Altronix AL600ULACMCBR Installation Instructions

Page 1
ACMCB Series
Access Power Controllers with Power Supplies Installation Guide
Models Include:
AL400ULACMCB AL600ULACMCB
- 4 amp @ 12VDC - 6 amp @ 12VDC or 24VDC.
or 3 amp @ 24VDC.
- PTC Outputs
AL1012ULACMCB AL1024ULACMCB
-
10 amp @ 12VDC. - 10 amp @ 24VDC.
- PTC Outputs - PTC Outputs
For a red enclosure, add an “R” suffix to the part # e.g. AL600ULACMCBR
Rev. 092503
Page 2
Overview:
T
hese units distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input
i
nto eight (8) independently controlled 12VDC or 24VDC PTC protected outputs. Outputs are activated by an open col-
l
ector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm discon­nect feature is individually selectable for any or all of the eight (8) outputs.
ACMCB Series Configuration Reference Chart:
Altronix Model Number
Current (amp)
12VDC Total Output
Current (amp)
24VDC Total Output
Outputs
AL400ULACMCB 4 3 8 Yes 1.9 amp 3.5A / 250V AL600ULACMCB 6 6 8 Yes 1.9 amp 3.5A / 250V
AL1012ULA
CMCB 10 --- 8 Yes 1.9 amp 3.5A / 250V
AL1024ULACMCB --- 10 8 Yes 4.4 amp 10A / 250V
wer Limited
Po
Class 2 Rated
(current draw)
115VAC 60Hz Input
Power Supply Board
Input Fuse Rating
Agency Listings
UL Listings and
File Numbers
UL File # BP6714
UL Listed for Access Control
System Units (UL 294).
“Signal Equipment”
Evaluated to
CSA Standard C22.2
No.205-M1983
Specifications:
• Power suppl
a) One (1) common power input for ACM8CB and lock power (factory installed). b) Two (2) isolated power inputs (external power supply is required).
(current is determined b
• Eight (8)
Input options:
Eight (8) normally open (NO) inputs.
a)
Eight (8) open collector inputs.
b) c) Any combination of the above.
• Eight (8) independently controlled Fail-Safe and/or Fail-Secure power outputs.
• Eight (8) auxiliary power outputs (unswitched) (PTC protected outputs are rated 2.5 amp).
• ACM8CB board main fuse is rated at 10 amp.
• Red LEDs indicate outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs.
Alar
ire
F a) Normally open (NO) or normally closed (NC) dry contact input. b) Polarity reversal input from FACP signaling circuit.. Alarm output relay indicates that FACP input is triggered
(form “C” contact rated @ 1 amp 28VDC not evaluated by UL).
• Green LED indicates when FACP disconnect is triggered.
• Filtered and electronically regulated outputs (built-in power supply).
Built-in charger for sealed lead acid or gel type batteries. AL400ULXB
AL1024ULXB (P
• Automatic switch over to stand-by battery when AC f ails.
• Zero voltage drop when unit switches over to batter y backup (AC failure condition).
• Thermal and short circuit protection with auto reset.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact).
y input options:
y the power suppl
y connected, not to exceed a maximum of 10 amp total).
Access Control System trigger inputs.
m disconnect input options:
, AL600ULXB and AL1012ULXB (Power Supply Board) maximum charge current .7 amp.
er Suppl
w
o
y Board) maximum charge current 3.6 amp.
- ACMCBseries
2
-
Page 3
• Battery fail and battery presence super vision (for m "C" contact).
Enclosure accommodates up to two (2) 12AH batteries.
E
nclosure dimensions: 15.5"H x 12"W x 4.5"D
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws Secure enclosure to earth ground. It is recommended to first review the following tables to facilitate installation:
Output Voltage and Stand-by Specifications Charts (pg. 3) T ypical Application Diagram (pg. 5) LED Diagnostics (pg. 6) Terminal Identification Tables (pg. 7) Hook-up Diagrams (pg. 8)
2. Set output voltage:
AL400ULACMCB and AL600ULACMCB set desired DC output voltage by setting switch SW1 to the appropriate position on the power supply board. AL1012ULA
(Output Voltage and Stand-by Specification Charts below).
3. Measure voltage before connecting devices. This helps avoid potential damage.
CMCB is 12VDC and
AL1024ULACMCB is 24VDC
(Enclosure Dimensions, pg. 10).
Output Voltage and Stand-by Specification Charts:
AL400ULACMCB
Voltage Switch Stand-by 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
Position Battery 12VDC SW1 - Closed 40 AH 3.5 amp / 3.5 amp .5 amp / 3.5 amp 24VDC SW1 - Open 40
AH 2.75 amp / 2.75 amp .75 amp / 2.75 amp
AL600ULACMCB
Voltage Switch Stand-by 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
Position Battery 12VDC SW1 - Closed 40 AH 5.5 amp / 5.5 amp .5 amp / 5.5 amp 24VDC SW1 - Open 40 AH 5.75 amp / 5.75 amp .75 amp / 5.75 amp
AL1012ULACMCB
Voltage Switch Stand-by 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
Position Battery 12VDC N/A 40 AH 9.5 amp / 9.5 amp .5 amp / 9.5 amp
AL1024ULACMCB - (refer to AL1024ULACMCB Battery Size Calculation Worksheet, pg. 9)
Voltage Stand-by 15 mins. Stand-by / 4 hr. Stand-by / 24 hr. Stand-by / 60 hr. Stand-by /
Battery 5 mins. Alarm 5 mins. Alarm 5 mins. Alarm 5 mins. Alarm
24VDC
12 A H 7.7 amp / 9 . 7 a m p 1.2 amp / 9 . 7 amp ------------------------- -------------------------
oltage
V
24VDC
ACMCBseries - 3 -
Stand-by 15 mins. Stand-by / 4 hr. Stand-by / 24 hr. Stand-by / 60 hr. Stand-by /
Battery 5 mins. Alarm 5 mins. Alarm 5 mins. Alarm & 5 mins. Alarm
65
AH
-------------------------
7.7 amp / 9.7 amp
1.2 amp / 9.7 amp
200mA / 9.7 amp
Page 4
4. Connect AC (Fig. 2, pg. 6):
C
onnect unswitched AC power (115VAC 60Hz) to terminals marked [L, G, N]. Use 14 AWG or larger for all power
c
onnections. Secure green wire lead to earth ground.
w
iring (115VAC 60Hz Input, Battery Wires). Minimum .25” spacing must be provided.
K
eep power limited wiring separate from non-power limited
5. Output options (Fig. 1, pg. 5):
The unit will provide eight (8) switched power outputs or eight (8) unswitched auxiliary power outputs.
(a) Switched Power outputs:
Connect the negative (-) input of the device being powered to the terminal marked [COM]. For Fail-Safe operation connect the positive (+) input of the device being powered to the terminal marked [NC]. For Fail-Secure operation connect the positive (+) input of the device being powered to the terminal marked [NO].
(b) Auxiliary Power outputs (unswitched):
Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (-) of the device being powered to the terminal marked [COM]. Output can be used to provide power for card readers, keypads etc.
Input trigger options (Fig. 1, pg. 5):
6.
(a) Normally Open [NO] input trigger:
Inputs 1-8 are activated by normally open or open collector sink inputs. Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND].
(b) Open Collector Sink inputs:
Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the negative (-) to the terminal marked [GND].
Fire Alarm Interface options (Figs. 4 through 8, pg. 8):
7. A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit will trigger selected outputs. To enable FACP Disconnect for an output open the corresponding switch [SW1-SW8]. To disab
le FACP disconnect for an output close the corresponding switch [SW1-SW8].
(a) Normally Open [NO] input:
For non-latching hook-up (Fig. 5, pg. 8). For latching hook-up (Fig. 6, pg. 8).
(b) Normally Closed [NC] input:
For non-latching hook-up (F
ig. 7, pg. 8)
or latching hook-up (Fig. 8, pg. 8)
. F
.
(c) FACP Signaling Circuit input trigger:
Connect the positive (+) and negative (-) from the FACP signaling circuit output to the terminals marked [+ INP -]. Connect the FACP EOL to the terminals marked [+ RET -] (polarity is referenced in an alarm condition). Jumper J3 must be cut
8.
FACP Dry form “C” output (Fig. 1A, pg. 5):
Connect desired device to be triggered b
(Fig. 4, pg. 8).
y the unit’
s dry contact output to the ter
minals marked [NO] and [C]
FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output.
9. Batter y Connections
ig. 2, pg. 6)
(F
: For Access Control applications batteries are optional. If batteries are not used a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked
AT +] for 12VDC operation. Use two (2) 12VDC batteries wired in series for 24VDC operation.
[- B
10.
Battery and AC Supervision output (Fig. 2, pg. 6):
It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] supervisory relay outputs marked [NC, C, NO] to appropriate notification devices. Use 22 AWG to 18 AWG for AC Fail & Low/No Battery reporting. Cut “AC delay” jumper to delay report 6 hour. Note: A tamper s
troub
11.
Multiple power supply inputs (Fig. 1, pg. 5):
witch must be installed and connected to the appropriate notification device to report a
le condition w
hen the enclosure door is open.
When using two (2) power supplies jumpers J1 and J2 (located to the left of the power/control terminals) must
(Fig. 1B, pg. 5 & Fig. 3 pg. 8). Connect power for the ACM8CB to the terminals marked [- Control +] and
be cut connect power for the locking devices to the terminals marked [- Power +]. When using DC power supplies polarity must be observed. When using AC power supplies polarity need not be observed. Note: For UL compliance the additional power supply must be power limited, UL Listed for Access Control
Systems and accessories.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under nor mal load conditions, the DC output voltage should be checked for proper voltage level
- ACMCBseries
4
-
Page 5
NC C NO COM OUTPUT 1
LED1
F1
NC C NO COM OUTPUT 2
IN GND1IN GND2IN GND3IN GND4IN GND5IN GND6IN GND
7
MAIN
IN GND
8
LED2 LED3
LED4 LED5 L
ED6
LED7 LED8
J2
J1
TRG
NC C NO COM OUTPUT 3
NC C NO COM OUTPUT 4
NC C NO COM OUTPUT 5
NC C NO COM OUTPUT 6
NO C NC + INP --- T + RET -
NC C NO COM OUTPUT 7
NC C NO COM OUTPUT 8
--- +
Power
--- +
Control
F
2
F3
F6 F7 F8
F4
F5
J3
J2
J1
3
.5A 250V 3.5A 250V 3.5A 250V3.5A 250V 3.5A 250V3.5A 250V3.5A 250V 3.5A 250V
FACP INTERFACE
10A 250V
N
C
NO
C
K
EYPAD
NORMALLY OPEN
N.O. DOOR
RELEASING DEVICE
A
CCESS CONTROL
PANEL
OUTPUT
RELAY
MAG. LOCK
MAG. LOCK
ELECTRIC
STRIKE
ELECTROMAGNETIC
DOOR HOLDERS
AC or DC
POWER
SUPPLY
(optional)
AC or DC
POWER
SUPPLY
(req'd.)
F
ACP
(
Fire Alarm
Control Panel)
UL Listed POWER SUPPLY
For this application corresponding fuse F8 must be removed.
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
FACP Interface Enabled
FACP Interface Disabled
SW1-SW8
FACP Dry Form "C"
Output
NO C NC
FACP
(Output Voltage and Stand-by Specification Charts, pg. 3).
B
attery Test: Under normal load conditions check that the batter y is fully charged, check specified voltage at
t
he battery terminals and at the board terminals marked [- BAT +] to insure that there is no break in the battery
c
onnection wires.
Note: AL400ULXB, AL600ULXB, AL1012ULXB (Power Supply Board) maximum charge current is .7 amp.
AL1024ULXB (Power Supply Board) maximum charge current is 3.6 amp.
Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary.
Typical Application Diagram:
Fig. 1
Fig. 1A
ACMCBseries - 5 -
Fig. 1B
Page 6
LED Diagnostics:
--- DC
+
L G N
ALTRONIX CORP.
BKLYN, N.Y. 11220
MADE IN USA
--- BAT
+
A
C FAIL
B
AT FAIL
Battery and AC
Supervision Circuit
(power limited)
Battery connection (non-power limited)
Door
Wire Strap (from Enclosure to Door)
DC Output to devices (power limited)
Fire Alarm Interface
Insulating Barrier
Inputs (power limited)
unswitched 115VAC
power mains
(non-power limited)
Power Supply Board
CAUTION: De-energize unit prior to servicing.
For continued protection against fire hazard replace
fuse with the same type and rating .
Replace fuse cover before energizing.
Green
Lead
Green
L
ead
Keep power limited wiring separate from non-power limited. Use minimum .25" spacing.
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Power Supply Board
LED
Red (DC) Green (AC) Power Supply Status ON ON Normal operating condition. ON OFF Loss of AC, Stand-by battery supplying power. OFF ON No DC output. Short circuit or ther mal overload condition. OFF OFF No DC output. Loss of AC. Discharged battery.
ACM8 Access Power Controller
LED ON OFF LED 1- LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized. Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition).
Fig. 2
- ACMCBseries
6
-
Page 7
Terminal Identification Tables:
Power Supply Board
T
erminal Function/Description
L
egend
L, G, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral, G to ground.
- DC + AL400ULACMCB - 12VDC @ 4 amp or 24VDC @ 3 amp to ACM8CB board (power limited). AL600ULACMCB - 12VDC/24VDC @ 6 amp to ACM8CB board (power limited). AL1012ULACMCB - 12VDC @ 10 amp to ACM8CB board (power limited). AL1024ULACMCB - 24VDC @ 10 amp to ACM8CB board (power limited).
AC FAIL Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay NC, C, NO normally energized when AC power is present. Contact rating 1 amp @ 28VDC.
AC or brownout fail is reported within 1 minute of event. To delay reporting of up to 6 hrs., cut “AC delay” jumper and reset power to unit.
BAT FAIL Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally NC, C, NO energized when DC power is present. Contact rating 1 amp @ 28VDC.
A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute. Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULACMCB), 24VDC output threshold set @ approximately 21VDC (N/A for AL1012ULACMCB).
- BAT + Stand-by battery connections. AL400ULXB, AL600ULXB and AL1012ULXB (Power Supply Board) maximum char maximum charge current is 3.6 amp.
ge current is .7 amp. AL1024ULXB (Power Supply Board)
ACM8CB Access Power Controller
Terminal Legend
- Power + 12VDC or 24VDC input from power supply board.
- Control + These terminals can be connected to a separate power limited, UL listed power supply to
TRIGGER From normally open and/or open collector sink trigger inputs INPUT 1- INPUT 8 (request to exit buttons, exit pir’s, etc.). IN, GND
OUTPUT 1-OUTPUT 8 12 to 24 volts AC/DC trigger controlled outputs: NC, C, NO, COM Fail-Safe [NC positive (+) & COM Negative (-)],
FACP INTERFACE Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open, T, + INPUT -- normally closed from an FACP output circuit
CE
F
A
CP
INTERF
A
NC, C, NO (This output has not been evaluated by UL).
Function/Description
provide isolated operating po
ail-Secure [NO positi
F Auxiliar
y output [C positi
ve (+) & COM Negative (-)],
e (+) & COM Ne
v
wer for the
ACM8 (jumpers J1and J2 Must be removed).
ative (-)]
g (When using AC power supplies polarity need not be observed), NC, C, NO become form “C” 5 amp 24VAC/VDC rated dry outputs when fuses are
ved. Contacts shown in a non-triggered state.
remo
(Fig. 4 through 8 , pg. 8).
m “C” relay contact rated @ 1 amp 28VDC for alarm reporting.
or
F
ACMCBseries - 7 -
Page 8
Hook-up Diagrams:
JUMPER
N.C. DRY TRIGGER
INPUT
TRG
J3
NO C NC
FACP INTERFACE
N.C. TRIGGER
INPUT
N.C. RESET
SWITCH
JUMPER
TRG
J3
J2
J1
C
UT JUMPERS
J1 AND J2
ISOLATED POWER INPUT
12 OR 24 VAC OR VDC
(LOCK POWER)
ISOLATED POWER INPUT
12 OR 24 VAC OR VDC
(ACM8CB POWER)
C
UT
J
UMPER J3
FROM FACP
OUTPUT CIRCUIT
+
--
F
ACP 
OUTPUT EOL
TRG
J3
NO C NC
FACP INTERFACE
N.O. TRIGGER
INPUT
TRG
J3
NO C NC
FACP INTERFACE
N.C. RESET
SWITCH
N.O.
TRIGGER
INPUT
JUMPER
TRG
J3
NO C NC
Fig. 3 Optional hook-up using two (2) isolated
power supply inputs:
F
ig. 4Polarity reversal input from FACP signaling circuit
o
utput (polarity is referenced in alarm condition):
Fig. 5 Normally Open - Non-Latching FACP
trigger input:
Fig
. 7
Normall
y Closed - Non-Latching FACP
trigger input:
Fig. 6 Normally Open FACP Latching trigger input
with reset: (This output has not been evaluated by UL)
Fig. 8 Normally Closed - Latching FACP trigger input
with reset: (This output has not been evaluated by UL)
-
- ACMCBseries
8
Page 9
AL1024ULACMCB Battery Size Calculation Worksheet.
A. AL1024ULACMCB internal current consumption (standby) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ .35 A
B. Load current consumption (standby) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ A
C. Standby time required (hours) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ H
D. Battery capacity required for standby (A+B)*C _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ AH
E. AL1024ULACMCB internal power consumption (Alarm) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ .35 A
F . Load current consumption (Alarm) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ A
G. Alarm duration (Hours, example:15 Min=.25 Hour) (Alarm) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ H
H. Battery capacity required for Alarm (E+F)*G _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ AH
I. Total calculated battery capacity D+H _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ AH
J. Battery capacity required
I* 1 . 8 ( s afe t y f a ctor ) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ A H
Note: AL1024ULACMCB power supply is designed to work with batteries up to 65AH. Please note, line [I]
must not exceed 36AH. You have to reduce either standby current consumption or standby time in order to compl
y with requirement.
To determine actual battery size please round line [J] to the nearest larger standard batter y size.
ACMCBseries - 9 -
Page 10
.875"
1"
0
00
0
10.75"
1.5"
6"
10.5"
2"
0
1.25"
4.5"
12"
15.5"
4.5"
4.5"
1.25"
1.25"
14.25"
13.5"
10"
6.625"
TOP & BOTTOM
1
5.5”H x 12”W x 4.5”D
Enclosure Dimensions:
- ACMCBseries
10
-
Page 11
Notes:
ACMCBseries - 11 -
Page 12
Notes:
Altronix is not responsib
Altronix Cor 140 58th Street, Brookl web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. IIACMCB series L06G
12
-
p.
- ACMCBseries
le for an
ork 11220 USA, 718-567-8181, fax: 718-567-9056
Y
w
yn, Ne
graphical errors.
y typo
MEMBER
Loading...