Airflow 72687103, 72612601, 72573602 Installation Instructions

Modules for 230V Fan Range
Installation and Operating Guide
PCM – 72573602
TM – 72612601 DTM – 72675702 HTM – 72687103
PRTM – 72687104
PRHTM – 72687102
iCON 230V Fan Range Available Modules
Page 2 of 8
Page 3 of 8
Electrical installation
Page 4 of 8
Mechanical installation
Airflow iCON fans can be controlled by optional control mod­ules. For the 230V range you can choose between seven modules.
* For blister pack add Bat the end of part number.
** Not for kitchen applications with iCON 15! Approved Document Part F required continuous extract rates: 6 l/s for WC, 8 l/s for bathroom / utility room and 13 l/s for kitchen.
SAFETY FIRST: ALWAYS ISOLATE THE FAN UNIT FROM THE POWER SUPPLY BEFORE DOING ANY WORK ON THE FAN/MODULE.
Part no* Model Description
Wiring
Diagram
72573602 PCM Pull cord (Manual on/off) A
72612601 TM Timer (Run on timer 1 - 30 min) B
72675702 DTM Delayed timer (2 min delay, Run on timer 2 - 45 min, Pull cord) B
72687103 HTM
Humidity timer (40 - 90% RH, Run on timer 2 - 45 min, Pull
cord)
A, B
72687104 PRTM PIR timer (Motion sensor, Run on timer 2 - 45min) A, B
72687102 PRHTM
PIR humidity timer (Motion sensor, 40 - 90% RH, Run on timer
2 - 45 min)
A, B
72675703 2SHM**
2 speed humidity (Low speed 8 or 13 l/s, Boost at 40 - 90%
RH, Pull Cord)
A, B
All electrical installation work to be carried out by an ap-
proved competent person in compliance with U.K. Building Regulations and to the latest IET standards, or the appropri­ate regulations in the country of installation. (for fan installa­tion see the iCON 230V Fan Range Installation and Operat­ing Guide).
Diagram A - module wiring with no external switching (module functionality / pull cord activation only):
Diagram B - module wiring with external switching (live trigger connection used):
To install the module in an iCON fan follow the instructions
below. See page 5 - 8 for instructional drawings.
1. Remove the iCON fan front cover (see page 5).
2. Lift the fan electrical terminal away from its mounting pillars and position on the module connector pins. Tighten the two screws with a suitable screwdriver. Ensure the leads are under the module retaining cable clamp.
3. Fit the module at a slight angle into the fan housing, ensur- ing that the locating slot is fully engaged in to the locating block on the fan.
4. Push the module against housing, ensuring the module clip holds it in place (clicks at the cable clamp). With iCON 15 & 30 the terminal will reposition back over mounting pillars.
Modules with pull cord: Ensure that the pull cord is properly located within the cord slot at the bottom of the fan.
Modules with PIR control: Remove the oval logo cap fitted at the bottom of the front cover of the fan. Replace it with translucent lens supplied with the PIR module. Note: The lens must be replaced in order for the PIR module to function properly. Ensure the orientation of the lens is correct (i.e. the lens should be flush with the surface).
Connecting mains cable into the module
Connect the cable to the 3-way supply connector block (see wiring diagrams on page 3) ensuring that the supplied cable clamp is fitted. Refit the front cover.
Note: When using DTM module on initial connection the fan will start immediately and continue running for the duration set on the timer function of the module.
Certificate No. FM 00152
BS EN ISO 9001:2015
Certificate No. EMS 569454
BS EN ISO 14001:2015
Mechanical Installation
Page 5 of 8
Page 6 of 8
Module adjustment
Front Cover Removal
Page 7 of 8
Module
locating block
3-way supply
connector
Two module
connector pins
Module
locating slot
Cable entry
PIR lens
location
To remove front cover assembly, first make sure the fan is
off, isolated from the power supply and the iris shutter is fully closed.
1. Undo the locking screw at the bottom edge of the cover
using a screwdriver.
2. Rotate the cover a few degrees anticlockwise until it clicks out from the fittings.
3. Remove the cover by pulling it out.
To refit the cover, reverse the above procedure. The iris shutter should be in closed position after refit. If not, wait approximately 1 min after fan switch off allowing the actuator to retract back in the closed position and then refit the cover again.
3
1
2
iCON module
Module cable
clamp
Terminal block
fitting (pillars)
iCON module overview.
A module with Timer and/or Humidistat is supplied pre-set,
but may be adjusted by the installer. All adjustments must be done using the supplied Adjustment Tool.
Humidity settings
The humidistat is factory pre-set at approx. 70% RH (relative humidity). Adjusting the “% RHtowards 40% will result in fan activation at lower humidity (more sensitive). Adjusting the “% RHtowards “90%” will result in fan activation at higher humidity (less sensitive).
Time settings
The overrun timer is factory pre-set at approx. 15 min. Ad­justing the Timertowards MINwill result in a timer overrun decrease towards 1/2 minutes (depends on module). Adjust­ing the Timertowards MAXwill result in a timer overrun increase towards 30/45 minutes (depends on module).
2SHM speed settings
The bathroom/kitchen (low/high) trickle speed depends on fan model used: 7.2/9.5 l/s (iC15), 19.2/23.4 l/s (iC30) or
21.2/25.6 l/s (iC60). You can set it by a two position slide
switch. Boost (pull cord or humidity sensor activated) will always be fansmaximum speed.
Warranty
Applicable to units installed and used in the United Kingdom.
Airflow Developments Ltd guarantees the iCON range for 3 years (incl. modules) from date of purchase against faulty material or workmanship. You can register your
warranty on-line (for more information check at www.airflow.com). Warranty only covers the product, not a reinstallation if required.
For detailed standard warranty terms and conditions see our website or contact Customer Service.
Adjustment
tool
Timer control
Humidistat
control
Humidistat
MIN = 40% RH MAX = 90% RH
Timer
MIN = 1/2 min MAX = 30/45 min
Module clip
© Airflow Developments Ltd. Airflow Developments Limited reserve the right, in the interests of continuous develop­ment, to alter specifications without prior notice. All orders are accepted subject to our
conditions of sale which are available on request.
www.airflow.com
UK Head-Office
AIRFLOW DEVELOPMENTS Ltd Aidelle House, Lancaster Road Cressex Business Park High Wycombe Buckinghamshire HP12 3QP United Kingdom
Tel: +44 (0) 1494 525252 Email: info@airflow.com Web: www.airflow.com
Czech Republic
AIRFLOW LUFTTECHNIK GmbH o.s. Praha Hostýnská 520 108 00 Praha 10 Malešice Czech Republic
Tel: +42 (0) 2 7477 2230 Email: info@airflow.cz Web: www.airflow.cz
Germany
AIRFLOW LUFTTECHNIK GmbH Wolbersacker 16 53359 Rheinbach Germany
Tel: +49 (0) 222 69205 0 Email: info@airflow.de Web: www.airflow.de
80000438 Issue 3 08/21