![](/html/4e/4e1a/4e1a0e3ba4c1a1db6e8e575812cb53f94a0f07f95fb42bb4615d25f461797c6d/bg1.png)
AL600ULACMJ, AL600ULACMCBJ
Power Supply/Chargers w/Multi-Output
Access Power Controllers
Overview
• The AL600ULACMJ / AL600ULACMCBJ converts an 115VAC 60Hz input
into eight (8) independently controlled 12VDC or 24VDC Fail-Safe and/or
Fail-Secure outputs with a total of 6 amp continuous supply current. These
power outputs can be converted to dry form "C" contacts (AL600ULACMJ
only). Outputs are activated by an open collector sink or normally open (NO)
dry trigger input from an Access Control System, Card Reader, Keypad, Push
Button, PIR, etc. These units will route power to a variety of access control
hardware devices including Mag Locks, Electric Strikes, Magnetic Door
Holders, etc. The outputs will operate in both Fail-Safe and/or Fail-Secure
modes. The units are designed to be powered by one common power source
(factory installed) which will provide power for both the board operation and
locking devices, or two (2) totally independent power sources, one (1)
providing power for board operation and the other for lock / accessory power.
The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be
used to trigger other auxiliary devices. The fire alarm disconnect feature is
individually selectable for any or all of the eight (8) outputs.
AL600ULACMJ
• Eight (8) independently controlled
fuse protected outputs.
Specifications
• 12VDC or 24VDC @ 6 amp supply current.
• Power supply input options:
a) One (1) common po
ACM8CB and lock power (factory installed).
b) Two (2) isolated power inputs - One (1) to power
the ACM8/A
accessory power, (external power supply
is required). (Current is deter
wer supply connected, not to exceed a
po
maximum of 10 amp total).
• Eight (8) Access Control System trigger inputs.
Input options:
a) Eight (8) normally open (NO) inputs.
Eight (8) open collector inputs.
b)
c) Any combination of the above.
• Eight (8) independently controlled outputs.
Output options:
Eight (8) Fail-Safe and/or Fail-Secure
a)
power outputs.
b) Eight (8) dry form “C” 5 amp rated relay outputs
(AL600ULA
c) Any combination of the above
(AL600ULA
Eight (8) auxiliar
•
• Output ratings:
- Fuses are rated @ 3.5 amp (AL600ULACMJ).
- PTCs are rated @ 2.5 amp (AL600ULACMCBJ).
• ACM8 board main fuse is rated at 10 amp.
• Input 115VAC 60Hz rated @ 1.9 amp.
• Filtered and electronically regulated outputs
uilt-in power supply)
(b
• Red LEDs indicate outputs are triggered (relays energized).
CM8CB and one (1) for lock
CMJ onl
CMJ onl
wer input for ACM8/
mined b
y).
y).
er outputs (unswitched)
w
y po
y the
Rev. DSAL600ULACMJ - J16F
AL600ULACMCBJ
• Eight (8) independently controlled
PTC protected outputs.
• Class 2 Rated po
• Fire Alarm disconnect (latching or non-latching) is
individually selectable for any or all of the
eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC)
dry contact input.
b) Polarity reversal input from FACP
signaling circuit.
• Alarm output relay indicates that FACP input
is triggered (form “C” contact rated @ 1 amp 28VDC
not evaluated by UL).
• Green LED indicates when FACP disconnect
is triggered.
Built-in char
•
• AL600ULXB (Power Supply Board)
maximum charge current .7 amp.
• Automatic switch over to stand-by battery
hen AC fails.
w
• AC input and DC output LED indicators.
• Zero voltage drop when unit switches over to battery
backup (A
• Short circuit and thermal overload protection.
C fail supervision (form "C" contact).
A
•
Batter
•
(form "C" contact).
• Enclosure accommodates up to two (2) 12AH batteries.
• Product weight:
- AL600ULACMJ: 11.3 lbs.
AL600ULA
Shipping w
•
- AL600ULACMJ: 12.6 lbs.
AL600ULACMCBJ: 12.5 lbs.
-
ger for sealed lead acid or gel type batteries.
ailure condition).
C f
ail and batter
y f
CMCBJ: 11.2 lbs.
eight:
y presence supervision
wer limited outputs.
![](/html/4e/4e1a/4e1a0e3ba4c1a1db6e8e575812cb53f94a0f07f95fb42bb4615d25f461797c6d/bg2.png)
Agency Approvals
1
.50"
1.25"
2.50"
6.00"
2
.50"
1
.50"
2.50"
1.50"
1.00"
1.50"
1.00"
1.50"
2.75"
4.50" 4.50"
1
.00"
1.00"
1
.25"
1.50"
8
.50"
1.00"
1.00"
2.75"
18.00"
14.50"
18.00"
18.00"
1
4.50"
UL Listed for Access Control Systems Units
(UL 294).
CUL Listed - CSA Standard C22.2
No.205-M1983 Signal Equipment.
Enclosure Dimensions
18”H x 14.5”W x 4.625”D
457mm x 368mm x 117mm
MEA - NYC Department of
B
uildings Approved.
CSFM - California State Fire
Marshal Approved.
Altr
onix Cor
- 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.com
p.