Altronix AL400ULXPD16R Installation Guide

Page 1
AL400ULX Series
Power Supply/Charger
Installation Guide
Models Include:
AL400ULX
AL400ULPD4
- Four (4) Fuse Protected Outputs.
AL400ULPD8
- Eight (8) Fuse Protected Outputs.
AL400ULXPD16
- Sixteen (16) Fuse Protected Outputs.
For a red enclosure add an “R” suffix to the part #, e.g. AL400ULPD8R
Rev. 102512
AL400ULPD4CB
- Four (4) PTC Protected Outputs.
AL400ULPD8CB
- Eight (8) PTC Protected Outputs.
AL400ULXPD16CB
- Sixteen (16) PTC Protected Outputs.
More than just power.
TM
Page 2
Altronix AL400ULX is a power supply that converts a 115VAC, 60Hz input to a 12VDC or 24VDC regulating
Altronix Corp.
output (see specifications below). The AL400ULX is a base power supply unit for the UL Listed multi-output power supply/charger series: AL400ULPD4, AL400ULPD4CB, AL400ULPD8, AL400ULPD8CB, AL400ULXPD16, AL400ULXPD16CB (Refer to AL400ULX Series Power Supply Configuration Reference Chart below).
AL400ULX Series Power Supply Configuration Reference Chart:
Overview:
Altronix Model Number
AL400ULX AL400ULXX AL400ULXR
AL400ULPD4
AL400ULPD4CB
AL400ULPD8
AL400ULPD8CB
AL400ULXPD16
AL400ULXPD16CB
Accessory Power
Distribution
Module(s)
Number of Outputs
Fused Outputs
PTC Outputs (auto-resettable)
12VDC Total
Output Current (A)
1 4 3 2.5
PD4UL
P
4
PD4ULCB
PD8UL
PD8ULCB
Two (2) PD8UL
P
8
P
P
3.5
4 3
P
3.5
16
Two (2)
PD8ULCB
P
24VDC Total
Output Current (A)
Output Rating (A) per Output
Power Supply
Input Fuse Rating
Power Supply
5A/
15A/
250V
32V
3.5 5A/
15A/
250V
32V
2.5
5A/
15A/
250V
32V
2.5
5A/
15A/
250V
32V
2.5
Agency
Output Fuse Rating
Listings
140 58th St. Brooklyn, NY
NYC
California
Dept. of
State Fire
Buildings
Marshal
UL Listings and
File Numbers
UL File # S4707
UL 294
UL Listed for Access
Control
System Units.
-------------­UL 603
UL Listed for Power
Supplies for Use
with Burglar-Alarms
Systems.
--------------
UL 1069
UL Listed Hospital
Signaling and Nurse
Call Equipment.
--------------
UL 1481
UL Listed for Power
Supplies for Fire
Protective Signaling
Systems
--------------
“Signal Equipment”
Evaluated to
CSA Standard C22.2
No.205-M1983
- 2 - AL400ULX Series
Page 3
Specifications:
ON - 12V
Input:
• Input 115VAC, 60Hz, 3.5A.
• AC input and DC output LED indicators.
Output:
• Class 2 Rated power-limited output(s).
• 12VDC or 24VDC selectable output(s). Burglar Alarm Aplications (UL 603): 12VDC = 10VDC-13.2VDC. 24VDC = 20VDC-26.4VDC.
• 4A total supply current at 12VDC or 3A total supply current at 24VDC.
• Filtered and electronically regulated output(s).
• Short circuit and thermal overload protection.
Power Supply Output Specifications:
Output Switch Position
12VDC SW1 - ON
24VDC SW1 - OFF
Stand-by Specifications (total current shown):
Output
12VDC / 40AH Battery
24VDC / 12AH Battery --------
24VDC / 40AH Battery
4 hr. of Stand-by and
5 Minutes of Alarm
Stand-by = 4.0A
Alarm = 4.0A
Stand-by = 3.0A
Alarm = 3.0A
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when AC fails.
• Maximum charge current 0.7A.
• Zero voltage drop when switched over to battery backup.
Supervision:
• AC fail supervision (form “C” contacts).
• Low battery and battery presence supervision (form “C” contacts).
Additional Features:
• Power supply, enclosure, cam lock and battery leads.
• All models are available in red enclosure (add an “R” suffix to the part #, e.g. AL400ULPD8R).
ON
OFF - 24V
24 hr. of Stand-by and
5 Minutes of Alarm
Stand-by = 1.0A
Alarm = 4.0A
Stand-by = 200mA
Alarm = 3.0A
Stand-by = 1.0A
Alarm = 3.0A
60 hr. of Stand-by and
5 Minutes of Alarm
Stand-by = 300mA
Alarm = 4.0A
--------
Stand-by = 300mA
Alarm = 3.0A
AL400ULX Series - 3 -
Page 4
Fig. 1
Power
Distribution
Module(s)
+ DC ---
NC C NO NC C NO
+ BAT ---
AC DC Bat
Risk of Fire,
Replace Fuses
As Marked
AC Fail
Bat Fail
J1
SW1
5A 250V
15A 250V
AC Delay
15
L G N
Door
CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture.
Green
Lead
Battery connection (non power limited)
Switch Position: 24VDC = SW1 OFF 12VDC = SW1 ON
Wire Strap (from Enclosure to Door)
115VAC
power mains
non-power
limited
Battery & AC
Supervision
Circuit
(power limited)
Class 1
-
Divider
power limited
For 12VDC Operation
use hook-up in the
inset on the right
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power limited wiring separate from non-power limited. Use minimum 0.25" spacing.
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
SW1
Battery & AC Supervision
Circuit
(power-limited)
NC C NO NC C NO AC Fail
Bat Fail
J1
AC Delay
OFF - 24V ON - 12V
ON
1
OFF - 24V
ON - 12V
ON
1
Fig. 1a
Fig. 1b
Fig. 1c
- 4 - AL400ULX Series
Page 5
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with
Installation Instructions:
all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 11, 12). Secure enclosure to earth ground.
2. Set the unit to the desired DC output voltage by setting SW1 (Fig. 1c, pg. 4) to the appropriate position (Power Supply Output Specification Chart, pg. 3).
3. Secure cabinet to earth ground. Connect AC power (115VAC / 60 Hz to the terminals marked [L, N] (Fig. 1, pg. 4). Use 14 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power-limited circuits (AC fail/Low Battery reporting). Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input,
Battery Wires). Minimum 0.25” spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
For Fire Alarm applications the outputs are “Special Applications” only see list (refer to Appendix A, pg. 8). For other devices contact Underwriters Laboratories to ensure compatibility.
4. Measure output voltage before connecting device. This helps avoiding potential damage. When servicing the unit, AC mains should be removed.
5. Connect devices to be powered: a. For AL400ULX Power Supply: connect devices to the terminals marked [+ DC –] (Fig. 1, pg. 4). b. For other Power Distribution Models: connect devices to be powered to the terminal pairs 1 to 4 marked [1P & 1N] through [4P & 4N] (Fig. 2a & 2b, pg. 7) or 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3a & 3b, pg. 7), carefully observing correct polarity.
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked [+ BAT –] for 12VDC operation. Use two (2) 12VDC batteries wired in series for 24VDC operation.
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1a, pg. 4) supervisory relay outputs. Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be utilized to visually indicate that AC power is on. To delay report for 6 hours cut “AC Delay” jumper (Fig. 1b, pg. 4).
8. Please ensure that the cover is secured with the provided key lock.
Use 14 AWG or larger for all power connections. Note: Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions the DC output voltage should be checked for the proper voltage level (Power Supply Voltage Output Specifications Chart, pg. 3). Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at the battery terminal and at the board terminals marked [+ BAT –] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 0.7A. Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.
AL400ULX Series - 5 -
Wiring:
Page 6
LED Diagnostics:
Power Supply Board
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Red (Bat) Battery Status
ON Normal operating condition. OFF Battery fail/low battery.
Power Distribution Module
Green Power Distribution Module Status
ON Normal operating condition.
OFF No Power Output.
Terminal Identification:
Power Supply Board
Terminal Legend Function/Description
L, G, N
+ DC – 12VDC @ 4A or 24VDC @ 3A continuous power-limited output.
AC Fail NC, C, NO
Bat Fail NC, C, NO
+ BAT – Stand-by battery connections. Maximum charge current 0.7A.
Connect 115VAC 60Hz. to these terminals: L to Hot, N to Neutral. Do not use the [G] terminal.
Indicates loss of AC power, e.g. connect to annunciator/alarm panel. Relay normally ener­gized when AC power is present. Contact rating 1A @ 28VDC. AC Fail condition will report approximately within one (1) minute after loss of AC. To delay report for 6 hours cut jumper J1 on the Power Supply Board (AC trouble output delay option). If this mode is selected, the Power Supply Board must be reset by removing all power to it for 30 seconds.
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. Low battery conditions will report approximately 21VDC (24VDC output setting) or approximately 10.5VDC (12VDC output setting). Battery presence detection will report approximately 1 minute after battery remains undetected (missing or removed).
Power Distribution Module
Terminal Legend
PD4UL/PD4ULCB PD8UL/PD8ULCB
1P to 4P 1P to 8P Positive DC power outputs. 1N to 4N 1N to 8N Negative DC power outputs.
- 6 - AL400ULX Series
Function/Description
Page 7
Power Distribution Module(s):
Replace fuses with the same type and rating 3.5A, 250V.
()
Fig. 2a - PD4UL Power Distribution Board Fig. 2b - PD4ULCB - Power Distribution Board Non Power-Limited Outputs Class 2 Power-Limited Outputs
F1 F2 F3 F4
2N
2P
1N
1P
1P-4P Power Outputs,
()
1N-4N Common Outputs
3P
DC Output to devices
3N
4N
4P
From Power Supply
(Factory Installed)
LED
Board
F1 F2 F3 F4
2N
2P
1N
1P
POWER OUTPUTS
()
1N-4N Common Outputs
3P
DC Output to devices 1P-4P Power Outputs,
3N
4N
4P
From Power Supply
(Factory Installed)
LED
INPUT
Board
Fig. 3a - PD8UL Power Distribution Board Fig. 3b - PD8ULCB - Power Distribution Board Non Power-Limited Outputs Class 2 Power-Limited Outputs
Replace fuses with the same type and rating 3.5A, 250V.
1 2 3 4 5 6 7 8
P
FUSED POWER OUTPUTS
N
COMMON POWER OUTPUTS
DC Output to devices 1P-8P Power Outputs,
()
1N-8N Common Outputs
From Power Supply
(Factory Installed)
D1
R1
Board
LED
INPUT
1 2 3 4 5 6 7 8
P
FUSED POWER OUTPUTS
N
COMMON POWER OUTPUTS
DC Output to devices 1P-8P Power Outputs,
1N-8N Common Outputs
D1
LED
R1
INPUT
From Power Supply
Board
(Factory Installed)
AL400ULX Series - 7 -
Page 8
Appendix A - UL Listed Compatible Devices
A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with AL400ULX output.
System Sensor Smoke Detector/Base
Detector Type
B112LP Base 0.12 36
B114LP Base * *
B404B Base * *
DH100ACDC Photoelectric 0.15 0.70
DH100ACDCLP Photoelectric 0.15 0.70
DH100ACDCLPW Photoelectric 0.15 0.70
DH400ACDCI Ionization Duct 25 95
DH400ACDCP Photoelectric Duct 25 95
1112/24/D Ionization 0.05 50
1424 Ionization 0.10 41
1451 (w/B402B Base) Ionization 0.10 39
2112/24ATR Photoelectric 0.50 60/70
2112/24AITR Photoelectric 0.50 60/70
2112/24/D Photoelectric 0.05 50
2112/24T/D Photoelectric w/135
2112/24TSRB Photoelectric w/135
o
o
Thermal Supervisory Relay 15 45
Thermal 0.05 50
2312/24TB Photoelectric 0.12 50
2412 (12 volt) Photoelectric 0.12 77
2424 Photoelectric 0.10 41
2451 Photoelectric 0.10 39
2451TH (with/B402B Base) Photoelectric 0.10 39
2W-MOD Loop Test/Maintenance Mod. 30 50
4W-B (12/24 volt) Photoelectric I
3
4WT-B (12/24 volt) Photoelectric I3 w/Therm 0.05 23
3
4WTA-B (12/24 volt) I
4WTR-B (12/24 volt) I
4WITAR-B (12/24 volt) I
Photo w/Therm/Sounder 0.05 35
3
3
Photo w/Therm/Relay 0.05 35
Photo w/Isolated Therm/Sounder/Relay 0.05 50
2W-MOD2 I3 Loop Test/Maintenance Mod. 0.05 *
RRS-MOD I
3
Reversing Relay/Sync Module 0.05 *
6424 Projected Beam 10 28.4
Beam 1224(S) Projected Beam 17 38.5
* Contact manufacturer for current draws.
Max Stand-by Current (mA)
0.05 23
Alarm
Current (mA)
A.2 Relays
Table A-2 below lists relays compatible with AL400ULX output.
Manufacturer Model Current (mA) Manufacturer Model Current (mA)
PR-1 PR-2
System Sensor
PR-3
EOLR-1
R-10T R-14T
- 8 - AL400ULX Series
15 30 30 30
System Sensor
23 23
R-20T R-24T R-10E R-14E R-20E R-24E
40 40 23 23 40 40
Page 9
Notes:
AL400ULX Series - 9 -
Page 10
Notes:
- 10 - AL400ULX Series
Page 11
Enclosure Dimensions (BC300):
(
)
(
)
(
)
AL400ULX, AL400ULXR, AL400ULPD4, AL400ULPD4CB, AL400ULPD8, AL400ULPD8CB
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
1.40”
(36mm)
1.20”
(31mm)
0.75”
(19mm)
1.40”
(36mm)
4.85”
(123mm)
12.5”
(318mm)
11.0”
(279mm)
4.85”
(123mm)
1.40”
(36mm)
0.75”
(19mm)
1.20”
(31mm)
0.9375” (24mm)
3.25”
(83mm)
1.20”
(31mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
3.25”
(83mm)
(330mm)
1.0”
(25mm)
5.10”
(130mm)
13.0”
6.5625”
(167mm)
0.9375” (24mm)
3.25”
(83mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
25mm
10.5”
267mm
1.0”
25mm
AL400ULX Series - 11 -
Page 12
Enclosure Dimensions (BC400):
AL400ULXX, AL400ULXXR, AL400ULXPD4, AL400ULXPD4CB, AL400ULXPD8, AL400ULXPD8CB, AL400ULXPD16, AL400ULXPD16CB
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
1.5”
(38.1mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
0.91”
(23.114mm)
1.5”
(38.1mm)
1.1”
(27.94mm)
4.615”
(117.22mm)
12.23”
(310.64mm)
4.615”
(117.22mm)
(38.1mm)
1.5”
1.1”
(27.94mm)
1.75”
(44.45mm)
0.91”
(23.114mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
4.5”
(114.3mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
2.0”
(50.8mm)
2.0”
(50.8mm)
5.0”
(127.0mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
(27.94mm)
1.5”
(38.1mm)
15.5”
(393.7mm)
5.0”
(127.0mm)
0.79”
1.1”
(20.06mm)
1.75”
(44.45mm)
1.25”
(31.75mm)
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A. IIAL400ULX Series C02R
- 12 - AL400ULX Series
MEMBER
Loading...