A.J. Antunes & Co TFH 8503130044 User Manual

A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
TFH Installation Information
IMPORTANT
Please read these instructions carefully to assure correct installation. This equipment must be installed by a licensed electrician. Prior to being put into operation, check all wiring and function of the unit.
Specifications
Sensor Type: 100K Thermistor (Dual) - Length (15 ft.)
Other lengths available upon request.
Accuracy: +/-3ºF of Setpoint
Power Input: 24 VAC, 120 VAC
Control Operation: Low Limit - Closes on Rise
High Limit - Opens on Rise
Output Ratings: Low Limit - 8 Amp S.P.D.T. Relay Max. @ 240 VAC Max.
High Limit - 8 Amp S.P.S.T. Relay Max. @ 240 VAC Max.
(Resistive Load)
Adjustable Time Delay Range: 1–8.5 Minutes
Adjustable Temperature Range: Low Limit: 30ºF to 65ºF
High Limit: 100ºF to 220ºF
Ambient Operating Temperature: -30ºF to 140ºF (-35ºF to 60ºC)
Connections: 1/4” Quick Connects,
6” Wire Leads (Optional)
Package: Aluminum “C” Bracket - 5.1”L x 5.9”W x 3.1”D (shown) Full Enclosure w/conduit knockout (optional)
Shipping Weight: 2 lbs. (.9 kg)
Dimensions
5”
(127 mm)
4.7”
(119 mm)
5.87”
(149 mm)
NOTE: Dimensions are for reference only.
Panel Cutout
Sensor Input
White
Black
Red
T1 T3 T2
R6 DS2 DS1
Connections
K1 HI
K2 LO
Thermistor Input: T1, T2 & T3 (100K ohm @ 25°C)
Power Input: T4 & T5 (24-120 VAC)
T11 T5 T7T6 T8T4 T10T9
Low Limit Relay: T8 (N.O.), T9 (COM) & T10 (N.C.)
High Limit Relay: T6 (N.O.), T7 (COM)
Installation Note: For optimum accuracy, the sensor
must be mounted with a minimum of two feet of cable at the sensor lug end being exposed to the same tempera-
GND COMN.O. N.O.VAC N.C.COM
Input Power
(24 VAC)
System Shutdown
Over-Temp. Contacts
System Shutdown Time-out Contacts
ture as the sensor lug.
1-630-784-1000 Fax: 630-784-1651 Page 1 of 4 P/N 1011095 06/10 1-800-253-2991
A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
TFH Installation Information
Operation: Low Limit/Timer
After power is applied to the TFH, the TFH checks the temperature of the Thermistor Sensor to verify that its temperature is below the Low Limit set-point potentiometer. If the thermistor temperature is below the Low Limit temperature then an internal timer is reset and activated. While the timer is activated it will continuously check the thermistor to see if its temperature rises above the Low Limit temperature. If the thermistor temperature stays below the Low Limit set-point for longer than the time set on the TFH’s time potentiometer, then the unit’s Low Limit Relay will be activated (energized) and latched. Note: Once the Low Limit relay has latched only the removal of input power will reset the TFH’s Low Limit/ timer circuitry. If the thermistor temperature rises above the Low Limit set-point before the timer has “timed – out”, i.e. Limit Relay activated, then the Timer is held in reset state until the thermistor temperature drops below the Low Limit set-point and the timer circuit again is then re-activated. The TFH has a visual front panel indicator for when Low Limit Relay has been activated (lit). This indicator is located on the left hand side of the front panel.
Warranty
1. Antunes Controls products are guaranteed to be free from mechanical and electrical defects for a period of one year from date of shipment under normal use and service provided installation is made in accordance with manufacturers’ recommendations.
2. Parts deemed defective shall be repaired or replaced at manufacturers option and at manufacturers expense but shall not include foreign or federal excise taxes, state or municipal sale or use taxes, all such taxes not limited to the foregoing being responsibility of the purchaser.
3. No charge for travel and/or mileage will be allowed to purchaser.
4. Antunes Controls reserves the right to make changes in design or make any improvements on any products. The right is always reserved to modify our equipment because of new technology, underwriter’s requirements and/or government regulations.
5. The following are not covered under warranty:
a. Failure from neglect, abuse, careless handling and
mis-application of unit.
Operation: High Limit
The High Limit circuitry of the TFH checks for a thermistor temperature above the High Limit set-point potentiometer. If the sensor temperature rises above the High Limit potentiometer then the High Limit Relay is de-energized. This relay is normally activated (energized) when power is applied and is de-activated only if the thermistor temperature exceeds the High Limit set-point potentiometer. Once the High Limit Relay is de-activated it will stay de-activated even if the thermistor temperature drops below the High Limit set-point. The High Limit Relay can only be re-activated if first the sensor temperature is below the High Limit set-point and then the Reset button, on the TFH’s front panel, is depressed. The de-activation of the High Limit Relay also results in the right side indicator becoming activated (lit).
b. Failure to observe guidelines for installation or
improper voltage hook-up.
c. Failure caused by improper maintenance.
d. Unless specifically allowed by Antunes Controls, no
other charges may be included under warranty.
Limitation of Liability: If it is understood and agreed
that seller’s liability whether in contract, in tort, under
any warranty, in negligence or otherwise, shall not
exceed the return of the amount of the purchase price
paid by purchaser and under no circumstances shall
seller be liable for special, indirect or consequential
damages. The price stated for the equipment is a
consideration in limiting seller’s liability. No action, regardless of form, arising out of the transactions may be brought by purchaser more than one year after the
cause of action has accrued.
1-630-784-1000 Fax: 630-784-1651 Page 2 of 4 P/N 1011095 06/10 1-800-253-2991