more accurate data. 8-port models have 2 sensor ports. In this case, Sensor 1 needs to be installed at the intake of the rack and sensor 2 needs to be placed at the exhaust of IT equipment of the rack. A sensor-enabled installation is required to generate a more complete energy-efficient data and chart. Higher sensor installation density is helpful to generate more accurate data. Available sensors are show in the table, below:
Sensor Management
Sensors can be managed via the eco PDU’s built-in graphical user interface (GUI) or with the ALTUSEN eco Sensors software that can be downloaded from the ATEN website. The download link can be found on the software CD provided with the eco PDU package.
Cable Holders
Cable holders are optional accessories. For added safety, use ATEN Lock­Your-Plug cable holders to secure the cables from your attached devices in place on the eco PDU unit. Use only the ATEN Lock-Your-Plug cable holders that have been specifically designed to work with the eco PDU. Using any other kind of cable securing device could be highly dangerous.
Sensor Part Number
Temperature EA1140
Temperature / Humidity EA1240
Differential Pressure / Temperature EA1340
Cable Holder Part Number
Lock-Your-Plug 0X12-0017-300G
8
Components
PE1108A / PE3108A Front View
PE1208A / PE3208A Front View
PE1108A / PE1208A / PE3108A / PE3208A Rear View
6
1
2
3
4
5
6
1
2
3
4
5
8
9
7
Chapter 1. Introduction
9
PE1108A / PE1208A / PE3108A / PE3208A Readout Section
No. Item Description
1 Circuit Breaker
Pushbutton
As a safety measure, if there is an overcurrent situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
2 Power Sockets
8 x NEMA 5-15R or 8 x NEMA 5-20R Note: Holes for ATEN Lock-Your-Plug cable holders are located
around the sockets. See Securing the Cables, page 19, for further information.
3 Readout Section
The selection (PDU Current / Outlet Current / IP Address) appears
in the first (1-digit) display window.
PDU Current / Outlet Current / IP Address appear in the second
(3-digit) display window
The LEDs above the items indicate which one the readout relates
to.
Press the button next to the first display window to cycle the
selection among the items.
4 Power LED
The LED lights when the eco PDU is powered up and ready to operate.
5 LAN Port and
LEDs
The cable that connects the eco PDU to the LAN plugs in here. The Link and LAN LEDs are built into the LAN port:
Link: Lights GREEN to indicate that a connection via the eco PDU's RJ-45 Ethernet port has been established. Flashes to indicate data is being transmitted.
LAN: Lights ORANGE to indicate 10 Mbps data transmission speed. The LED lights GREEN to indicate 100 Mbps data transmission speed.
6 Reset Switch
This switch is recessed and must be pushed with a thin object, such as the end of a paper clip.
Press and release to reboot the device.Press and hold for more that three seconds to reset the eco
PDU to its factory default settings
7 Grounding
Terminal
The wire used to ground the unit connects here.
8 Sensor Ports
External sensors plug into these two RJ-11 ports.
9 Power Socket
The power cord that connects the unit to an AC power source plugs in here.
3
SELECT
PDU
CURRENT
OUTLET
CURRENT
IP
ADDRESS
SENSOR
1
SENSOR
2
10
PE1108B / PE1108G / PE3108B / PE3108G Front View
PE1208B / PE1208G / PE3208B / PE3208G Front View
PE1108B / PE1108G / PE1208B / PE1208G / PE3108B / PE3108G / PE3208B / PE3208G Rear View
6
1
2
3
4
5
1
2
3
4
5
6
8
9
7
Chapter 1. Introduction
11
PE1108B / PE1108G / PE1208B / PE1208G / PE3108B / PE3108G / PE3208B / PE3208G Readout Section
No. Item Description
1 Circuit Breaker
Pushbutton
As a safety measure, if there is an overcurrent situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
2 Power Sockets
8 x IEC320 C13 or 7 x IEC320 C13 + 1 x C19 Note: Holes for ATEN Lock-Your-Plug cable holders are located
around the sockets. See Securing the Cables, page 19, for further information.
3 Readout Section
The selection (PDU Current / Outlet Current / IP Address) appears
in the first (1-digit) display window.
PDU Current / Outlet Current / IP Address appear in the second
(3-digit) display window
The LEDs above the items indicate which one the readout relates
to.
Press the button next to the first display window to cycle the
selection among the items.
4 Power LED
Lights when the unit is powered up and ready to operate.
5 LAN Port and
LEDs
The cable that connects the eco PDU to the LAN plugs in here. The Link and LAN LEDs are built into the LAN port:
Link: Lights GREEN to indicate that a connection via the eco PDU's RJ-45 Ethernet port has been established. Flashes to indicate data is being transmitted.
LAN: Lights ORANGE to indicate 10 Mbps data transmission speed. The LED lights GREEN to indicate 100 Mbps data transmission speed.
6 Reset Switch
This switch is recessed and must be pushed with a thin object, such as the end of a paper clip.
Press and release to reboot the device.Press and hold for more that three seconds to reset the eco
PDU to its factory default settings
7
Grounding Terminal The wire used to ground the unit connects here.
8 Sensor Ports
External sensors plug into these two RJ-11 ports.
9 Power Socket
The power cord that connects the unit to an AC power source plugs in here.
3
SELECT
PDU
CURRENT
OUTLET
CURRENT
IP
ADDRESS
SENSOR
1
SENSOR
2
12
PE6108A / PE8108A Front View
PE6208A / PE8208A Front View
PE6108A / PE6208A / PE8108A / PE8208A Rear View
6
1
2
3
4
5
6
1
2
3
4
5
8
9
7
Chapter 1. Introduction
13
PE6108A / PE6208A / PE8108A / PE8208A Readout Section
No. Item Description
1 Circuit Breaker
Pushbutton
As a safety measure, if there is an overcurrent situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
2 Power Sockets
8 x NEMA 5-15R or 8 x NEMA 5-20R Note: Holes for ATEN Lock-Your-Plug cable holders are located
around the sockets. See Securing the Cables, page 19, for further information.
3 Readout Section
The selection (PDU Current / Outlet Current / IP Address) appears
in the first (1-digit) display window.
PDU Current / Outlet Current / IP Address appear in the second
(3-digit) display window
The LEDs above the items indicate which one the readout relates
to.
Press the button next to the first display window to cycle the
selection among the items.
4 Power LED
The LED lights when the eco PDU is ready to operate.
5 LAN Port and
LEDs
The cable that connects the eco PDU to the LAN plugs in here. The Link and LAN LEDs are built into the LAN port:
Link: Lights GREEN to indicate that a connection via the eco PDU's RJ-45 Ethernet port has been established. Flashes to indicate data is being transmitted.
LAN: Lights ORANGE to indicate 10 Mbps data transmission speed. The LED lights GREEN to indicate 100 Mbps data transmission speed.
6 Reset Switch
This switch is recessed and must be pushed with a thin object, such as the end of a paper clip.
Press and release to reboot the device.Press and hold for more that three seconds to reset the eco
PDU to its factory default settings
7
Grounding Terminal The wire used to ground the unit connects here.
8 Sensor Ports
External sensors plug into these two RJ-11 ports.
9 Power Socket
The power cord that connects the unit to an AC power source plugs in here.
3
SELECT
PDU
CURRENT
OUTLET
CURRENT
IP
ADDRESS
SENSOR
1
SENSOR
2
OUTLET STATUS
14
PE6108B / PE6108G / PE8108B / PE8108G Front View
PE6208B / PE6208G / PE8208B / PE8208G Front View
PE6108B / PE6108G / PE6208B / PE6208G / PE8108B / PE8108G / PE8208B / PE8208G Rear View
6
1
2
3
4
5
6
1
2
3
4
5
8
9
7
Chapter 1. Introduction
15
PE6108B / PE6108G / PE6208B / PE6208G / PE8108B / PE8108G / PE8208B / PE8208G Readout Section
No. Item Description
1 Circuit Breaker
Pushbutton
As a safety measure, if there is an overcurrent situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
2 Power Sockets
8 x IEC320 C13 or 7 x IEC320 C13 + 1 x C19 Note: Holes for ATEN Lock-Your-Plug cable holders are located
around the sockets. See Securing the Cables, page 19, for further information.
3 Readout Section
The selection (PDU Current / Outlet Current / IP Address) appears
in the first (1-digit) display window.
PDU Current / Outlet Current / IP Address appear in the second
(3-digit) display window
The LEDs above the items indicate which one the readout relates
to.
Press the button next to the first display window to cycle the
selection among the items.
4 Power LED
Lights when the unit is powered up and ready to operate.
5 LAN Port and
LEDs
The cable that connects the eco PDU to the LAN plugs in here. The Link and LAN LEDs are built into the LAN port:
Link: Lights GREEN to indicate that a connection via the eco PDU's RJ-45 Ethernet port has been established. Flashes to indicate data is being transmitted.
LAN: Lights ORANGE to indicate 10 Mbps data transmission speed. The LED lights GREEN to indicate 100 Mbps data transmission speed.
6 Reset Switch
This switch is recessed and must be pushed with a thin object, such as the end of a paper clip.
Press and release to reboot the device.Press and hold for more that three seconds to reset the eco
PDU to its factory default settings
7
Grounding Terminal The wire used to ground the unit connects here.
8 Sensor Ports
External sensors plug into these two RJ-11 ports.
9 Power Socket
The power cord that connects the unit to an AC power source plugs in here.
3
SELECT
PDU
CURRENT
OUTLET
CURRENT
IP
ADDRESS
SENSOR
1
SENSOR
2
OUTLET STATUS
16
This Page Intentionally Left Blank
17
Chapter 2
Hardware Setup
Before You Begin
Rack Mounting
The eco PDU can be mounted in a 19” (1U) rack. To rack mount the device, use the rack mounting brackets that came with your device. The brackets can be screwed to the front or rear sides of the device, and then the unit can slide into the front of the rack, as shown in the diagram below:
1. Important safety information regarding the placement of this device is provided on page 55. Please review it before proceeding.
2. Make sure that power to all the devices you will be connecting have been turned off. You must unplug the power cords of any computers that have the Keyboard Power On function.
18
Installation
To set up your eco PDU installation, refer to the installation diagram on the next page (the numbers in the diagram correspond to the numbered steps), and do the following:
1. Use a grounding wire to ground the eco PDU by connecting one end of the wire to its grounding terminal, and the other end of the wire to a suitable grounded object.
Note: Do not omit this step. Proper grounding helps to prevent damage to
the unit from surges or static electricity.
2. For each device you want to connect, use its power cable to connect from the device's AC socket to any available outlet on the eco PDU.
3. Plug the cable that connects the eco PDU to the LAN into the eco PDU's LAN port.
4. If you are using sensors in your eco PDU installation, connect them to the sensor ports on the unit’s front panel.
Note: Sensors are optional. Please see Optional Accessories, page 7, and
the detailed sensor installation diagrams later in this chapter for further information.
5. Connect the eco PDU's power cord to an AC power source.
Note: We strongly advise that you do not plug the eco PDU into a multi
socket extension cord, since it may not receive enough amperage to operate correctly.
Once you have finished these installation steps, you can turn on the eco PDU and the connected devices.
Note: We strongly recommend using cable ties and cable bars to safely and
securely route the cables attached to the front of the unit.
Chapter 2. Hardware Setup
19
Securing the Cables
For added safety, use ATEN Lock-Your-Plug cable holders to secure the cables from your attached devices in place on the eco PDU unit. Secure the cable holders using the specially designed holes around the individual power outlets, as shown below:
Note: 1. Cable holders are an optional accessory. See Cable Holders, page 7.
2. Use only the ATEN Lock-Your-Plug cable holders that have been specifically designed to work with the eco PDU. Using any other kind of cable securing device could be highly dangerous.
1
3
2
4
5
20
Securing the Sensors
Connect the sensors to the eco PDU’s front panel sensor ports and secure them using sensor mounts, tie wraps, and adhesive cable tie holders. If you use a tie wrap to secure the sensor, tighten the tie wrap over the recessed channel on the sensor, as shown in the following diagram:
Note: 1. The sensors shown in the above diagram are for reference purposes
only. The sensors for the eco PDU may look slightly different.
2. Depending on the model and type of sensor, sensor mounts, tie wraps, and adhesive cable tie holders may or may not be provided in the package.
21
Chapter 3
Basic Operation and
First Time Setup
Operation Methods
ALTUSEN eco PDU models provide three methods to access and manage your installation: Browser, eco Sensors (eco PDU Management Software), and SNMP.
Note: The following sections of this chapter contain information concerning
Browser operation. For eco Sensors operation, please reference the separate eco Sensors User Manual. The eco Sensors software and User Manual can be downloaded from the ATEN website.
Browser
The eco PDU can be accessed and controlled via any supported Internet browser from any platform. See First Time Setup, page 22, and the following sections in this chapter, for full details.
eco Sensors
The eco PDU supports ALTUSEN eco Sensors (eco PDU Manager Software). ALTUSEN eco Sensors provides you with an easy method for managing multiple devices, offering an intuitive and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it. ALTUSEN eco Sensors can be downloaded from the ATEN website, along with a separate eco Sensors User Manual.
SNMP
The eco PDU supports any 3rd party V3 SNMP Manager Software. SNMP Management Information Database (MIB) files for the eco PDU device can be found on the software CD provided with the eco PDU package.
22
First Time Setup
Once the eco PDU installation has been cabled up, the next task the Administrator needs to perform involve configuring the network parameters, changing the default Super Administrator login settings, and adding users.
The easiest way to accomplish this is to log in over the Net with a browser.
Note: 1. Since this is the first time you are logging in, use the default
Username: administrator; and the default Password: password. For security purposes we recommend changing them to something unique (see Changing the Administrator Login, page 24).
2. For remote methods of getting logged in to the network, see IP Address Determination, page 59.
After you successfully log in, the eco PDU Outlet Access/Connections page appears:
Note: Operation details are discussed in Outlet Access, page 28, in the next
chapter. For further setup information, continue with this chapter
Chapter 3. Basic Operation and First Time
23
Network Configuration
To set up the network, do the following:
1. Click the Device Management tab.
2. The interface displays the Device Configuration page. A screen similar to the one below appears:
3. Fill in the fields according to the information provided under Device Configuration, page 36.
24
Changing the Administrator Login
To change the default Administrator username and password, do the following:
1. Click the User Management tab. The User Management page has a detailed list of users – with more
information about them – in the large central panel:
2. In the Administrator Information section, reset the name and password fields to something unique, then click Save (at the bottom of the page.)
Note: If you forget the Administrator’s name or password, short the
mainboard jumper to restore the default Administrator account. See see Administrator Login Failure, page 67 in the Appendix for full details.
Moving On
After setting up the network and changing the default Administrator username and password, you can proceed to other administration activities – including adding users. This is covered in the next chapter.
25
Chapter 4
Browser Operation
Logging In
The eco PDU can be accessed via a supported Internet browser from any platform.
Note: Browsers must support SSL 128 bit encryption.
To access the eco PDU do the following:
1. Open your browser and specify the IP address of the eco PDU you want to
access in the browser's URL location bar.
Note: You can get the IP address from the eco PDU administrator, or see
IP Address Determination, page 59, for information about setting it up yourself.
2. If a Security Alert dialog box appears, accept the certificate – it can be
trusted. The Login page appears:
3. Provide a valid Username and Password (set by the eco PDU
administrator), and select your language. (Options are: English [default]; Traditional Chinese; Simplified Chinese; Japanese; German; Italian; Spanish; French).
4. Then Click Login to bring up the browser Main Page.
26
The eco PDU Main Page
After you have successfully logged in, the eco PDU Main Page comes up with the Outlet Access Connections page displayed:
Note: The screen depicts an Administrator’s page. Depending on a user’s type
and permissions, not all of these elements appear.
Chapter 4. Browser Operation
27
Page Components
The web page screen components are described in the table, below:
No. Item Description
1 Tab Bar The tab bar contains the eco PDU’s main operation
categories. The items that appear in the tab bar are determined by the user’s type, and the authorization options that were selected when the user’s account was created.
2 Menu Bar The menu bar contains operational sub-categories
that pertain to the item selected in the tab bar. The items that appear in the menu bar are determined by the user’s type, and the authorization options that were selected when the user’s account was created.
3 Sidebar The Sidebar provides a tree view listing of outlets
that relate to the various tab bar and menu bar selections.
4 Help Connects to on-line help at the ATEN website for the
device’s configuration and operation.
5 Logout Click this button to log out of your eco PDU session.
6 Interactive Display Panel This is your main work area. The screens that
appear reflect your menu choices and Sidebar node selection.
28
Outlet Access
Connections
When you log in to the eco PDU, the interface opens with its default selection of the Outlet Access tab; and the Connections menu. The contents of the PDU
Status and Outlet Status sections are displayed in the main panel.
Note: Only enabled eco PDU models will display the Outlet Status submenu
section. Other models provide only PDU Status monitoring. See PE Series eco PDU Comparison Chart, page 3, for which models support
PDU and Outlet Status or PDU Status only monitoring.
Chapter 4. Browser Operation
29
PDU Status
All eco PDU models support PDU device level monitoring. The PDU Status section allows you to set up a power management configuration for the PDU device as a whole:
PDU Threshold Settings
These fields are used to set the maximum, minimum, and fluctuation threshold settings for Current, Voltage, Power, and Power Dissipation. If a range falls below the minimum setting, or exceeds the maximum setting an alarm is triggered.
On / Off / Reboot
You can manually turn the device On and Off from this page by clicking the radio buttons. To Reboot the device, enable the Reboot checkbox and click on Save (located at the bottom of the page).
Sensor 1 / Sensor 2
If you have sensors installed in your installation, use these fields to set the maximum, minimum, and fluctuation threshold settings for Temperature, Humidity, and Differential Pressure.
Note: Sensors are optional accessories. Check with your dealer for
information about ALTUSEN eco Sensors software.
30
Outlet Status
If your eco PDU models supports outlet level monitoring, the main panel Outlet Status section allows you to set up a power management configuration for each outlet at an individual level.
Outlet Threshold Settings
These fields are used to set the maximum, minimum, and fluctuation threshold settings for Current, Voltage, Power, and Power Dissipation. If a range falls below the minimum setting, or exceeds the maximum setting an alarm is triggered.
On / Off / Reboot
You can manually turn the outlet On and Off from this page by clicking the radio buttons. To Reboot the outlet, enable the Reboot checkbox and click on Save (located at the bottom of the page).
Chapter 4. Browser Operation
31
Configuration
The Configuration page is used to configure the settings of the eco PDU at the individual power outlet level:
This page lets you set up the power management configuration for the selected outlet. The meanings of the field headings are given in the following table
:
(Continues on next page.)
Heading Meaning
Outlet Name Each outlet can be given a distinctive name. The maximum number
of characters is 15.
Confirmation Required
If this option is enabled (there is a check in the checkbox), a dialog box comes up asking you to confirm a power operation before it is performed. If it is disabled (there is no check in the checkbox), the operation is performed without confirmation.
32
(Continued from previous page.)
When you have finished making your configuration settings, click Save.
Power ON Delay Sets the amount of time the eco PDU waits after the Power Button
is clicked (see Outlet Status, page 30), before it turns on the power to the outlet.
Note: The default delay time is 0 seconds; the maximum is 999 seconds. When a series of outlets are scheduled to be powered up, they turn on in sequence with a default delay of 10 milliseconds between each outlet.
Power OFF Delay Sets the amount of time the eco PDU waits after the Power Button
is clicked (see Outlet Status, page 30), before it turns off the power to the outlet.
For the System after AC Back option (see below), after the delay time expires, the eco PDU waits another fifteen seconds, then shuts the computer down.
The default delay time is 15 seconds. The maximum delay time is 999 seconds.
Remote Turn ON Method
Use the drop-down menu to select one of the choices, below:
Wake on LAN: This is a Safe Shutdown and Restart option. If this
is selected, when an Outlet is turned Off, the eco PDU first sends a message to the computer telling it to prepare for a shutdown; it then waits for the amount time set in the Power Off Delay field to give the OS time to close down before the computer is powered down to standby mode.
Likewise, when the Outlet is turned On, the eco PDU waits for the amount time set in the Power On Delay field, then sends an Ethernet message to the computer connected to the Outlet telling the computer to turn itself On.
Note: For Safe Shutdown and Restart, the computer must be running Windows (98 or higher), or Linux, and the Safe Shutdown program (available by download from our website), must be installed and running on the computer.
System after AC Back: This is a Safe Shutdown and Restart
option. If this is selected, when an Outlet is turned Off, the eco PDU first sends a message to the computer telling it to prepare for a shutdown; it then waits for the amount time set in the Power Off Delay field to give the OS time to close down before the computer is powered down.
When the Outlet is turned On, the eco PDU waits for the amount time set in the Power On Delay field, then sends power to the server. When the server receives the power, it turns itself on.
Note: For Safe Shutdown and Reboot, the computer must be running Windows (98 or higher), or Linux, and the Safe Shutdown program (available by download from our website), must be installed and running on the computer.
Kill the Power: If this option is selected, the eco PFDU waits for
the amount time set in the Power Off Delay field, and then turns the Outlet's power Off. Turning the power off performs a cold (non-safe) shutdown.
MAC Address In order to use either of the Safe Shutdown and Restart methods
the MAC address of the computer connected to the outlet must be filled in here.
Chapter 4. Browser Operation
33
User Management
When you select the User Management tab the screen comes up with Administrator Information and User Information displayed in the main panel.
The eco PDU supports one Administrator account and up to eight User accounts.
Note: 1. Each account can support 2 login sessions
2. The eco PDU supports a total of 9 concurrent login sessions.
Administrator Information
This section is used to set the Administrator name and password. Only Administrators can view this section. For details, see Changing the Administrator Login, page 24.
User Information
To add a user, do the following:
1. Select the user type in the Management drop-down menu.
2. Key in a name and password in the Name and Password fields.
3. Set the outlet-by-outlet permissions of the user in the Outlet field.
4. Set the Management field to Enable.
5. Click Save to save your settings.
Note: Values must be entered in both the Name and Password fields in
order to enable an account.
34
The various options are explained in more detail in the following table:
Field Description
Management The Management field allows you to Enable or Disable a
user’s account:
Enable – stores the user account (see User Information,
page 33
Disable – disables the user account
Name From 1 to 16 characters are allowed depending on the
Account Policy settings. See Account Policy, page 45.
Password From 1 to 16 characters are allowed depending on the
Account Policy settings. See Account Policy, page 45.
Outlet This field allows you to set the outlet-by-outlet permissions of
the user. Click on the user/port icon to cycle through the three permissions options, as follows:
User has complete access to this outlet.
User has read-only access to this outlet.
User has no access to this outlet.
Save Click this button to save your operation or changes
Chapter 4. Browser Operation
35
Log
The eco PDU keeps a record of transactions that take place on its installation, and stores up to 128 events at one time. The System Log page provides a powerful array of filters and functions that allow you to view and export the log file data, as well as be informed by email of specified events as they occur.
The System Log Event List
Clicking on a device in the Sidebar displays its log events in the main
panel’s log event list.
Clicking the Refresh button brings the log list up to date with the latest
events.
The entry box to the right of the Refresh button lets you set the number of
events to display per page. Simply key in the number of your choice.
The top right of the main panel shows the total number of pages in the log
file, and what page you are currently viewing.
The buttons on the bottom row function as follows:
Clear – click to erase the contents of the log event list First Page – click to go to the first page of the log event list Previous Page – click to move to the previous page of the log event
list
Next Page – click to move to the next page of the log event list Last Page – click to move to the last page of the log event list Export Log – click to save the contents of the log event list to file.
36
Device Management
The Device Management page allows super administrators, administrators, and users with device management permission to configure and control overall eco PDU operations.
Device Configuration
This page presents information about the selected device, as described in the following sections:
General
Item Meaning
PDU Name This field lets you give the device a unique name. Simply delete
whatever is in the text box and key in the name of your choice. Click Save (located at the bottom of the page) to save the new name.
MAC Address This item displays the eco PDU’s MAC address.
Firmware Version This item displays the current firmware version number. You can
reference it to see if there are newer versions available on the ALTUSEN website.
Rack Location Name
This field lets you give the rack location a unique name for easy reference.
Chapter 4. Browser Operation
37
Service Ports
As a security measure, if a firewall is being used, the Administrator can specify the port numbers that the firewall will allow. If a port other than the default is used, users must specify the port number as part of the IP address when they log in. If an invalid port number (or no port number) is specified, the eco PDU will not be found.
An explanation of the fields is given in the table below:
Note: 1. Valid entries for all of the Service Ports are from 1–65535.
2. The service ports cannot have the same value. You must set a different value for each one.
3. If there is no firewall (on an Intranet, for example), it doesn’t matter what these numbers are set to, since they have no effect.
Field Explanation
HTTP The port number for a browser login. The default is 80.
HTTPS The port number for a secure browser login. The default is 443.
38
IPv4 Configuration
The PDU’s IPv4 IP and DNS addresses (the traditional method of specifying IP addresses) can either be assigned dynamically (DHCP), or a fixed IP address can be specified.
For dynamic IP address assignment, select the Obtain IP address
automatically radio button. (This is the default setting.)
To specify a fixed IP address, select the Set IP address manually radio
button and fill in the IP address with values appropriate for your network.
For automatic DNS Server address assignment, select the Obtain DNS
Server address automatically radio button.
To specify the DNS Server address manually, select the Set DNS server
address manually radio button, and fill in the addresses for the Preferred
and Alternate DNS servers with values appropriate for your network.
Note: 1. If you choose Obtain IP address automatically, when the device starts
up it waits to get its IP address from the DHCP server. If it hasn’t obtained the address after one minute, it automatically reverts to its factory default IP address (192.168.0.60.)
2. If the device is on a network that uses DHCP to assign network addresses, and you need to ascertain its IP address, see IP Address Determination, page 59, for information.
3. Specifying the Alternate DNS Server address is optional.
Chapter 4. Browser Operation
39
Event Notification
The Event Notification section is divided into three sections: SMTP Settings; SNMP Trap Receivers; and Syslog Server. Each section is described below.
SMTP Settings
To have the eco PDU device email reports from the SMTP server to you, do the following:
1. Enable the Enable report from the following SMTP server, and key in the IP address of your SMTP server.
2. If your server requires authentication, put a check in the My server requires authentication checkbox.
3. Key in the appropriate account information in the Account Name, Password, and From fields.
Note: Only one email address is allowed in the From fields, and it cannot
exceed 64 characters.)
4. Key in the email address (addresses) of where you want the event reports sent to in the To field.
Note: If you are sending the report to more than one email address,
separate the addresses with a semicolon. The total cannot exceed 256 characters.
40
SNMP Trap Receivers
Up to four SNMP management stations can be specified. If you want to use SNMP trap notifications, do the following:
1. Check Enable SNMP Trap.
2. Key in the IP address(es) and the service port number(s) of the computer(s) to be notified of SNMP trap events. The valid port range is 1–65535. The default port number is 162.
Note: Make sure that the port number you specify here matches the port
number used by the SNMP receiver computer.
3. Key in the privacy password(s) that correspond to each of the stations.
Chapter 4. Browser Operation
41
Syslog Server
To record all the events that take place on eco PDU devices and write them to the eco PDU Syslog server, do the following:
1. Check Enable Syslog Server.
2. Key in the IP address and the port number of the Syslog server. The valid
port range is 1-65535. The default port number is 514.
42
Date/Time
The Date/Time dialog page sets the eco PDU time parameters:
Set the parameters according to the information described below.
Time Zone
To establish the time zone that the eco PDU is located in, drop down the
Time Zone list and choose the city that most closely corresponds to where it is at.
If your country or region employs Daylight Saving Time (Summer Time),
check the corresponding checkbox.
Chapter 4. Browser Operation
43
Manual Input
Use this section to specify the eco PDU ’s date and time manually.
Click the calendar icon and click the calendar entry for the date. Key the time into the Time field, using the HH:MM:SS (hours, minutes,
seconds) format.
Note: This section is only enabled when auto adjustment (in the Network Time
section) is disabled (the checkbox is unchecked).
As an alternative to specifying the date and time by entering them into the date and time fields, you can click to put a check in the Sync with PC checkbox, in which case the eco PDU will take its date and time settings from the locally connected PC.
Network Time
To have the time automatically synchronized to a network time server, do the following:
1. Check the Enable auto adjustment checkbox.
2. Drop down the time server list to select your preferred time server
– or –
Check the Preferred custom server IP checkbox, and key in the IP address of the time server of your choice.
3. If you want to configure an alternate time server, check the Alternate time
server checkbox, and repeat step 2 for the alternate time server entries.
4. Key in your choice for the number of days between synchronization
procedures.
Finishing Up
When you have finished making your settings on this page, click Save.
After you have saved your changes, if you want to synchronize immediately, click Adjust Time Now.
44
Security
The Security page controls access to the eco PDU device.
Login Failures
Allowed sets the number of consecutive failed login attempts that are
permitted from a remote user.
Timeout sets the amount of time a remote user must wait before
attempting to login again after exceeding the number of allowed failures.
Working Mode
If ICMP is enabled, the eco PDU device can be pinged. If it is not
enabled, the device cannot be pinged. The default is Enabled.
When you have finished making your settings on this page, click Save.
Chapter 4. Browser Operation
45
Account Policy
The Account Policy section governs policies in regard to usernames and passwords.
Check a policy and enter the required information in the appropriate fields.
Item Description
Minimum Username Length Sets the minimum number of characters required for
a username. Acceptable values are from 1–16.
Minimum Password Length Sets the minimum number of characters required for
a password. Acceptable values are from 1–16.
Password Must Contain At Least Checking any of these items requires users to include
at least one of the specified items in their password.
Note: This policy does not affect existing user accounts. Only new user accounts created after this policy has been enabled, and users required to change their passwords are affected.
Disable Duplicate Login Check this to prevent users from logging in with the
same account at the same time.
46
Login String / IP Filter / Mac Filter
Login String
The Login String entry field is used to specify a login string (in addition to the IP address) that users must include when accessing the eco PDU device with a browser. For example:
192.168.0.126/abcdefg
The following characters are allowed:
0–9 a–z A–Z ~ ! @ $ * ( ) _ ‘ ,
The following characters are not allowed:
& ^ { } ‘ ’ < > | " % ” : / ? # \ [Space] + - = [ ] ;
Compound characters (É Ç ñ ... etc.)
Note: 1. There must be a forward slash between the IP address and the string.
2. If no login string is specified here, anyone will be able to access the eco PDU device login page using the IP address alone. This makes your installation less secure.
For security purposes, we recommend that you change this string occasionally.
Chapter 4. Browser Operation
47
IP Filter / MAC Filter
If any filters have been configured, they appear in the IP Filter and/or MAC Filter list boxes.
IP and MAC Filters control access to the eco PDU based on the IP and/or MAC addresses of the client computers attempting to connect. A maximum of 5 IP filters and 5 MAC filters are allowed.
To enable IP and/or MAC filtering, click to put a check mark in the IP Filter Enable and/or MAC Filter Enable checkbox.
If the include button is checked, all the addresses within the filter range are
allowed access; all other addresses are denied access.
If the exclude button is checked, all the addresses within the filter range
are denied access; all other addresses are allowed access.
Adding Filters
To add an IP filter, do the following:
1. Click Add. A dialog box similar to the one below appears:
2. Specify the filter address in the dialog box (for example, 192.168.0.200), then click OK.
A second dialog box, similar to the one below, appears:
48
3. To filter a single IP address, key in the same address as the start IP. To filter a continuous range of addresses, key in the end number of the range (for example, 192.168.0.225).
4. After filling in the address, click OK.
Repeat these steps for any additional IP addresses you want to filter.
To add a MAC filter, do the following:
1. Click Add. A dialog box similar to the one below appears:
2. Specify the MAC address in the dialog box (for example, 001074670000), then click OK.
Repeat these steps for any additional MAC addresses you want to filter.
IP Filter / MAC Filter Conflict
If there is a conflict between an IP filter and a MAC filter – for example, where a computer’s IP address is allowed by the IP filter but its MAC address is excluded by the MAC filter – then that computer’s access is blocked.
In other words, if either filter blocks a computer, then the computer is blocked, no matter what the other filter is set to.
Modifying Filters
To modify a filter, select it in the IP Filter or MAC Filter list box and click Modify. The Modify dialog box is similar to the Add dialog box. When it comes up, simply delete the old address(es) and replace it with the new one(s).
Deleting Filters
To delete a filter, select it in the IP Filter or MAC Filter list box and click Delete.
Chapter 4. Browser Operation
49
Authentication & Authorization
The Authentication & Authorization page is used to set up login authentication and authorization management from external sources.
Disable Local Authentication
Selecting this option will disable login authentication locally on the eco PDU. The device can only be accessed using RADIUS authentication.
50
RADIUS Settings
To allow authentication and authorization for the eco PDU device through a RADIUS server, do the following:
1. Check Enable.
2. Fill in the IP addresses and service port numbers for the Preferred and Alternate RADIUS servers. The default port number for the Preferred server is 1812; the default port number for the Alternate server is 1645.
Note: Make sure that the port numbers you specify here match the port
numbers used by the RADIUS servers.
3. In the Timeout field, set the time in seconds that the eco PDU device waits for a RADIUS server reply before it times out.
4. In the Retries field, set the number of allowed retries for attempting to connect to the RADIUS server.
5. In the Shared Secret field, key in the character string that you want to use for authentication between the eco PDU device and the RADIUS Server.
6. On the RADIUS server, set the entry for each user as follows:
su/administrator or su/user
Where xxxx represents the Username given to the user when the account was created on the eco PDU device. The user’s access rights are the ones assigned for the eco PDU device, as well. (See User Information, page 33.)
Note: su/user supports view ports only; su/administrator supports all eco PDU
functions.
Chapter 4. Browser Operation
51
Private Certificate
When logging in over a secure (SSL) connection, a signed certificate is used to verify that the user is logging in to the intended site. For enhanced security, the Private Certificate section allows you to use your own private encryption key and signed certificate, rather than the default ATEN certificate.
There are two methods for establishing your private certificate: generating a self-signed certificate; and importing a third-party certificate authority (CA) signed certificate.
Generating a Self-Signed Certificate
If you wish to create your own self-signed certificate, a free utility – openssl.exe – is available for download over the web.
Obtaining a CA Signed SSL Server Certificate
For the greatest security, we recommend using a third party certificate authority (CA) signed certificate. To obtain a third party signed certificate, go to a CA (Certificate Authority) website to apply for an SSL certificate. After the CA sends you the certificate and private encryption key, save them to a convenient location on your computer.
Importing the Private Certificate
To import the private certificate, do the following:
1. Click Browse to the right of Private Key; browse to where your private
encryption key file is located; and select it.
2. Click Browse to the right of Certificate; browse to where your certificate
file is located; and select it.
3. Click Upload to complete the procedure.
Note: 1. Clicking Restore Default returns the device to using the default
ATEN certificate.
2. Both the private encryption key and the signed certificate must be imported at the same time.
When you have finished making your settings on this page, click Save.
52
Maintenance
The Maintenance function is used to upgrade the eco PDU’s firmware, and to backup and restore the device’s configuration settings.
Firmware File
When you click the Maintenance tab, the display opens with the Firmware Upgrade menu page, which looks similar to the one below:
A description of the items shown in this panel are given in the table, below:
Item Description
Check Main Firmware Version
If you enable Check Main Firmware Version, the eco PDU’s current firmware level is compared with that of the upgrade file. If the current version is equal to or higher than the upgrade version, a popup message appears, to inform you of the situation and stops the upgrade procedure.
Name
Lists all of the
eco PDU devices. Click to put a check in the
checkbox of the device’s whose firmware you want to upgrade.
F/W Version Displays the eco PDU’s current firmware version.
Filename As new versions of the firmware become available, they are
posted on our website and can be downloaded to a convenient location on your computer. Click the Browse button to select the downloaded upgrade file.
Upgrade Click this button to upgrade the firmware of the selected devices.
Chapter 4. Browser Operation
53
Upgrading the Firmware
To upgrade the firmware refer to the screenshot on the preceding page, and do the following:
1. Go to our website and download the new firmware file to a convenient location on your computer.
2. Click the Browse button; navigate to where the firmware file is located and select it.
3. Click Upgrade to start the upgrade procedure. If you enabled Check Main Firmware Version the current firmware
level is compared with that of the upgrade file. If the current version is equal to or higher than the upgrade version, a popup message appears, to inform you of the situation and stops the upgrade procedure.
If you didn't enable Check Main Firmware Version, the upgrade file is
installed without checking what its level is.
Once the upgrade completes successfully, the switch resets itself.
4. Log in again, and check the firmware version to be sure it is the new one.
Firmware Upgrade Recovery
Should the eco PDU’s firmware upgrade procedure fail, and the device becomes unusable, the following firmware upgrade recovery procedure will resolve the problem:
1. Power off the device.
2. Press and hold the Reset Switch in (see page 9).
3. While holding the Reset Switch in, power the switch back on.
This causes the switch to use the original factory installed main firmware version. Once the switch is operational, you can try upgrading the main firmware again.
54
Backup/Restore
Selecting Backup/Restore on the menu bar gives you the ability to back up the switch’s configuration and user profile information:
Backup
To backup the device’s settings do the following:
1. In the Password field, key in a password for the file.
Note: Entering a password is optional. If you do enter a password, make a
note of it, since you will need it to be able to restore the file.
2. Click Save.
3. When the browser asks what you want to do with the file, select Save to disk; then save it in a convenient location.
Restore
To restore a previous backup, do the following:
1. Click Browse; navigate to the file and select it.
Note: If you renamed the file, you can leave the new name. There is no
need to return it to its original name.
2. In the Password field, key in the same password that you used to save the file.
Note: If you did not set a password when you created the backup file, you
can omit this step.
3. Select as many of the options that are presented as you wish to restore.
4. Click Restore. After the file is restored, a message appears to inform you that the
procedure succeeded.
55
Appendix
Safety Instructions
General
Read all of these instructions. Save them for future reference. Follow all warnings and instructions marked on the device. Do not place the device on any unstable surface (cart, stand, table, etc.). If
the device falls, serious damage will result.
Do not use the device near water. Do not place the device near, or over, radiators or heat registers. The device cabinet is provided with slots and openings to allow for
adequate ventilation. To ensure reliable operation, and to protect against overheating, these openings must never be blocked or covered.
The device should never be placed on a soft surface (bed, sofa, rug, etc.) as
this will block its ventilation openings. Likewise, the device should not be placed in a built in enclosure unless adequate ventilation has been provided.
Never spill liquid of any kind on the device. Unplug the device from the wall outlet before cleaning. Do not use liquid
or aerosol cleaners. Use a damp cloth for cleaning.
The device should be operated from the type of power source indicated on
the marking label. If you are not sure of the type of power available, consult your dealer or local power company.
To prevent damage to your installation it is important that all devices are
properly grounded.
The device is equipped with a 3-wire grounding type plug. This is a safety
feature. If you are unable to insert the plug into the outlet, contact your electrician to replace your obsolete outlet. Do not attempt to defeat the purpose of the grounding-type plug. Always follow your local/national wiring codes.
The equipment should be installed near the wall socket outlet and the
disconnect device (appliance coupler) should be readily accessible.
Do not allow anything to rest on the power cord or cables. Route the
power cord and cables so that they cannot be stepped on or tripped over.
56
To help protect your system from sudden, transient increases and
decreases in electrical power, use a surge suppressor, line conditioner, or uninterruptible power supply (UPS).
Position system cables and power cables carefully; Be sure that nothing
rests on any cables.
When connecting or disconnecting power to hot pluggable power supplies,
observe the following guidelines: Install the power supply before connecting the power cable to the
power supply.
Unplug the power cable before removing the power supply. If the system has multiple sources of power, disconnect power from the
system by unplugging all power cables from the power supplies.
Never push objects of any kind into or through cabinet slots. They may
touch dangerous voltage points or short out parts resulting in a risk of fire or electrical shock.
Do not attempt to service the device yourself. Refer all servicing to
qualified service personnel.
If the following conditions occur, unplug the device from the wall outlet
and bring it to qualified service personnel for repair.
The power cord or plug has become damaged or frayed. Liquid has been spilled into the device. The device has been exposed to rain or water. The device has been dropped, or the cabinet has been damaged. The device exhibits a distinct change in performance, indicating a need
for service.
The device does not operate normally when the operating instructions
are followed.
Only adjust those controls that are covered in the operating instructions.
Improper adjustment of other controls may result in damage that will require extensive work by a qualified technician to repair.
Do not connect the RJ-11 connector marked “Sensor” to a public
telecommunication network.
Appendix
57
Rack Mounting
Before working on the rack, make sure that the stabilizers are secured to
the rack, extended to the floor, and that the full weight of the rack rests on the floor. Install front and side stabilizers on a single rack or front stabilizers for joined multiple racks before working on the rack.
Always load the rack from the bottom up, and load the heaviest item in the
rack first.
Make sure that the rack is level and stable before extending a device from
the rack.
Use caution when pressing the device rail release latches and sliding a
device into or out of a rack; the slide rails can pinch your fingers.
After a device is inserted into the rack, carefully extend the rail into a
locking position, and then slide the device into the rack.
Do not overload the AC supply branch circuit that provides power to the
rack. The total rack load should not exceed 80 percent of the branch circuit rating.
Make sure that all equipment used on the rack – including power strips and
other electrical connectors – is properly grounded.
Ensure that proper airflow is provided to devices in the rack. Ensure that the operating ambient temperature of the rack environment
does not exceed the maximum ambient temperature specified for the equipment by the manufacturer
Do not step on or stand on any device when servicing other devices in a
rack.
The eco PDU’s Main Power Cord
Use the power cord supplied with this package. If it becomes necessary to replace the cord supplied with this package, be sure to use a cord of at least the same standard as the one provided.
Securing the Power Cables
To secure the cables in the eco PDU’s power outlets, use only the
ATEN Lock-Your-Plug cable holders that have been specifically designed to work with the eco PDU. Using any other kind of cable securing device could be highly dangerous. Please contact your ATEN dealer for information about ATEN Lock-Your-Plugs.
58
Technical Support
International
For online technical support – including troubleshooting, documentation,
and software updates: http://support.aten.com
For telephone support, see Telephone Support, page iii
North America
When you contact us, please have the following information ready beforehand:
Product model number, serial number, and date of purchase. Your computer configuration, including operating system, revision level,
expansion cards, and software.
Any error messages displayed at the time the error occurred. The sequence of operations that led up to the error. Any other information you feel may be of help.
Email Support support@aten-usa.com
Online Technical Support
Troubleshooting Documentation Software Updates
http://www.aten-usa.com/support
Telephone Support 1-888-999-ATEN ext 4988
Appendix
59
IP Address Determination
If you are an administrator logging in for the first time, you need to access the eco PDU in order to give it an IP address that users can connect to. There are two methods to choose from. In each case, your client computer must be on the same network segment as the eco PDU. After you have connected and logged in you can give the device its fixed network address. (See Device Management, page 36.)
Method 1:
For computers running Windows, an IP address can be determined and/or assigned with the IP Installer utility. The utility can be obtained from the
Download area of our web site or from the software CD. Look under Driver/ SW, and the model of your device. After downloading the utility to your
computer, do the following:
1. Unzip the contents of IPInstaller.zip to a directory on your hard drive.
2. Go to the directory that you unzipped the IPInstaller program to and run
IPInstaller.exe. A dialog box similar to the one below appears:
(Continues on next page.)
60
(Continued from previous page.)
3. Select the device in the Device List.
Note: 1. If the list is empty, or your device doesn't appear, click
Enumerate to refresh the Device List.
2. If there is more than one device in the list, use the MAC address to pick the one you want. The eco PDU's MAC address is located on its bottom panel.
4. Select either Obtain an IP address automatically (DHCP), or Specify an IP address. If you chose the latter, fill the IP Address, Subnet Mask, and Gateway fields with the information appropriate to your network.
5. Click Set IP.
6. After the IP address shows up in the Device List, click Exit to end the program.
Method 2:
1. Set your computer's IP address to 192.168.0.XXX
Where XXX represents any number or numbers except 60. (192.168.0.60) is the default address of the eco PDU.)
2. Specify the device’s default IP address (192.168.0.60) in your browser, and you will be able to connect.
3. Assign a fixed IP address for the device (see IPv4 Configuration, page 38), that is suitable for the network segment that it resides on.
4. After you log out, reset your computer's IP address to its original value.
5. Once you have logged in, go to Network Settings to set up the permanent IP environment (see IPv4 Configuration, page 38).
Method 3:
ALTUSEN eco Sensors allows you to determine/assign an IP address in order to configure a PDU device and monitor power status of the equipment connected to it. ALTUSEN eco Sensors can be obtained from the Download area of the ATEN web site.
Appendix
61
Specifications
PE1108A / PE1208A / PE3108A / PE3208A
Function PE1108A / PE3108A PE1208A / PE3208A
Power Outlets Direct 8
Connectors Power Inlet 1 x IEC 320 C20
Power
Outlets
NEMA 8 x NEMA 5-15R 8 x NEMA 5-20R
IEC NA
Sensor 2 x RJ-11
LAN 1 x RJ-45 (F)
LEDs Outlet Status NA
Selection 1-digit 7-segment (Orange)
PDU Current / Outlet
Current / IP Address
3 (Green)
Current / IP Address 3-digit 7-segment (Orange)
Power 1 (Blue)
LAN 10/100M 1 (Orange / Green)
Link 1 (Green)
Sensor 2 (Green)
Switches Reset 1 x Semi-recessed Pushbutton
Power 1 x Non-fuse Breaker
I/P Rating 100–120V~; 50/60Hz; 12A 100–120V~; 50/60Hz; 16A
Load Capacity 1440W 1920W
O/P Rating Per Port 100–120V~; 50/60Hz; 12A 100–120V~; 50/60Hz; 16A
Total 100–120V~; 50/60Hz; 12A 100–120V~; 50/60Hz; 16A
Environment Operating Temperature
0–50
o
C
Storage Temperature
-20–60
o
C
Humidity 0–80% RH Non-condensing
Physical
Properties
Housing Metal
Weight 2.63 kg / 2.68 kg 2.64 kg / 2.69 kg
Dimensions (L x W x H) 43.24 x 21.93 x 4.40 cm
62
PE1108B / PE1208B / PE3108B / PE3208B
Function PE1108B / PE3108B PE1208B / PE3208B
Power Outlets Direct 8
Connectors Power Inlet 1 x IEC 320 C20
Power
Outlets
NEMA NA
IEC 8 x IEC 320 C13 7 x IEC 320 C13 (Ports 2–8);
1 x C19 (Port 1)
Sensor 2 x RJ-11
LAN 1 x RJ-45 (F)
LEDs Outlet Status NA
Selection 1-digit 7-segment (Orange)
PDU Current / Outlet
Current / IP Address
3 (Green)
Current / IP Address 3-digit 7-segment (Orange)
Power 1 (Blue)
LAN 10/100M 1 (Orange / Green)
Link 1 (Green)
Sensor 2 (Green)
Switches Reset 1 x Semi-recessed Pushbutton
Power 1 x Non-fuse Breaker
I/P Rating 100–240V~; 50/60Hz; 12A 100–240V~; 50/60Hz; 16A
Load Capacity 2880W 3840W
O/P Rating Per
Port
C13 100-240V~; 50/60Hz, 12A
C19 NA 100-240V~; 50/60Hz, 16A
Total 100-240V~; 50/60Hz, 12A 100-240V~; 50/60Hz, 16A
Environment Operating Temp.
0–50
o
C
Storage Temp.
-20–60
o
C
Humidity 0–80% RH Non-condensing
Physical
Properties
Housing Metal
Weight 2.70 kg / 2.73 kg 2.71 kg / 2.74 kg
Dimensions
(L x W x H) 43.24 x 21.93 x 4.40 cm
Appendix
63
PE1108G / PE1208G / PE3108G / PE3208G
Function PE1108G / PE3108G PE1208G / PE3208G
Power Outlets Direct 8
Connectors Power Inlet 1 x IEC 320 C20
Power
Outlets
NEMA NA
IEC 8 x IEC 320 C13 7 x IEC 320 C13 (Ports 2–8);
1 x C19 (Port 1)
Sensor 2 x RJ-11
LAN 1 x RJ-45 (F)
LEDs Outlet Status NA
Selection 1-digit 7-segment (Orange)
PDU Current / Outlet
Current / IP Address
3 (Green)
Current / IP Address 3-digit 7-segment (Orange)
Power 1 (Blue)
LAN 10/100M 1 (Orange / Green)
Link 1 (Green)
Sensor 2 (Green)
Switches Reset 1 x Semi-recessed Pushbutton
Power 1 x Non-fuse Breaker
I/P Rating 100–240V~; 50/60Hz; 10A 100–240V~; 50/60Hz; 16A
Load Capacity 2400W 3840W
O/P Rating Per
Port
C13 100-240V; 50/60Hz, 10A
C19 NA 100-240V~; 50/60Hz, 16A
Total 100-240V~; 50/60Hz, 10A 100-240V~; 50/60Hz, 16A
Environment Operating Temp.
0–50
o
C
Storage Temp.
-20–60
o
C
Humidity 0–80% RH Non-condensing
Physical
Properties
Housing Metal
Weight 2.70 kg / 2.72 kg 2.71 kg / 2.74 kg
Dimensions
(L x W x H) 43.24 x 21.93 x 4.40 cm
64
PE6108A / PE6208A / PE8108A / PE8208A
Function PE6108A / PE8108A PE6208A / PE8208A
Power Outlets Direct 8
Connectors Power Inlet 1 x IEC 320 C20
Power
Outlets
NEMA 8 x NEMA 5-15R 8 x NEMA 5-20R
IEC NA
Sensor 2 x RJ-11
LAN 1 x RJ-45 (F)
LEDs Outlet Status 8 (Orange)
Selection 1-digit 7-segment (Orange)
PDU Current / Outlet
Current / IP Address
3 (Green)
Current / IP Address 3-digit 7-segment (Orange)
Power 1 (Blue)
LAN 10/100M 1 (Orange / Green)
Link 1 (Green)
Sensor 2 (Green)
Switches Reset 1 x Semi-recessed Pushbutton
Power 1 x Non-fuse Breaker
I/P Rating 100–120V~; 50/60Hz; 12A 100–120V~; 50/60Hz; 16A
Load Capacity 1440W 1920W
O/P Rating Per Port 100–120V~; 50/60Hz; 12A 100–120V~; 50/60Hz; 16A
Total 100–120V~; 50/60Hz; 12A 100–120V~; 50/60Hz; 16A
Environment Operating Temperature
0–50
o
C
Storage Temperature
-20–60
o
C
Humidity 0–80% RH Non-condensing
Physical
Properties
Housing Metal
Weight 2.77 kg / 2.80 kg 2.77 kg / 2.82 kg
Dimensions (L x W x H) 43.24 x 21.93 x 4.40 cm
Appendix
65
PE6108B / PE6208B / PE8108B / PE8208B
Function PE6108B / PE8108B PE6208B/ PE8208B
Power Outlets Direct 8
Connectors Power Inlet 1 x IEC 320 C20
Power
Outlets
NEMA NA
IEC 8 x IEC 320 C13 7 x IEC 320 C13 (Ports 2–8);
1 x C19 (Port 1)
Sensor 2 x RJ-11
LAN 1 x RJ-45 (F)
LEDs Outlet Status 8 (Orange)
Selection 1-digit 7-segment (Orange)
PDU Current / Outlet
Current / IP Address
3 (Green)
Current / IP Address 3-digit 7-segment (Orange)
Power 1 (Blue)
LAN 10/100M 1 (Orange / Green)
Link 1 (Green)
Sensor 2 (Green)
Switches Reset 1 x Semi-recessed Pushbutton
Power 1 x Non-fuse Breaker
I/P Rating 100–240V~; 50/60Hz; 12A 100–240V~; 50/60Hz; 16A
Load Capacity 2880W 3840W
O/P Rating Per
Port
C13 100-240V; 50/60Hz, 12A
C19 NA 100-240V~; 50/60Hz, 16A
Total 100-240V~; 50/60Hz, 12A 100-240V~; 50/60Hz, 16A
Environment Operating Temp
0–50
o
C
Storage Temp.
-20–60
o
C
Humidity 0–80% RH Non-condensing
Physical
Properties
Housing Metal
Weight 2.82 kg / 2.87 kg 2.79 kg / 2.87 kg
Dimensions
(L x W x H) 43.24 x 21.93 x 4.40 cm
66
PE6108G / PE6208G / PE8108G / PE8208G
Function PE6108G / PE8108G PE6208G/ PE8208G
Power Outlets Direct 8
Connectors Power Inlet 1 x IEC 320 C20
Power
Outlets
NEMA NA
IEC 8 x IEC 320 C13 7 x IEC 320 C13 (Ports 2–8);
1 x C19 (Port 1)
Sensor 2 x RJ-11
LAN 1 x RJ-45 (F)
LEDs Outlet Status 8 (Orange)
Selection 1-digit 7-segment (Orange)
PDU Current / Outlet
Current / IP Address
3 (Green)
Current / IP Address 3-digit 7-segment (Orange)
Power 1 (Blue)
Link 1 (Green)
LAN 1 (Orange / Green)
Sensor 2 (Green)
Switches Reset 1 x Semi-recessed Pushbutton
Power 1 x Non-fuse Breaker
I/P Rating 100–240V~; 50/60Hz; 10A 100–240V~; 50/60Hz; 16A
Load Capacity 2400W 3840W
O/P Rating Per
Port
C13 100-240V; 50/60Hz, 10A
C19 NA 100-240V~; 50/60Hz, 16A
Total 100-240V~; 50/60Hz, 10A 100-240V~; 50/60Hz, 16A
Environment Operating Temp.
0–50
o
C
Storage Temp.
-20–60
o
C
Humidity 0–80% RH Non-condensing
Physical
Properties
Housing Metal
Weight 2.82 kg / 2.87 kg 2.79 kg / 2.87 kg
Dimensions
(L x W x H) 43.24 x 20.0 x 4.40 cm
Appendix
67
Administrator Login Failure
If you are unable to perform an Administrator login (because the Username and Password information has become corrupted, or you have forgotten it, for example), you can clear the login information with the following procedure:
1. Power off the eco PDU and remove its housing.
2. Short the jumper labeled J6 (PIN10 and PIN9).
3. Power on the eco PDU.
4. When the 1-digit, 7-segment display shows “P”, power off the switch.
5. Remove the jumper cap from J6.
6. Close the housing and start the eco PDU.
After you start, you can use the default Username and Password to log in.
68
Limited Warranty
ATEN warrants this product against defects in material or workmanship for a period of one (1) year from the date of purchase. If this product proves to be defective, contact ATEN's support department for repair or replacement of your unit. ATEN will not issue a refund. Return requests can not be processed without the original proof of purchase.
When returning the product, you must ship the product in its original packaging or packaging that gives an equal degree of protection. Include your proof of purchase in the packaging and the RMA number clearly marked on the outside of the package.
This warranty becomes invalid if the factory-supplied serial number has been removed or altered on the product.
This warranty does not cover cosmetic damage or damage due to acts of God, accident, misuse, abuse, negligence or modification of any part of the product. This warranty does not cover damage due to improper operation or maintenance, connection to improper equipment, or attempted repair by anyone other than ATEN. This warranty does not cover products sold AS IS or WITH FAULTS.
IN NO EVENT SHALL ATEN'S LIABILITY EXCEED THE PRICE PAID FOR THE PRODUCT. FURTHER, ATEN SHALL NOT BE RESPONSIBLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM THE USE OF THE PRODUCT, ITS ACCOMPANYING SOFTWARE, OR ITS DOCUMENTATION. ATEN SHALL NOT IN ANY WAY BE RESPONSIBLE FOR, WITHOUT LIMITATION, LOSS OF DATA, LOSS OF PROFITS, DOWNTIME, GOODWILL, DAMAGE OR REPLACEMENT OF EQUIPMENT OR PROPERTY, AND ANY EXPENSES FROM RECOVERY, PROGRAMMING, AND REPRODUCTION OF ANY PROGRAM OR DATA.
ATEN makes no warranty or representation, expressed, implied, or statutory with respect to its products, contents or use of this documentation and all accompanying software, and specifically disclaims its quality, performance, merchantability, or fitness for any particular purpose.
ATEN reserves the right to revise or update its product, software or documentation without obligation to notify any individual or entity of such revisions, or update.
For details about extended warranties, please contact one of our dedicated value added resellers
eco PDU PE Series User Manual
1
Contents
FCC Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
SJ/T 11364-2006. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Online Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Telephone Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
User Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
PE Device Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Package Contents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viii
Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viii
Product Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Chapter 1.
Introduction
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PE Series eco PDU Comparison Chart. . . . . . . . . . . . . . . . . . . . . . . . . 3
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Remote Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Cable Holders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
PE1108A / PE3108A Front View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
PE1208A / PE3208A Front View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
PE1108A / PE1208A / PE3108A / PE3208A Rear View . . . . . . . . . . . . 8
PE1108A / PE1208A / PE3108A / PE3208A Readout Section . . . . . . . 9
PE1108B / PE1108G / PE3108B / PE3108G Front View . . . . . . . . . . 10
PE1208B / PE1208G / PE3208B / PE3208G Front View . . . . . . . . . . 10
PE1108B / PE1108G / PE1208B / PE1208G / PE3108B / PE3108G /
PE3208B / PE3208G Rear View . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
PE1108B / PE1108G / PE1208B / PE1208G / PE3108B / PE3108G /
PE3208B / PE3208G Readout Section . . . . . . . . . . . . . . . . . . . . . . . . 11
PE6108A / PE8108A Front View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
PE6208A / PE8208A Front View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
PE6108A / PE6208A / PE8108A / PE8208A Rear View . . . . . . . . . . . 12
PE6108A / PE6208A / PE8108A / PE8208A Readout Section . . . . . . 13
PE6108B / PE6108G / PE8108B / PE8108G Front View . . . . . . . . . . 14
PE6208B / PE6208G / PE8208B / PE8208G Front View . . . . . . . . . . 14
PE6108B / PE6108G / PE6208B / PE6208G / PE8108B / PE8108G /
2
PE8208B / PE8208G Rear View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
PE6108B / PE6108G / PE6208B / PE6208G / PE8108B / PE8108G /
PE8208B / PE8208G Readout Section. . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 2.
Hardware Setup
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Securing the Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Securing the Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 3.
Basic Operation and First Time Setup
Operation Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Browser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
eco Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
First Time Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Network Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Changing the Administrator Login. . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Moving On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Chapter 4.
Browser Operation
Logging In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
The eco PDU Main Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Page Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Outlet Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
User Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Administrator Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
The System Log Event List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Device Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Device Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Date/Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Login Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Working Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Account Policy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Login String / IP Filter / Mac Filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Authentication & Authorization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
eco PDU PE Series User Manual
3
Private Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Firmware File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Backup/Restore. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Appendix
Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
The eco PDU’s Main Power Cord . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Securing the Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
International. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
IP Address Determination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
PE1108A / PE1208A / PE3108A / PE3208A. . . . . . . . . . . . . . . . . . . .61
PE1108B / PE1208B / PE3108B / PE3208B. . . . . . . . . . . . . . . . . . . .62
PE1108G / PE1208G / PE3108G / PE3208G . . . . . . . . . . . . . . . . . . . 63
PE6108A / PE6208A / PE8108A / PE8208A. . . . . . . . . . . . . . . . . . . .64
PE6108B / PE6208B / PE8108B / PE8208B. . . . . . . . . . . . . . . . . . . .65
PE6108G / PE6208G / PE8108G / PE8208G . . . . . . . . . . . . . . . . . . . 66
Administrator Login Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68