For a red enclosure add an “R” suffix to the part #, e.g. AL400ULPD8R
Rev. 102512
AL400ULPD4CB
- Four (4) PTC Protected Outputs.
AL400ULPD8CB
- Eight (8) PTC Protected Outputs.
AL400ULXPD16CB
- Sixteen (16) PTC Protected Outputs.
More than just power.
TM
Page 2
Altronix AL400ULX is a power supply that converts a 115VAC, 60Hz input to a 12VDC or 24VDC regulating
Altronix Corp.
output (see specifications below).
The AL400ULX is a base power supply unit for the UL Listed multi-output power supply/charger series:
AL400ULPD4, AL400ULPD4CB, AL400ULPD8, AL400ULPD8CB, AL400ULXPD16, AL400ULXPD16CB
(Refer to AL400ULX Series Power Supply Configuration Reference Chart below).
AL400ULX Series Power Supply Configuration Reference Chart:
• 4A total supply current at 12VDC or
3A total supply current at 24VDC.
• Filtered and electronically regulated output(s).
• Short circuit and thermal overload protection.
Power Supply Output Specifications:
OutputSwitch Position
12VDCSW1 - ON
24VDCSW1 - OFF
Stand-by Specifications (total current shown):
Output
12VDC / 40AH Battery
24VDC / 12AH Battery--------
24VDC / 40AH Battery
4 hr. of Stand-by and
5 Minutes of Alarm
Stand-by = 4.0A
Alarm = 4.0A
Stand-by = 3.0A
Alarm = 3.0A
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery when
AC fails.
• Maximum charge current 0.7A.
• Zero voltage drop when switched over to
battery backup.
Supervision:
• AC fail supervision (form “C” contacts).
• Low battery and battery presence supervision
(form “C” contacts).
Additional Features:
• Power supply, enclosure, cam lock and battery leads.
• All models are available in red enclosure
(add an “R” suffix to the part #, e.g. AL400ULPD8R).
ON
OFF - 24V
24 hr. of Stand-by and
5 Minutes of Alarm
Stand-by = 1.0A
Alarm = 4.0A
Stand-by = 200mA
Alarm = 3.0A
Stand-by = 1.0A
Alarm = 3.0A
60 hr. of Stand-by and
5 Minutes of Alarm
Stand-by = 300mA
Alarm = 4.0A
--------
Stand-by = 300mA
Alarm = 3.0A
AL400ULX Series - 3 -
Page 4
Fig. 1
Power
Distribution
Module(s)
+ DC ---
NC C NO NC C NO
+ BAT ---
AC DC Bat
Risk of Fire,
Replace Fuses
As Marked
AC Fail
Bat Fail
J1
SW1
5A 250V
15A 250V
AC Delay
15
L G N
Door
CAUTION: De-energize unit prior to servicing. For continued protection against risk
of electric shock and fire hazard replace fuse with the same type and rating.
Do not expose to rain or moisture.
Green
Lead
Battery connection (non power limited)
Switch Position:
24VDC = SW1 OFF
12VDC = SW1 ON
Wire
Strap
(from
Enclosure
to Door)
115VAC
power mains
non-power
limited
Battery & AC
Supervision
Circuit
(power limited)
Class 1
-
Divider
power limited
For 12VDC Operation
use hook-up in the
inset on the right
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC
stand-by battery.
Keep power limited wiring separate from non-power limited. Use minimum 0.25" spacing.
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
SW1
Battery & AC Supervision
Circuit
(power-limited)
NC C NO NC C NO AC Fail
Bat Fail
J1
AC Delay
OFF - 24V
ON - 12V
ON
1
OFF - 24V
ON - 12V
ON
1
Fig. 1a
Fig. 1b
Fig. 1c
- 4 - AL400ULX Series
Page 5
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with
Installation Instructions:
all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place
the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower
two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper
keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pgs. 11, 12). Secure enclosure to earth ground.
2. Set the unit to the desired DC output voltage by setting SW1 (Fig. 1c, pg. 4) to the appropriate position
(Power Supply Output Specification Chart, pg. 3).
3. Secure cabinet to earth ground. Connect AC power (115VAC / 60 Hz to the terminals marked [L, N]
(Fig. 1, pg. 4). Use 14 AWG or larger for all power connections (Battery, DC output, AC input).
Use 22 AWG to 18 AWG for power-limited circuits (AC fail/Low Battery reporting).
Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input,
Battery Wires). Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing
equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified
service personnel.
For Fire Alarm applications the outputs are “Special Applications” only see list (refer to Appendix A, pg. 8).
For other devices contact Underwriters Laboratories to ensure compatibility.
4. Measure output voltage before connecting device. This helps avoiding potential damage.
When servicing the unit, AC mains should be removed.
5. Connect devices to be powered:
a. For AL400ULX Power Supply: connect devices to the terminals marked [+ DC –] (Fig. 1, pg. 4).
b. For other Power Distribution Models: connect devices to be powered to the terminal pairs 1 to 4 marked
[1P & 1N] through [4P & 4N] (Fig. 2a & 2b, pg. 7) or 1 to 8 marked [1P & 1N] through [8P & 8N]
(Fig. 3a & 3b, pg. 7), carefully observing correct polarity.
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result
in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
Connect one (1) 12VDC battery to the terminals marked [+ BAT –] for 12VDC operation.
Use two (2) 12VDC batteries wired in series for 24VDC operation.
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1a, pg. 4) supervisory
relay outputs.
Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be
utilized to visually indicate that AC power is on. To delay report for 6 hours cut “AC Delay” jumper
(Fig. 1b, pg. 4).
8. Please ensure that the cover is secured with the provided key lock.
Use 14 AWG or larger for all power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for the proper
voltage level (Power Supply Voltage Output Specifications Chart, pg. 3).Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage
both at the battery terminal and at the board terminals marked [+ BAT –] to ensure that there is no break in the
battery connection wires.
Note: Maximum charging current under discharges is 0.7A.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.
AL400ULX Series - 5 -
Wiring:
Page 6
LED Diagnostics:
Power Supply Board
Red (DC)Green (AC)Power Supply Status
ONONNormal operating condition.
ONOFFLoss of AC. Stand-by battery supplying power.
OFFONNo DC output.
OFFOFFLoss of AC. Discharged or no stand-by battery. No DC output.
+ DC –12VDC @ 4A or 24VDC @ 3A continuous power-limited output.
AC Fail
NC, C, NO
Bat Fail
NC, C, NO
+ BAT –Stand-by battery connections. Maximum charge current 0.7A.
Connect 115VAC 60Hz. to these terminals: L to Hot, N to Neutral.
Do not use the [G] terminal.
Indicates loss of AC power, e.g. connect to annunciator/alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. AC Fail condition will
report approximately within one (1) minute after loss of AC. To delay report for 6 hours
cut jumper J1 on the Power Supply Board (AC trouble output delay option). If this mode is
selected, the Power Supply Board must be reset by removing all power to it for 30 seconds.
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized
when DC power is present. Contact rating 1A @ 28VDC. Low battery conditions will
report approximately 21VDC (24VDC output setting) or approximately 10.5VDC (12VDC
output setting). Battery presence detection will report approximately 1 minute after battery
remains undetected (missing or removed).
Power Distribution Module
Terminal Legend
PD4UL/PD4ULCBPD8UL/PD8ULCB
1P to 4P1P to 8PPositive DC power outputs.
1N to 4N1N to 8NNegative DC power outputs.
- 6 - AL400ULX Series
Function/Description
Page 7
Power Distribution Module(s):
Replace fuses with the same type and rating 3.5A, 250V.
()
Fig. 2a - PD4UL Power Distribution Board Fig. 2b - PD4ULCB - Power Distribution Board
Non Power-Limited Outputs Class 2 Power-Limited Outputs
F1F2F3F4
2N
2P
1N
1P
1P-4P Power Outputs,
()
1N-4N Common Outputs
3P
DC Output to devices
3N
4N
4P
From Power Supply
(Factory Installed)
LED
Board
F1F2F3F4
2N
2P
1N
1P
POWER OUTPUTS
()
1N-4N Common Outputs
3P
DC Output to devices
1P-4P Power Outputs,
3N
4N
4P
From Power Supply
(Factory Installed)
LED
INPUT
Board
Fig. 3a - PD8UL Power Distribution Board Fig. 3b - PD8ULCB - Power Distribution Board
Non Power-Limited Outputs Class 2 Power-Limited Outputs
Replace fuses with the same type and rating 3.5A, 250V.
1 2 3 4 5 6 7 8
P
FUSED POWER OUTPUTS
N
COMMON POWER OUTPUTS
DC Output to devices
1P-8P Power Outputs,
()
1N-8N Common Outputs
From Power Supply
(Factory Installed)
D1
R1
Board
LED
INPUT
1 2 3 4 5 6 7 8
P
FUSED POWER OUTPUTS
N
COMMON POWER OUTPUTS
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
D1
LED
R1
INPUT
From Power Supply
Board
(Factory Installed)
AL400ULX Series - 7 -
Page 8
Appendix A - UL Listed Compatible Devices
A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with AL400ULX output.
System Sensor
Smoke Detector/Base
Detector Type
B112LPBase0.1236
B114LPBase**
B404BBase**
DH100ACDCPhotoelectric0.150.70
DH100ACDCLPPhotoelectric0.150.70
DH100ACDCLPWPhotoelectric0.150.70
DH400ACDCIIonization Duct2595
DH400ACDCPPhotoelectric Duct2595
1112/24/DIonization0.0550
1424Ionization0.1041
1451 (w/B402B Base)Ionization0.1039
2112/24ATRPhotoelectric0.5060/70
2112/24AITRPhotoelectric0.5060/70
2112/24/DPhotoelectric0.0550
2112/24T/DPhotoelectric w/135
2112/24TSRBPhotoelectric w/135
o
o
Thermal Supervisory Relay1545
Thermal0.0550
2312/24TBPhotoelectric0.1250
2412 (12 volt)Photoelectric0.1277
2424Photoelectric0.1041
2451Photoelectric0.1039
2451TH (with/B402B Base)Photoelectric0.1039
2W-MODLoop Test/Maintenance Mod.3050
4W-B (12/24 volt)Photoelectric I
3
4WT-B (12/24 volt)Photoelectric I3 w/Therm0.0523
3
4WTA-B (12/24 volt)I
4WTR-B (12/24 volt)I
4WITAR-B (12/24 volt)I
Photo w/Therm/Sounder0.0535
3
3
Photo w/Therm/Relay0.0535
Photo w/Isolated Therm/Sounder/Relay0.0550
2W-MOD2I3 Loop Test/Maintenance Mod.0.05*
RRS-MODI
3
Reversing Relay/Sync Module0.05*
6424Projected Beam1028.4
Beam 1224(S)Projected Beam1738.5
* Contact manufacturer for current draws.
Max Stand-by
Current (mA)
0.0523
Alarm
Current (mA)
A.2 Relays
Table A-2 below lists relays compatible with AL400ULX output.
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A.
IIAL400ULX Series C02R