Altronix AL400ULPD4CBR, AL400ULPD4R Specsheet

AL400ULX Series
Power Supply/Chargers
Description
Altronix AL400ULX series power supply/chargers convert a 115VAC, 60Hz input into a
single fused, four (4), eight (8) or sixteen (16) fuse or PTC protected outputs. Outputs
are selectable for 12VDC with a total of 4A max. or 24VDC with a total of 3A max.
Key Features
- Available with 1, 4, 8 or 16 outputs.
- Short circuit and overload protection.
AL400ULPD8
- Fused or PTC ptotected outputs.
- Supervision:
- AC Fail
- Built-in charger for sealed lead acid or gel type batteries.
- Instantaneous transfer to stand-by batteries.
*AL400ULXJ’s enclosure is red. For grey enclosure order model AL400ULXJG
AL400ULX Series Power Supply Configuration Reference Chart
Altronix Model Number
AL400ULX AL400ULXX AL400ULXJ(G) AL400ULPD4 AL400ULPD4CB AL400ULPD8 AL400ULPD8CB AL400ULXPD16 AL400ULXPD16CB
12VDC
Total Output Rating
24VDC
Total Output Rating
(A)
4A 3A 3.5A 5A/250V 15A/32V
(A)
Input
Rating:
115VAC,
60Hz
Input Fuse
Rating
Power Supply Output
Fuse
Rating
- AC input and DC output options.
- UL Listed in the U.S. and Canada.
- CSFM and MEA Approved.
- Lifetime Warranty / Made in the U.S.A.
- All units are available in grey or red enclosure*.
Power
Distribution
Modiule
N/A 1 3.5A
PD4UL 4 3.5A Two (2) 7AH
PD4ULCB 4 2.5A Two (2) 7AH
PD8UL 8 3.5A Two (2) 7AH
PD8ULCB 8 2.5A Two (2) 7AH
Two (2) PD8UL 16 3.5A Two (2) 12AH
Two (2) PD8ULCB 16 2.5A Two (2) 12AH
Number
of
Outputs
Fused
Output
Ratings
PTC Auto-Resettable Outputs Ratings
Accommodates
Batteries
Two (2) 7AH Two (2) 12AH Two (2) 18AH
Rev. AL400ULX-01312018
AL400ULX Series
Power Supply/Chargers
Specifications
Input
Voltage 115VAC, 60Hz, 3.5A max. Fusing 5A / 250V.
Outputs
Voltage 12VDC or 24VDC selectable. Current 4A @ 12VDC or 3A @ 24VDC continuous max. Protection Fused 3.5A / PTC 2.5A. Other Overvoltage protection.
Filtered and regulated.
Back-up Battery (not included)
Capacity 7AH / 12VDC (1 or 2 within enclosure). 12AH / 12VDC (requires larger “X” enclosure). 18AH / 12VDC (requires larger “J” enclosure). 40 AH / 65 AH (requires separate enclosure).
Type Sealed lead acid or gel type. Fuse Rating 15A @ 32VDC. Failover Upon AC loss, instantaneous.
Supervision
AC Failure Form “C” contacts. Battery Form “C” contacts.
Indicators (LED)
Input 115VAC is present. DC Output Powered. Battery Discharged or not connected.
Agency Listings All Models:
UL:
UL294 Access Control System Units. UL603 Power Supplies for Use with
Burglar-Alarms Systems. UL 1069 UL Listed Hospital Signaling and
Nurse Call Equipment. UL1481 Power Supplies for
Fire Protective Signaling Systems.
cUL:
CSA C22.2 No.205 Signal Equipment.
AL400ULX and AL400ULXX only:
CSFM California State Fire Marshall Approved. MEA NYC Department of Buildings Approved. FM Factory Mutual Approved.
Physical and Environmental
Dimensions (H x W x D)
AL400ULX, AL400ULPD4(CB), AL400ULPD8(CB):
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm). AL400ULXX, AL400ULXPD16(CB):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm). AL400ULXJ:
18” x 14.5” x 4.625” (457.2mm x 368.3mm x 117.48mm).
Product / Shipping Weight (approx.)
Model Product Weight Shipping Weight
AL400ULX 6.95 lbs. (3.15 kg) 8.75 lbs. (4.0 kg) AL400ULXX 8.55 lbs. (3.88 kg) 10.85 lbs. (4.92 kg) AL400ULXJ(G) 11.5 lbs. (5.22 kg) 13.7 lbs (6.21 kg) AL400ULPD4(CB) 7.1 lbs. (3.22 kg) 8.9 lbs (4.04 kg) AL400ULPD8(CB) 7.2 lbs. (3.27 kg) 9.0 lbs (4.08 kg) AL400ULXPD16(CB) 7.3 lbs. (3.31 kg) 9.1 lbs (4.13 kg)
Temperature Operating 0ºC to 49ºC (32ºF to 120ºF). Storage -20ºC to 70ºC (-4ºF to 158ºF). Relative Humidity 85% +/-5%. BTU/Hr (approx.):
12VDC: 25 BTU/Hr. 24VDC: 37 BTU/Hr.
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
Loading...