Airflow 72683701, 72574202, 72574204, 72573603, 72574201 Installation Instructions

SELV 12V Fan Range Installation and Operating Guide
Fan Dimensions
Page 2 of 16
iCON SELV 12V DC fans are designed for ventilation domes-
tic premises and available in two model sizes. They are pow­ered Safety Extra Low Voltage fans and can be fitted to a wall or ceiling.
The iCON SELV range can be used as a simple extract SELV fan operated by a remote switch (standard), or can
be fitted with an internal control module to give a range of control options (which includes: timer, humidity, motion sensor, pull cord or combinations of these functions).
These optional modules are available separately and can be fitted at the time of installation or retrofitted (see page 6).
All electrical installation work to be carried out by an approved
competent person in compliance with U.K. Building Regula­tions and to the latest IET standards, or the appropriate regu­lations in the country of installation.
The fan requires a 12V DC supply (included in the box), class III equipment (marked as stated in BS EN 60417).
The power supply unit requires 100-240V 50/60Hz supply (class II). It is self resetting for over current and short circuit
protection. An external 3A fuse and 30mA RCD is required for
each unit. The LED indicator shows the unit is switched on
The iCON SELV fan range is IPX4 rated and therefore it is suitable for mounting in bathrooms (incl. zones 1 and 2), toi­lets, kitchens and utility rooms, as long as it is not exposed to water jets (i.e. can be installed above fixed shower head).
The power supply unit must be fitted outside of wet zones (usually outside of the room). The maximum length of wire between the unit and the fan should not exceed 5 meters using 1.5mm2 wire. Never cover the power supply unit with thermal insulation materials.
Important
Do not place the ventilator near direct heat sources, e.g. radi­ant heaters, or where temperatures can exceed 40°C (104°F).
iCON Optional Colour Covers
iCON SELV 12V Optional Modules
Part no. Model Description
72573603 PCS Pull cord (Manual on/off)
72574204 PCTS Pull cord timer (Run on timer 1-30 min)
72682307 DTS
Delayed timer (2 min delay, Run on timer 2-45 min, Pull cord)
72574202 HTS
Humidity timer (40-90% RH, Run on timer 2-45 min, Pull cord)
72574203 PRTS PIR timer (Motion sensor, Run on timer 2-45 min)
72574201 PRHTS
PIR with humidity timer (Motion sensor, 40-90% RH, Run on
iCON fans can be recessed in a wall or ceiling (iCON 30S is supplied with surface mounting kit). See pages 9 -11 for details.
Always ensure free running of the fan impeller and that duct
connections are not over tightened to the fan outlet spigot.
Fix the sealed grommet supplied into the cable entry hole. Pierce the grommet to allow the mains cable to be pulled through while maintaining the integrity of the seal.
Airflow Developments recommends that rigid ducting is used where possible instead of flexible ducting, this will ensure maximum performance.
Before carrying out the installation see pages 12 & 13 for best practise recommendations.
To remove front cover assembly, first make sure the fan is off, isolated from the power supply and the iris shutter is fully closed.
1. Undo the locking screw at the bottom edge of the cover using a screwdriver.
2. Rotate the cover a few degrees anticlockwise until it clicks out from the fittings.
3. Remove the cover by pulling it out.
To refit the cover, reverse the above procedure. If when refit­ting the front cover the iris stays open, remove the cover and don’t attempt to refit it for approx. two minutes (allowing the actuator to retract back in the closed position). Then try again.
Model A B C D E F G H I
iCON 30S (R)
225 144 101 97 43 51 20 30 148
iCON 30S (S)
225 144 92 97 - - - 29 -
Model A B C D E
iCON 15S 197 108.5 67.5 100 40
Page 3 of 16
Range Overview
Part no. Model Fan Size
Air flow
[l/s / m3/h]
Power
[W]
Current
[A]
Noise level
[dB(A) @ 3m]
72683701 iCON 15S 100mm 21 / 77 6.1 0.07 32.4
72683801 iCON 30S 100mm 37 / 132 12.2 0.10 36.2
Page 4 of 16
Electrical Installation
Electrical Installation
Page 5 of 16
Page 7 of 16
Mechanical Installation
Module clip
Cable entry
Cable clamp
Module
locating block
Module fitting
place
Front Cover Removal
iCON 15S
iCON 30S
Page 8 of 16
3
1
2
Page 6 of 16
Modules & Covers
Terminal
connector
Wiring with no control module fitted:
Wiring for control modules with no external switching:
Wiring for control modules with external switching
Wiring and installation of iCON modules can be found in the Instructions included within the module packaging.
Certificate No. FM 00152
BS EN ISO 9001:2015
Certificate No. EMS 569454
BS EN ISO 14001:2015
Fixing lugs
Fixing lugs
Cover / Fan iCON 15S iCON 30S
Chrome 52634502B -
Anthracite 52634503B 52634506B
Sandstone 52634505B 52634508B
Silver 52634504B 52634507B
Ulmate Grey 52634514B 52634517B
Navy Blue 52634516B 52634519B
Turquoise 52634515B 52634518B
iCON 15S – 72683701 iCON 30S – 72683801
Recessing fan in the wall
The iCON 15S requires a 110mm diameter hole through the wall lined with a 100mm internal diameter duct.
The iCON 30S requires a 110mm diameter hole through the
wall, counter board 160mm to a depth of 80mm. The hole
should be lined with a 100mm internal diameter duct.
Surface mounting fan on the wall
When surface mounting the iCON 30S the supplied mounting skirt should be used.
The iCON 30S requires a 110mm diameter hole through the wall lined with a 100 mm internal diameter duct.
Ensure all vapour barriers are properly restored.
Ceiling Surface Mounting
When surface mounting the iCON 30S, the mounting skirt provided should be used. The mounting skirt should be fixed, with the screws provided, into the support. The fan is then fitted into the skirt.
The iCON 30S requires a 110mm diameter hole through the ceiling.
When recessing or surface mounting in the ceiling, a plywood support (min. 18mm thick) must be mounted between the ceiling joists. Any fixing screws should be fitted through the
plaster board into the support.
Measurements and Commissioning
The Building Regulations 2010, imposes a requirement that testing and reporting of mechanical ventilation performance
(see Approved Document F1) is conducted in accordance with
an approved procedure.
Compliance with this requirement by an assessed and regis­tered Competent Personshould follow a Best Practisepro­cess and adopt air flow measurement, Method A - The Uncon­ditional Method - using a suitable UKAS certified measuring instrument. Generically referred to as Zero Pressure Air Flow Meteror Powered Flow Meter’.
Further information on this method is detailed in NHBC Build­ing Regulations Guidance Note G272a 10/13 and BSRIA Guide document BG 64/2016.
Installation with flexible ducting
Where flexible ducting is used the diameter must be main­tained and it is good ventilation practice that the ducting is extended to a minimum of 90% its possible length in order to maintain the best possible air flow.
Ensure that flexible duct connections are not over tightened to the spigots.
To maximise the air flow rigid ducting should be used where possible. The fan and ducting should be installed in accord­ance with the requirements of the Domestic Ventilation Com-
pliance Guide, part of the Building Regulations.
SAFETY FIRST: ALWAYS ISOLATE THE FAN UNIT FROM THE POWER SUPPLY BEFORE DOING ANY WORK ON THE FAN/MODULE.
When installed according to these instructions the iCON range
is completely safe. The materials used do not constitute a hazard.
Cleaning
Fan and ducting should be inspected and cleaned on a regular basis to keep fan performance. The external hous-
ing of the fan can be wiped with a damp cloth. Do not use household cleaners containing abrasives. Cleaning of the internal parts such as the impeller should be carried out by using a soft brush. Never clean any parts of the fan assembly by immersing in water or using a dishwasher.
Warning
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children should not play with the appliance. Cleaning and user maintenance shall not be carried out by children without adult supervision.
Airflow Developments Ltd guarantees the iCON for 3 years from date of purchase against faulty material or workmanship. Applicable to units installed and used in the
United Kingdom.
You can register your warranty online (for more information check at www.airflow.com).
Warranty only covers the fan, not the reinstallation if required. In the event of any defective parts being found, Airflow Devel­opments Ltd reserve the right to repair or at our discretion replace without charge provided that the unit:
1. Has been installed and used in accordance with the fitting and wiring instructions supplied with each unit.
2. Has not been connected to an unsuitable electrical supply.
3. Has not been subjected to misuse, neglect or damage.
4. Has not been modified or repaired by any person not au- thorised by Airflow Developments Ltd
5. Has been installed in accordance with latest Building Regu- lations and IET wiring regulations by a person who is recog­nised as a competent installer who is part of a competent scheme provider (e.g. NICEIC Ventilation Scheme).
UK Head-Office
AIRFLOW DEVELOPMENTS Ltd
Aidelle House, Lancaster Road Cressex Business Park High Wycombe Buckinghamshire HP12 3QP United Kingdom
Tel: +44 (0) 1494 525252 Email: info@airflow.com Web: www.airflow.com
Czech Republic
AIRFLOW LUFTTECHNIK GmbH
o.s. Praha Hostýnská 520 108 00 Praha 10 Malešice Czech Republic
Tel: +42 (0) 2 7477 2230 Email: info@airflow.cz Web: www.airflow.cz
Germany
AIRFLOW LUFTTECHNIK GmbH
Wolbersacker 16 53359 Rheinbach Germany
Tel: +49 (0) 222 69205 0 Email: info@airflow.de Web: www.airflow.de
© Airflow Developments Ltd. Airflow Developments Limited reserve the right, in the interests of continuous develop­ment, to alter specifications without prior notice. All orders are accepted subject to our conditions of sale which are available on request.
Page 9 of 16
Wall Installation
iCON 15S iCON 30S (R)
Ceiling Installation
Page 10 of 16
Ceiling Recess
The fan should be fitted in the hole, fixed with the screws provided into the support.
The iCON 15S requires a 110mm diameter hole through the ceiling.
The iCON 30S requires a 160mm diameter hole through the ceiling.
Where flexible duct is used the diameter must be maintained.
Possible cable
routing
Duct
Joist
Ceiling
Plywood
Ceiling Installation
Page 11 of 16
Possible cable
routing
Duct
Joist
Ceiling
Plywood
Mounting skirt
Best Practise Recommendations
Page 12 of 16
Best Practice Recommendations
Page 13 of 16
Page 14 of 16
Maintenance
Page 15 of 16
Warranty
www.airflow.com
80000439 Issue 2 08/21
Airflow Developments Ltd shall not be liable for any loss, injury or other consequential damage, in the event of a failure of the equipment or arising from, or in connection with the equipment excepting only that nothing in this condi-
tion shall be construed as to exclude or restrict liability for
negligence.
This warranty does not in any way affect any statutory or other consumer rights.
For detailed standard warranty terms and conditions see our website or contact Customer Service.
To avoid the backflow of condensation into the fan in ceiling installations it is good practice to fit a condensation trap to
the vertical outlet duct of the fan.
With through the wall installation fit the duct in an approx.
5° angle down to outside.
Plastic
Condensation
trap
Outlet
Fan