Alpha INEX 100A STS User Manual

INEX 100A STS Module and MBS+PDU User Manual
019-061-B2
This page intentionally left blank.
Argus Technologies reserves the right to make changes to the products and information contained in this document without notice. Copyright 2009 Argus Technologies Ltd. Argus Printed in Canada.
®
is a registered trademark of Argus Technologies Ltd. All Rights Reserved.
INEX 100A STS Module and MBS+PDU User Manual
019-061-B2
Applies to 019-061-10, 030-440-10, 020-438-10, and 018-593-1 0.
The following documents and drawings are included in this manual to provide the necessa ry information required for installation, operation and fault diagnosis of the unit:
• Specifications: 019-061-B1
• Installation and Operation Instructions: 019-061-C0
• Service Centers: 048-693-10
Argus Technologies Ltd. 019-061-B2 Rev A WC
Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS and INEX are registered trademarks of Argus Technologies Ltd. All Rights Reserved.
This page intentionally left blank.
Specifications for INEX 100A STS Module and MBS+PDU

DC Auxiliary Power Input

Operating Range: 40 to 60Vdc within rated limits

AC Input

Voltage Range: 110/115/120Vac: 89 to 138Vac
208/220/230/240Vac: 176 to 276Vac
Over Voltage Threshold: 276 / 138Vac
Under Voltage Threshold: 176 / 89Vac
Back-feed Protection: Comply with safety requirement
Redundant Power Supply Design: Startup by priority source or alternative
NOTE: the over/under voltage must be set by controller, if there is no additional setting, STS will adopt the widest range
to set over/under voltage in order to guarantee its performance, for 110/115/120Vac system, the range is 89Vac (under voltage point) to 138Vac (over voltage point), for 208/220/230/240Vac system, the range is 176Vac (under voltage point) to 276Vac (over voltage point). But once the STS is set by user, it will keep the setting whether a controller exists or not, until such time that the STS is set by user again or next time the source connected to STS is changed from 120V (110/115/120) to 230V (208/220/230/240) or 230V (208/220/230/240) to 120V (110/115/120).

AC Output

Waveform: Sinusoidal
Nominal Output Voltage: Same as mains AC or the output of inverter modules
Permissible Frequency Area: Max. ±2.5% (synchronize area of inverter)
Transfer Time: Typical 1/4 cycle, DIN VDE 0558 Part 5; IEC 146-4
Rated Power: 100A for 120 / 230Vac
Operation Methods: Inverter priority / Mains priority
Over Load Capability: 1.2 x Inom 20s
1.6 x Inom 5s 3200A 10ms (Mains bypass) Inom = 100A
Argus Technologies Ltd. 019-061-B1 Rev A WC
Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved. Page 1 of 2
Specifications for INEX 100A STS Module and MBS+PDU Continued

Mechanical

STS Module: Dimensions: 88mm H x 218mm W x 270mm D
[3.5" H x 8.6" W x 10.6" D] Weight: 2.1 kg (4.6 lb.)
STS Shelf: Dimensions: 88.1mm H x 483mm W x 330mm D
[3.5" H x 19" W x 13" D] Weight: 7.0 kg (15.4 lb.)
Hot Swappable: STS hot swappable only available when MBS at Mains Bypass and
Inverter Bypass position
Mechanical Bypass Switch Requirement: The STS module used with a Mechanical Bypass Switch module shall
provide voltage free system maintenance. It should be interlocked with the static switch module so that the static switch module cannot be removed without the maintenance bypass being activated.
Force Cooling: Two fans
Alarm Relay: Dry contact alarm output

Environmental

Operating Temperature: -20 to +70°C (-4 to +158°F)
-20 to +50°C (-4 to +122°F) with full performance
Storage Temperature: -30 to +85°C (-22 to +185°F)
Operating Humidity: 0 to 95% relative, non-condensing
Heat Dissipation: Forced air cooling
Operating Altitude: 1500m (4922 feet)
Audible Noise: 55dB ETS 300 753 Class 3.1

Standards

Safety Compliance: EN 62040-1-1/IEC 62310-1/UL-1778
Certification: CE, UL
RoHS: Compliant
EMC: EN55022 Class B
MTBF: >200,000 hours as per Telcordia SR-332
The above information is valid at the time of publication. Consult factory for up-to-date ordering information. Specifications are subject to change without notice.
Argus Technologies Ltd. 019-061-B1 Rev A WC
Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved. Page 2 of 2

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS
This section contains important instructions that should be followed during the installation and maintenance of equipment and batteries. Please read all of the instructions before operating the equipment, and save this manual for future reference.
The following safety symbols will be found throughout this manual, carefully read all information and abide by the instructions:
DANGEROUS VOLTAGE
This symbol indicates a dangerous voltage
exists in this area of the product.
GAS HAZARD
This symbol indicates a gas hazard
exists in the area of vented batteries.
NO MATCHES OR OPEN FLAMES
This symbol indicates a fire or explosive hazard
exists in the area of the product.
The following levels of warning will be used with the above symbols:
DANGER: You WILL be KILLED or SERIOUSLY INJURED if instructions are not followed closely. WARNING: You CAN be KILLED or SERIOUSLY INJURED if instructions are not followed closely. CAUTION: You CAN be INJURED or equipment can be DAMAGED if instructions are not followed closely.
Before using the product, read all instructions and cautionary markings on the product and any equipment connected to the product.
This unit is designed for indoor use only. Do not expose the product to rain or snow; install only in a clean, dry environment.
CAUTION – To reduce the risk of fire hazard, do not cover or obstruct the ventilation openings. Do not install the inverter in a zero-clearance compartment.
CAUTION – Unless otherwise noted, use of an attachment not recommended or sold by the product manufacturer may result in a risk of fire, electric shock, or injury to persons.
CAUTION – Do not operate the product if it has received a sharp blow, it has been dropped, or otherwise damaged in any way – return it to a qualified service center for repair.
CAUTION – Do not disassemble the product – call our qualified service centers for servici ng. Incorrect reassembling may result in a risk of electrical shock or fire.
WARNING – The input and output voltages of the product are hazardous. Extreme caution should be maintained when servicing or touching conductive components conne cted to the product.
Mechanical Safety
Power equipment can reach extreme temperatures under load. Use caution around sheet metal components and sharp edges.
Electrical Safety
WARNING To avoid a risk of fire and electric shock, make sure that existing wiring is in good condition and that wire is not undersized. Do not operate the inverter with damaged or substandard wiring.
Before working with any live battery or power system, follow these precautions:
Remove all metallic jewelry; e.g., watches, rings, metal rimmed glasses, necklaces.
Wear safety glasses with side shields (and prescription lenses if necessary) at all times during installation.
Use OSHA approved insulated hand tools.
Do not work alone under hazardous conditions. Ensure no liquids or wet clothes contact internal components.
Battery Safety
Servicing and connection of batteries shall be performed by, or under the direct supervision of, personnel knowledgeable of batteries and the required safety precautions.
Never reverse DC+ and DC- to battery. Keeps the battery away from heat sources including direct sunlight, open fires, microwave ovens and high-voltage
container. Temperatures over 60ºC may cause damage. Make sure the area around the battery is well ventilated. Always wear eye protection, rubber gloves, and a protective vest when working near batteries. Remove all
metallic objects from hands and neck. Use OSHA approved insulated hand tools. Do not rest tools on top of batteries. Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or eyes. Batteries contain or emit chemicals known to the State of California to cause cancer and birth defects or other
reproductive harm. Battery post terminals and related accessories contain lea d and lead compounds; wash hands after handling (California Proposition 65).
If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters your eye, immediately flood it with running cold water for at least twenty minutes and get medical attention immediately.
If you need to remove a battery, always remove the grounded terminal from the battery first. Make sure all accessories are off so you don’t cause a spark.
WARNING Follow battery manufacturer’s safety recommendations when working around battery systems.
WARNING Do not smoke or present an open flame when batteries (especially vented batteries) are on charge. Batteries vent hydrogen gas when on charge, which creates an explosion hazard.
Batteries are hazardous to the environment and should be disposed of safely at a recycling facility. Consult the battery manufacturer for recommended local authorized recycl ers.
Wiring Requirements
Inverter is intended to be installed as part of a permanently grounded electrical per the National Electric Code ANSI/NFPA 70 (current edition). This is the single point earth ground for the unit.
The ground on the inverter is marked with this symbol: G / The AC voltage and current on the inverter is marked with this symbol: L / N The DC voltage and current on the inverter is marked with this symbol:
TABLE OF CONTENTS
SECTION PAGE
1 INTRODUCTION .............................................................................................................................................................1
1.1 Scope of the Manual..................................................................................................................................... 1
1.2 Product Overview............................................................................................................... ...........................1
1.3 Illustration of Operation.................................................................................................................................2
1.4 STS Operating Principles.............................................................................................................................. 2
1.5 Voltage and Frequency Range.....................................................................................................................5
2 INSPECTION..................................................................................................................................................................6
2.1 Packing Materials..........................................................................................................................................6
2.2 Check for Damage........................................................................................................................................ 6
2.3 Handling and Storage ...................................................................................................................................7
3 INSTALLATION..............................................................................................................................................................8
3.1 Location......................................................................................................................................................... 8
3.2 Frame Assembly...........................................................................................................................................8
4 WIRING......................................................................................................................................................................10
4.1 Inverter Shelf Wiring With STS Chassis .....................................................................................................11
4.2 STS Shelf Wiring With MBS/PDU...............................................................................................................13
5 STS MODULE INSTALLATION......................................................................................................................................15
5.1 Installation Check........................................................................................................................................15
6 OPERATION................................................................................................................................................................16
6.1 MBS Position (0—Low, 1—High)................................................................................................................16
7 MAINT E NANCE AN D TROUBLESHOOTING...................................................................................................................... 18
7.1 Preventative Maintenance ..........................................................................................................................18
7.2 Troubleshooting Guide................................................................................................................................ 18
8 ARGUS CONVENTIONS................................................................................................................................................24
8.1 Numbering System......................................................................................................................................24
8.2 Acronyms and Definitions ...........................................................................................................................24
9 OUTLINE DRAWINGS...................................................................................................................................................25
This page intentionally left blank.
1 Introduction

1.1 Scope of the Manual

This instruction manual explains the features, installation, startup and maintenance of the INEX 100A STS Module and MBS+PDU.
NOTE: Images contained in this document are for illustrative purposes only and may not exactly match your installation.
1.2 Product Overview
The STS (Static Transfer Switch) module increases system reliability by automatically switching between the inverter output and the AC mains. By setting up the priority of operation mode, users can change the system status of “on line mode” or “off line mode”. The on line mode will keep the input power provided by inverter line and when inverter fails, the line will switch to AC utility line. In off line mode, the system power is always connected to the AC utility line and will switch to inverter power line when AC utility fails. The transfer time is less than 1/4 cycle which can avoid the power interruption. The reliable performance of the STS module can provide the maximum protection to the connected telecommunication equipment against possible da mage caused by the system power failure.
STS Module Features:
Small footprint and weight
Universal input range
Hot-swap replacement in shelf (w/ MBS option)
Back-feed protection
Redundant fan design
Fast transfer time, typically less than 1/4 cycle
Low audible noise <55dBa
No cross connect
Optional maintenance bypass switch function
Operation Priority Setup of transfer side by setting in Control Module
Figure 1–INEX 100A STS Module and MBS+PDU
Argus Technologies Ltd. 019-061-C0 Rev A WC
Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved. Page 1 of 26

1.3 Illustration of Operation

STS-100 is designed to avoid operational disruptions of critical loads. This automatic static transfer switch (STS) automatically transfers critical loads from the primary AC power source to an alternative AC power source in the event of interruption or abnormal conditions.
Alternative AC Source (UPS, generator, utility)
Sine Wave Output
STS Module
Inverter Output Voltage
Load
Power Line Communication Line
Figure 2–STS-100 operation illustrated
STS-100 transfers the critical load between power sources in less than 1/4 cycle upon loss of sou r ce. The fast transfer enables further redundancy in distribution, adding level of availability, flexibility and reliability to our customer’s power infrastructure.

1.4 STS Operating Principles

MBS Status Schematic operating principle of STS Description
Mains
Mains
Bypass
(P1)
Inverter
MBS Main Contact1
Backfeed Relay
Bypass Relay
SCR1
SCR2
MBS Main Contact2
Load
Mains Bypass:
Load is powered through the
MBS by Mains AC
STS can be removed from the
system
MBS can only be switched
from P1 to P2 position
SCR2 open, SCR1 and Back-
feed Relay closed
Argus Technologies Ltd. 019-061-C0 Rev A WC
Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved. Page 2 of 26
Loading...
+ 28 hidden pages