Alarm Controls SREX-100 Installation Instructions

ACTIVE INFRARED
REQUEST TO EXIT SENSOR
MODEL SREX-100
OPERATING INSTRUCTIONS
PN:111
YOUR SOURCE FOR QUALITY
SECURITY EQUIPMENT
REQUEST TO EXIT STATIONS
DIGITAL KEYPADS
PUSHBUTTON CONTROL STATIONS
PNEUMATIC TIME DELAY STATIONS
VANDAL RESISTANT PUSH PLATES
MORTISE CYLINDER STATIONS
EXPLOSION-PROOF STATIONS
VANDAL RESISTANT STATIONS
EIGHT ZONE ANNUNCIATORS
CUSTOM GRAPHIC ANNUNCIATORS
PUSH BARS
RELAYS
ALARM CONTROLS
713
ALARM CONTROLS
WWW.ALARMCONTROLS.COM
ASSA ABLOY, the global leader in door opening solutions
ASSA ABLOY, the global leader in door opening solutions
SPECIFICATION
OPERATING VOLTAGE: 12 OR 24 VOLTS AC/DC, AUTO VOLTAGE SELECTIONCURRENT DRAW: 155 MA., (SOUNDER OFF), 200 MA., (SOUNDER MAXIMUM VOLUME)RELAY CONTACT RATING: 1.3 A. @ 30 VOLTS DC OR 24 VOLTS ACRELAY CONTACT ARRANGEMENT: DOUBLE POLE-DOUBLE THROW, (2 FORM C)TEMPERATURE: FOR U.L. LISTED INSTALLATIONS +32 F TO +120 F, (0 C TO +49C)HUMIDITY: 0% TO 93% NON-CONDENSING FOR ULC-S319 INSTALLATIONS, 0% TO 85%
NON-CONDENSING FOR UL-294 LISTED INSTALL
ATIONS.
REQUEST TO EXIT INPUT: NORMALLY-OPEN DRY CONTACTSKEYPAD OR CARD READER INPUT: NORMALLY-CLOSED DRY CONTACTSDOOR POSITION SWITCH INPUT: NORMALLY-OPEN DRY CONTACTSSIZE: 6.875” L (174.63mm) x 1.875” H (47.63mm) x 2” W (51mm)MATERIAL: BLACK ANODIZED ALUMINUM AND ABS PLASTICWIRING INTERFACE: 14 PIN CONNECTOR WITH 4 FEET OF CABLECERTIFICATIONS: UL/CUL 294/S319, FCC PART BTHE SREX-100 HAS A THREE YEAR WARRANTY
PAGE 6PAGE 1
The SREX-100 is an active infrared request to exit sensor for interior applications located within the protected premise. It is U.L. listed as a request to exit device under the U.L. UL294 and the CAN/ULC-S319 standard. The SREX-100 is rated a “class 1” as per the CAN/ ULC-S319 standard. The SREX-100 is designed to mount over the door header so that its de­tection pattern is placed directly over the door handle. When the user reaches for the door handle the exit device releases allowing the person to exit. The active detection curtain is well defined to keep the door secure while rejecting parallel traffic and objects placed under it.
TYPICAL INSTALLATION WIRING
B R
O
W
N
/
W
H
I T E
B R
O
W
N
O R
A N G
E
/ W H
I T E
O R A N G E
B L U E
/
W
H
I
T E
B L U E
W
H
I T E
C
O M
B
G R E E N
N
/
O
B
Y E L L O
W
N
/
C
B
W
H
I T E
/ B L A C K
C
O M
A
Y E L L O
W
/ B L A C K
N
/ C
A
G R E E N
/ B L A C K
N
/ O
A
B L A C K
P
W
R
R E D
P
W
R
12 OR 24 VDC
I.T.E.
MODEL
AMS4-240100FU
U.L. LISTED
POWER SUPPLY
FILE NUMBER
E141650
+
N/C DOOR
POSITION
SWITCH
MODEL
KP-100
DIP SW. 2
MUST BE
ON WHEN
DOOR
POSITION
SWITCH
IS USED.
USE
COMMON
AND
NORMALLY
OPEN
CONTACTS
USE
COMMON
AND
NORMALLY
CLOSED
MOMENTARY
CONTACTS
TECHNICAL ASSISTANCE
IF TECHNICAL ASSISTANCE IS REQUIRED CALL 1 800 645-5538
MODEL TS-2
U.L. FILE NUMBER
SA32686
ALARM CONTROLS
U.L. LISTED
MAGNETIC LOCKS
FILE NUMBER
R16759
NOTE:
FOR U.L. LISTED INSTALLATIONS THE SREX-100 SHOULD ONLY BE POWERED BY A U.L. 294 LISTED POWER SUPPLY, AS WELL AS CONNECTED TO A U.L. LISTED ELECTRICAL LOCKING (EL) DEVICE. FOR CAN/ULC-S319 LISTED INSTALLATIONS THE SREX-100 SHOULD ONLY BE POWERED BY A ULC--S319 LISTED POWER SUPPLY AS WELL AS CONNECTED TO A ULC­S319 LISTED ELECTRICAL LOCKING (EL) DEVICE, CARD READER/KEYPAD AND DOOR/REX SWITCHES.
THE USE OF ANY ADD-ON, EXPANSION, MEMORY OR OTHER MODULE MANUFACTURED OR SUPPLIED BY THE MANUFACTURER’S REPRESENTATIVE WILL INVALIDATE THE CAN/ULC­S319 CERTIFICATION.
WHEN USED WITH ELECTRIC STRIKES ON SUPERVISED PORTALS, REQUEST-TO-EXIT DE­VICES SHALL BY-PASS PORTAL ALERTS CAUSED BY EXITING. WHEN USED WITH ELECTRO­MAGNETIC LOCKS ON SUPERVISED PORTALS, REQUEST-TO-EXIT DEVICES SHALL SIGNAL THE ACCESS CONTROL UNIT TO RELEASE THE ELECTROMAGNETIC LOCKS AS WELL AS TO BYPASS PORTAL ALERTS CAUSED BY EXITING.
TERMINAL AND LEADS COMPLY WITH CSA, C22.1, CANADIAN ELECTRICAL CODE, PART I, SAFETY STANDARD FOR ELECTRICAL INSTALLATIONS.
FOR U.L. 294 AND NFPA 101 SECTIONS 7.2.6.2.1 WIRE THE LOCKING DEVICE FOR FAIL-SAFE OPERATION.
CAN/ULC-S319 LIMITS THE RATED OUTPUT OF THE AUDIBLE SIGNAL DEVICE, (STATED AS A SOUND PRESSURE LEVEL), (SPL), FROM 70 dBA TO A MAXIMUM OF 100 dBA AT 1 METER.
UL-294 LIMITS THE RATED OUTPUT OF THE AUDIBLE SIGNAL TO A MINIMUM OF 85 dBA AT 10 FEET.
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTER­FERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED THAT MAY CAUSE UNDESIRED OPERATION.
NOTE: THE THREE INPUTS TO THE SREX-100 MUST BE USED AS A DRY INPUT WITH NO
VOLTAGE APPLIED FROM THE CARD READER, DOOR POSITION SWITCH OR THE REQUEST TO EXIT STATION.