AERCO GF-114 User Manual

GF-114
OMM-0035_0C
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
Modbus® is a registered
Released: 05/18/2012
MODBUS
USER MANUAL
Installation, Operation, and Maintenance
MODBUS Communication For:
C-More Boiler Controllers
Boiler Management System
(BMS/BMS II)
AERCO Control System
(ACS)
Communication
®
trademark of AEG Modicon
GF-114
Technical Support:
www.aerco.com
OMM-0035_0B USER MANUAL
MODBUS
(Mon–Fri, 8am-5pm EST)
Communication
1-800-526-0288
Disclaimer
The information contained in this manual is subject to change without notice from AERCO International, Inc. AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
Page 2 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
Contents USER MANUAL
MODBUS
Communication GF-114
OMM-0035_0C
TABLE OF CONTENTS
TABLE OF CONTENTS ............................................................................................................... 3
CHAPTER 1: INTRODUCTION AND GENERAL DESCRIPTION ....................... 7
1.1 INTRODUCTION................................................................................................................... 7
1.2 AERCO BMS AND C-MORE CONTROLLER MODELS COVERED ................................... 7
1.3 MIMIMUM MODBUS SUPPORT REQUIREMENTS ............................................................ 8
1.3.1 Communication Medium ................................................................................................ 9
1.3.2 Address Support............................................................................................................ 9
1.3.3 Modbus Transmission Modes ....................................................................................... 9
1.3.4 Timing Specifications .................................................................................................... 9
1.4 MODBUS FUNCTION SET SUPPORT .............................................................................. 10
1.5 EXCEPTION RESPONSES ................................................................................................ 11
1.6 PHRASES, ABBREVIATIONS & ACRONYMS ................................................................. 11
CHAPTER 2: STANDARD REGISTER ASSIGMENTS .................................... 13
2.1 INTRODUCTION................................................................................................................. 13
2.1.1 Input Registers ............................................................................................................ 13
2.1.2 Holding Registers ........................................................................................................ 13
2.2 C-MORE BOILER CONTROLLER STANDARD REGISTER ASSIGNMENTS ................. 14
2.2.1 C-More Boiler Controller Standard Input Register Assignments ................................. 14
2.2.2 C-More Boiler Controller Standard Holding Register Assignments ............................. 17
2.3 BMS/BMS II CONTROLLER STANDARD REGISTER ASSIGNMENTS .......................... 21
2.3.1 BMS/BMS II Controller Standard Input Register Assignments .................................... 21
2.3.2 BMS/BMS II Controller Standard Holding Register Assignments ............................... 28
2.4 ACS CONTROLLER (ONLY) STANDARD REGISTER ASSIGNMENTS ......................... 36
2.4.1 ACS Controller Standard Input Register Assignments ................................................ 36
2.4.2 ACS Controller Standard Holding Register Assignments ............................................ 43
CHAPTER 3: STANDARD APPLICATION OPERATIONS ............................... 53
3.1 INTRODUCTION................................................................................................................. 53
3.2 C-MORE CONTROLLER STANDARD APPLICATION OPERATIONS ............................ 53
3.2.1 Password Protection for Input and Holding Register Access ...................................... 53
3.2.2 Simultaneous RS232 & RS485 Access to C-More Controller Variables ..................... 54
3.2.3 Direct Drive Control ..................................................................................................... 54
3.2.4 Remote Setpoint Control ............................................................................................. 54
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 3 of 200
GF-114
OMM-0035_0C USER MANUAL Contents
3.2.5 Combination Control (BMS/ACS Only) ........................................................................ 55
3.2.6 Physical Slave Address Zero ...................................................................................... 55
3.3 BMS/BMS II/ACS STANDARD APPLICATION OPERATIONS ........................................ 55
3.3.1 Password Protection for BMS/BMS II/ACS Input and Holding Register Access ......... 55
3.3.2 Remote Setpoint Control of BMS/BMS II/ACS Slave By EMS Master ........................ 55
3.3.3 BMS/BMS II/ACS Master Control of C-More Slaves Via Network ............................... 56
3.3.4 BMS Combination Mode Boiler Control of C-More Slaves (BMS and ACS Only) ....... 56
CHAPTER 4: MODBUS NETWORK HARDWARE SETUP & INSTALLATION . 57
4.1 INTRODUCTION................................................................................................................. 57
4.2 PHYSICAL MODBUS RS485 NETWORK WIRING CONNECTIONS ............................... 57
4.2.1 BMS Slave To EMS Master Wiring Connections ........................................................ 57
4.2.2 BMS II/ACS Slave To EMS Master Wiring Connections ............................................. 61
4.2.3 BMS/BMS II/ACS Master To C-More Boiler Controller Slaves .................................... 64
MODBUS
Communication
4.2.4 C-More Slaves To BMS/BMS II/ACS or EMS Master ................................................. 66
4.3 RS485 LOOP TERMINATING RESISTORS AND BIAS .................................................... 66
4.3.1 BMS Terminating Resistor .......................................................................................... 66
4.3.2 C-More Boiler Controller Terminating Resistor and Bias ............................................ 66
4.4 MODBUS NETWORK WIRING DIAGRAMS ...................................................................... 70
4.4.1 Wiring Diagrams for Master EMS Controlling BMS Slaves With Legacy (PWM) Boilers 70
4.4.2 Wiring Diagram for Master BMS/BMS II/ACS Controlling Networked C-More Slaves 70
4.4.3 Wiring Diagram For EMS Master Controlling C-More Controller Slaves ..................... 70
CHAPTER 5: MODBUS SOFTWARE SETUP: C-MORE & BMS ...................... 75
5.1 INTRODUCTION................................................................................................................. 75
5.2 C-MORE BOILER CONTROLLER SETUP FOR MODBUS OPERATION ........................ 75
5.2.1 Monitoring and Configuration Control .......................................................................... 76
5.2.2 Modbus Direct Drive Control and Monitoring .............................................................. 76
5.2.3 Modbus Remote Setpoint Control ............................................................................... 76
5.3 BMS SETUP FOR OPERATION AS A SLAVE TO AN EMS MASTER ............................ 77
5.3.1 BMS Monitoring and Configuration By An EMS Master .............................................. 77
5.3.2 BMS Modbus Remote Setpoint Control By An EMS Master ....................................... 77
5.4 BMS SETUP AS MASTER TO C-MORE BOILER CONTROLLERS ................................ 78
Page 4 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
Contents USER MANUAL
CHAPTER 6: MODBUS SOFTWARE SETUP: C-MORE & BMS II/ACS ........... 81
6.1 INTRODUCTION................................................................................................................. 81
6.2 C-MORE BOILER CONTROLLER SETUP FOR MODBUS OPERATION ........................ 81
6.2.1 Monitoring and Configuration Control .......................................................................... 81
6.2.2 Modbus Direct Drive Control and Monitoring .............................................................. 82
6.2.3 Modbus Remote Setpoint Control ............................................................................... 82
6.3 BMS II/ACS SETUP FOR OPERATION AS A SLAVE TO AN EMS MASTER ................. 83
6.3.1 BMS II/ACS Monitoring and Configuration By An EMS Master ................................... 83
6.3.2 BMS II/ACS Modbus Remote Setpoint Control By An EMS Master ............................ 83
6.4 BMS II/ACS SETUP AS MASTER TO C-MORE BOILER CONTROLLERS ..................... 84
APPENDIX A: C-MORE BOILER CONTROLLER STATUS & FAULT MESSAGES, CONVERSION EQUATIONS, BCM FAULT CODES, BMM FAULT CODES, AND I/O STATUS TABLES……………………………………………………………………………………………….87
MODBUS
Communication GF-114
OMM-0035_0C
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 5 of 200
GF-114
OMM-0035_0C USER MANUAL Contents
MODBUS
(This page intentionally blank)
Communication
Page 6 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
Chapter 1 Introduction & Description USER MANUAL
MODBUS
Communication GF-114
OMM-0035_0C
CHAPTER 1. INTRODUCTION AND GENERAL
DESCRIPTION

1.1 INTRODUCTION

The information contained in this manual provides general guidelines for implementing a Modbus® communications network utilizing AERCO’s Boiler Management System (BMS) Model 168, Boiler Management System II (BMS II) Model 5R5-384, or AERCO Control System (ACS) and C-More Boiler Controllers.
Throughout this document, the following terminology shall be used when referring to BMS Model 168 and BMS II Model 5R5-384:
BMS: Applies to BMS Model 168 Only
BMS II: Applies to BMS II Model 5R5-384 Only
BMS/BMS II: Applies to Both Models (BMS and BMS II)
BMS II/ACS: Applies to Both Models (BMS II and ACS)
ACS: Applies to ACS Only
All Modbus networks are implemented utilizing a Master-Slave technique where only one device, the Master, can initiate a communication sequence. AERCO C-More Controllers can only function as Slave devices in a Modbus network. However, the AERCO BMS can function both as a Master controlling C-More Slaves, or as a Slave controlled by an Energy Management System (EMS) or Building Automation System (BAS) developed by other manufacturers.

1.2 AERCO BMS AND C-MORE CONTROLLER MODELS COVERED

To easily determine if your AERCO BMS or C-More Boiler Controller is equipped with Modbus capabilities, check the current software version as follows:
For BMS:
Apply power to the BMS
The BMS will display: INITIALIZING followed by EPROM REV K
If REV K or higher is displayed, the BMS Controller can support Modbus
If the REV level is lower than K, the BMS Controller cannot support Modbus
For BMS II/ACS:
All BMS II Controllers support Modbus
For C-More:
Apply external power to the C-More Controller
Scroll through the Setup Menu and observe the displayed Software Version
If 2.00 or higher is displayed, the C-More Controller can support Modbus
If a Software Version lower than 2.00 is displayed, the C-More Controller cannot support
Modbus
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 7 of 200
GF-114
Communication Medium: Allowable Cable Lengths:
PWM:
1,000 Feet, Maximum
Address Support From Master:
1 to 127 (From Master BMS/BMS II/ACS or
0 is Reserved for Broadcast
Messages
Transmission Mode Support
RTU (Remote Terminal Unit)
Timing Specifications:
last character of
Seconds
OMM-0035_0C USER MANUAL Introduction & Description
MODBUS
Communication Chapter 1

1.3 MIMIMUM MODBUS SUPPORT REQUIREMENTS

Implementation of a Modbus communication network utilizing the AERCO C-More Controller and BMS/BMS II will be limited to the minimum support requirements listed in Table 1-1 which follows. The remaining paragraphs in this Section provide more detailed descriptions for each of the items listed.
Table 1-1: Modbus Communication and Support Requirements
CHARACTERISTIC REQUIREMENT
EMS Master-To-BMS/BMS II/ACS Slave:
BMS/BMS II/ACS Master-To-C-More Slave:
EMS Master-To- C-More Slave:
RS232:
RS485:
BMS/BMS II/ACS:
C-More Controller (Slave):
Broadcast Messages:
Baud Rate:
Message Framing:
Character Framing:
Heartbeat Timeout:
RS232 (or RS485 With Optional Converter)
RS485, 2-Wire Differential Bus With Shield
RS485, 2-Wire Differential Bus With Shield
50 Feet, Maximum
4,000 Feet, Maximum
128 to 247 (From a Master EMS)
EMS)
Address
Fixed at 9600 For C-More
Adjustable For BMS/BMS II/ACS: 2400, 4800, 9600, 14.4k, 19.2k Default = 9600
Silent period of at least 3.5 character times Before first character and After message
No more than 1.5 character times of silence between received and transmitted characters
Page 8 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
Fixed at 10 seconds For C-More Adjustable For BMS/BMS II/ACS: 5 to 240
Chapter 1 Introduction & Description USER MANUAL
MODBUS
Communication GF-114
OMM-0035_0C

1.3.1 Communication Medium

The communication medium for each of the possible Modbus network configurations may vary depending on the Master/Slave scenario being implemented. Detailed installation procedures and wiring diagrams for the configurations described in the following paragraphs are provided in Section 4 of this manual.
1.3.1.1 EMS Master To BMS/BMS II/ACS Slave
The Modbus network connections between the EMS and BMS/BMS II/ACS will depend on the type of port provide on the EMS Master. If the EMS contains a RS232 port, a direct connection can be made directly to the BMS/BMS II/ACS RS232 port. For optimum results the wire length between the EMS and BMS/BMS II/ACS RS232 connection should not exceed 50 feet. If the EMS Master contains a RS485 port, a RS485-to-RS232 converter will be required to implement the Modbus network.
1.3.1.2 BMS/BMS II/ACS Master To C-More Boiler Controller Slaves
Up to a total of 32 C-More Boiler Controllers can be connected to a BMS/BMS II/ACS Master on the Modbus Network. Multi-point drop network connections are made using shielded, twisted­pair wire. In addition to the Modbus Network Boilers, up to 8 additional Legacy Boilers can be connected to the BMS Pulse Width Modulation (PWM) wiring connection. The BMS II and ACS do not support PWM. It should be noted that the BMS, BMS II, and ACS include a Modbus Pass-Thru feature which, when enabled, permits an EMS to monitor and configure (but not directly control) the boilers.
1.3.1.3 EMS Master To C-More Boiler Controller Slaves
The number of C-More Boiler Controllers which can be connected to a Modbus Network which utilizes a third party EMS Master will depend on the EMS’s limitations. Theoretically, the maximum number of Slave devices is limited to 127. If the EMS contains a RS232 port, a RS232-to-RS485 converter will be required to provide the necessary RS485 interfaces and signal levels for the C-More Boiler Controllers. Multi-drop network connections are made using shielded, twisted-pair wire.

1.3.2 Address Support

Address support is assigned as follows:
BMS/BMS II/ACS Address Support From EMS Master: 128 – 247 (80 – F7 hex)
C-More Address Support From BMS/BMS II/ACS or EMS Master: 1 – 127 (01 – 7F hex)
Broadcast Messages: Address 0 is reserved for all Broadcast messages

1.3.3 Modbus Transmission Modes

Many Modbus Controllers can be set up to transmit using either the ASCII (American Standard Code for Information Interchange) transmission mode, or the RTU (Remote Terminal Unit) transmission mode. However, since RTU messages can be formatted using far fewer binary bits than the corresponding ASCII message, it is far more efficient. Therefore, all Modbus messages for the AERCO BMS/BMS II/ACS and C-More Boiler Controllers use RTU transmission ONLY. If a third-party EMS Master is being used in the Modbus network, ensure that it is set for RTU transmission.

1.3.4 Timing Specifications

As Table 1-1 shows, Baud Rate and Heartbeat Timeout will vary depending on the Configurations of the AERCO BMS/BMS II/ACS and C-More Boiler Controllers being used in the Modbus Network. Ensure that the Baud Rate used by the controlling Master (BMS/BMS II/ACS
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 9 of 200
GF-114
Function Code
Function Name
Read Holding Register (Read Multiple Registers)
04
Read Input Registers
06
Preset (Write) Single Register
Diagnostics
Codes)
17
Report Slave ID
Sub-
Code
00
Return Query Data
Loop-Back
01
Restart Communications Options
Resets the Slave. Cancels Listen Only Mode.
02
Return Diagnostic Register
Not Used
04
Force Listen Only Mode
Reset by Restart Communications Option
Also cleared at power up. Clears only the counters
12
Return Bus Communication Error Count
Slave CRC errors only.
13
Return Bus Exception Error Count
Slave Exception Response count.
Number of messages addressed to the slave
broadcast messages.
Number of messages addressed to the slave for which no response was returned.
18
Return Bus Character Overrun Count
Number of overrun and framing errors.
OMM-0035_0C USER MANUAL Introduction & Description
MODBUS
Communication Chapter 1
or EMS) matches the appropriate Baud Rate supported by the Network Slaves (BMS/BMS II/ACS or C-More Controllers). Also, ensure that the Modbus Master can refresh the control information to all C-More Slaves before the Heartbeat Timeout period expires.

1.4 MODBUS FUNCTION SET SUPPORT

The complete Modbus protocol includes a total of 24 Function Codes. However, for AERCO BMS/BMS II/ACS and C-More Boiler Controllers, only the Codes listed in Table 1-2 are supported. The supported Diagnostic Sub-Function Codes associated with Diagnostic Function Code 08 are listed in Table 1-3.
Table 1-2: Required Function Code Set
03
08
(See Table 1-3 for supported Sub-Function
Table 1-3: Minimum Diagnostic (Function Code 08) Sub-Function Set
Function
10 Clear Counters and Diagnostic Register
Sub-Function Name Comments
14 Return Slave Message Count
15 Return Slave No Response Count
Page 10 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
and successfully processed. Includes
Chapter 1
Exception Code
Description
Comments
The function code received is not valid or is not supported.
The data address received is invalid or is not accessible due to security setting.
03
Illegal Data Value
The data value received is not valid
Phrase, Abbreviation
or Acronym
ACS
AERCO Control System
ASCII
American Standard Code for Information Interchange
BAS
Building Automation System
Baud
Bits per Second (bps)
BMS (BMS II)
Boiler Management System (Boiler Management System II)
(or Control Box)
used in all Benchmark and KC Series product lines
EMS
Energy Management System
FDX
Full-Duplex
HDX
Half-Duplex
Hex
Hexadecimal Number (0 - 9, A - F)
Input/Output (I/O) Box currently used on all Benchmark and KC Series products
LSB
Least Significant Byte
A serial, half-duplex data transmission protocol developed by AEG Modicon
MSB
Most Significant Byte
A standard for serial, full-duplex (FDX) transmission of data based on the RS232 Standard
A standard for serial, full-duplex (FDX) transmission of data based on the RS422 Standard
based on the RS485 Standard
RTU
Remote Terminal Unit
Introduction & Description USER MANUAL
MODBUS
Communication GF-114
OMM-0035_0C

1.5 EXCEPTION RESPONSES

With the exception of Broadcast Messages, queries transmitted by the Master expect a normal response from the addressed Slave on the network. However, if the addressed Slave cannot process or interpret the message, it will respond with one of the Exception Codes listed in Table 1-4.
Table 1-4: Minimum Exception Code Set
01 Illegal Function
02 Illegal Data Address

1.6 PHRASES, ABBREVIATIONS & ACRONYMS

The phrases, abbreviations and acronyms used in this manual are listed in Table 1-5.
Table 1-5: Phrases, Abbreviations and Acronyms
C-More Controller
I/O Box
Modbus®
RS232
Meaning
A control system developed by AERCO International and currently
RS422
RS485
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 11 of 200
A standard for serial, half-duplex (HDX) transmission of data
GF-114
OMM-0035_0C USER MANUAL Introduction & Description
MODBUS
(This page intentionbally blank)
Communication Chapter 1
Page 12 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
Chapter 2 Standard Register Assignments USER MANUAL
MODBUS
Communication GF-114
OMM-0035_0C

CHAPTER 2. STANDARD REGISTER ASSIGMENTS

2.1 INTRODUCTION

This Section provides the standard data register addresses assigned to the AERCO and C­More Boiler Controllers, the AERCO Boiler Management System (BMS/BMS II), and AERCO Control System (ACS). These data registers consist of Input Registers and Holding Registers. All register addresses provided throughout this manual are expressed as hexadecimal numbers.

2.1.1 Input Registers

The Input Registers for the AERCO C-More Boiler Controllers and AERCO BMS/BMS II/ACS are intended for information and functions that cannot or should not be controlled remotely. Therefore, unless otherwise specified, ALL Input Register data are READ ONLY.
IMPORTANT
All Modbus addresses specified in this manual are written generically in decimal/hexadecimal format. However, many Building Automation Systems utilize another form of addressing where:
40001 is added to the generic address for a Holding Register address.
And
30001 is added to the generic address for an Input Register address. Be sure to check the addressing scheme being used by the BAS that is being interfaced to the XPC Gateway.

2.1.2 Holding Registers

The Holding Registers for the AERCO C-More Boiler Controllers and AERCO BMS/BMS II/ACS are intended for information and functions that can be read or written (R/W). Therefore unless otherwise specified, all Holding Register data are R/W.
CAUTION
DO NOT write in any Register Addresses marked as “Reserved” in the Input Register and Holding Register Tables which follow. Failure to observe this precaution may result in unstable operation.
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 13 of 200
GF-114
Modbus Data
Decimal (Hex)
Default Message Display Code
See Appendix A, Table A-1 for listing
Enum (0, 1, 2, 3, 4, 5)
5 = Unit Status Fault
See Appendix A,
Conversions
See Appendix A,
Conversions
See Appendix A,
Conversions
See Appendix A,
Conversions
See Appendix A,
Conversions
See Appendix A,
Conversions
8 (0x0008)
Fire Rate Out
% (0 to 100)
9 (0x0009)
O2 Level
% (0 to 25)
10 (0x000A)
CO Level
PPM (0 to 500)
The actual range for run
0 to 999,999
12 (0x000C)
Run Cycles High (MSB)
Int (0 to 15)
OMM-0035_0C USER MANUAL Standard Register Assignments
MODBUS
Communication Chapter 2

2.2 C-MORE BOILER CONTROLLER STANDARD REGISTER ASSIGNMENTS

2.2.1 C-More Boiler Controller Standard Input Register Assignments

The Read Only Input Register addresses are listed in Table 2-1 which follows:
Table 2-1: C-More Boiler Controller Standard Input Register Address Mapping
Address
0 (0x0000)
1 (0x0001) Unit Status
2 (0x0002) Outlet Temp
3 (0x0003) Inlet Temp DEGREES_1 (0 to 1000)
4 (0x0004) Aux Temp
Menu Item Units and Range
Enum (1 to 64)
0 = Unit Status Disabled 1 = Unit Status Standby 2 = Unit Status Manual 3 = Unit Status Remote 4 = Unit Status Auto
DEGREES_1 (0 to 1000)
DEGREES_1 (0 to 1000)
Default/
Comments
Tables A-2 and A-3 for
Tables A-2 and A-3 for
Tables A-2 and A-3 for
5 (0x0005) Outdoor Temp DEGREES_2 (0 to 1000)
6(0x0006) Exhaust Temp DEGREES_2 (0 to 1000)
7 (0x0007) FFWD Temp DEGREES_1 (0 to 1000)
11 (0x000B) Run Cycles Low (LSB) int (0 to 65535)
Page 14 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
Tables A-2 and A-3 for
Tables A-2 and A-3 for
Tables A-2 and A-3 for
cycles is from
Chapter 2
Modbus Data
Decimal (Hex)
The actual range for run hours
0 to 999,999
Run Hours High (MSB)
15 (0x000F)
Flame Strength
% (0 to 100)
See Appendix A,
Conversions
17 (0x0011)
Fire Rate In
% (0 to 100)
Only applicable when in the
the front panel interface
Default = 0
communications
20 (0x0014)
Software Version
int (0 to 65535)
21 (0x0015) 22 (0x0016)
23 (0x0017)
Fault Log Code
Fault Log
The internal variable type for
and the range is 0 to 999999
Fault Log Cycle (HIGH)
Fault Log Date
Int (1 to 65535) 1 count/day
Fault Log Time
Int (0 to 1439) 1 count/min.
See Appendix A,
Conversions
Standard Register Assignments USER MANUAL
MODBUS
Communication GF-114
OMM-0035_0C
Table 2-1: C-More Boiler Controller Standard Input Register Address Mapping
(Continued)
Address
13 (0x000D)
14 (0x000E)
16 (0x0010) Active Set point DEGREES_1 (0 to 1000)
18 (0x0012) Manual Fire Rate % (0 to 100)
19 (0x0013)
Menu Item Units and Range
Run Hours Low (LSB)
Comm Address
int (0 to 65535)
int (0 to 15)
Int (0 to 127)
Default/
Comments
is from
Tables A-2 and A-3 for
Manual Mode and controlled by
Comm Address 0 disables the Controller’s Modbus
24 (0x0018)
25 (0x0019)
26 (0x001A)
27 (0x001B)
28 (0x001C)
(Reserved)
Fault Log Cycle (LOW)
Sensor Log Active Setpoint
int (0 to 65535)
Int (0 to 15)
DEGREES_1 (0 to 1000)
fault log display cycle is long
Tables A-2 and A-3 for
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 15 of 200
GF-114
Modbus Data
Decimal (Hex)
See Appendix A,
Conversions
See Appendix A,
Conversions
See Appendix A,
Conversions
See Appendix A,
Conversions
See Appendix A,
Conversions
See Appendix A,
Conversions
Sensor Log CO xmitter
Sensor Log O2 xmitter
Sensor Log Flow Meter
73 (“I”) = Ignition
82 (“R”) = Run
Time Log Fire Rate
Time Log Flame Strength
Time Log Run Length
Time Log Date
Int (0 to 65535) 1 count/day
Time Log Time
Int (0 to 1439) 1 count/min.
OMM-0035_0C USER MANUAL Standard Register Assignments
MODBUS
Communication Chapter 2
Table 2-1: C-More Boiler Controller Standard Input Register Address Mapping
(Continued)
Address
29 (0x001D)
30 (0x001E)
31 (0x001F)
32 (0x0020)
33 (0x0021)
34 (0x0022)
Menu Item Units and Range
Sensor Log Outlet Temp
Sensor Log Inlet Temp
Sensor Log FFWD Temp
Sensor Log Exhaust Temp
Sensor Log Outdoor Temp
Sensor Log Aux Temp
DEGREES_1 (0 to 1000)
DEGREES_1 (0 to 1000)
DEGREES_1 (0 to 1000)
DEGREES_3 (0 to 1000)
DEGREES_2 (0 to 1000)
DEGREES_1 (0 to 1000)
Default/
Comments
Tables A-2 and A-3 for
Tables A-2 and A-3 for
Tables A-2 and A-3 for
Tables A-2 and A-3 for
Tables A-2 and A-3 for
Tables A-2 and A-3 for
35 (0x0023)
36 (0x0024)
37 (0x0025)
38 (0x0026)
39 (0x0027)
40 (0x0028)
41 (0x0029)
42 (0x002A)
43 (0x002B)
Time Log Status
PPM_UNITS
% (0 to 100)
GPM_UNITS
74 (“O”) = Off 80 (“P”) = Power Up
% (0 to 100)
% (0 to 100)
Int (0 to 65535)
Page 16 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
Chapter 2
Modbus Data
Decimal (Hex)
See Appendix A,
Remote Set Point Mode
Normally Read Only. R/W ONLY in Direct Drive Mode.
2 (0x0002)
Modbus Password
int (0 to 65535)
Default = 0
3 (0x0003)
Password
int (0 to 65535)
Default = 0
See Appendix A,
Default = 130°F
5 (0x0005)
(Reserved)
Int (0 to 1439) 1count/min
Date count starts with Jan.
counts
bool (0, 1)
1=Degrees Celsius (°C)
enum (0, 1, 2, 3, 4)
3 = 19.2k
bool (0, 1)
1 = Water Heater
enum (0, 1, 2, 3, 4, 5)
5 = 3 MBTU
Standard Register Assignments USER MANUAL
MODBUS
Communication GF-114
OMM-0035_0C

2.2.2 C-More Boiler Controller Standard Holding Register Assignments

The Read/Write Input Register address assignments are listed in Table 2-2 which follows. Unless otherwise specified, all Holding Register menu items are Read/Write (R/W)
Table 2-2: C-More Controller Standard Holding Register Address Mapping
Address
0 (0x0000)
1 (0x0001) Net Direct Drive % (0 to 100)
4 (0x0004) Internal Set Point DEGREES_1 (0 to 1000)
6 (0x0006) Time
7 (0x0007) Date
Menu Item Units and Range Comments
Net Remote Set Point
DEGREES_1 (0 to 1000)
int (0 to 65535) 1count/day
Tables A-2 and A-3 for Conversions. R/W ONLY in
Tables A-2 and A-3 for Conversions
1, 2000. For Example: Jan. 1 2001 would equal 365
8 (0x0008) Unit of Temp
9 (0x0009) Baud Rate
10 (0x000A) Unit Type
11 (0x000B) Unit Size
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 17 of 200
0= Degrees Fahrenheit (°F)
0 = 2.4k 1 = 4.8k 2 = 9.6k
0 = Boiler
0 = 0.5 MBTU 1 = 1 MBTU 2 = 1.5 MBTU 3 = 2 MBTU 4 = 2.5 MBTU
Default = °F
For C-More RS232 port ONLY
Default = 2 (9.6k)
Default = Boiler
Default = 1 (1 MBTU)
GF-114
Modbus Data
Decimal (Hex)
enum (0, 1, 2, 3, 4):
4 = Outdoor Reset
enum (0, 1, 2, 3):
3 = Network
See Appendix A,
Conversions
Int (1 to 99 counts)
(Counts = Actual x 10)
Actual Default = 1.2
1.2 x 10 = 12 counts
bool (0,1)
1 = True
See Appendix A,
Default = 60°F
See Appendix A,
Default = 60°F
See Appendix A,
Default = 200°F
See Appendix A,
Default = 210°F
21 (0x0015)
Max Fire Rate
% (40 - 100)
Default = 100%
MIN_UNITS (0 to 30) 1count/min
SEC_UNITS (0 to 120) 1count/sec
OMM-0035_0C USER MANUAL Standard Register Assignments
MODBUS
Communication Chapter 2
Table 2-2: C-More Controller Standard Holding Register Address Mapping
(Continued)
Address
12 (0x000C) Boiler Mode
13 (0x000D) Remote Signal
14 (0x000E) Bldg Ref Temp DEGREES_1 (0 to 1000)
15 (0x000F) Reset Ratio
16 (0x0010)
Menu Item Units and Range Comments
0 = Constant Setpt 1 = Remote Setpt 2 = Direct Drive 3 = Combo Unit
0 = 4 - 20 mA /1 - 5V 1 = 0 -20mA/0 - 5V 2 = PWM Input
Actual Range = 0.1 to 9.9
Outdoor Sensor Enable
0 = False
Default = 0 (Constant Setpt)
Default = 0 (4 - 20 mA/1 - 5V)
Tables A-2 and A-3 for
Therefore:
Default = 0 (False)
17 (0x0011) System Start Temp
18 (0x0012) Set Point Lo Limit DEGREES_1 (0 to 1000)
19 (0x0013) Set Point Hi Limit DEGREES_1 (0 to 1000)
20 (0x0014) Temp Hi Limit
22 (0x0016) Pump Delay Timer
23 (0x0017) Aux Start On Delay
Page 18 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
DEGREES_2 (0 to 1000)
DEGREES_1 (0 to 1000)
Tables A-2 and A-3 for Conversions
Tables A-2 and A-3 for Conversions
Tables A-2 and A-3 for Conversions
Tables A-2 and A-3 for Conversions
Default = 0 min.
Default = 0 sec.
Chapter 2
Modbus Data
Decimal (Hex)
enum (0, 1)
1=Constant Setpoint
SEC_UNITS (2 to 60) 1count/sec
See Appendix A,
Conversions
27 (0x001B)
0.00 to 2.00
Actual x 100 Counts
Heater:1.60 (160 counts)
28 (0x001C)
Actual x 100 Counts
(10 counts)
29
Water Heater ONLY
Conversions
30 (0x001E)
Water Heater ONLY
Conversions
31 (0x001F)
bool (0, 1)
1 = On
32 (0x0020) Thru 59 (0x003B)
60 (0x003C)
bool (0, 1)
1 = Enabled
61 (0x003D)
See Appendix A,
Conversions
62 (0x003E) Thru 66 (0x0042)
MODBUS
Communication GF-114
Standard Register Assignments USER MANUAL
Table 2-2: C-More Controller Standard Holding Register Address Mapping
(Continued)
OMM-0035_0C
Address
24 (0x0018) Failsafe Mode
25 (0x0019) Low Fire Timer
26 (0x001A) Prop Band
Integral Gain
(0x001D) Min Load Adjust
Menu Item Units and Range Comments
Derivative Time
0=Shutdown
ABS_DEG_1 (0 to 1000)
(0.01 increments)
MIN_UNITS (0.00 to 2.00) (0.01 min. increments) 1count/0.01min
ABS_DEG_1 (0 to 1000)
Default = 0 (Shutdown)
Default = 2 sec.
Tables A-2 and A-3 for
Defaults: Boiler: 0.10 (10 counts),
Defaults: Boiler: 0.00 min. (0 counts) Heater: 0.10 min
See Appendix A, Tables A-2 and A-3 for
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 19 of 200
Max Load Adjust
Outlet Feedback
(Reserved)
Set Point Limit Band
Set Point Limiting
(Reserved)
ABS_DEG_1 (0 to 1000)
0 = Off
0 = Disabled
ABS_DEG_1 (0 to 1000)
See Appendix A, Tables A-2 and A-3 for
Default = 1 (On) Water Heater ONLY
Default = 0 (Disabled)
Tables A-2 and A-3 for
GF-114
Modbus Data
Decimal (Hex)
67 (0x0043)
Enum (0 to 8)
8 = 24 Hrs.
68 (0x0044)
Fault Log Pointer
int 0 - 9
69 (0x0045)
Sensor Log Pointer
int 0 - 1199
70 (0x0046)
Time Log Pointer
int 0 - 10239
71 (0x0047)
65535 (0xFFFF)
OMM-0035_0C USER MANUAL Standard Register Assignments
MODBUS
Communication Chapter 2
Table 2-2: C-More Controller Standard Holding Register Address Mapping
(Continued)
Thru
Address
Sensor Log Interval
Menu Item Units and Range Comments
0 = Off 1 = 1 Min. 2 = 5 Min. 3 = 15 Min. 4 = 30 Min. 5 = 1 Hr. 6 = 6 Hrs 7 = 12 Hrs.
(Reserved)
Default = 4 (30 min)
Available for future expansion.
Page 20 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
Chapter 2
Modbus Data
Decimal (Hex)
0 (0x0000)
(Reserved)
1 (0x0001)
Header Temperature
40 to 220°F
Outside Air Temperature
Indoor Air/Return Temperature
Indoor Air Temp = BMS Return Temp = BMS II
0 to 100% (out to boilers)
Header Set Temperature
Default = 128
is Off-Line as a Slave)
0 to 40 (for BMS) 0 to 32 (for BMS II)
0 to 40 (for BMS) 0 to 32 (for BMS II)
9 (0x0009)
(Reserved)
0 to 65535
5 = 4-20mA Input Error
11 (0x000B)
15 (0x000F)
1 to 40 (for BMS) 1 to 32 (for BMS II)
Standard Register Assignments USER MANUAL
MODBUS
Communication GF-114
OMM-0035_0C

2.3 BMS/BMS II CONTROLLER STANDARD REGISTER ASSIGNMENTS

2.3.1 BMS/BMS II Controller Standard Input Register Assignments

The Read Only Input Register address assignments for the BMS/BMS II are listed in Table 2-3 which follows:
Table 2-3: BMS/BMS II Standard Input Register Address Mapping
Address
2 0x0002)
3 (0x0003)
4 (0x0004) Fire Rate Out
5 (0x0005)
6 (0x0006) Network Address
7 (0x0007) Total Boilers Fired
8 (0x0008) Total Boilers On Line
Menu Item Units and Range
-60 to 120°F
40 to 220°F
40 to 220°F
128 to 247
Default/
Comments
(If Address = 0, BMS/ BMS II
10 (0x000A)
thru
16 (0x0010) Lead Boiler Number
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 21 of 200
Bit: 0 = Outside Air Sensor
Fault/Message Code
(Reserved)
1 = Header Sensor Error 2 = Interlock 1 Error 3 = Interlock 2 Error 4 = Indoor Air Sensor Error/ Return Sensor Error
Interpret Bit 4 as follows:
Indoor Air Sensor Error applies to BMS.
Return Sensor Error applies to BMS II.
GF-114
Dec. (Hex)
119 = Not On-Line
1–40 = Fired & Sequence
Boilers 1 - 8 are referred to as the Legacy (PWM) Boilers.(BMS Only)
Boiler 2 Status (PWM Boiler 2)
(Same As Above) (BMS Only)
Boiler 3 Status (PWM Boiler 3)
(Same As Above) (BMS Only)
Boiler 4 Status (PWM Boiler 4)
(Same As Above) (BMS Only)
Boiler 5 Status (PWM Boiler 5)
(Same As Above) (BMS Only)
Boiler 6 Status (PWM Boiler 6)
(Same As Above) (BMS Only)
Boiler 7 Status (PWM Boiler 7)
(Same As Above) (BMS Only)
Boiler 8 Status (PWM Boiler 8)
(Same As Above) (BMS Only)
119 = Not On-Line
Faulted
Boiler 10 Status (BMS) (Net Boiler 2) Boiler 2 Status (BMS II)
Boiler 11 Status (BMS) (Net Boiler 3) Boiler 3 Status (BMS II)
Boiler 12 Status (BMS) (Net Boiler 4) Boiler 4 Status (BMS II)
Boiler 13 Status (BMS) (Net Boiler 5) Boiler 5 Status (BMS II)
Boiler 14 Status (BMS) (Net Boiler 6) Boiler 6 Status (BMS II)
Boiler 15 Status (BMS) (Net Boiler 7) Boiler 7 Status (BMS II)
Boiler 16 Status (BMS) (Net Boiler 8) Boiler 8 Status (BMS II)
OMM-0035_0C USER MANUAL Standard Register Assignments
MODBUS
Communication Chapter 2
Table 2-3: BMS/BMS II Standard Input Register Address Mapping (Continued)
Modbus Data
Address
Menu Item Units and Range Comments
17 (0x0011)
18 (0x0012)
19 (0x0013)
20 (0x0014)
21 (0x0015)
22 (0x0016)
23 (0x0017)
24 (0x0018)
25 (0x0019)
Boiler 1 Status (PWM Boiler 1)
Boiler 9 Status (BMS) (Net Boiler 1) Boiler 1 Status (BMS II)
120 = On-Line But Not Fired
(Same As Above)
(Same As Above)
(Same As Above)
(Same As Above)
(Same As Above)
(Same As Above)
(Same As Above)
120 = On-Line But Not Fired 1–40 = Fired & Sequence 121 = On-Line But Disabled 122 = On-Line But
Boilers 9 - 32 are the Network Boilers. BMS II has only Network Boilers, therefore Net Boiler 1 = Boiler 1, etc.
26 (0x001A)
27 (0x001B)
28 (0x001C)
29 (0x001D)
30 (0x001E)
31 (0x001F)
32 (0x0020)
Page 22 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
Same As Above
Same As Above
Same As Above
Same As Above
Same As Above
Same As Above
Same As Above
Chapter 2
Decimal (Hex)
(Net Boiler 9)
119 = Not On-Line
122 = On-Line But Faulted
Boiler 18 Status (BMS) (Net Boiler
Boiler 10 Status (BMS II)
Boiler 19 Status (BMS) (Net Boiler
Boiler 11 Status (BMS II)
Boiler 20 Status (Net Boiler 12) Boiler 12 Status (BMS II)
Boiler 21 Status (Net Boiler 13) Boiler 13 Status (BMS II)
Boiler 22 Status (Net Boiler 14) Boiler 14 Status (BMS II)
Boiler 23 Status (Net Boiler 15) Boiler 15 Status (BMS II)
Boiler 24 Status (Net Boiler 16) Boiler 16 Status (BMS II)
Boiler 25 Status (Net Boiler 17) Boiler 17 Status (BMS II)
Boiler 26 Status Net Boiler 18) Boiler 18 Status (BMS II)
Boiler 27 Status (Net Boiler 19) Boiler 19 Status (BMS II)
Boiler 28 Status (Net Boiler 20) Boiler 20 Status (BMS II)
Boiler 29 Status (Net Boiler 21) Boiler 21 Status (BMS II)
Boiler 30 Status (Net Boiler 22) Boiler 22 Status (BMS II)
Standard Register Assignments USER MANUAL
MODBUS
Communication GF-114
OMM-0035_0C
Table 2-3: BMS/BMS II Standard Input Register Address Mapping (Continued)
Modbus Data
Address
Menu Item Units and Range Comments
33 (0x0021)
34 (0x0022)
35 (0x0023)
36 (0x0024)
37 (0x0025)
38 (0x0026)
39 (0x0027)
40 (0x0028)
Boiler 17 Status (BMS) Boiler 9 Status (BMS II)
10)
11)
120 = On-Line But Not Fired 1–40 = Fired & Sequence 121 = On-Line But Disabled
Same As Above
Same As Above
Same As Above
Same As Above
Same As Above
Same As Above
Same As Above
41 (0x0029)
42 (0x002A)
43 (0x002B)
44 (0x002C)
45 (0x002D)
46 (0x002E)
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 23 of 200
Same As Above
Same As Above
Same As Above
Same As Above
Same As Above
Same As Above
GF-114
Decimal (Hex)
119 = Not On-Line
Faulted
Boiler 32 Status (Net Boiler 24) Boiler 24 Status (BMS II)
Boiler 33 Status (Net Boiler 25) Boiler 25 Status (BMS II)
Boiler 34 Status (Net Boiler 26) Boiler 26 Status (BMS II)
Boiler 35 Status (Net Boiler 27) Boiler 27 Status (BMS II)
Boiler 36 Status (Net Boiler 28) Boiler 28 Status (BMS II)
Boiler 37 Status (Net Boiler 29) Boiler 29 Status (BMS II)
Boiler 38 Status (Net Boiler 30) Boiler 30 Status (BMS II)
Boiler 39 Status (Net Boiler 31) Boiler 31 Status (BMS II)
Boiler 40 Status (Net Boiler 32) Boiler 32 Status (BMS II)
Bit map of Input/Output
Bit 7 = Empty
58 (0x003A)
Return Sensor Temp
40 °F to 220°F
BMS II Only
OMM-0035_0C USER MANUAL Standard Register Assignments
MODBUS
Communication Chapter 2
Table 2-3: BMS/BMS II Standard Input Register Address Mapping (Continued)
Modbus Data
Address
47 (0x002F)
Boiler 31 Status (Net Boiler 23) Boiler 23 Status (BMS II)
Menu Item Units and Range Comments
120 = On-Line But Not Fired 1–40 = Fired & Sequence 121 = On-Line But Disabled 122 = On-Line But
48 (0x0030)
49 (0x0031)
50 (0x0032)
51 (0x0033)
52 (0x0034)
53 (0x0035)
54 (0x0036)
55 (0x0037)
56 (0x0038)
57 (0x0039) I/O Status 0 to 255
Same As Above
Same As Above
Same As Above
Same As Above
Same As Above
Same As Above
Same As Above
Same As Above
status (BMS II Only) Bit 0 = AUX Relay Bit 1 = Fault Relay Bit 2 = Sys Start Relay Bit 3 = Empty Bit 4 = Setback Bit 5 = Interlock 2 Bit 6 = Interlock 1
Page 24 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
Chapter 2
Decimal (Hex)
59 (0x003B)
Net Blr 1 Outlet Temp
40°F to 220°F
When Blr Cntl Type = 1 or 2
60 (0x003C)
Net Blr 2 Outlet Temp
40°F to 220°F
61 (0x003D)
Net Blr 3 Outlet Temp
40°F to 220°F
62 (0x003E)
Net Blr 4 Outlet Temp
40°F to 220°F
63 (0x003F)
Net Blr 5 Outlet Temp
40°F to 220°F
64 (0x0040)
Net Blr 6 Outlet Temp
40°F to 220°F
65 (0x0041)
Net Blr 7 Outlet Temp
40°F to 220°F
66 (0x0042)
Net Blr 8 Outlet Temp
40°F to 220°F
67 (0x0043)
Net Blr 9 Outlet Temp
40°F to 220°F
68 (0x0044)
Net Blr 10 Outlet Temp
40°F to 220°F
69 (0x0045)
Net Blr 11 Outlet Temp
40°F to 220°F
70 (0x0046)
Net Blr 12 Outlet Temp
40°F to 220°F
71 (0x0047)
Net Blr 13 Outlet Temp
40°F to 220°F
72 (0x0048)
Net Blr 14 Outlet Temp
40°F to 220°F
73 (0x0049)
Net Blr 15 Outlet Temp
40°F to 220°F
74 (0x004A)
Net Blr 16 Outlet Temp
40°F to 220°F
75 (0x004B)
Net Blr 17 Outlet Temp
40°F to 220°F
76 (0x004C)
Net Blr 18 Outlet Temp
40°F to 220°F
77 (0x004D)
Net Blr 19 Outlet Temp
40°F to 220°F
78 (0x004E)
Net Blr 20 Outlet Temp
40°F to 220°F
79 (0x004F)
Net Blr 21 Outlet Temp
40°F to 220°F
80 (0x0050)
Net Blr 22 Outlet Temp
40°F to 220°F
81 (0x0051)
Net Blr 23 Outlet Temp
40°F to 220°F
82 (0x0052)
Net Blr 24 Outlet Temp
40°F to 220°F
83 (0x0053)
Net Blr 25 Outlet Temp
40°F to 220°F
84 (0x0054)
Net Blr 26 Outlet Temp
40°F to 220°F
85 (0x0055)
Net Blr 27 Outlet Temp
40°F to 220°F
Standard Register Assignments USER MANUAL
MODBUS
Communication GF-114
OMM-0035_0C
Table 2-3: BMS/BMS II Standard Input Register Address Mapping (Continued)
Modbus Data
Address
Menu Item
Units and
Comments
Range
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 25 of 200
GF-114
Decimal (Hex)
86 (0x0056)
Net Blr 28 Outlet Temp
40°F to 220°F
87 (0x0057)
Net Blr 29 Outlet Temp
40°F to 220°F
88 (0x0058)
Net Blr 30 Outlet Temp
40°F to 220°F
89 (0x0059)
Net Blr 31 Outlet Temp
40°F to 220°F
90 (0x005A)
Net Blr 32 Outlet Temp
40°F to 220°F
0 to 64 for Cmore; 0 to 65535 for MLX (BCM)
93 (0x005D)
Net Blr 2 Code
Same as Above
94 (0x005E)
Net Blr 3 Code
Same as Above
95 (0x005F)
Net Blr 4 Code
Same as Above
96 (0x0060)
Net Blr 5 Code
Same as Above
97 (0x0061)
Net Blr 6 Code
Same as Above
98 (0x0062)
Net Blr 7 Code
Same as Above
99 (0x0063)
Net Blr 8 Code
Same as Above
100 (0x0064)
Net Blr 9 Code
Same as Above
101 (0x0065)
Net Blr 10 Code
Same as Above
102 (0x0066)
Net Blr 11 Code
Same as Above
103 (0x0067)
Net Blr 12 Code
Same as Above
104 (0x0068)
Net Blr 13 Code
Same as Above
105 (0x0069)
Net Blr 14 Code
Same as Above
106 (0x006A)
Net Blr 15 Code
Same as Above
107 (0x006B)
Net Blr 16 Code
Same as Above
108 (0x006C)
Net Blr 17 Code
Same as Above
109 (0x006D)
Net Blr 18 Code
Same as Above
110 (0x006E)
Net Blr 19 Code
Same as Above
111 (0x006F)
Net Blr 20 Code
Same as Above
112 (0x0070)
Net Blr 21 Code
Same as Above
OMM-0035_0C USER MANUAL Standard Register Assignments
MODBUS
Communication Chapter 2
Table 2-3: BMS/BMS II Standard Input Register Address Mapping (Continued)
Modbus Data
Address
92 (0x005C) Net Blr 1 Code
Menu Item
Units and
Comments
Range
Page 26 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
Chapter 2
Decimal (Hex)
0 to 64 for Cmore; 0 to 65535 for MLX (BCM)
113 (0x0071)
Net Blr 22 Code
Same as Above
114 (0x0072)
Net Blr 23 Code
Same as Above
115 (0x0073)
Net Blr 24 Code
Same as Above
116 (0x0074)
Net Blr 25 Code
Same as Above
117 (0x0075)
Net Blr 26 Code
Same as Above
118 (0x0076)
Net Blr 27 Code
Same as Above
119 (0x0077)
Net Blr 28 Code
Same as Above
120 (0x0078)
Net Blr 29 Code
Same as Above
121 (0x0079)
Net Blr 30 Code
Same as Above
122 (0x007A)
Net Blr 31 Code
Same as Above
123 (0x007B)
Net Blr 32 Code
Same as Above
124 (0x007C)
Standard Register Assignments USER MANUAL
MODBUS
Communication GF-114
OMM-0035_0C
Table 2-3: BMS/BMS II Standard Input Register Address Mapping (Continued)
Modbus Data
Address
Menu Item Units and Range Comments
112 (0x0070) Net Blr 21 Code
Thru
65535 (0xFFFF)
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 27 of 200
(Reserved for future expansion)
GF-114
Modbus Data
Decimal (Hex)
0 (0x0000)
(Reserved)
1 (0x0001)
(Reserved)
2 (0x0002)
(Reserved)
3 (0x0003)
(Reserved)
Valid when Header Set Mode =
Signal = Network
5 (0x0005)
System Start Temp
32 to 120°F
Default = 70°F
0 or 1, 0 = Temp Only, 1 = Temp and Load
Manual Hdr Set Temp/Internal Setpt
8 (0x0008)
Bldg Ref Temp
40 to 220°F
Default = 70°F
0.0 to 20.0°F/°F (0.5°F/°F increments)
Default = 00.0°F/°F (Value x 10) (BMS Only)
Indoor Setpoint Temp
Default = 70°F (BMS Only)
0.3 to 3.0 (0.1 increments),
Default = 1.2 (Value x 10)
12 (0x000C)
Max Header Temp
40 to 220°F
Default = 220°F
13 (0x000D)
Min Header Temp
40 to 220°F
Default = 40°F
Default = 45% (BMS) Default = 20% (BMS II)
Default = 18% (BMS) Default = 16% (BMS II)
0.00 to 9.99 Rep/Min (in 0.01 increments
Default = 0.15 Rep/Min (Value x 100)
0, 1, or 2
2 = Remote Setpt
OMM-0035_0C USER MANUAL Standard Register Assignments
MODBUS
Communication Chapter 2

2.3.2 BMS/BMS II Controller Standard Holding Register Assignments

The Holding Register address assignments for the BMS/BMS II/ACS are listed in Table 2-4 which follows. Unless otherwise specified, all Holding Register Menu items are Read/Write (R/W).
Table 2-4: BMS/BMS II Standard Holding Register Address Mapping
Address
4 (0x0004)
6 (0x0006) System Start Option
7 (0x0007)
9 (0x0009) Indoor Prop Band
Menu Item Units and Range
Net Header Set Temp
Default/
Comments
40 to 220°F
40 to 220°F Default = 160°F
Remote Setpt and Remote
Default = 0
10 (0x000A)
11 (0x000B) Reset Ratio
14 (0x000E) Start Percent 25 to 100%
15 (0x000F) Stop Percent 10 to 45%
16 (0x0010) Integral Gain
17 (0x0011) Header Set Mode
Page 28 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
50 to 150°F
0 = Constant Setpt 1 = In/Outdoor Reset
Default = 0 (Constant Setpt))
Chapter 2
Decimal (Hex)
-2.00 to 2.00
19 0x0013)
Header Temp Bandwidth
5 to 120°F
Default = 70°F
20 (0x0014)
Aux Relay Open
0 to 99%
Default = 45%
0 or 1
1 = 100% Fire Rate and Off
0 or 1
Setpt
0, 1, 2, 3
3 = Interlock 2
0 or 1
1 = Manual
0, 1 or 2
2 = Combination
Default = 0 (BMS Only)
assign Combo Boilers)
27 (0x001B)
(Reserved)
28 (0x001C)
(Reserved)
29 (0x001D)
(Reserved)
Max Power Input
Default = 100% (Fire Rate)
Interlock 1 Method
(BMS II)
0 or 1
1 = Start Enabled
MODBUS
Communication GF-114
Standard Register Assignments USER MANUAL
Table 2-4: BMS/BMS II Standard Holding Register Address Mapping (Cont.)
OMM-0035_0C
Modbus Data
Address
18 (0x0012) Derivative Gain
21 (0x0015) Aux Relay Mode
22 (0x0016)
23 (0x0017)
Menu Item Units and Range
Temp Sensor Fail Mode/Failsafe Mode
Fault Alarm Relay Mode
(0.00 increments)
0 = 100% Fire Rate
0 = Shutdown 1 = Switch Inputs/Constant
0 = All Faults, 1 = No Interlock 2 = Interlock 1
Default/
Comments
Default = 0.15 (Value x 100)
Default = 1 (100% Fire Rate & Off)
Default = 0 (Shutdown)
Default = 0 (All Faults)
24 (0x0018) Fault Alarm Clear Method
25 (0x0019) Boiler Operation Mode
Number Of
26 (0x001A)
30 (0x001E)
31 (0x001F)
Combination Mode Boilers
(BMS)/Sys Intlk Config
0 = Automatic
0 = Parallel 1 = Sequential
0 to 4
50 to 100%
0 = Always Enabled
Default = 0 (Automatic)
Default = 1 (Sequential)
(Start at Boiler 8 and work back to Boiler 5 to
Default = 1 (Start Enabled)
05/18/12 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 29 of 200
GF-114
Decimal (Hex)
32 (0x0020)
Real Time Clock Minutes
00 to 59 Minutes
Present Time
Real Time Clock Hours
Real Time Clock Day of Week
Real Time Clock Year
Real Time Clock Day of Month
Real Time Clock Month
38 (0x0026)
Offset Temp Day 1
-50 to 50°F
Default = 0°F
39 (0x0027)
Offset Temp Day 2
-50 to 50°F
Default = 0°F
40 (0x0028)
Offset Temp Day 3
-50 to 50°F
Default = 0°F
41 (0x0029)
Offset Temp Day 4
-50 to 50°F
Default = 0°F
42 (0x002A)
Offset Temp Day 5
-50 to 50°F
Default = 0°F
43 (0x002B)
Offset Temp Day 6
-50 to 50°F
Default = 0°F
44 (0x002C)
Offset Temp Day 7
-50 to 50°F
Default = 0°F
Offset On Time Day 1 – Minutes
Offset On Time Day 2 – Minutes
Offset On Time Day 3 – Minutes
Offset On Time Day 4 – Minutes
Offset On Time Day 5 – Minutes
Offset On Time Day 6 – Minutes
Offset On Time Day 7 – Minutes
OMM-0035_0C USER MANUAL Standard Register Assignments
MODBUS
Communication Chapter 2
Table 2-4: BMS/BMS II Standard Holding Register Address Mapping (Cont.)
Modbus Data
Address
33 (0x0021)
34 (0x0022)
35 (0x0023)
36 (0x0024)
37 (0x0025)
Menu Item
Units and
Range
00 to 23 Hours Present Time
1 to 7 Present Day
00 to 99 Present Year
01 to 31 Present Day of Month
01 to 12 Present Month
Default/
Comments
45 (0x002D)
46 (0x002E)
47 (0x002F)
48 (0x0030)
49 (0x0031)
50 (0x0032)
51 (0x0033)
00 to 59 Minutes Default = 0
00 to 59 Minutes Default = 0
00 to 59 Minutes Default = 0
00 to 59 Minutes Default = 0
00 to 59 Minutes Default = 0
00 to 59 Minutes Default = 0
00 to 59 Minutes Default = 0
Page 30 of 200 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph.: 800-526-0288 05/18/12
Loading...
+ 70 hidden pages