A.J. Antunes & Co TTD 815131004 User Manual

A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
TTD Installation Information
IMPORTANT
Please read these instructions carefully to assure correct installation. This equipment must be installed by a licensed electrician. Prior to being put into operation, check all wiring and function of the unit.
Specifications
Sensor Type: Thermocouple (Type J or K)
NOTE: Ungrounded thermocouples are required when multiple controllers/indicators are used or if the transform­er is grounded.
Accuracy: 1% Full Scale ± LSD
Power: 12 VAC/DC (24 VAC, 115 VAC, 230 VAC with
remote transformer), 50/60 Hz.
Temperature Range: 50º to 990ºF (10ºC to 530ºC)
Ambient Operating Temperature: -30ºF to 140ºF
(-35ºF to 60ºC)
Ambient Storage Temperature: -40ºF to 180ºF (-40ºF to 82ºC)
Connections: Terminal - Screw Terminal
Display: 3-Digit LED (0.56” Ht.)
Package: Panel Mount Epoxy Encapsulated
Shipping Weight: 1 lbs. (.45 kg)
Bracket and Screw Positions
Dimensions
2.80”
(71 mm)
3.10”
(79 mm)
(36 mm)
2.0”
0.38”
(10 mm)
(51 mm)
1.40”
Panel Cutout
2.82”
1.13”
2.82”
(72 mm)
1.10”
(28 mm)
1.13”
(29 mm)
Mounting Bracket and Screw
Panel Cut Out
NOTE: Dimensions are for reference only.
1-630-784-1000 Fax: 630-784-1651 Page 1 of 4 P/N 1011093 06/10 1-800-253-2991
A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
TTD Installation Information
Wiring Diagram Assembly
1. Remove bracket and insulator from TTD unit.
2. Place TTD unit through panel cutout.
Zero
Power
Input
{
Span
TC-
TC+
12 VAC/DC at 250 mA must be supplied to the indicator for power. This is connected to the power terminals as shown. If the indicator is to be powered by a transformer, then 115 VAC or 230 VAC must be supplied to the transformer primary (as required by the transformer type), and the 12 VAC output of the transformer is connected to the indicator power terminals as shown. Refer to wiring diagram for transformer and thermocouple connections.
For long thermocouple wire runs the proper thermocouple extension wire must be used, and the correct polarity must be maintained. If these precautions are not observed, the unit may not meet specifications.
Power and thermocouple wire should not be placed in the same conduit or wiring trough. However, wires from several thermocouples may be in the same conduit or wiring trough.
3. Place insulator on TTD unit and attach bracket.
NOTE: Bracket is not to touch the metal surface of the panel. The bracket must rest on the insulator. Any other method of mounting will cause damage to the internal operation of the TTD unit.
If shielded thermocouples are used, the shields should be insulated electrically from the thermocouple wires and terminated to earth ground.
Ungrounded thermocouples are required when multiple controllers/indicators are used or if the transformer is grounded.
1-630-784-1000 Fax: 630-784-1651 Page 2 of 4 P/N 1011093 06/10 1-800-253-2991