Allen-Bradley 900-TC8, 900-TC8RGTH1Z25, 900-TC8RGTZ25, 900-TC8RVGTZ25, 900-TC8VGTZ25 Selection Manual

...
SELECTION GUIDE
BULLETIN 900-TC
Single-Loop Electronic Temperature/Process Controllers
Visit our website: www.ab.com/catalogs
Bulletin 900-TC
3
Bulletin 900 Controllers with Enhanced Features
Both the hardware and function set of the Bulletin 900-TC8 and 900-TC16 temperature controller product lines offer an enhanced feature set as compared to the 900-TC32. The controller enhancements allow the Bulletin 900-TC8 and 900-TC16 line a much wider range of process applications. Key enhancements include:
ModBus is a registered trademark of Group Schneider.
• Analog voltage and current inputs
• The combination of thermocouple and platinum RTD controller types into one Global Temperature (GT) controller which incorporates both sensor input types
• A second voltage (SSR) or Triac (electronic relay) control output without loss of an alarm output
• 0...20 mA analog output in addition to the existing 4...20 mA output
• Analog transfer output function to allow easy connection to a strip chart recorder or PLC input
• Manual control of the output from the controller keypad, with bumpless transfer to the Automatic PID mode
• 11-segment alphanumeric LED readouts to display the controller parameters in a more understandable format
• Single- and three-phase heater burnout and short circuit detection
• Faster sampling rate to 250 ms
• Direct connection to your PC's USB port and 4-pin serial port on the controller using the 900-CPOEM1 cable. Allows 1-to-1 (non-network) parameter configuration and monitoring without the need of an option communication unit/module.
• ModBus
®
RTU (master/slave) protocol
Bulletin 900-TC8 and 900-TC16 Series B Added Features and Functions
In addition to the above enhanced features/functions associated with the Bulletin 900-TC8 and 900-TC16 controllers, the Series B version (released in October 2008) offers additional features over the series A controllers.
MV (Manipulated Variable) Display Ye s N o
PF Key (addition to keypad: allows one touch assignment of Auto/Manual, Run/Stop, etc) Yes No
Thermocouple Types: Added W and PL II Ye s Ye s
Thermocouple Accuracy: Improved from +/-0.5% of PV to +/-0.3% of PV Yes Yes
RTD Accuracy: Improved from +/-0.5% of PV to +/-0.2% of PV Ye s Yes
Analog Output Resolution: Expanded from 2,700 to 10,000 Ye s Yes
Max. Network Communications Rate: Increased to 57.6 Kbps
Ye s7
Yes
Simultaneous Network and USB Cable (900-CPOEM1) communications Yes Yes
Modbus Communications: 1 data, 2-byte mode added Ye s Yes
Manipulated Variable Limiter Ye s Yes
40% Auto-tuning Ye s Yes
Auto-tuning for cooling when heating & cooling is selected Ye s
Direct/Reverse mode change selection by input interrupt Yes §
Yes
Square Root extraction function for analog input Ye s Yes
PV rate of change alarm Ye s Yes
Over current alarm Yes
³ Yes ³
9
Version 1.2 of 900BuilderLite is required to configure Series B controllers if the software configuration option is used versus the controller keypad. NOTE: Version 1.1 saved parameter cannot be downloaded using Version 1.2
7 Requires the use of a communication option unit: 900-TC8232 (Series B) for RS232C or 900-TC8COM (Series B) for RS485 communications.
Requires the use of a Series B RS485 communication option unit: Refer to Table “Option Units”. NOTE: Series A option units cannot be used with Series B
controllers and vice versa.
§ Requires the use of an event Input option unit: 900-TC8EIM (Series B)
Requires the use of a Series B Event Input option unit: Refer to Table “Option Units”. NOTE: Series A option units cannot be used with Series B controllers and
vice versa.
Ye s
New Series B Feature/Functionality
9 900-TC8 900-TC16
Bulletin 900-TC Digital Temperature Controllers
Page 4
Bulletin 900-CONV Interface Converter
Page 23
Bulletin 900 900BuilderLite™ Software
Page 26
Bulletin 900 900Builder™ Software
Page 27
Bulletin 900 — Temperature/Process Controllers
³ Requires the use of a current transformer: 900-CT1 or 900-CT2
y Single-Loop, High Value, ON/OFF, or Analog Output Controllers y 1/8 DIN (Bulletin 900-TC8), 1/16 DIN (Bulletin 900-TC16), and 1/32 DIN (Bulletin 900-TC32)
Sizes
y Various Sensor Inputs
– Thermocouple – Platinum RTD – Non-Contact Temperature Sensor – Analog Input 4...20 mA, 0...20 mA, 1...5, 0...5 or 0...10V DC and 0…50 mV (TC8 and TC16)
y Auto-Tuning and Self-tuning Available to Simplify Startup y Heating, Cooling, or Heating/Cooling Control Available y Manual Output Control (TC8 and TC16) y High Visibility 4-digit, 11-segment LED Displays, Easy to See in High Levels of Ambient Light y Integral Keypad with Tactile Feedback for Setup and Modification of Parameters y Security Modes/Levels y Event Input (TC8 and TC16) for Multiple SP Selection, Controller RUN/STOP and Auto/Manual
Mode Change
y Water-Resistant Construction UL Type 4X or IP66 for Indoor Use y On-Board Wiring Diagrams to Simplify Startup y cULus, CE
Visit our website: www.ab.com/catalogs
Bulletin 900-TC
Single-Loop Temperature/Process Controller
4
Product Overview/Quick Selection
Bulletin
900-TC32
Bulletin
900-TC16
Bulletin
900-TC8
Bulletin 900 — Temperature/Process Controllers
Product Selection...... 5
Accessories..................
General Functions .....78
Inputs Ranges............. 10
Specifications.............. 1 2
Approximate
Dimensions................... 15
Wiring Terminals ......... 1 7
Option Units................. 19
Installation .................... 20
Controller Config.
from Keypad................ 22
Bulletin 900-TCx Quick Selection
Bulletin 900 — Temperature/Process Controllers
Item
Bulletin No.
900-TC8
900-TC16
900-TC32
Dimensions 48 x 96 x 78 mm 48 x 48 x 78 mm 48 x 24 x 100 mm
Alphanumeric Display Types PV, SV, MV PV, SV PV, SV
Sample Rate 250 ms 500 ms
Indication Accuracy
Thermocouple: ±0.3% of PV; RTD: ±0.2% of PV;
Analog: ±0.2% of F.S.
±0.5% PV +1 digit max.
Heating/Cooling Control Mode Yes Yes Yes
Control Method
ON/OFF or 2-PID (auto-tune and self-tune) with time proportioning ON/OFF outputs
or Analog Output (900-TC8 & 900-TC16)
Inputs
Thermocouple Input and 0...50 mV Yes Yes Yes
Platinum Resistance Temperature Sensor Yes Yes Yes
Analog Input 0...20 mA, 4...20 mA,
1...5V DC, 0...5V DC, 0...10V DC
Yes Yes No
Non-Contact Temperature Sensor Yes Yes Yes
Control Output 1 Type
ON/OFF Relay Output (Electro­Mechanical)
Ye s Ye s Ye s
ON/OFF Voltage Output for Solid-State Relay
Ye s Ye s Ye s
ON/OFF Triac (AC Only) No Yes No
4…20 and 0...20 mA (DC) Analog Yes Yes No
Control Output 2 Types
ON/OFF Relay
No a No a No a
ON/OFF Triac
Yes
³
No No
ON/OFF Voltage SSR
Yes
³
Yes No
Maximum Number of Auxiliary/ Alarm Outputs
None No No
Ye s7
1 Output No No Yes
2 Outputs No Yes No
3 Outputs Yes Yes No
RS-232C Communications Function Yes § No No
RS-485 Communications Function Yes § Yes §
Yes
³
Event Input Yes § Ye s§ No
Run/Stop via Keypad or Interrupts Yes Yes Keypad
Multiple SP Selection via Keypad or Interrupts
Yes Yes
Keypad
Manual Output Control via Keypad or Interrupts
Yes Yes
No
Transfer Output Function (Requires Analog Output) Yes Yes No
Heater Burnout, Heater Overcurrent or Heater Short Alarm (Single or 3­Phase)
Ye s Ye s
No
7 When RS-485 communication is required.
§ Requires an option unit. Refer to Option Unit table on page 6
Interrupts require an event input option unit. Refer to Option Unit table on page 6.
³ Determined by controller catalog number.
a One of the controller alarm relays can be used as a second control output (i.e., a heating and cooling application).
Requires an option unit with an SSR output.
Requires addition of hardware. One current transformer (900-CT1 or 900-CT2) for single-phase and two current transformers for 3-phase detection. For the
900-TC16, the appropriate option unit must be purchased. Refer to Option Units in Product Selection on page 6.
Visit our website: www.ab.com/catalogs
Bulletin 900-TC
Single-Loop Temperature/Process Controller
5
Product Selection
Bulletin 900-TC8 Controller Models
Bulletin
No.
DIN Size
(DImensions)
(mm)
Sensor Input
Type
Power
Supply
Voltage
Max No. of
Auxiliary
Outputs
Supported
³ Control Output 1 Type Control Output 2 Type
Supports
Heater Burnout
(Open) and
Heater Short-
Circuit Alarm
Controller Cat. No.
900-TC8
97
1/8 DIN 48 mm (W) x 96 mm (H) x 78 mm (D)
Thermocouple
or RTD
100…
240V AC
3
Relay
—No
900-TC8RGTZ25
Yes (1-Phase) 900-TC8RGTH1Z25
Voltage (for driving SSR) No 900-TC8RVGTZ25
Yes (3-Phase)
900-TC8RGTH3Z25
Voltage (for driving SSR)
—No900-TC8VGTZ25
Yes (1-Phase) 900-TC8VGTH1Z25
Triac
No
900-TC8VYGTZ25
Voltage (for driving SSR) No 900-TC8VVGTZ25
Yes (3-Phase) 900-TC8VGTH3Z25
0...20 or 4...20 mA Analog Output
—No
900-TC8ACGTZ25
Triac
No
900-TC8ACYGTZ25
Voltage (for driving SSR) No 900-TC8ACVGTZ25
Thermocouple
or RTD
24V
AC/DC
3
Relay
—No
900-TC8RGTU25
Yes (1-Phase) 900-TC8RGTH1U25
Voltage (for driving SSR)
—No900-TC8VGTU25
Yes (1-Phase) 900-TC8VGTH1U25
0...20 or 4...20 mA Analog Output
—No
900-TC8ACGTU25
Analog Current
& Voltage 0...20
and 4...20 mA
0...5, 1...5, and
0...10V DC
100…
240V AC
3
Relay Yes (1-Phase)
900-TC8RABH1Z25
Relay No
900-TC8RABZ25
Voltage (for driving SSR) Yes (1-Phase)
900-TC8VABH1Z25
Voltage (for driving SSR) No
900-TC8VABZ25
Voltage (for driving SSR)
Triac
No
900-TC8VYABZ25
0...20 or 4...20 mA Analog Output
—No
900-TC8ACABZ25
Bulletin 900-TC16 Controller Models
Bulletin
No.
DIN Size
(DImensions)
(mm)
Sensor Input
Type
Power
Supply
Voltage
Max No. of
Auxiliary
Outputs
Supported
³ Control Output Type §
Supports Heater
Burnout (Open)
and Heater
Short-Circuit
Alarm
Controller Cat. No.
900-TC16
97
1/16 DIN 48 mm (W) x 48 mm (H) x 78 mm (D)
Thermocouple
or RTD
100…
240V AC
2
Relay Output Yes
900-TC16RGTU25
Triac
Ye s
900-TC16YGTZ25
Voltage output (for driving SSR) Yes 900-TC16VGTZ25
0...20 or 4...20 mA Analog Output No 900-TC16ACGTZ25
Thermocouple
or RTD
24V
AC/DC
2
Relay Output Yes
900-TC16RGTU25
Voltage output (for driving SSR) Yes 900-TC16VGTU25
0...20 or 4...20 mA Analog Output No 900-TC16ACGTZ25
Analog Current
& Voltage 0...20
and 4...20 mA
0...5, 1...5, and
0...10V DC
100…
240V AC
2
Relay Yes
900-TC16RABZ25
Triac
Yes
900-TC16YABZ25
Voltage (for driving SSR) Yes
900-TC16VABZ25
0...20 or 4...20 mA Analog Output No
900-TC16ACABZ25
24V
AC/DC
Relay Yes
900-TC16RABU25
Voltage (for driving SSR) Yes 900-TC16VABU25
0...20 or 4...20 mA Analog Output No
900-TC16ACABU25
9 A current transformer (CT) is not provided with the unit.
7 When the heating and cooling function or the heater burnout alarm is used, one of the relay alarm outputs can be used as the heating or cooling output or
heater burnout alarm.
To implement the single-phase or three-phase heater burnout and heater short alarm function, an option module must be inserted into the 900-TC16 controller.
For a list of 900-TC16 option modules, refer to the Option Units table, page 6. The heater burnout and heater short alarm is available by mounting the appropriate option module into any 900-TC16 controller that supports (yes) the heater burnout (open) or heater short-circuit feature.
§ The Bulletin 900-TC16 can have a second ON/OFF control output (SSR) by adding an option unit to the controller. Refer to Option Units table on page 6.
For AC voltage operation only
³ Typically used for alarms or cooling output in a heat/cool application
Visit our website: www.ab.com/catalogs
Bulletin 900-TC
Single-Loop Temperature/Process Controller
6
Product Selection
Bulletin 900-TC32 Standard Controller Models
Bulletin
No.
DIN Size
(DImensions)
(mm)
Power
Supply
Voltage
Max No. of
Alarms
Supported
³ Control Output Type
Supports
Heater
Burnout
(Open) and
Heater Short-
Circuit Alarm
Controller Cat. No.
with Thermocouple
Support
Controller Cat. No. with Platinum RTD
Support
900-TC32
97
1/32 DIN 48 mm (W) x 24 mm (H) x 100 mm (D)
100…
240V AC
1
Relay Output
No
900-TC32RTZ25 900-TC32RPZ25
Voltage output (for driving SSR) 900-TC32VTZ25 900-TC32VPZ25
24V AC/DC 1
Relay Output
No
900-TC32RTU25 900-TC32RPU25
Voltage output (for driving SSR)
900-TC32VTU25 900-TC32VPU25
100…
240V AC
RS485
Relay Output
No
900-TC32CRTZ25 900-TC32CRPZ25
Voltage output (for driving SSR)
900-TC32CVTZ25 900-TC32CVPZ25
24V AC/DC RS485
Relay Output
No
900-TC32CRTU25 900-TC32CRPU25
Voltage output (for driving SSR) 900-TC32CVTU25 900-TC32CVPU25
9 If the heating/cooling function is used, ALM1 will be used for the cooling control output and so the alarm output relay will not be available.
7 Cat. Nos. with a C designator (e.g., Cat. No. 900-TC32C___) include RS-485 communications, but do not have an alarm (or cooling) output.
³ Typically used for alarms or cooling output in a heat/cool application
Option Units (Bulletins 900-TC8 and 900-TC16 — Only One Option Unit per Controller)
The unit provides communications or event input functionality.
Bulletin No. Name Function Cat. No.
900-TC8
Communications Unit
RS-232C communications
900-TC8232(B)
RS-485 communications
900-TC8COM(B)
Event Input Unit
Event inputa
900-TC8EIM
900-TC16
Communications and 1-Phase Heater
Burnout Unit and Heater Short
RS-485 communications with single-phase heater burnout (open) and heater
short-circuit failure detection
900-TC16NCOM(B)♠§
Event Input Unit with 1-Phase Heater
Burnout and Heater Short
Event Input with single-phase heater burnout (open) and heater short-circuit
failure detectiona
900-TC16NEIM(B)
Event Input Unit
Event Inputa
900-TC16NACEIM(B)
Communications Unit RS-485 communications
900-
TC16NACCOM
(B)♠§
Communications and 3-Phase Heater
Burnout and Heater Short Unit
RS-485 communications with 3-phase heater burnout (open) and heater short-
circuit failure detection
900-
TC16NCOMP3
(B)♠§
Communications and Second Voltage
(SSR) Output Unit
RS-485 communications and a second voltage (SSR) output
900-
TC16NCOMV2
(B)♠§
1-Phase Heater Burnout and second
voltage (SSR) output
1-Phase Heater burnout (open) and heater short-circuit failure detection with a
second control voltage (SSR) output
900-TC16P1V2(B)
Enables direct RS-232 connection to personal computer using 900BuilderLite™ software. A Cat. No. 900-CP1X cable or equivalent is also required.
aProvides two event inputs. Allows selecting up to 4 different pre-configured set points, controller Run/Stop or Auto/Manual mode, from 2 external inputs.Heater bur nout is not available for 0...20 or 4…20 mA analog output style 900-TC16 controllers such as the 900-TC16AC.To obtain 57.6 k baud rate, Series B communication units must be used with any 900-TC8 controller catalog number from the Product Selection table on the
previous page.
Series B option units must be used with Series B 900-TC16 controllers. Series A option units cannot be used with Series B controllers and vice versa.
§ Series B provides 57.6 K baud rate.
Visit our website: www.ab.com/catalogs
Bulletin 900-TC
Single-Loop Temperature/Process Controller
7
Accessories
Accessories
For Use With Bulletin No. Hole Diameter Cat. No.
900-TC8, 900-TC16
5.8 dia.
900-CT1
12.0 dia. 900-CT2
The hole diameter is the only functional difference between the Cat. No. 900-CT1 and the Cat. No. 900-CT2. Current output to controller is the same.
Interface Converter (RS-232/USB to RS-485) Model
Converts personal computer RS-232 or USB (Ser. B or later) communications to RS-485. Use for interface with a single Bulletin 900-TC8, or Bulletin 900-TC16 with a Cat. No. 900-TCxxCOM unit installed or a single Cat. No. 900-TC32C_ designated controller. Also allows interface to up to 31 controllers connected on a RS-485 link/network. See Bulletin 900-CONV, page 24 for additional details.
Bulletin No. Size Power Supply Voltage Cat. No.
900-CONV 30 mm (W) x 80 mm (H) x 78 mm (D)
100…240V AC
900-CONVZ25
24V AC/DC 900-CONVU25
RS-232 Interface Cable
Allows connection between a 900-TC8 with a 900-TC8232 option unit and a PC using 900BuilderLite software (see page 25) or PC with software and a 900-CONV RS232-to-RS485 converter (see Bulletin 900-CONV, page 24).
900Builder™ Personal Computer Configuration Software (for Bulletin 900-TC32 Controllers)
Allows online and offline graphical configuration and online (direct or network) monitoring of controller parameters with data-logging and trending, plus program upload/download capability for any Bulletin 900-TC32 controller.
Accessory Cat. No.
900Builder™ Personal Computer Configuration Software for Bulletin 900-TC32 Temperature Controllers (available in CD format only)
900-BLDSW1
Current Transformer (Use with Bulletins 900-TC8 and 900-TC16 Only for Heater Burnout or Heater Short)
USB Direct Communication Cable
This cable allows direct 1-to-1 (no network capability) communication between a PC USB port and the serial port of a Bulletin 900-TC16 or a 900-TC8 controller. No communication option unit is required. The cable can be used with the 900BuilderLite™ software to modify parameters, monitor controller operation, and upload or download parameters to/from PC disk media.
Accessory Cat. No.
RS-232 cable with 9-pin female D shell and 3 flying leads (3 m)
900-CP1X
Accessory Cat. No.
USB-Serial Conversion Cable
900-CPOEM1
900BuilderLite™ Personal Computer Configuration Software for Bulletin 900-TC8 and 900-TC16 Controllers
Accessory Cat. No.
Free configuration software for Enhanced Functionality Bulletin 900-TC8 and 900-TC16 controllers.
900-BLDLTSW1
Free software. Allows online configuration and monitoring (direct or network) plus program upload/download capability to/from PC disk media for any Bulletin 900-TC8 or 900-TC16 controller.
Note 1: To obtain the free software, go to http://www.ab.com and use the A-Z Product Directory under "Resources" to locate the Temperature Controller home page. With the Bulletin 900-TC Single-Loop website displayed, go to the "Get Software" selection in the upper right and click on 900BuilderLite. Follow the download instructions.
Note 2: Version 1.2 of 900BuilderLite is required to configure Series B controllers. Version 1.1 saved parameter cannot be downloaded to a Series B controllers using Version 1.2.
Visit our website: www.ab.com/catalogs
Bulletin 900-TC
Single-Loop Temperature/Process Controller
8
Bulletin 900-TC8
General Functions
USB-Serial Conversion Cable (900-CPOEM1)
(2,100)
250
1,765
USB connector (type A plug) Serial connector
LED indicator
(RD)
LED indicator (SD)
y Note: To use the cable you must first download a USB driver (free download). To get the driver, go to http://www.ab.com and use the A-Z
Product Directory under "Resources" to locate the Temperature Controller home page. When the Bulletin 900-TC Single-Loop Controller website is displayed, go to "Get Software" selection in the upper right and click on 900-CPOEM1 driver. Follow the instructions.
y Do not connect or disconnect the Conversion Cable connector repeatedly over a short period of time. The computer may malfunction.
y After connecting the Conversion Cable to the computer, check the COM port number before starting communications. The computer
requires time to recognize the cable connection. This delay does not indicate failure.
y Do not connect the Conversion Cable through a USB hub. Doing so may damage the Conversion Cable.
y Do not use an extension cable to extend the Conversion Cable length when connecting to the computer. Doing so may damage the
Conversion Cable.
SUB 1 SUB 2 SUB 3
A
6. MANU (Manual Mode) — Lights when the controller mode is in manual.
7. (Key) — Lights when thesettings change protection is ON ( Keys disabled).
auxiliary 1 output is ON auxiliary 2 output is ON auxiliary 3 output is ON
57$
57$
57$
*#
Green, , Amber
No. 2 Display (Green)
Displays the set point, manipulated variable, or configured value (setup) of the parameter.
No. 3 Display (Amber)
Displays manipulated variable soak time remaining or multi SP.
PV
SV
5612176
/#07
%/9176
MV
2(
#/
4-pin Serial Port For USB Cable (900-CPOEM 1)
Visit our website: www.ab.com/catalogs
Bulletin 900-TC
Single-Loop Temperature/Process Controller
9
General Functions, Continued
Bulletin 900-TC16
Bulletin 900-TC32
SUB
SUB
, or Amber
6. MANU (Manual Mode) — Lights when the controller mode is in manual.
7. (Key) — Lights when thesettings change protection is ON ( Keys disabled).
failure (open or short)
A
SUB2 — Lights when auxiliary 2 output is ON.
SUB1 — Lights when auxiliary 1 output is ON.
configured value (setup) of the parameter.