Alpha COM5 User Manual

Operation and Service
Commercial Generator Sets
Models:
COM5
TP-6482 8/06
California Proposition 65
Engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
Product Identification Information
Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory Number Accessory Description
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer
Model Designation
Serial Number
Table of Contents
Product Identification Information 2............................................................
Safety Precautions and Instructions 5........................................................
Introduction 9...............................................................................
Maintenance and Service Parts 10.............................................................
Service Assistance 10........................................................................
Section 1 Specifications 11...................................................................
1.1 System Description 11....................................................
1.2 Generator Set Functional Description 11....................................
1.3 Specifications 11.........................................................
1.4 Service Views 13........................................................
Section 2 Operation 15.......................................................................
2.1 Prestart Checklist 15.....................................................
2.2 Exercising Generator Set 15...............................................
2.3 Controller Operation 16...................................................
2.3.1 Control Connections 16...........................................
2.3.2 Remote Start/Stop Connections 18.................................
2.3.3 Starting Generator Set 18.........................................
2.3.4 Stopping Generator Set 19........................................
2.3.5 Status Indicators 19..............................................
2.3.6 Fault Shutdowns 20..............................................
2.3.7 Control Resetting Procedure (Following Fault Shutdown) 20...........
2.4 Circuit Protection 20......................................................
Section 3 Scheduled Maintenance 21..........................................................
3.1 Routine Maintenance 21..................................................
3.2 Service Schedule 22.....................................................
3.3 Service Access 23.......................................................
3.4 Lubrication System 24....................................................
3.4.1 Oil Check 24....................................................
3.4.2 Engine Oil Recommendation 25....................................
3.4.3 Oil Change Procedure 25.........................................
3.4.4 Low Oil Pressure Shutdown 26....................................
3.5 Air Cleaner Element and Precleaner 26.....................................
3.5.1 Precleaner Service 26............................................
3.5.2 Paper Element Service 27.........................................
3.6 Fuel System 27..........................................................
3.7 Battery 28...............................................................
3.8 Ignition System 29.......................................................
3.8.1 Ignition System Description 29.....................................
3.8.2 Spark Plug 29...................................................
3.9 Cooling System 29.......................................................
3.10 Electronic Governor 30...................................................
3.11 Exhaust System 30......................................................
3.12 Alternator Service 30.....................................................
Section 4 General Troubleshooting 31.........................................................
4.1 Troubleshooting Chart 32.................................................
4.2 Generator Set/Controller System Troubleshooting Flowcharts 34...............
Section 5 Component Testing and Adjustment 41..............................................
5.1 Operating Generator Set Outside Enclosure 41
5.1.1 Test Equipment 41...............................................
5.1.2 Lifting Generator Set 42...........................................
5.2 Circuit Protection 43......................................................
5.3 Voltage Rectifier 43......................................................
..............................
TP-6482 8/06 Table of Contents 3
Table of Contents, continued
5.4 Electronic Governor 43...................................................
5.4.1 Governor Checks 43.............................................
5.4.2 Stepper Motor Check 44..........................................
5.5 Ignition System 45.......................................................
5.5.1 Ignition Trigger 45................................................
5.5.2 Ignition Module 46...............................................
5.5.3 Ignition Coil 47...................................................
5.6 Starter 47...............................................................
5.7 Fuel System 48..........................................................
5.7.1 Fuel Regulators 49...............................................
5.7.2 Fuel Solenoid Valve 50...........................................
5.7.3 Fuel Conversion 50..............................................
5.7.4 Fuel System Recalibration 51......................................
5.7.5 Choke 51.......................................................
5.8 Alternator 52............................................................
5.8.1 Stator 52........................................................
5.8.2 Rotor 53........................................................
5.9 Fault Shutdown Switches 53...............................................
Section 6 Controller Operation and Test 55....................................................
6.1 Sequence of Operation 55................................................
6.1.1 Starting Sequence 55.............................................
6.1.2 Running Sequence 55............................................
6.1.3 Stopping Sequence 55............................................
6.2 Control Connections 56...................................................
6.2.1 Generator Set Master Switch 56...................................
6.2.2 Remote Start/Stop Connections 56.................................
6.2.3 Status Indicators 56..............................................
6.3 Fault Shutdowns 56......................................................
6.3.1 Control Resetting Procedure (Following Fault Shutdown) 57...........
6.4 Fault Shutdown Tests 57..................................................
6.4.1 Low Oil Pressure (LOP) Shutdown 58...............................
6.4.2 High Engine Temperature (HET) Shutdown 58.......................
6.4.3 Overcrank Shutdown 58..........................................
6.4.4 Overspeed Shutdown 58..........................................
6.5 Control Board Tests 59...................................................
6.5.1 Fuel Control Circuit 59............................................
6.5.2 Speed Sensing and Governor (Throttle Control) Circuits 59............
6.5.3 Start Circuits 59..................................................
6.5.4 Ignition Circuits 60...............................................
6.6 Voltage Programming Shunt 60............................................
6.7 Control Board Replacement 60............................................
Section 7 Disassembly/Reassembly 63........................................................
7.1 Disassembly Procedure 63................................................
7.2 Reassembly Procedure 65................................................
Section 8 Diagrams and Drawings 67..........................................................
Appendix A Abbreviations 71................................................................
Appendix B Common Hardware Application Guidelines 73.....................................
Appendix C General Torque Specifications 74.................................................
Appendix D Common Hardware Identification 75..............................................
Appendix E Common Hardware List 76
.......................................................
TP-6482 8/06Table of Contents4
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has severaltypesofsafety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury,death,orsubstantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury,death,or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Place the generator set start/stop switch in the STOP position. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
WARNING
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolatethe battery charger from explosive fumes.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid
can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. Ifbattery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a containerwith4L(1gal.)ofwaterand mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
TP-6482 8/06 5Safety Precautions and Instructions
Battery gases. Explosion can cause severe injury or death. Battery gases
can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Engine Backfire/Flash Fire
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building unless the exhaust gas is piped safely outside. Never operate the generator set where exhaust gas could accumulate and seep back inside a potentially occupied building.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Fuel System
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Check the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator
set with the air cleaner removed.
TP-6482 8/066 Safety Precautions and Instructions
Hazardous Noise
CAUTION
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets
not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Hazardous Voltage/ Electrical Shock
WARNING
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
High voltage test. Hazardous voltage can cause severe injury or death. Follow the instructions of the
test equipment manufacturer when performing high-voltage tests on the rotor or stator. An improper test procedure can damage equipment or lead to generator set failure.
Connecting the battery and the battery charger. Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies).
Hot Parts
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the alternator. Hot parts can cause severe injury or death.
Avoid touching the alternator field or exciter armature. When shorted, the alternator field and exciter armature become hot enough to cause severe burns.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
Moving Parts
WARNING
Hazardous voltage. Can cause severe injury or death.
Only authorized personnel should open the enclosure.
(600 volts and under)
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Moving rotor.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have
trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically.
(600 volts and under)
Rotating parts. Can cause severe injury or death.
Operate the generator set only when all guards, screens, and covers are in place.
Tightening the hardware. Flying projectiles can cause severe injury or death. Loose hardware can cause
the hardware or pulley to release from the generator set engine and can cause personal injury. Retorque all crankshaft and rotor hardware after servicing. Do not loosen the crankshaft hardware or rotor thrubolt when making adjustments or servicing the generator set. Rotate the crankshaft manually in a clockwise direction only. Turning the crankshaft bolt or rotor thrubolt counterclockwise can loosen the hardware.
TP-6482 8/06 7Safety Precautions and Instructions
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death.
Keep hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
Notice
NOTICE
Hardware damage. The engine and generator set may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of the bolt heads and nuts.
NOTICE
When replacing hardware, do not substitute with inferior grade hardware. Screws and nuts are
available in different hardness ratings. To indicate hardness, American Standard hardware uses a series of markings, and metric hardware uses a numeric system. Check the markings on the bolt heads and nuts for identification.
NOTICE
Electrostatic discharge damage.
Electrostatic discharge (ESD) damages electronic circuit boards. Prevent electrostatic discharge damage by wearing an approved grounding wrist strap when handling electronic circuit boards or integrated circuits. An approved grounding wrist strap provides a high resistance (about 1 megohm), not a direct short,to ground.
NOTICE
Fuse replacement. Replace fuses with fuses of the same ampere rating and type (for example: 3AB or 314, ceramic). Do not substitute clear glass-type fuses for ceramic fuses. Refer to the wiring diagram when the ampere rating is unknown or questionable.
TP-6482 8/068 Safety Precautions and Instructions
Introduction
This manual provides operation, troubleshooting, and repair instructions for model Alpha 5 and COM5 generator sets and controllers.
The generator sets use a Kohlerr CV-14 engine with modified ignition, governor, and fuel systems. Refer to the engine service manual for engine information not covered in this manual.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
The equipment service requirements are very important to safe and efficient operation. Inspect the parts often and perform required service at the prescribed intervals. Maintenance work must be performed by appropriately skilled and suitably-trained maintenance personnel familiar with generator set operation and service.
California Emission Certification
This engine/generator is certified to operate using natural gas or propane fuel.
This engine is certified with engine modifications made by the generator set manufacturer.
IMPORTANT ENGINE INFORMATION
THIS ENGINE MEETS U.S. EPA PHASE 1 AND CALIFORNIA 2006 AND LATER EMISSION CONTROL REGULATIONS FOR SI SORE
FAMILY DISPL (CC) MODEL NO. SPEC. NO. SERIAL NO.
EMISSION COMPLIANCE PERIOD: EPA: CARB: EXTENDED
THIS ENGINE IS CERTIFIED TO OPERATE ON: PROPANE / NATURAL GAS
REFER TO OWNER’S MANUAL FOR SAFETY, MAINTENANCE SPECS AND ADJUSTMENTS.
FOR SALES AND SERVICE IN US/CANADA, CALL:
1--800--544 -- 2444
WWW.KOHLERENGINES.COM
N11236
The Emission Compliance Period referred to on the Emission Control or Air Index label indicates the number of operating hours for which the engine has been shown to meet CARB emission requirements. The following table provides the Engine Compliance Period (in hours) associated with the category descriptor found on the certification label.
An engine or generator set with one of the following identification labels is certified to meet Small Off-Road
CARB Moderate, 125 Intermediate, 250 Extended, 500
Emission Compliance Period (hours)
Engine (SORE) emission standards for EPA/CARB.
Refer to certification label for engine displacement.
Exhaust Emission Control System for COM5 (CV14) is EM.
*
* Spark-Ignited Small Off-Road Engines
TP-6482 8/06 9Introduction
Maintenance and Service Parts
Figure 1 lists some routine maintenance and service parts for your generator set. Parts Catalog TP-6091 provides a complete list of replacement parts.
Part Description Part Number Part Description Part Number
Maintenance Parts: Test Fixtures:
Air Cleaner Foam Element 12 083 07 Controller board GM17820
Air Cleaner Paper Element 12 083 15 Cover plate GM23579
Exhaust gasket 12 041 03 Exhaust extension with test port GM23580
Fuse, 200 amp (36 volt) GM13492 Extended wiring harness GM23713
Fuse, 150 amp (48 volt) 337123 Silencer GM11509
Oil Filter 12 050 01
Spark Plug 24 132 03
Figure 1 Maintenance and Service Parts
Service Assistance
For professional advice on generator set power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric
D Visit the Kohler Power Systems website at
KohlerPowerSystems.com
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents included with the product
D Call toll free in the US and Canada 1-800-544-2444
D Outside the US and Canada, call the nearest regional
office
Headquarters Europe, Middle East, Africa (EMEA)
Kohler Power Systems ZI Senia 122 12, rue des Hauts Flouviers 94517 Thiais Cedex France Phone: (33) 1 41 735500 Fax: (33) 1 41 735501
Asia Pacific
Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
TP-6482 8/0610 Maintenance and Service Parts
Section 1 Specifications
1.1 System Description
The COM5 generator set provides reliable backup DC power to cable TV systems or telecommunication sites in place of, or in addition to, batteries. The COM5 is available in 36 and 48 VDC models. The generator set nameplate indicates the unit’s rated voltage.
The system batteries provide power at 36 or 48 volts. When power fails, the control system signals the generator set to start. The generator set provides DC power for continued or reserve operation of the system.
The COM5 generator set has both local and remote annunciation and control capabilities. The unit runs on natural gas or LP vapor.
1.2 Generator Set Functional Description
The COM5 generator set system consists of the generator set (engine and generator) and the control system. The generator set provides regulated DC voltage to the telecommunications power system. The control system provides complete control of the engine and generator, accepts remote control commands, and delivers local and remote annunciation of unit status. Internal control functions include start and stop logic, fault monitoring, unit voltage control, engine speed (rpm) governing, and local LEDs for fault annunciation. Status indicators include low oil pressure, high temperature, overspeed, overcrank, and engine running.
Under very light loads, the generator set operates at low speed. As loads increase, the control system maintains constant generator output voltage by increasing the generator set engine speed.
The Kohler CV14 engine drives a direct-connected, variable-speed, 3-phase, voltage-specific generator to produce high-frequency AC power. A 3-phase, full­wave rectifier in the control system rectifies the output to produce low-ripple, unfiltered DC power. The DC inline fuse provides protection for downstream devices in case of overload.
1.3 Specifications
Figure 1-1, Figure 1-2, and Figure 1-3 contain generator set, alternator, and engine specifications. Refer to Section 3, Scheduled Maintenance, for service details.
Item 36 VDC 48 VDC
Manufacturer Kohler
Dimensions, L x W x H, mm (in.)
Weight,dry,kg(lb.) 68 (150)
Rated kW* 5 3.5 or 5[
Rated voltage (after rectifier) 39 52
Rated amps 128 96
* Derate approximately 3.5% per 300 m (1000 ft.) over 600 m
(2000 ft.) above sea level. Derate 1% for each 5.5°C(10°F) increase in temperature above 49°C (120°F).
[ Check the generator set nameplate for the kW rating.
Figure 1-1 Generator Set Specifications
Item 36 VDC 48 VDC
Stator resistance, ohms 0.014 0.024
Stator type 3-Phase, 3-Lead,
Excitation method (rotor) Permanent-Magnet,
Coupling type Direct-to-Engine
Insulation (stator) Class 155, Epoxy
Winding material Copper
Stator-to-alternator adapter bolt torque, Nm (ft. lb.)
Flywheel-to-shaft bolt torque, Nm (ft. lb.) 67 (49.4)
Rotor-to-flywheel bolt torque, Nm (ft. lb.) 38 (28.0)
Fan-to-flywheel bolt torque, Nm (ft. lb.) 25 (18.4)
Figure 1-2 Alternator Specifications
495 x 380 x 514
(19.5 x 15 x 20.24)
Ungrounded
Brushless
Var n ish,
Vacuum-Impregnated
11 (8.1 )
TP-6482 8/06 11Section 1 Specifications
Item
Manufacturer Kohler
Make/model CV14
Cycle 4
Compression ratio 8.5:1
Displacement, cc (cu. in.) 398 (24.3)
Rated horsepower (using natural gas fuel), HP 10.5
Engine speed, rpm 2800--3600
Overspeed shutdown, rpm 3750
Bore,mm(in.) 87 (3.43)
Stroke,mm(in.) 67 (2.64)
Valve train Overhead Valve
Valve material:
Intake Steel
Exhaust Stelliter Face
Cylinders, qty. 1
Cylinder block material Aluminum w/Cast Iron Liners
Cylinder head material Aluminum
Piston rings: qty., type 2 Compression, 1 Oil
Crankshaft material Heat Treated, Ductile Iron Casting
Bearings: qty., type 2, Replaceable Sleeve
Governor Electronic
Starter motor Electric, Solenoid Shift
Lubrication system Full Pressure
Oil capacity (with filter and cooler), L (qt.) 2.0 (2.1)
Oil type (summer/winter) Synthetic 5W-30
Oil pressure, kPa (psi) 172--241 (25--35)
Low oil pressure, kPa (psi) 13.8--34.5 (2--5)
Fuel type Natural Gas or Propane
Fuel pressure, kPa (in. water column) 1.7to2.7(7to11)
Fuel consumption at 5 kW:
Natural gas, 1000 Btu/ft.
m3/hr. ( cfh)
Propane, 2516 Btu/ft.
m3/hr. (cfh) kg/hr. (lb./hr.) Lph (gph)
Battery voltage, VDC 12
Battery ground Negative
Battery recommendation (minimum) 425 CCA at -- 18_C(0°F)
Spark plug type (Kohler Part No.) 24 132 03
Spark plug gap, mm (in.) 0.75 (0.030)
Spark plug tightening torque, Nm (ft. lb.) 24.4--29.8 (18--22)
Ignition system Battery/Coil
Cooling system Integrated Air Cooling
High engine temperature, _C(_F)
3
3
Specification
2.3 (80)
1.1 (40);
2.1 (4.66)
4.2 (1.1)
152 (305)
Figure 1-3 Engine Specifications
TP-6482 8/0612 Section 1 Specifications
1.4 Service Views
2
1
12
4
3
5
11
6
21
13
20
+
10
Left Side View
1. Decal, engine serial number
2. Decal, emission
3. Engine interface connector
4. Engine starting battery connector
5. Ignition module
6. Engine oil fill and dipstick
7. Ignition coil
8. Spark plug (not visible)
9. Fuel supply connection (3/4 in. NPT)
10. High engine temperature (HET) sensor
11. DC output connector
12. Muffler
13. Generator set compartment outline
14. Fuel block
15. Secondary fuel pressure regulator
16. Hourmeter location
17. Fuel metering valves (sealed)
18. Oil filter
19. Exhaust pipe connection
20. Generator set control circuit board (location may vary)
21. Fuse
22. Cooling fan (inside)
23. Engine oil cooler
24. Alternator (inside)
25. Low oil pressure (LOP) switch
26. Oil drain (3/8 in. NPT)
27. Carburetor
28. Air cleaner
29. Throttle linkage
30. Governor
7
--
14
8
G
NGLP
15
16
17
9
18
19
30
Front View
22
23
24
29
28
27
25
26
Right Side View
GM14140B-AL
Figure 1-4 COM5 Service Views
TP-6482 8/06 13Section 1 Specifications
123 4
5
9
8
Left Side View
1. Engine interface connector
2. Engine starting battery connector
3. Ignition module
4. Engine oil fill and dipstick
5. Ignition coil
6. Spark plug
7. Fuel supply connection
8. High temperature (HET) sensor
9. DC output connector
10. Fuel block
11. Secondary fuel pressure regulator
12. Hourmeter location
13. Fuel metering valves, sealed
14. Oil filter
15. Exhaust pipe connection
16. Governor
17. Engine oil cooler
18. Alternator (inside)
19. Low oil pressure (LOP) switch
20. Oil drain
21. Carburetor
22. Air cleaner
23. Throttle linkage
6
10
11
12
7
15
14
13
Front View
16
23
22
21
17
18
19
20
Right Side View
ADV-6536-A
Figure 1-5 Alpha 5
TP-6482 8/0614 Section 1 Specifications
Section 2 Operation
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Combustible materials. A fire can cause severe injury or death. Generator set engine fuels and fuel vapors are
flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
CAUTION
Air Cleaner. Check for a clean and installed air cleaner element to prevent unfiltered air from entering the engine.
Air Inlets and Outlets. Check for clean and unobstructed cabinet air inlets and outlets. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave rags, tools, or debris on or near the generator set.
Battery. Check for clean and tight battery connections. Consult the battery manufacturer’s instructions regarding battery care and maintenance.
Exhaust System. Check for exhaust leaks and blockages. Check the silencer and piping condition and check for tight exhaust system connections.
Inspect the exhaust system components (exhaust manifold, exhaust line, flexible exhaust, clamps, silencer, and outlet pipe) for cracks, leaks, and corrosion.
D Check for corroded or broken metal parts and replace
them as needed.
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Moving rotor.
2.1 Prestart Checklist
To ensure satisfactory operation, perform the following checks or inspections before or at each startup, as designated, and at the intervals specified in the service schedule. Some checks require verification after the unit starts.
D Check for loose, corroded, or missing clamps and
hangers. Tighten or replace the exhaust clamps and/ or hangers as needed.
D Check that the exhaust outlet is unobstructed.
D Visually inspect for exhaust leaks. Check for carbon
or soot residue on exhaust components. Carbon and soot residue indicates an exhaust leak. Replace or repair leaking parts as needed.
Oil Level. Maintain the oil level at or near, not over, the full mark on the dipstick.
2.2 Exercising Generator Set
Operate the generator set under load weekly. Perform all of the prestart checks before starting the exercise procedure. Start the generator set according to the starting procedure in Section 2.3.3. While the generator set is operating, listen for a smooth-running engine and visually inspect the generator set for fluid or exhaust leaks.
TP-6482 8/06 15Section 2 Operation
2.3 Controller Operation
Microprocessor-based controls provide complete control of the engine and generator. The control system accepts remote control inputs for generator start and run and delivers local and remote annunciation of unit status. Internal functions of the controls include start and stop logic, fault monitoring, generator voltage and engine speed governing, and fault annunciation through local LEDs.
A three-position generator set master switch on the control board allows local or remote control of the generator set. The RUN and STOP positions provide local control of the generator set. The STOP position also resets controller faults. The AUTO position allows a remote device to start and stop the generator set. See Section 2.3.2 for remote start/stop connection information.
1
Note: Set the generator set master switch to the AUTO
position to allow remote control of generator set.
1
2
1. Generator set master switch
2. Common fault indicator LED
STOP
AUTO
RUN
FAULT
M-337000C-B
Figure 2-1 Generator Set Controls
TP6076
1. Generator set master switch
Figure 2-2 Generator Set Master Switch Location
2.3.1 Control Connections
Wiring harnesses connect the generator set control board to the remote controls and the engine. Figure 2-3 shows the wiring harness connections to the control board. Refer to the wiring diagrams in Section 8 for connector pin identification. Figure 2-5 defines the abbreviations used for the pin diagrams.
1
3
1. Cabinet interface harness
2. Generator set control circuit board
3. Engine interface harness
GM14140-AL
Figure 2-3 Generator Set Control Connections
TP-6482 8/0616 Section 2 Operation
2
Figure 2-4 Cabinet Interface Harness Connectors
Abbreviation Definition
70 Run
71 Crank
AC1 Speed sensing
AC2 Speed sensing
DCN DC negative
DCP DC positive
LOP Low oil pressure
M1 Throttle control
M2 Throttle control
M3 Throttle control
M4 Throttle control
N Ground
N/C Not connected
OVC Overcrank
OVS Overspeed
OVT Overtemperature
P Positive
STP Stop
STT Start
GM14245-A
Figure 2-5 Pin Abbreviations
TP-6482 8/06 17Section 2 Operation
Figure 2-6 Engine Interface Harness Connectors
GM14244-B
2.3.2 Remote Start/Stop Connections
To operate the generator set from a remote location, use a three-wire start/stop switch connected to pins 5, 6, and 7 of connector P6 on the cabinet interface harness. See the wiring diagrams in Section 8.
Set the generator set master switch to the AUTO position for remote operation. To start the generator set, open a contact between pins 6 and 7 and close a contact between pins 5 and 6 of connector P6. Close the contact between pins 6 and 7 to stop the generator set.
2.3.3 Starting Generator Set
The following procedures describe the actions required to start the generator set.
Local Starting. Move the generator set master switch to the RUN position to immediately start the generator set.
Remote Starting. Move the generator set master switch to the AUTO position to allow startup by the remote start/stop contacts. See Section 2.3.2 for the remote start/stop switch connections.
At initial startup, the engine’s hydraulic lifters may produce a metallic clicking sound. This is caused by the hydraulic lifter leakdown during storage. Run the generator for 5 minutes. The noise will normally cease in the first minute. If the noise continues, run the generator at mid throttle for 20 minutes.
Note: The control board provides up to 70 seconds of
cyclic cranking before overcrank shutdown occurs.
TP-6482 8/0618 Section 2 Operation
2.3.4 Stopping Generator Set
The following procedures describe the actions required to stop the generator set.
Local Stopping. Move the generator set master switch to the STOP position. The generator set stops immediately.
Remote Stopping. Close a remote contact between pins 6 and 7 of connector P6 of the cabinet interface harness. The generator set shuts down regardless of the generator set master switch position.
LED Indicates
1 Overspeed shutdown Yes
2 Overtemperature shutdown Yes
3 Engine running status indicator Ye s
4 Low oil pressure fault shutdown Yes
5 Overcrank shutdown Yes
6 Ignition energized No
7 Cranking energized No
8 Common fault indicator No
Figure 2-7 Control Board LEDs
Remote
Annunciation
2.3.5 Status Indicators
Eight LEDs on the generator set control board provide system status and fault annunciation. LEDs indicate the status or fault shutdowns listed in Figure 2-7.
1
R37
LED6
LED1
LED2
Common fault LED8 is located on the edge of the control board. Figure 2-8 shows the LED locations.
2
STOP
AUTO
3
RUN
FAULT
LED3
P3
LED8
P2
LED7
P1
LED4
LED5
4
M-337000C-B
1. Control circuit board
2. Generator set master switch
3. Common fault annunciation LED
4. LEDs 1--7
Figure 2-8 Control Board LEDs
TP-6482 8/06 19Section 2 Operation
2.3.6 Fault Shutdowns
The generator set shuts down automatically under the fault conditions listed in Figure 2-9 and cannot be restarted until the controls are reset. Reset the controller by placing either the remote control switch or the generator set master switch in the STOP position. The high engine temperature fault automatically resets when the generator set cools.
2.3.7 Control Resetting Procedure (Following Fault Shutdown)
Use the following procedure to restart the generator set after a fault shutdown. Set either the remote control switch or the generator set master switch to the STOP position to reset the controls.
1. Move either the generator set master switch or the remote switch to the STOP position.
Fault Description
High engine temperature
Low oil pressure
Overcrank Shuts down after 70 seconds of cyclic cranking.
Overspeed Shuts down immediately if the engine speed
Shuts down 5 seconds after the fault. When the engine cools, the fault clears and allows generator set to be started without resetting the controller. The high engine temperature shutdown does not function during the first 30 seconds after startup.
Shuts down 5 seconds after fault. The low oil pressure shutdown does not function during the first 30 seconds after startup.
Note: The low oil pressure shutdown does not protect against low oil level.
The factory sets the circuit board for three starting attempts: crank 20 seconds, rest 5 seconds, crank 20 seconds, rest 5 seconds, crank 20 seconds, overcrank fault.
Overcrank shutdown also occurs in the case of a locked rotor. Shuts down 1 second after the fault is detected.
exceeds 3750 rpm.
Figure 2-9 Fault Shutdowns
2. Correct the cause of the fault shutdown. See the safety precautions at the beginning of this section before proceeding.
3. Start the generator set locally by moving the generator set master switch to the RUN position, or move the master switch to the AUTO position and start the generator set using the remote start switch. Run the generator set to verify that the cause of the shutdown has been corrected.
4. Move the generator set master switch to the STOP position to stop the generator set.
5. Move the generator set master switch to the AUTO position to return to standby operation.
2.4 Circuit Protection
A DC line limiter (fuse) interrupts the generator output in the event of a 50% overload or a short circuit in the wiring between the generator and the load. Replace the line limiter if it blows. See Maintenance and Service Parts in the Introduction of this manual for the fuse part number.
TP-6482 8/0620 Section 2 Operation
Section 3 Scheduled Maintenance
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
Moving rotor.
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely hot during operation.
DANGER
Hazardous voltage. Will cause severe injury or death.
Only authorized personnel should open the enclosure.
3.1 Routine Maintenance
Refer to the following service schedule and the hourmeter located on the generator set to schedule routine maintenance. Perform maintenance on each item in the service schedule at the designated interval for the life of the generator set. Service units subject to extreme weather, long operating hours, or dusty or dirty conditions more frequently.
Generator set service. Have an authorized Kohler service distributor/dealer perform all generator set service. See the Safety Precautions and Instructions at the beginning of this manual before attempting to service or repair the generator set.
Engine service. Perform generator set engine service at the intervals specified by the service schedule in this section. For additional information contact an authorized Kohler service distributor/dealer to obtain engine service literature.
Generator service. Refer to the service schedule for items that require maintenance.
TP-6482 8/06 21Section 3 Scheduled Maintenance
Tools. Tools and instruments used to perform some
3.2 Service Schedule
maintenance are not generally available to the generator set owner. It is recommended that service requiring special tools be performed by an authorized distributor/dealer.
Perform the service listed in Figure 3-1 at the designated intervals for the life of the generator set. Refer to the service views in Section 1.4 for system component locations.
Procedure
Visually
System Component or Procedure See Section Fuel 3.6
Inspect flexible lines and connections. Replace cracked or spongy hoses. *
Check the main LP tank supply level, if used. X M
Inspect fuel piping for damage or corrosion. X Y
Lubrication 3.4
Check the oil level. 3.4.1 X X M or before use
Change the oil and replace the oil filter. 3.4.2, 3.4.3 R Y or 100 hr.
Cooling 3.9
Check that air ducts and louvers are clean and unobstructed.
Exhaust System 3.11
Check for leakage. Carbon or soot residue indicates a leak. Repair leaks.
Check for fire hazards. X X X Y
Check for loose or broken hangers and supports. Tighten or replace as needed.
Battery
Check battery charger operation and charge rate (if equipped).
Clean and tighten battery terminals. 3.7 X X X Y
Electrical System
Inspect wiring and components for visible wear or damage.
Check for abrasions where wiring is subject to motion.
Engine And Mounting
Inspect for visible wear or damage. X M
Inspect the air cleaner element; replace it if necessary.*
Clean and oil the foam precleaner. 3.5.1 X 100
Inspect the spark plug; replace if necessary.* 3.8.2 X R Y or 500 hr.
Control System
Check remote control operation. Controller
Generator Set
Check items listed in the Prestart Checklist. 2.1 X M
Exercise the generator set. 2.2 X W
General Condition Of Equipment
Check for signs of vibration, leakage, excessive noise, extreme temperature, or deterioration.
Inspect and clean the cabinet interior. X X Q
* Contact your local distributor/dealer for parts or service. XAction
Battery charger
manual
3.5 X R Y or 500 hr.
manufacturer’s
instructions.
Inspect
R Replace as necessary
Check Change Clean Test
X R Q
X X X M or before use
X X R Y
X X R Y
X X M
X Q
X X S
X X X M
Frequency
X M
W=Weekly M=Monthly Q=Quarterly S=Six Months Y=Yearly
Figure 3-1 Service Schedule
TP-6482 8/0622 Section 3 Scheduled Maintenance
3.3 Service Access
Use the following procedure to gain access to the generator set for maintenance or service. See Figure 3-2 and Figure 3-3.
A key is required to open the enclosure. Obtain the enclosure key from the equipment owner. Use the following procedure to gain access to the generator set for maintenance or service. See Figure 3-3.
Refer to the enclosure manufacturer’s instruction manual for more information.
Note: Allow the exhaust system to cool before
disconnecting the exhaust pipe. Inspect the exhaust gasket and replace it if necessary when reassembling the exhaust system. See the list of routine service parts in the Introduction of this manual for the gasket part number.
Generator Set Service Access
1. Remove the front door of the cabinet.
6. Remove the back panel of the cabinet to gain access to the exhaust connection near the bottom of the unit.
7. Disconnect the engine exhaust pipe at the location show in Figure 3-2.
8. Grasp the generator tray at the sides and pull the generator set forward.
9. Remove the four bolts securing the generator set to the enclosure rails. Use appropriate lifting equipment to lift the generator set off the rails. The generator set weighs approximately 68 kg (150 lb.).
Note: Service fixtures are required to run the generator
set outside the enclosure. Refer to Section 5.1 for instructions and precautions.
2. Place the generator set master switch in the STOP position.
3. Remove the front panel from the generator set compartment.
4. Disconnect the generator set battery harness, engine wiring harness, and load leads at the quick­disconnect plugs.
5. Turn off the fuel supply at the upstream valve and disconnect the fuel line on the right side of the cabinet. See Figure 3-3.
+
--
+
--
NGLP
1
1
2
5
3
4
GM14140B-AL
1. Load lead connector
1. Exhaust connection
Figure 3-2 Exhaust Connection
2. Battery harness connector
3. Engine harness connector
4. Fuel connection
5. Exhaust pipe connection (not visible in this photo)
Figure 3-3 Generator Set Installed in Cabinet
(door and front panel removed)
TP-6482 8/06 23Section 3 Scheduled Maintenance
TP6076
Return to Operation
Slide the generator set back into the enclosure and reconnect the exhaust pipe, fuel system, and wiring harnesses as described below.
10. Reinstall the generator set compartment front panel.
11. Reinstall the enclosure door.
1. Verify that the generator set master switch is in the STOP position.
2. Slide the generator set back into the enclosure.
3. Install the exhaust gasket and reconnect the exhaust pipe.
4. Reinstall the enclosure back panel.
5. Reconnect the fuel line and turn on the fuel supply.
6. Check for fuel leaks.
7. Reconnect the engine wiring harness, load leads, and battery harness.
8. Reconnect the generator set engine battery harness.
9. Move the generator set master switch to the center (AUTO) position to return the generator set to standby service.
3.4 Lubrication System
See the service schedule in Section 3.2 for oil change and oil filter replacement intervals. See Figure 3-4 and Figure 3-5 for the oil drain, oil check, oil fill, and oil filter locations. The list of routine service parts in the Introduction of this manual shows the oil filter part number.
3.4.1 Oil Check
The generator set is shipped with oil. Before operating a new generator set check the engine oil in the crankcase. See Figure 3-4 and Figure 3-5. Verify that the oil level is at the F mark on the dipstick. See Section 3.4.2 for engine oil recommendations.
Do not check the oil level when operating the generator set. To obtain the most accurate oil level reading, shut down the generator set and wait several minutes before checking the oil.
3
1
5
2
1. Oil check, fill
2. Exhaust pipe connection
3. Oil cooler
4. Oil drain
5. Oil filter
Figure 3-4 Lubrication System, Specification Numbers PA-195023 and PA-195027
4
M-337000B-B
TP-6482 8/0624 Section 3 Scheduled Maintenance
Loading...
+ 56 hidden pages