Operation and Care Manual #8452/53/55
PG.2
Knowledge of proper procedures is essential to the safe
operation of electrically energized equipment. In
accordance with generally accepted product safety labeling
guidelines for potential hazards, the following signal
words and symbols are used throughout this manual.
Used to indicate the presence of a hazard
which will cause severe personal injury,
death, or substantial property damage in
the event the statement is ignored.
Warning used to indicate the presence of a
hazard which can cause personal injury and
possibly death, or major property damage,
in the event the statement is ignored.
Caution is used to indicate the presence of a
hazard which will or can cause minor
personal injury or property damage in the
event the statement is ignored.
Used to indicate the presence of an
electrical hazard which will or can cause
personal injury or property damage in the
event the statement is ignored.
Note is used to notify personnel of
installation, operation, or maintenance
information which is important but not
hazard related.
HAZARD COMMUNICATION STANDARD (HCS)
The procedure in this manual may include the use of
chemical products. These chemical products will be
highlighted with bold face letters followed by the
abbreviation (HCS). See the
Hazard Communications
Standard
section of this manual for the appropriate
Material Safety Data Sheet(s).
1. This ventilator hood system is designed as part of a
deep fat fryer system. No other use of this product is
authorized or recommended.
2. This ventilator and attendant fryer are intended for
use in commercial establishments where all operators
are familiar with the appliance use, limitations, and
associated hazards. Operating instructions and
warnings must be read and understood by all
operators and users.
3. This ventilator hood system is designed to reduce odor
emissions, but will not completely eliminate cooking
odors. Air exchange at the installation site must
comply with the requirements of the local
jurisdictional authority. To ensure that odors do not
build up, recommended minimum air exchange is
400 cfm (11,3m
3
) into and out of the site.
4. This equipment is made in the USA and has American
size hardware.
5. Any trouble shooting guides, component views or
parts lists included in this manual are for general
reference only, and are intended for use by qualified
technical personnel.
6. This manual should be considered a permanent part of
this appliance. The manual with all supplied
instructions, diagrams, schematics, part breakdowns,
notices, and labels must remain with the appliance if it
is sold or moved to another location.
SAFETY PROCEDURES
PRECAUTIONS & GENERAL INFORMATION
1. Verify vertical clearances. Ventilator fryers require a
minimum of 96" (244cm) floor to overhead to allow for
adequate air circulation.
2. Verify that the ventilator hood assembly is properly
and securely assembled to the fryer before beginning
the installation procedure.
3. If a remote pull station is to be used, replace the rear
casters with fixed legs.
4. Adjust the fixed legs with a spirit level until the unit
is level front-to-back and side-to-side.
NOTE
EQUIPMENT SET-UP PRECAUTIONS