JD-2 Installation Information
IMPORTANT
Please read these instructions carefully to assure correct installation. This equipment must be installed only by a licensed electrician who is experienced with combustion safeguard control systems and understands the functions of inter­locking switches, such as gas pressure switches. Prior to being put into operation in conjunction with the combustion safeguard systems, all switches should be tested for proper range setting and proper wiring. Check piping connections and switch house for leaks with a soap bubble test. All exhaust fans and blowers should be inspected and checked for proper rotation prior to starting up.
JD-2 Switches
You are installing one of the finest switches of its type on the market. Design of this switch is based on the same principles of sensitivity, accuracy, and dependability that have made Antunes Controls Air Flow Switches so suc­cessful. These switches are fully approved. They are UL listed and recognized for the U.S. and Canada, and approved by FM.
Specifications
Blue Spring: .07” to 1.7” W.C. (2 mm to 43 mm)
Grey Spring: 0.1” to 4” W.C. (3 mm to 102 mm)
Purple Spring: 0.1” to 10” W.C. (3mm to 250 mm)
Red Spring: 0.1” to 24” W.C. (3 mm to 600 mm)
Orange Spring: 5” to 35” W.C. (125 mm to 875 mm)
Electrical: 10 A, 1/8 HP, 125 VAC; 5 A, 1/4 HP, 250 VAC;
Pilot Duty, 125 VA @ 125-250 VAC.
Field wiring by others must be rated at 194°F (90°C) for industrial use.
Max. Operating Pressure: 35” W.C.
Max. Surge Pressure: 3 PSIG
Max. Ambient Operating Temperature: 140°F (60°C)
Min. Ambient Operating Temperature: -20°F (-28°C)
Shipping Weight: 1 lbs. (.45 kg)
Switches manufactured by Antunes Controls are tested, listed, and approved by Underwriters Laboratories File # MH8009-504, Factory Mutual Serial #18221, Canadian Standards Association File #25144.
Dimensions
Note: Dimensions are for reference only.
Range Adjustment
The JD-2 switch is adjustable within its range, as shown on the range scale located on the top of the unit.
Mounting
The JD-2 is always mounted with the stem up. An optional mounting bracket can be fastened to the bottom section of the switch housing with a 5/16-18 x 1/2” bolt (supplied with the bracket).
2 5/8”
(67 mm)
1/2”
(13 mm)
7/8”
(22 mm)
1 1/8”
(28 mm)
Large
Mounting
Holes:
5/16”
(8 mm) dia.
Small
Mounting
Holes:
7/32”
(5.5 mm) dia.
7/8”
(22 mm)
1-630-784-1000 Fax: 630-784-1651 Page 1 of 4 P/N 1011082 06/10 1-800-253-2991
A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
JD-2 Installation Information
Air Connections
Tubing recommended as minimums: 1/4” copper or alu­minum tubing, or 1/8” pipe. All tubing and pipe must be clean and free from oil, dirt, and chips. If piping runs over five feet long, use a larger size tubing or pipe, and reduce size at switch.
Air Supply
The switch is equipped with two 1/8” NPT connection ports. Connect air supply as shown below. When used for vacuum or pressure applications, the JD-2 must always be vented as shown. No venting is required for differential applications.
Terminal Connections
Indicator Position Terminal
Off
On
C and NO open C and NC closed
C and NO closed C and NC open
Conduit Connection
Differential Inlet Connection
.1 .5 1
2
3
4
IN W.C.
ING
Low Vacuum or
Low Pressure
High Vacuum or
High Pressure
Vacuum Only Inlet Connection
Vacuum Connection
.1 .5 1
2
3
4
IN W.C.
ING
top chamber
C NO
NC
Vent Leave
Open