Altronix ALTV1224DC1CB Installation Instructions

Page 1
ALTV1224DC Series
CCTV Power Supplies
Installation Guide
Models Include:
ALTV1224DC
- Eight (8) Fuse Protected Outputs.
ALTV1224DC1
- 12VDC or 24VDC @ 4A.
- Sixteen (16) Fuse Protected Outputs.
ALTV1224DC2
- 12VDC or 24VDC @ 6A.
- Sixteen (16) Fuse Protected Outputs.
Rev. 022505
ALTV1224DCCB
- Eight (8) PTC Protected Outputs.
ALTV1224DC1CB
- 12VDC or 24VDC @ 4A.
- Sixteen (16) PTC Protected Outputs.
ALTV1224DC2CB
- 12VDC or 24VDC @ 6A.
- Sixteen (16) PTC Protected Outputs.
More than just power.
TM
Page 2
Altronix ALTV1224DC Series DC CCTV power supplies are designed to power CCTV Cameras and acces­sories. Units provide 12VDC or 24VDC distributed via eight (8) or sixteen (16) fused or PTC protected outputs with a total of 4A or 6A continuous supply current.
Eight (8) or Sixteen (16) Output ALTV1224DC Reference Chart:
Overview:
Altronix Model Number
ALTV1224DC
ALTV1224DCCB
ALTV1224DC1
ALTV1224DC1CB
ALTV1224DC2
ALTV1224DC2CB
Total
Output Current (Power)
4A
6A
Number
of
Outputs
8
16
PTC Protected
Auto-Resettable
Outputs
P
P
P
Fuse
Protected
Outputs
P
2.5A
P
2.5A
P
2.5A
Output
Current
(max per
output)
3.5A
3.5A
3.5A
115VAC 50/60Hz
Input
Current
1.45A
2.5A
Specifications:
Input:
• Input 115VAC, 50/60Hz.
Output:
• Eight (8) or sixteen (16) fuse or PTC protected outputs.
• 12VDC or 24VDC.
• Outputs are rated @ 3.5A (fused) or 2.5A (PTC).
• Filtered and electronically regulated outputs.
Features:
• AC input and DC output LED indicators.
• Power ON/OFF switch.
• Unit maintains camera synchronization.
• Ease of installation saves time and eliminates costly labor.
Enclosure Dimensions (H x W x D approx.):
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm).
Installation Instructions:
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 8). Secure enclosure to earth ground.
2. Slide switch to the OFF position (Fig. 1, pg. 3, Fig. 2, pg. 4 or Fig. 3, pg. 5).
3. Set the unit to desired DC output voltage range by setting switch (SW1) on the power supply board to the appropriate position. Use trimpot to adjust voltage if necessary (Fig. 1, pg. 3, Fig. 2, pg. 4 or Fig. 3, pg. 5).
4. Connect the AC (115VAC, 50/60 Hz) to the terminals marked [L] and [N]. Connect earth ground (Fig. 1, pg. 3, Fig. 2, pg. 4 or Fig. 3, pg. 5).
5. Measure output voltage before connecting devices. This helps avoiding potential damage.
6. Connect each DC device to the output terminals 1 through 8 (Fig. 1, pg. 3) or terminals 1 through 16 (Fig. 2, pg. 4 or Fig. 3, pg. 5). Note: Be careful to observe camera polarity.
7. When batteries are being used the DC output voltage must be adjusted by turning the trim pot VR1 (Fig. 1, pg. 3, Fig. 2, pg. 4 or Fig. 3, pg. 5) clockwise to increase the output voltage to 13.7VDC for 12VDC operation and 27.1VDC for 24VDC operation. Connect battery to the terminals marked [– BAT +] (battery leads included) (Fig. 1, pg. 3, Fig. 2, pg. 4 or Fig. 3, pg. 5). Use two (2) 12VDC batteries connected in series for 24VDC operation.
8. Slide switch to the ON position (Fig. 1, pg. 3, Fig. 2, pg. 4 or Fig. 3, pg. 5).
9. Green LED on the PD8/PD8CB or PD16W/PD16WCB board will illuminate when power is present.
10. Upon completion of the wiring secure enclosure door with screws (supplied).
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes.
- 2 - ALTV1224DC Series
Page 3
ALTV1224DC/CB Terminal Identification:
CAUTION: De-energize unit prior to servicing.
OLS127 - Power Supply
Terminal Legend Function/Description
L, N 115VAC power mains connection.
– DC + 12VDC or 24VDC @ 4A total continuous output.
– BAT + Stand-by battery connections. Maximum charge rate 0.5A.
PD8/PD8CB - Power Distribution Module
Terminal Legend Function/Description
1P - 8P Positive DC power outputs.
1N - 8N Negative DC power outputs.
Fig. 1
For continued protection against fire hazard replace fuse with the same type and rating. Do not expose unit to rain or moisture.
Door
Wire Strap
(from
Enclosure
to Door)
Green Flying
Lead
115VAC
power mains
ON - 12V
OFF - 24V
ON
Divider
OFF ON
ON
OFF - 24V ON - 12V
(example: ALTV1224DCCB)
LED
INPUT
D1
R1
FUSED POWER OUTPUTS
P
COMMON POWER OUTPUTS
N
1 2 3 4 5 6 7 8
Switch disables power mains line voltage input.
If stand-by battery (batteries) are connected the DC output remains on.
SW1 24VDC output - OFF 12VDC output - ON
Trimpot Adjusts output voltage on power supply
Used on PTC Models
ALTV1224DC Series - 3 -
Page 4
ALTV1224DC1/CB Terminal Identification:
OLS127 - Power Supply
Terminal Legend Function/Description
L, N 115VAC power mains connection.
– DC + 12VDC or 24VDC @ 4A total continuous output.
– BAT + Stand-by battery connections. Maximum charge rate 0.5A.
PD16W/PD16WCB - Power Distribution Module
Terminal Legend Function/Description
1P - 16P Positive DC power outputs.
1N - 16N Negative DC power outputs.
Fig. 2
CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating. Do not expose unit to rain or moisture.
Divider
Door
Wire Strap
(from
Enclosure
to Door)
115VAC
power mains
Green
Flying
Lead
Used on PTC Models
(example: ALTV1224DC1CB)
ON - 12V
OFF - 24V
12345678
3.5A 250V
Switch disables power mains
OFF ON
ON
line voltage input.
If stand-by battery (batteries) are connected the DC output remains on.
OFF - 24V ON - 12V
ON
Trimpot Adjusts output voltage on power supply
12345678
9 10 11 12 13 14 15 16
common
outputs protected
outputs
SW1 24VDC output - OFF 12VDC output - ON
9 10 11 12 13 14 15 16
common
outputs
protected
outputs
N
P
NP
NPS
XFMR Input
N
P
NP
NPS
XFMR Input
- 4 - ALTV1224DC Series
Page 5
CAUTION: De-energize unit prior to servicing.
ALTV1224DC2/CB Terminal Identification:
OLS187 - Power Supply
Terminal Legend Function/Description
L, N 115VAC power mains connection.
– DC + 12VDC or 24VDC @ 6A total continuous output.
– BAT + Stand-by battery connections. Maximum charge rate 0.5A.
PD16W/PD16WCB - Power Distribution Module
Terminal Legend Function/Description
1P - 16P Positive DC power outputs.
1N - 16N Negative DC power outputs.
Fig. 3
For continued protection against fire hazard replace fuse with the same type and rating. Do not expose unit to rain or moisture.
Door
Wire Strap
(from
Enclosure
to Door)
ON OFF
5A 250V
LGN
115VAC
power mains
Green Flying
Lead
--- BAT + --- DC +
AC
DC
Used on PTC Models
(example: ALTV1224DC2CB)
ON - 12V
OFF - 24V
ON
Divider
12345678
OFF ON
OFF - 24V ON - 12V
ON
12345678
common
outputs protected
outputs
For continuous protection against risk of fire
replace fuses with same type and rating.
3.5A 250V
Switch disables power mains line voltage input.
If stand-by battery (batteries) are connected the DC output remains on.
SW1 24VDC output - OFF 12VDC output - ON
Trimpot Adjusts output voltage on power supply
common
outputs
protected
outputs
9 10 11 12 13 14 15 16
9 10 11 12 13 14 15 16
N
P
NP
NPS
XFMR Input
N
P
NP
NPS
XFMR Input
ALTV1224DC Series - 5 -
Page 6
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.
- 6 - ALTV1224DC Series
Page 7
Notes:
ALTV1224DC Series - 7 -
Page 8
1.40”
(
)
(
)
(
)
(36mm)
1.20”
(31mm)
Enclosure Dimensions (H x W x D):
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
0.75”
(19mm)
1.40”
(36mm)
4.85”
(123mm)
12.5”
(318mm)
11.0”
(279mm)
4.85”
(123mm)
1.40”
(36mm)
0.75”
(19mm)
1.20”
(31mm)
0.9375” (24mm)
3.25”
(83mm)
1.20”
(31mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
3.25”
(83mm)
(330mm)
1.0”
(25mm)
5.10”
(130mm)
13.0”
6.5625”
(167mm)
0.9375” (24mm)
3.25”
(83mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
25mm
10.5”
267mm
1.0”
25mm
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A. IIALTV1224DCSeries E07R
- 8 - ALTV1224DC Series
MEMBER
Loading...